General Specifications

Similar documents
General Specifications

Model JDF Field Indicator

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Rosemount 1151 Smart Pressure Transmitter

TFRH Hygienic RTD temperature sensor. CombiTemp TM

TFR5 Room or outdoor temperature sensor. CombiTemp TM

TFRN Industrial RTD temperature sensor. CombiTemp TM

Flow Measurement SITRANS F M

MB 204/MB 204-Ex. Multi-Barrier for PROFIBUS PA and FOUNDATION Fieldbus 10/ EN

TFRN Industrial RTD temperature sensor. CombiTemp TM

FBT-6. Relcom. Fieldbus. fieldbus powered USB. FOUNDATION Fieldbus. segment. Recording the. segment. The Monitor collects this transfer to.

GOYEN PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS CLEAN AIR SOLUTIONS PRODUCT LEAFLET

PROPORTIONAL VALVES Sentronic plus

Ex td A21 IP66 T58 C. max. 3 x 4 mm 2 or 1 x 10 mm 2 with pin cable lug + 1 x 2.5 mm 2 fine wire. max. 4 x M20 metal thread

SITRANS F flowmeters SITRANS F M. Transmitter MAG 6000 I/6000 I Ex d e 4/43

General Specifications

PMG. Vibration Energy Harvesters

Inductive sensor. 2-wire, analog output BI8-M18-LI-EXI

Inductive sensor BI1.5-EG08K-Y1

RMA 3000 Remote Meter Assemblies Specifications

TFR5 Room or outdoor temperature sensor. CombiTemp TM

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0,35 % FSO. Nominal pressure

Inductive sensor NI10-M18-Y1X-H1141

Inductive sensor NI3-EG08K-Y1-H1341

Pendant Light Fitting IEC Series 6470/2

General Specifications

Pressure transmitter For applications in hazardous areas Model IS-3

DMP 331i DMP 333i. Precision Pressure Transmitter. Stainless Steel Sensor. accuracy according to IEC 60770: 0.1 % FSO

DMP 331 DMP 331. Industrial Pressure Transmitter. for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial. tri-matic.

SAFJ HI-LUMEN LED S A H I L U M. LED Area Lighting for Hazardous Locations

TEK-LCD 7801A. NEMA 4X Loop-Powered Feet and Inches Level Meter. ACCESSORIES. Technology Solutions

3.3. Ex-Escape sign luminaires. Ex-Lite Metal version with LED technology for Zone 1 and Zone 21 / NEC applications

DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. accuracy according to IEC 60770: 0.5 % FSO.

General Specifications

Magnetic field sensor for pneumatic cylinders BIM-IKT-Y1X

EXLUX ECOLUX 6480 Series

DMP 331i / DMP 333i LMP 331 i

associates APPLICATION GUIDE AG334 Externally powered pulse input Rate Totalisers For models with an 'E' or 'G' suffix

Level Measurement. Continuous level measurement Radar transmitters. SITRANS LR250 Flanged Encapsulated Antenna. 4/228 Siemens FI

Explosion Proof Audible Signal db(a) Series YA60

PSI-MOS-RS232/FO 850 E Serial to Fiber Converter

Process Transmitter RMA 422

FIELD MOUNTED RATE TOTALISER MODEL 202D

Contactor 4 kw / 400 V with 3 Main Contacts and max. 4 Auxiliary Contacts Series 8510/122

Material: Weight: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:

EXLUX ECOLUX C-LUX 6480 Series

Material: Weight: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:

Level Measurement Continuous level measurement - Radar transmitters

Level Measurement Continuous level measurement - Radar transmitters

Inductive sensor With analog output BI15-M30-LI-EXI

RIA46. Technical Information. Field meter Digital field meter with control unit for monitoring and visualizing analog measured values

Viper Ex the hazard free way to precise weighing results. Ex ia. The intrinsically safe compact scales combine leadingedge

ACT20X Series for hazardous area applications Section A

Hazard Gard EVLL Series Explosionproof LED Luminaires Class I, Division 1 factory-sealed LED luminaire for general illumination

Explosion Proof Audible Signal db(a) Series YA60

Magnetic Field Sensor for pneumatic cylinders BIM-IKT-Y1X

DMP 339. Pressure Transmitter. with G ¼" flush diaphragm. Pressure Transmitter. Industrial. accuracy according to IEC 60770: 0.

Sentronic PLUS Electronic Pressure Regulator. Installation Manual

IECEx International Conference 2017 Shanghai, China. Electrical Installations Design, Selection, Erection and Inspection Part 2 of 2

Pendant Light Fittings Series 6050

CAPACITIVE SENSORS KAS. Series 26. Level Control Food Industry Pharmaceutical Industry Semiconductor Industry Chemical Industry

DMP 331Pi. Precision. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm. Pressure Transmitter.

Level Measurement Point level measurement - RF Capacitance switches

XML LED X M L L E D. Explosionproof Linear LED Lighting

Modular Lube Lubrication Systems System Controls

Installation instructions Ex frames

Level Measurement Continuous level measurement - Capacitance transmitters

DMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial

Lighting: Fluorescent Lighting FD Series: Cylindrical Fluorescent Lighting Fixtures, Standard and Emergency Battery Back-Up Flameproof

RIA45. Technical Information. Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values

Level instruments. Continuous level measurement - Radar transmitters SITRANS LR250. 5/224 Siemens FI Overview.

Process transmitter RMA422

Capacitance Level Measurement Electronic insert FEC 12

FLEX Ex System Certification

Level Measurement Continuous level measurement Radar transmitters

ATEX-manual for units

IEPE Premium Accelerometer, Side Connector

7 Lighting Technology

EXPlora. Introduction

AE-341 SERIES PROCESS INDICATORS 2 TO 6 DIGITS 0-20 MA, 4-20 MA, 0-5V, OR 0-10V SCALED INPUT

IEPE Premium Accelerometer, Top Connector

Sentronic PLUS. Electronic Pressure Regulator. Installation Manual

9 Control Equipment. Measurement- and Control Equipment Series 8214, 8218

DS 210. Electronic Pressure Switch. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure

RMA42. Technical Information

All Control Electronics, No Electronics. And Host System Connections M06 Industrial-Grade Fiber Optic Cabling (Recommended)

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

MODEL HS35 DRAWWORKS OPTICAL ENCODER

Circuit-Breakers for Motor Protection Series 8523/8

JUMO extherm-at Type , Explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22

Guided Radar (TDR) Level Transmitter for storage and process applications

JUMO extherm-at Type , explosion-proof surface-mounted thermostat for zones 1, 2, 21, and 22

Liquid Level Sensor AKS 4100U

Micro-DCI 53ML5100 Manual Loader

1 Inductive proximity switches. 5 Connecting cables. Highlights: New:

OPTIFLEX 2200 C/F Technical Datasheet

Level Measurement Point level measurement RF Capacitance switches

Level Switch. LS Ex KS Ex RS Ex. Manual. AQ Elteknik AB

General Specifications

Transcription:

General Specifications FVX110 Fieldbus Segment Indicator The FVX110 is a field indicator that allows you to switch and display up to 16 indicated values for FOUNDATION TM fieldbus devices. Turn the scroll knob on the case to switch displays. No complex operation is needed in the field and you can observe the indicated values easily. An LCD display with LED backlight and a variety of displays has increased user-friendliness and visibility. The FVX110 offers as standard not only the functions of a field indicator, but also PID function block, Link master, and software download functions. FEATURES Interoperability Field instruments that comply with the FOUNDATION fieldbus specifications are fully interoperable; no longer is there a need for custom designed software to communicate with other devices. Up to 16 process variables can be switched and displayed Up to 16 process variables from multiple field instruments can be displayed, significantly reducing instrumentation costs. Furthermore, support of the FOUNDATION fieldbus digital communications protocol enables the display of signal data from third-party fieldbus compliant field devices. Full dot matrix LCD with backlight The backlit full dot-matrix LCD clearly displays text and graphics such as bar graphs, a scroll bar, and icons that indicate the page turning direction and scroll knob turning direction. Link master function The FVX110 supports a link master function that enables backup of network management and allows local control using field devices. Function blocks To facilitate device diagnostics, two functions blocks each are provided for the multiple analog output (MAO), arithmetic (AR), and input selector (IS), and a single function block is provided for the following: signal characterizer (SC), integrator (IT), and PID. Self-diagnosis function A reliable self-diagnostic function based on the NAMUR NE107 standard detects failures in the ambient temperature limit, communications, and hardware such as the LCD and amplifier assembly. STANDARD SPECIFICATIONS FUNCTIONAL SPECIFICATIONS Functional specifications for Fieldbus communication conform to the standard specifications (H1) of FOUNDATION fieldbus. Supply Voltage 9 to 32 V DC for general use, flame proof type, Type n, or nonincendive. 9 to 24 V DC for intrinsically safe type Entity model 9 to 17.5 V DC for intrinsically safe type FISCO model Communication Requirements Supply Voltage: 9 to 32 V DC Current consumption: Steady condition: 15 ma (max) Software download condition: 24 ma (max) Ambient Temperature Limits -20 to 70 C (-4 to 158 F) Ambient Humidity Limits 0 to 100 %RH Software download function With this function, it is possible to download updates or upgrades to the FVX110 software. Typical uses of this function are the addition of function blocks and diagnostics for existing devices. Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 Copyright Sep. 2010 4th Edition Feb. 2014

LCD Display 84 column x 32 lines full-dot matrix with LED backlight. 3 lines indication as - Top line 14 alphanumerics indication of main description (Main Tag) such as PD TAG of field device. Scroll up to maximum 32 alphanumerics - Middle line process value including +/- sign and unit of 5digits x 2 lines - Bottom line 14 alphanumerics of communication status and indicate description (Sub Tag) such as block information. Bar graph, Scroll bar, Page information, Scroll direction information, Squawk Process value (Middle line) 14 characters Top line Unit (Middle line) PHYSICAL SPECIFICATIONS Enclosure Material Housing: Low copper cast aluminum alloy with polyurethane, mint-green paint (Munsell 5.6BG 3.3/2.9 or its equivalent) or ASTM CF-8M stainless steel. Body: 316L SST Scroll Knob: 316L SST Cover O-rings: Buna-N Name plate and tag: 316 SST Wired tag plate: 316 SST Degrees of Protection IP67, NEMA4X Weight 1.2 kg (2.6 lb) * *: Without mounting bracket. Add 1.5 kg (3.3 lb) for Amplifier housing code 2. Electrical Connections Refer to MODEL AND SUFFIX CODE 2 14 characters Bottom line F00.ai Display Scroll Functions Single scroll and cyclic scroll (Scan mode) Display up to 16 variables EMC Conformity Standard: EN61326-1 Class A, Table 2 (For use in industrial location) Link Master Function: Link Master function is supported. Function Block: Block name Number Execution time Note MAO 2 30 ms Output eight analog signals from field deveces IS 2 30 ms Input Selector block provides selection of up to eight inputsand generate an output based on the configured action AR 2 30 ms Arithmetic block permits simple use of popular measurement math function PID 2 45 ms Works as a field controller in conjunction with another function block. SC 1 30 ms An output of Signal Characterizer block is a nonlinear function of the respective input. The function is determined by a table IT 1 30 ms Integrator block integrates a variable as a function of the time or accumulates the counts Oct. 21, 2011-00

3 MODEL AND SUFFIX CODES Model Suffix code Description FVX110................. Fieldbus segment indicator Output signal -F............... Digital communication (FOUNDATION Fieldbus protocol) Amplifier 1............. Cast aluminum alloy housing 2............. ASTM CF-8M stainless steel *1 Electrical connection 0........... G 1/2 female, one electrical connection without blind plug 2........... 1/2 NPT female, two electrical connections without blind plugs 4........... M20 female, two electrical connections without blind plugs 5........... G 1/2 female, two electrical connections and a blind plug 7........... 1/2 NPT female, two electrical connections and a blind plug 9........... M20 female, two electrical connections and a blind plug A........... G 1/2 female, two electrical connections and a 316 SST blind plug C........... 1/2 NPT female, two electrical connections and a 316 SST blind plug D........... M20 female, two electrical connections and a 316 SST blind plug Mounting bracket L........ 316 SST 2-inch pipe mounting N........ None Optional Codes / Optional Specification *1: Not applicable for electrical connection code 0, 5, 7 or 9 OPTIONAL SPECIFICATIONS (For Explosion Protected type) Item Description Code FM Explosionproof Approval *1 Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250 Explosionproof for Class I, Division 1, Groups B, C and D, FF1 Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G, Enclosure Rating: NEMA Type 4X Temperature class: T6, Amb. Temp.: 40 to 60 C ( 40 to 140 F) Factory Mutual (FM) CENELEC ATEX FM Intrinsically Safe and Nonincendive Approval *1 Applicable Standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA 250, ISA60079-27 Intrinsically Safe for Class I,II, & III, Division 1, Groups A,B,C,D,E,F & G, Entity, FISCO. /Class I, Zone 0, AEx ia IIC, Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: 40 to 60 C ( 40 to 140 F). Intrinsically Apparatus Parameters : [FISCO (IIC)] Ui=17.5 V, Ii=500 ma, Pi=5.5 W, Ci=1.76 nf, Li=0 µh [FISCO (IIB)] Ui=17.5 V, Ii=500 ma, Pi=5.5 W, Ci=1.76 nf, Li=0 µh [Entity] Ui=24 V, Ii=250 ma, Pi=1.2 W, Ci=1.76 nf, Li=0 µh Nonincendive for Class I, Division 2, Groups A, B, C and D, NIFW, FNICO Class I, Zone 2, Group IIC, NIFW, FNICO Class II, Division 2, Groups F&G, and Class III, Division 1 Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: 40 to 60 C ( 40 to 140 F) Nonincendive Apparatus Parameters : Vmax.= 32 V, Ci = 1.76 nf, Li = 0 µh CENELEC ATEX (KEMA) Flameproof Approval *1 Applicable Standard: EN 60079-0, EN 60079-1, EN 61241-0, EN 61241-1 Certificate: KEMA 10ATEX0157 II 2G, 2D Ex d IIC T6 Ex td A21 IP6X T80 Degree of protection : IP66 and IP67 Amb. Temp. (Tamb) for gas-proof : T6; 50 to 75 C ( 58 to 167 F) Max. surface Temp. for dust-proof : T80 C (Tamb: 40 to 167 F) CENELEC ATEX (DEKRA) Intrinsically safe Approval *1 Certificate: DEKRA 11ATEX0022 X Applicable standards: EN 60079-0, EN 60079-11, EN 60079-26, EN 60079-27, EN 61241-11 II 1G Ex ia IIB/IIC T4 Ga, II 1D Ex ia IIIC T80 C Da IP6X Amb. Temp. : 40 to 60 C ( 40 to 140 F) Max. Surface Temp. for dust-proof: T80 C (Tamb.: 40 to 140 F) Enclosure : IP66 and IP67 [FISCO (IIC)] Ui=17.5V, Ii=500mA, Pi=5.5W, Ci=3.52nF, Li=0µH [FISCO (IIB)] Ui=17.5V, Ii=500mA, Pi=5.5W, Ci=3.52nF, Li=0µH [Entity] Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH FS15 KF25 KS25 June 03, 2011-00

4 Item Description Code CSA Explosionproof Approval *1 Certificate: 2325751 Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.213, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1-04 Explosion-proof for Class I, Groups B, C and D. CF1 Dustignition-proof for Class II/III, Groups E, F and G. When installed in Division 2, "SEAL NOT REQUIRED" Enclosure: TYPE 4X, Temp. Class: T6 Ex d IIC T6 Enclosure: IP66 and IP67 Amb.Temp.: 50 to 75 C ( 58 to 167 F) Canadian Standards Association (CSA) IECEx Scheme CSA Intrinsically safe Approval *1 Certificate: 2346277 Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1-04 CAN/CSA E60079-0, CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529 Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III Division 4; Ex ia IIC T4 Amb. Temp.: 40 to 60 C( 40 to 140 F) Encl. Type 4X, IP66 and IP67 Entity Parameters for Intrinsically Safe : Ui (Vmax) = 24V, Ii (Imax) = 250mA, Pi (Pmax) =1.2W, Ci = 1.76nF, Li = 0µH or Ui (Vmax) = 17.5V, Ii (Imax) = 500mA, Pi (Pmax) = 5.5W, Ci = 1.76nF, Li = 0µH Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups F & G, Class III Division 1; Ex nl IIC T4 Amb. Temp.: 40 to 60 C ( 40 to 140 F) Encl. Type 4X, IP66 and IP67 Entity Parameters for Nonincendive : Ui = 32V, Ci = 1.76nF, Li = 0µH IECEx Flameproof Approval *1 Applicable Standard: IEC 60079-0, IEC60079-1 Certificate: IECEx KEM 10.0071 Flameproof for Zone 1, Ex d IIC T6 Enclosure: IP66 and IP67 Amb.Temp.: 50 to 75 C( 58 to 167 F) IECEx Intrinsically safe and type n Approval *1 No. IECEx DEK 11.0004 X Applicable Standard: IEC 60079-0, IEC 60079-11, IEC 60079-26, IEC 60079-27, Ex ia IIB/IIC T4 Ga, Ex ic IIC T4 GC Ambient Temperature : 40 to 60 C Enclosure: IP66 and IP67 Intrinsically safe ratings (Ex ia IIB/IIC T4) [Entity] Ui = 24 V, Ii= 250 ma, Pi = 1.2 W, Ci = 3.52 nf, Li = 0 µh [FISCO IIC] Ui = 17.5 V, Ii = 500 ma, Pi = 5.5 W, Ci = 3.52 nf, Li = 0 µh [FISCO IIB] Ui = 17.5 V, Ii = 500 ma, Pi = 5.5 W, Ci = 3.52 nf, Li = 0 µh Intrinsically safe ratings (Ex ic IIC T4): Ui = 32 V, Ci = 3.52 nf, Li = 0 µh Note 1 : Applicable for Electrical connection code 2, 4, 7, 9, C and D. CS15 SF25 SS25 OPTIONAL SPECIFICATIONS Item Description Optional code Painting Color change Amplifier cover only *1 P Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR Coating change Anti-corrosion coating *1*2 X2 316 SST exterior parts 316 SST name plate, tag plate and screw *3 HC Lightning protector Power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type, 9 to 32 V DC for Fieldbus communication type) Allowable current: Max. 6000A (1x40μs), Repeating 1000A (1x40μs) A 100times Wired tag plate 316 SST tag plate wired onto indicator N4 *1: Not applicable for amplifier housing code 2 *2: Not applicable with color change option *3: 316 SST or 316 LSST. The specification is included in amplifier housing code 2. Oct. 21, 2011-00

5 DIMENSIONS 95 (3.74) 60 (2.36) 50 (1.97) 110 (4.33) 188 (7.40) Unit: mm (approx.inch) Conduit connection Scroll knob Conduit connection 12 (0.47) 39 (1.54) 126 (4.96) 139 (5.47) 159 (6.26) Ø78 (3.07) Ground terminal Ø70 (2.76) 110 (4.33) Body Mounting bracket (optional) 12 (0.47) 6 (0.24) 2-inch pipe (O.D. 60.5 mm) 54 (2.13) 129 (5.08) Electrical connection for code 5, 9, A and D F01E.ai Terminal Configuration Terminal Wiring SUPPLY + 1 2 Power supply and output terminals Ground terminal Terminal 1 Terminal 2 <Ordering Information> Specify the following when ordering 1. Model, suffix codes, and option codes 2. Tag Number; Specify software tag (up to 32 letters) to be written on the amplifier memory and Tag number (up to 18 letters) to be engraved on the tag plate separately. 3. Node Address 4. Operation Functional Class Select BASIC or LINK MASTER <Factory Setting> Tag Number (Tag plate) Software Tag (PD_TAG) Node Address Operation Functional Class As specified in order 'UI1001' unless otherwise both Tag Number and software Tag specified in order '0xF5' unless otherwise specified in order BASIC or as specified F02E.ai <Related Instruments> The customer should prepare instrument maintenance tool, terminator, fieldbus power supply etc. <Reference> FOUNDATION; Trademark of Fieldbus Foundation ; Trademark of YOKOGAWA Electric Corp. Subject to change without notice. Feb. 28, 2014-00