SnapStak Stackable Snap-In Cable Hanger Electrical and Mechanical Testing Performance

Similar documents
Jul03 Rev C EC

Non Magnetic Connectors

PERFORMANCE SPECIFICATION SHEET

Type "N" Connectors. Type "N" Interface Dimensions

SCHEDA TECNICA. Amarro per cavi 13,5mm Amarro per cavi 16,5mm. MS217F00 Amarro per cavi 13,5mm MS218F00 Amarro per cavi 16,5mm

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL, RADIO FREQUENCY (SERIES SMA (CABLED) - PLUG, PIN CONTACT, CLASS 2)

MCX - 75 Ohm Connectors

SMA One Piece Semi-Rigid Connectors

AMERICAN NATIONAL STANDARD

Materials Connector part Material Finish

Your Network Has Evolved. So Has Our Cable.

bmam connectors DIVIDER PAGE

8D with High Frequency Coaxial Contact

HDRFI Series Tensolite High-Performance Cable & Interconnect Systems. High Density RF Interconnect

Non Magnetic Connectors Product Catalog

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES TNC (CABLED), PIN CONTACT, RIGHT ANGLE, CLASS 2)

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES BNC (CABLED), PIN CONTACT, CLASS 2)

Series MCX 50 micro miniature connectors

INCH-POUND MIL-PRF-39012/29H w/amendment 3 25 January 2018 SUPERSEDING MIL-PRF-39012/29H w/amendment 2 21 November 2016

INCH-POUND MIL-PRF-39012/28H w/amendment 4 25 January 2018 SUPERSEDING MIL-PRF-39012/28H w/amendment 3 15 April 2017

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

SERIES HPQN CONNECTORS

Automatic Connector MHV Connectors MHV Introduction MHV series connectors Contents Polarized mating interfaces Anti-Rock mating interfaces

Cable Retention Force Testing of Trunk & Distribution Connectors

Materials Connector part Material Finish

HN Connectors. Automatic Connector. Introduction. Contents. 631/ FAX 631/

SMA - 50 Ohm Connectors

The Custom Interconnect Leader TM

SPECIFICATION FOR FIBER OPTIC SPLICE CLOSURE

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES BNC (CABLED), PIN CONTACT, CLASS 2)

Series SK (2.92 mm) prec. submini. connectors

e-enterable Fiber Optic Splice Closure (Re-Enterable Aerial Closure for Access Service)

RF Characterization Report

SUHNER QMA SUBMINIATURE CONNECTORS

SERIES BNC 50, COAXIAL MINIATURE CONNECTORS

DISTRIBUTION AMPLIFIER

THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS

MCX Miniature Coaxial Connectors

Intelligent Pendulum Hardness Tester BEVS 1306 User Manual

RF/Microwave Connectors & Cable Assemblies

SPECIFICATION. Spec No : VSS-1402-CS603B

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Stainless Steel SMA Connectors Product Catalog

Interface RF Connector with Switch

White Paper. Discone Antenna Design

TNC Connectors. RF Coax Connectors. Product Facts

RMS Communications Inc.,

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK

A449-6S 70 CENTIMETER FM YAGI ANTENNA MHz

Wide Band Power Amplifier 6GHz~12GHz. Parameter Min. Typ. Max. Units Frequency Range 6 12 GHz Gain db Gain Flatness ±2.0 ±3.

SPECIFICATION FIBER OPTIC SPLICE CLOSURE. Spec No : VSS-1007-BS403A-04A/SD. VSS-0107-BS403A-04A/SD R & D Center Manufacturing Division

Principles of Electrostatic Chucks 6 Rf Chuck Edge Design

Operating Manual. Automated Gear. Apollo Design Technology, Inc Fourier Drive Fort Wayne, IN USA

Ultra Small Surface Mount Coaxial Connectors - Low Profile 1.9mm or 2.4mm Mated Height

Dynatel Advanced Cable Locator 2250

Channel Cable Tray - Accessories

PAM-1840 Preamplifier Operation Manual

Highly Accelerated Stress Screening of the Atlas Liquid Argon Calorimeter Front End Boards

PANEL RADIATORS - TECHNICAL MANUAL

Illustrated Feature. Options

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Series SMPM-T. Description. Compatibility. Content. Interface dimensions (mm/inches) SMPM-T male (pin contact), smooth bore

DLP ANTENNA INSTRUCTION MANUAL. Dielectric LLC 22 Tower Road Raymond, Maine Phone:

Video Patching Systems ProPatch Miniature (PPM) Series

Electric Wall/Ceiling Projection Screen Saker Tab-Tension Series User s Guide

HexPort Multi-Band Antenna

Model FP 240 Drying and heating chambers Classic.Line with forced convection and program functions

Interface RF Connector with Switch, built-in interlock, DC to 3GHz

Mechanical aspects, FEA validation and geometry optimization

TECHNICAL SPECIFICATION

2.4 METER SERIES 1250 ANTENNA SYSTEM

Optimizing BNC PCB Footprint Designs for Digital Video Equipment

Low Loss RG 402 Equivalent

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Specification for F Connector, Male, Pin Type

ENGINEERING COMMITTEE

A CENTIMETER FM YAGI ANTENNA MHz

Electric Motorized Projection Screen PowerMax Tension Series

DOME OPTIC SPLICE CLOSURE

WLC60 Heavy Duty LED Light - PWM Dimmable

TEST REPORT CHOMERICS R&D. PREMIER EMI Shielding Thermoplastic Face Plate Shielding Effectiveness 84 DRAGON COURT WOBURN, MA 01801

INSTRUCTION MANUAL. Model V-4R Collinear Gain Vertical for MHz. General SPECIFICATIONS

PiMPro Rack Mount Analyzer

Agilent 87405C 100 MHz to 18 GHz Preamplifier

Moving to FN15vf Project to re-locate the WCARC VHF/UHF Weak Signal Beacons from FN15wg on the VE3XK Tower

PRJTPFL inch PRJTPFL inch PRJTPFL inch. Fixed Wall Mount Projector Screen. Universal Home/Office Projector Viewing Display

Ultra Small Surface Mount Coaxial Connectors 1.4mm Mated Height

Agilent 87075C Multiport Test Set Product Overview

Electric Wall/Ceiling Projection Screen Saker Series User s Guide

MS2540 Current Loop Receiver with RS485 Communication

ENGINEERING COMMITTEE

DISTANCE BETWEEN FIXTURES. * 2 " [61mm] on 1ft configuration. 5-year limited warranty.

SECTION 9 BNC/BNC 75 HDTV/BNC-TRX R141/R142/R266 SIMPLIFICATION IS OUR INNOVATON. Visit for more information

For Sales & Information, Call Toll Free: (888)

Agilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz

Amphenol Australia. AT Series PRODUCT SHORTFORM. Amphenol Australia Pty Ltd. AT Series

In-Ceiling Electric Motorized Front Projection Screen Evanesce Series. User s Guide

Coaxial Cable Termination

1.8 METER SERIES 1183 Az/El MOUNT ANTENNA SYSTEM

Interactive Satellite Terminal Installation / Validation Manual

Interactive Satellite Terminal Installation / Validation Manual

Transcription:

SnapStak Stackable Snap-In Cable Hanger Electrical and Mechanical Testing Performance Table of Contents Introduction................................1 Axial pull test and horizontal shear test............2 Return loss and TDR impact test................3 Wind tunnel testing...........................4 Vibration testing.............................5 Thermal shock..............................5 Corrosion..................................6 Introduction SnapStak self-stacking cable hangers enable installation engineers to neatly secure coaxial cables on congested communications towers simply by snapping them into place. Each SnapStak hanger accommodates one run of HELIAX coaxial cable. Hangers can be double or triple stacked, from the tower face, depending on cable size. Snapstak hangers also may be used for other coaxial cable brands. A major timesaving feature is the hanger's selfcontained spring fork and retention tab design that eliminates the need to use loose hardware to secure individual cable lines. Simply snap the hanger into a 3/4-inch hole in the prepunched tower mounting structure. Using various mounting accessories, you can mount SnapStak hangers directly to towers and also on building rooftops and water towers. Constructed of stainless steel, the SnapStak snap-in hanger is strong enough to withstand extreme weather conditions and highly corrosive environments. Multiple retention tabs on the hanger prevent cable slippage and hanger disengagement from the tower, even under heavy ice and wind loads. The retention tabs at the base of the hanger also allow limited hanger float on the mounting structure, thus reducing vibration. This eases stress on the connections at the jumper cable, antenna, and RF device. The Snapstak hanger has undergone an extensive battery of mechanical, environmental, and wind tunnel tests to ensure hanger safety and reliability, even under the most severe environmental conditions. SP50348 22 October 2001 Page 1 of 6

Results Results show that the SnapStak hangers placed at 3- foot (1 meter) intervals along the cable are capable of securing in place 14.5 to 40 times the weight of the cable. Also, the force required to release the hanger from the mounting structure is well in excess of that which could be encountered at the site. The average amount of force required to pull the hanger over the corrugated crest of each cable and to release the hanger from the 0.750" x 0.120" mounting hole is indicated in the table below. Horizontal shear in a common mounting structure, with an after galvanizing thickness of 0.150" improved up to 48% over the thinner material. Dead Weight Hang Test Axial Pull Test and Horizontal Sheer Test Cable hangers used in communicaton systems are typically subjected to heavy loading and other related stresses. Cable Size Axial Weight Horizontal Sheer lb (kg) lb (kg) 1/2" 18.3 (8.3) 128.8 (58.4) 7/8" 37.1 (16.8) 69.5 (31.5) 1-1/4" 36.3 (16.5) 69.5 (31.5) 1-5/8" 35.6 (16.1) 122 (55.3) The purpose of this test is to verify that the hanger is strong enough to withstand pulling, hoisting and side load shear forces encountered during normal field conditions. The test was performed in accordance with MIL-C-39012C-3.24, 4.6.21. Several samples of SnapStak hangers for 1/2", 7/8", 1-1/4", and 1-5/8" HELIAX cables were applied to fixturing to simulate normal field installation. HELIAX cable sizes LDF4-50A, LDF5-50A, LDF6-50, and LDF7-50A from standard production runs were pulled through the hangers to measure the hanger's ability to support the cable weight, with a high margin of safety. A Tinius Olsen Super L Force Machine was used in the load range of 0 to 1200 pounds. The hangers were also mounted in the horizontal plane to plates having thicknesses of 0.120" to 0.150". They were pulled axially to simulate a side load shear. SP50348 22 October 2001 Page 2 of 6

Virgin Return Loss (RL) and Time Domain Reflection (TDR) were recorded for each nine-foot cable sample. Then RL and TDR measurements were recorded after the application of each hanger, and one 90-degree bend to simulate normal field bending. Final RL and TDR measurements were recorded and plotted against the initial measurements. Test results, listed below, indicate no TDR impacting of the cable greater than that of a normal field bend (90 degrees) and no significant decrease in return loss performance of the cable. Return Loss and TDR setup. Notice hangers applied, and 90 bend in cable. Photo is for setup only. Return Loss and TDR Impact Test The purpose of this test is to verify that the SnapStak hanger, when properly mounted to a mounting structure, will not have any adverse effect on the electrical performance of the coaxial cable. This test was performed in accordance with Test Procedure 04AS00-01. SnapStak hangers were attached, at 16-inch intervals, on nine foot lengths of 1/2", 7/8", 1-1/4", and 1-5/8" HELIAX coaxial cables from standard production. An HP8753E Vector Network Analyzer, with a 1-port calibration, was used to record measurements. Return Loss Results Test Worst Case RL Condition at 6 GHz, db Null State -17.4 2 Hangers Applied -17.3 5 Hangers Applied -17.3 5 Hangers Applied and 90 Bend -17.7 The graph below was output directly from the MathCAD program. It details the TDR effects of the L4 SnapStak Hangers on a length of LDF4-50A cable. The upper trace is the TDR measurement with five L4 SnapStak hangers applied. Notice there is no significant impact. The lower trace is the same length of cable with the same five hangers applied, but with one 90 bend (normal field installation bend). Notice that the bend in the cable impacts the cable greater than that of the application of the hangers. Delta Plot of Voltage Reflection Coefficient for LDF4 cable sample with four L4 SnapStak hangers vs. LDF4 cable sample with one 90 bend, at 6 GHz 0.0045 delta_l44ht6 k0, delta_l4b1t6 k0, 0.003 0.0015 0 Cable Bend 0.0015 0.003 2 0.38 2.75 5.13 7.5 9.88 12.25 14.63 17 Time k SP50348 22 October 2001 Page 3 of 6

SnapStak hangers successfully passed all criteria required for high-speed wind survival. After exposures to wind tunnel speeds of 150 mph, the hangers did not release from the mounting structure and showed no signs of fatigue, fracturing, or deforming. The coaxial cable did not slip from hangers and the hanger cable grips did not penetrate the cable jacketing. Wind Tunnel Test in progress. Wind speed 150 mph Wind Tunnel Testing High winds are the most damaging forces that SnapStak hangers will be exposed to in a typical wireless communication system. This test evaluates the SnapStak hanger's ability to survive these conditions. SnapStak hangers were set in three and two stack configurations. Three sets of stacked hangers were attached to a fixture using 0.750" mounting holes, a wall thickness of 0.120" and 3 foot (1 meter) spacing. Seven foot lengths of 1/2", 7/8", 1-1/4", and 1 5/8" coaxial cable were installed in the hangers. The wind tunnel applied a wind speed of 150 mph in the X plane (direct side load). SP50348 22 October 2001 Page 4 of 6

Thermal Shock Extreme and rapid temperature change is common at wireless communications sites, such as when a hot summer day produces a thunderstorm that rapidly cools the site infrastructure. Tests were performed on SnapStak hangers to measure the effects, if any, of high and low temperatures extremes on the Snapstack hangers. SnapStak hangers were attached to standard production HELIAX coaxial cable in sizes 1/2", 7/8", 1-1/4", and 1-5/8" and exposed to thermal shock testing in accordance with standards: 04AS00-03-4.0, original revision and MIL-STD-202F, Method 107G. Samples were subjected to 25, one-hour cycles between the temperatures of +85 C and -55 C. Vibration setup in Y plane. Hangers in 3-out configuration Vibration Testing Vibration testing is performed to ensure extreme mechanical vibration induced on the cable and hanger system by winds will have no adverse affect on SnapStak hangers or the cable they are supporting. During and after the test, there was no evidence of cable loosening from hangers. Axial pull out forces averaged 11.8 ft-lb at initial slip, and 18.3 ft-lb over corrugated crests of cable. SnapStak hangers were mounted to the vibration test fixture with 3 foot (1 meter) spacing via adapter blocks with 0.750" inch (19mm) holes. Standard production HELIAX cable in 1/2" and 7/8" sizes was mounted in a three-stack configuration and 1-1/4" and 1-5/8" sizes in a two-stack configuration. To test normal variation in the thickness of the mounting structure, two sets of mounting blocks were 0.120" in material thickness and two sets were 0.150" thick. Varying wind directions and velocities were simulated in a four-hour sweep test in both X and Y planes with frequencies ranging from 10 to 2000 Hz. Maximum displacement was 0.65 inches at 10-55 Hz and acceleration was 6 Gs. During the four-hour test cycle, SnapStak hangers did not release from each other or the 0.750" (19mm) mounting blocks. HELIAX cable did not slip from the hanger and the hanger cable grips did not penetrate the cable jacketing to the point of making contact with the copper outer conductor. Close inspection of the hangers showed no signs of fatigue, fracturing, or deformation. SP50348 22 October 2001 Page 5 of 6

Results - L4 SnapStak Hangers after Corrosion Test. No effect Corrosion Coastal areas of the world are most prone to suffer the effects of salt spray. Any product that is to be used in these locations must be prepared to deal with the severe environmental effects. For this reason, the Snapstak hangers are made from stainless steel. To evaluate the suitability of the SnapStak hanger, several samples were placed in a salt fog chamber in accordance with MIL-STD-1344A, Method 1001.1. The hangers were exposed to a 5% salt solution with a PH between 6.5 and 7.2 at temperatures between 93 F and 97 F. After 96 hours of exposure, the hangers showed no signs of rust, oxidation, corrosion, cracking or degradation in any way. SP50348 22 October 2001 Page 6 of 6