Read and understand this manual for safely usage.

Similar documents
Thank you for purchasing SEIKO SHOOTING TIMER KT-401. Before using your SEIKO SHOOTING TIMER, please read this manual carefully for its proper use

Digital Indicating ORP Meter AER-101-ORP. Instruction Manual

TRF STEP-DOWN TRANSFORMER USER MANUAL

Installation Guide VL-MV10. Model No.

Colour Explosion Proof Video Camera USER MANUAL VID-C

Single Point Flow Monitor SW118 SW119

User s Manual Model WF100 Extension Cable for EXA100

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

CHECK LINE. Model LS-36-LED. Stationary Stroboscope. Operating Manual BY ELECTROMATIC

ZN-PD-SA. Air Particle Sensor. Continuously monitor dust fallout and particles which detract from product quality. Ordering Information.

Cylindrical Photoelectric Sensor CY-100 SERIES

Model Number Structure

GC61 Digital Pressure Gauge. Operation Manual

In-Ceiling Electric Motorized Front Projection Screen Evanesce Series. User s Guide

LED Thunder S-150 Code 1097

TC Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) User's Manual

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

Circulating Feed Delivery System Installation Instructions for Model 55, 75, 90, & HMC FLEX-AUGER Feed Delivery Systems

USER S MANUAL. FX2N-8AD Analog input block

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

LED Beam Moving Head. TWIST-150LED Order No INSTRUCTION MANUAL

User Manual. Tensioned Screens. Website: Tel:

Circulating Feed Delivery System Installation Instructions for Model 55, 75, 90, & HMC FLEX-AUGER Feed Delivery Systems

4 Wiring Brochure Wiring and installation of specific control

AP-40. AP-40 Series Features Industry s smallest-sensor head Ultra lightweight High-speed response Two-color LED digital pressure display

Solid-State Digital Timer

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

Gear Pump Units For single-line centralized lubrication systems

USER MANUAL. DE-1 Police-light. CAUTION! Keep this device away from rain and moisture! Unplug mains lead before opening the housing!

ALO 030 MKII. 30 Watt DMX LED scanner. User manual

GC30 Digital Differential Pressure Gauge Operation Manual

Spectra Batten (Order code: LEDJ95)

Indoor/Outdoor Security System with Quad Monitor User s Manual

PEGAS 160 T PULSE HF PEGAS 200 T PULSE HF

May result in personal injury or property loss. Indicate the behaviors that must be prohibited

Kramer Electronics, Ltd. USER MANUAL. Model: VM Video Component Distributor

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0,35 % FSO. Nominal pressure

estat20 Electronic Humidistat with remote sensor head Technical data Electrical data Humidity Temperature +125 C

Winch Adjustable Feed Level Tubes for the Adult Turkey Feeder Installation & Operator s Instruction Manual MF /99

User Manual TL-TP70-HDIR 70m Extender with ARC and IR All Rights Reserved Version: TL-TP70-HDIR_180723

DH551C/DH550C/DL550C Double Sided Display User Manual

Warner Photoscanner MCS-500 Series LED Photoelectric Control

Instructions. P MHz 1X/10X Passive Probe

KRF EMC Filters Installation, Operation and Maintenance Manual

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

Inductive sensor. 2-wire, analog output BI8-M18-LI-EXI

Installation Manual SaVi Note Underwater LED Light

ARS x4 MATRIX SWITCHER Instruction Manual

DMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial

User Manual PS-684. HDBaseT Extender Kit 70m. All Rights Reserved. Version: UHBT70P_2016V1.2

USERS GUIDE MCX-HTS. HDMI to 3G SDI Converter. Manual Number:

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

Operating instructions

General Specifications

T10 Float Level Switch

Mechanical flow switch for On/Off control

Model PSKIT-H540 Ultrasonic Power Supply Kit 40 khz 500 Watts

ELECTRICAL. DATA AND INDEX Not all complements shown A shown for reference. Index A leads B, CW (from shaft end) TERMINAL CONNECTIONS COM VCC CASE

ELECTRICAL SAFETY INSPECTION REPORT

LED Spere Direct Control 30 ORDERCODE 41125

01. Stay safe. Privacy information

DLP200M 2 Relay Module for Heating and Cooling Plants

SmartMix Manual V5350A

DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. accuracy according to IEC 60770: 0.5 % FSO.

Installation Manual Original Instructions - IW4001

Capacitance Limit Detection nivotester FTC 420/421/422

led port-a-cube CT-LLED CT-SLED INSTRUCTIONS

DMP 331 DMP 331. Industrial Pressure Transmitter. for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial. tri-matic.

DMP 339. Pressure Transmitter. with G ¼" flush diaphragm. Pressure Transmitter. Industrial. accuracy according to IEC 60770: 0.

Instruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER

MAXX BOX. MX102/202 Series. MAXX Box

CSA x2 Alarming RS-232 Seq. Video Switcher. Instruction Manual

DIGITAL TIME CLOCK. used with the Meal-Time Control Panel. AGRI-TIME TM Control Instruction Page 1

Electric Wall/Ceiling Projection Screen Saker Series User s Guide

VK-P10SE WARRANTY REGISTRATION FORM

DLP600M 6+1 Relay Module for Heating and Cooling Plants

User Manual TP70L. HDBaseT Extender. All Rights Reserved. Version: TP70L2016V1.1

Sentronic PLUS Electronic Pressure Regulator. Installation Manual

User Manual TL-2X1-HDV 2x1 HDMI & VGA Switcher All Rights Reserved Version: TL-2X1-HDV_160630

EGM Einthoven Goldberger Module Type 701

LIGHT COPILOT II. elationlighting.com Internet:

LCD Thermometer / Clock S No. 1253

USER INSTRUCTIONS MODEL CSI-200 COAXIAL SYSTEM INTERFACE

Electric Wall/Ceiling Projection Screen Saker Tab-Tension Series User s Guide

CS x1 RS-232 Computer Controlled Video Switcher. Instruction Manual

MANUAL ENGLISH Core Club Ordercode: D2314

General Specifications

ACCESSORIES MANUAL PART NUMBER: PRODUCT REVISION: 1 PNP202. Interconnect Box USER'S GUIDE

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Utility Amplifier GA6A Model

HDOB-ELS5IR28A. 5MP 4-in-1 Bullet Security Camera

TVAC20000 User manual

Contents. Instruction Manual T-Rex Page 2 of 16 Release 1.01

User Manual TL-2X1-HDVC 2x1 HDMI & VGA Switcher with Control All Rights Reserved Version: TL-2X1-HDVC_160630

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

User Instructions. 16 SCB Sync Station.

Owner s Manual. Backup Monitor System. LCD Monitor & CCD Color Camera

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

LED Driver Linear / area fixed output

User Manual TPHD-BYE. HDBaseT Extender Set 70m. All Rights Reserved. Version: TPHD-BYE_2014V1.0

Transcription:

TS02-0184 INSTRUCTION MANUAL FOR ELECTRODE LEVEL SENSOR MODEL:CE

Read and understand this manual for safely usage. This manual describes the product of standard specification. Read the other manual for the product of explosion-proof specification. This manual describes the handling, inspection and adjustment of the product which model is mentioned on cover page. Read and understand this manual before handling. Follow the additional document and/or direction, submitted by NOHKEN INC. and our distributor or agent, even if the terms are mentioned in this manual. Save this manual in proper place being available to refer immediately. The specification of product mentioned in this manual may not be satisfied by the condition of environment and usage. Check and consider carefully before using. Contact to sales office at NOHKEN INC. for any question or comment about this manual and product. The followings are the description of the terms in this manual. Indicates a potentially hazardous situation which, if not pay WARNING attention, could result in death, serious injury or serious disaster. CAUTION Indicates a hazardous situation which, if not pay attention, may result in minor or moderate injury or damage to device. Indicates prohibited matter. The explanation with this mark shall be followed Indicates instructed matter. The explanation with this mark shall be followed. -ADD 1 -

WARNING This product is not explosion-proof construction. Do not install this product to the place where the flammable gas or vapor is occurred. If installed, the flammable gas or vapor may be ignited, and serious disaster may be occurred. Use the product of explosion-proof construction in this case. Do not modify or disassemble the product. Otherwise, the product and connected device may be malfunctioned, damaged, fired, or miner injury and electric shock may be occurred. (Follow the additional document and/or direction, submitted by NOHKEN INC. and our distributor or agent.) Turn off the power, before wiring and inspection. Otherwise, electric leakage, fire caused by short circuit, and electric shock may be occurred. Ensure the wire is properly connected. The product and connected device may be malfunctioned, damaged, fired, or miner injury and electric shock may be occurred by improper wiring. Turn off the power immediately, if the smoke, strange smell and sound are occurred. Do not use it until the problem is solved. CAUTION Avoid shock and rough handling to this product. The product may be damaged by shock as dropping, falling, throwing, knocking, lugging, and etc. Follow the specification of operating temperature, operating pressure, switch rating, and etc. Otherwise, the product and connected device may be malfunctioned, damaged, fired, or miner injury and electric shock may be occurred. Check the manual or specification sheet. Operation test shall be done before practical usage. If the serious accident is expected to occur by malfunction of product, the other operating principle of product shall be installed in parallel. -ADD 2 -

CAUTION Check and deeply consider the chemical compatibility for material of product in advance. Hold the stem very close to mounting point, when carrying, installing, and removing. If hold the terminal box, it may be taken off from the flange or plug, and the product may be damaged by dropping. -ADD 3 -

INTRODUCTION A) This manual specifies the specification of general product. If you order special product, some details of specification may be different with the manual. B) We are glad to suggest and advice for Model selection and chemical resistant of material, but final decision has to be made by the customer. C) This manual has prepared with close attention. Ask sales office at NOHKEN INC. for any question or comment about the contents of this manual. D) For replacement parts The quality of product has frequently improved, so same spare part may not be supplied. In this case, replacement part or product may be supplied. Ask sales office at NOHKEN INC. for details. E) The contents of this manual are subject to change any time without notice due to the improvement of product. WARRANTY & DISCLAIMER A) NOHKEN INC. warrants this product against defect in design, material and workmanship for a period of 1(one) year from the date of original factory shipment. B) The warranty only covers the damage of products. The secondary and third kind disasters are not covered by NOHKEN INC. C) NOHKEN INC. shall not be liable for the following. C-a) Do not follow the description and direction in this manual. C-b) Damage due to improper installation, wiring, usage, maintenance, inspection, storing, and etc. C-c) Repair and modification are done by the person who is not employee of NOHKEN INC. and our distributor or agent. C-d) Improper parts are used and replaced. C-e) The damage is occurred by the device or machine except our products. C-f) Improper usage. (See "Proper of usage" in chapter 1 in this manual) C-g) Force Majeure including, but not limited to, fire, earthquake, tsunami, lightning, riots, revolution, war, radioactive pollution, acts of God, acts of government or governmental authorities, compliance with law, regulation, and order. THE TERMS OF WARRANTY AND DISCLAIMER SHALL IN NO WAY LIMIT YOUR REGAL LIGHT. -ADD 4 -

TABLE OF CONTENTS Page No. 1. PURPOSE OF USE 1 2. SPECIFICATIONS 1 2.1 Model and Suffix Code 1 2.2 Specifications 2 2.3 Dimensions 3 3.PRINCIPLE OF OPERATION 4 4.COMPONENTS NAMES 5 4.1 Component Names of Sensor 5 4.2 Component Names in Terminal Box 5 4.3 Component Names of Relay Unit 5 Page No. 5.4 Installation of Sensor 8 5.5 Installation of Relay Unit 9 6. WIRING 9 6.1 Cable inlet 9 6.2 Sensor Wiring 10 6.3 Wiring Diagram 10 7. TECHNICAL NOTE 13 8. INSPECTION / MAINTENANCE 13 9.TROUBLESHOOTING 14 5. INSTALLATION 6 5.1 Unpacking 6 5.2 Sensor Assembly 6 5.3 Installation location 8

1. PURPOSE OF USE This Cable Type Electrode Level Sensor is designed to measure for conductive liquid level, and prevent erroneous operation due to shot-circuit between electrodes compared with Electrode Type Level Sensor. Because of PVC body(outer insulation), it is difficult for short-circuiting to occur. This sensor will be used for conductive liquid where freezing can occur or for deep well use. Cable can be cut required length. This system consists of the sensor (model CE series) and the plug-in relay unit(model RE7 00 series). This system will controls the liquid level in tank. 2. SPECIFICATIONS 2.1 Model and Suffix Code (1) Detector (Exclude mounting parts) CE- Code Electrode Material 5 316 Stainless Steel 6 NW0001/NW0665 (Hastelloy B or equivalent) 7 NW0276 (Hastelloy C or equivalent) 8 Titanium (2) Sensor(Include mounting parts) CE - Number of detecting points 1 to 6 Select number of detecting points required. Code Electrode Material 55 316 Stainless Steel 66 NW0001/NW0665 (Hastelloy B or equivalent) 77 NW0276 (Hastelloy C or equivalent) 88 Titanium (3) Relay unit RE7 00 Code Sensitivity 0 Standard 1 High sensitivity 5 Two points - 1 -

2.2 Specifications (1) Detector Model CE-5 CE-6 CE-7 CE-8 Measuring object Conductive Liquid Allowable temperature -20 to +50 Material Body PVC 316 NW0001/NW0665 NW0276 Electrode Stainless (Hastelloy B *1 (Hastelloy C *1 Titanium Steel or equivalent) or equivalent) Cable PVC Sheath (VCTF 0.5 mm 2 2 cores) Mass Body Approx. 0.6 kg (Include cable 6 m) Cable 65 g/m (2) Sensor Model CE-55 CE-66 CE-77 CE-88 Measuring object Conductive liquid Allowable temperature -20 to +50 Construction IP 45 Electrode withstand pressure 200 kpa Max. Flange size JIS10K100A or equivalent (Proviso 4 holes) Material Terminal box ABS Flange PVC Body PVC 316 NW0001/NW0665 NW0276 Electrode Stainless (Hastelloy B *1 (Hastelloy C *1 Titanium Steel or equivalent) or equivalent) Cable Anchor weight Rope Clip PVC Sheath (VCTF 0.5 mm 2 2 cores) PVC (Built-in Steel Structure) Mass Mounting part Approx. 1.6 kg (Include terminal box, Flange) Cable inlet Body Approx. 0.3 kg (Include cable 1 m) Cable Anchor weight PE PVC 65 g/m Approx. 3 kg G 3/4 or equivalent Note *1 : Registered trademark of Mitsubishi Metal Corporation. - 2 -

(4) Relay Unit Model RE7000 RE7100 RE7500 Standard High Allowable temperature 0 to +50-10 to +55 Allowable humidity 85% RH Max. (Get rid of dew) Operating display(output) LED(Red) LED(Red) LED(Green) Operating resistance 4 kω or less 50 kω or less 3 kω or less 30 kω or less Reset resistance 15 kω or more 100 kω or more 11 kω or more 220 kω or more Power source to sensor 8 V, 5 ma AC Max. 12 V, 5 ma AC Max. Power supply 90 to 132 / 180 to 264 V AC, 50/60 Hz Power consumption 1.5 VA Max. 2 VA Max. Output signal Relay contact (S.P.D.T.) Relay contact Contact rating 240 V 5 A AC, 30 V 5 A DC (With resistive load) 250 V 3 A AC, 30 V 3 A DC (With resistive load) Wiring distance between sensor and relay unit 1 km Max. 100m Max. 1 km Max. 100m Max. Dimension Installation method Socket Mass W50mm H84mm D109mm Plug-in Option (Manufacturer: OMRON, Model:11PFA or equivalent) Approx.280g 2.3 Dimensions (1) Dimension of detector and sensor Dimension of detector Dimension of sensor Fig. 1-3 -

(2) Dimension of relay unit Dimension of relay unit Fig. 2 3. PRINCIPLE OF OPERATION Low AC voltage applied between electrodes, his system used to control functions such as latching for pump control or alarm setpoints. AC voltage is utilized to prevent electrical corrosion. Fig. 3-4 -

4. COMPONENT NAMES 4.1 Component Names of Sensor Fig. 4 4.2 Component Names of Terminal box Fig. 5 4.3 Component Names of Relay Unit Front panel 1 Power lamp 2 Relay operating lamp 3 Select switch 4 Sensitivity setting switch Fig. 6-5 -

5. INSTALLATION 5.1 Unpacking This unit has been thoroughly inspected and carefully packed at the factory to prevent from damage during shipment. When unpacking, care must be taken not to damage the instrument with mechanical shock. After unpacking, visually check the instrument exterior for damage. NOTE the following points: (1) During unpacking, care must be taken not to damage cables with sharp object. (2) Cable must be kept from vending forcefully during unpacking or carrying. (3) Be sure that the parts such as clip, rope and anchor weight are attached correctly. 5.2 Sensor Assembly Usually, the cable type electrode level sensor is set specified length before shipment. When not specified, each parts are packed separately. When that case, assemble this sensor to required measuring length. 5.2.1 Assembly procedure Proceed as follows: (1) Tie one end of rope to the eyebolt on flange, and another end of rope to the anchor weight in accordance with tank depth. (2) Remove the terminal box cover. (3) Pass the cables into terminal box through the boss located on flange. (4) Put the fixing gasket and the bushing into the cable. (Refer to Fig. 7) Fig. 7-6 -

(5) Set the detector with the clip in accordance with required measuring length. (Refer Fig. 8 and Fig. 9) (6) Bundle the cable and rope with band.(refer to Fig. 9) Fig. 8 Fig. 9 NOTE : Setting length must be kept following Fig. 10. Fig. 10 (7) Tighten the bushing securely. (8) Cut the useless part of cables. (9) Install solderless lugs fitted M3.5 screw to end of lead wire. NOTE : The outline of diameter of solderless lugs must be used 7 mm or less. (10) Connect each lead wires to the terminals.(refer to Fig. 11) (11) Reinstall the terminal box cover. - 7 -

Fig. 11 5.3 Installation Location This level sensor should be installed in an area where the following conditions: (1) Provide ample space for maintenance/inspection. (2) Low relative humidity and no exposure to moisture. (3) No corrosive gases. (Such as NH 3, SO 2, Cl 2 etc) (4) No excessive vibration. 5.4 Installation of Sensor This Level sensor installation method depend on flange type. (See Fig. 12) Fig. 12 NOTE the following points: (1) This sensor should be installed in an area where the ambient temperature range is -20 to 50. CAUTION Install a sun shield over the terminal box if temperature is high. Provide appropriate means to guard against moisture if temperature is low. Otherwise, the sensor may be damage. - 8 -

(2) Keep this sensor out of the direct flow of liquid. Failure to do this may cause the sensor to break. If necessary, install a baffle in order to divert the liquids. (3) Locate the sensor keep away from inlets or outlets, where excessive turbulence may exist. If necessary, install a stilling tube in order to divert the liquids. CAUTION During installation, care must be taken not to damage cables with sharp object. 5.5 Installation of Relay Unit This relay unit installation method depend on plug-in type. The socket (Manufacturer: OMRON, Model:11PFA or equivalent) must be prepared to install the relay unit. The socket for relay unit is option. 5.5.1 Installation of Socket (1) Wall installation (2) Rail installation Use the DIN rail (35mm). 6. WIRING 6.1 Cable inlet The size of the cable inlet is G 3/4. There are two ways for connecting the sensor cable. One is fixing the cable with a cable gland. The other is connecting a conduit to the housing. In either case, an adequate sealing should be provided to prevent water or dust ingress into the housing through the sensor cable. Secure the cable using sealing material for the conduit connection, or a proper tool when the gland is used, to protect the housing inside from dust or water. When water or moisture comes into the housing from the conduit, use putty to fill the inside of the conduit. - 9 -

6.2 Sensor Wiring Proceed as follows: (1) Remove the terminal box cover. (2) Bring the cable into the terminal box. (3) Connect the cable to the terminals as shown Fig. 13. (4) Make sure that there are no miswiring. (5) Reinstall the terminal box cover. (6) The cable inlet must be protected the sensor from rain splashing water and so on. Fig. 13 6.3 Wiring Diagram 6.3.1 Wiring diagram for high or low level alarm (see Fig. 14). (1) High level alarm (SELECT. SW.: H. ON side) (a) When the liquid level reaches detecting point, relay energize. (b) When the liquid level falls below detecting point, relay de-energize. (2) Low level alarm (SELECT. SW.: L. ON side) (a) When the liquid level falls below detecting point, relay energize. (b) When the liquid level reaches detecting point, relay de-energize. Fig. 14-10 -

6.3.2 Wiring diagram for latching (inflow or outflow control) (See Fig.15) (1) Outflow control (SELECT. SW. :H.ON side) (a) When the liquid level reaches upper detecting point, relay energize. (b) When the liquid level falls below upper detecting point, relay energize. (c) When the liquid level falls below lower detecting point, relay de-energize. (d) When the liquid level reaches lower detecting point, relay de-energize. Fig. 15 (2) Inflow control (SELECT. SW. :L. ON) (a) When the liquid level falls below lower detecting point, relay energize. (b) When the liquid level reaches lower detecting point, relay energize. (c) When the liquid level reaches upper detecting point, relay de-energize. (d) When the liquid level falls below upper detecting point, relay energize. WARNING Earth terminal 4 shall be grounded. If it is not grounded, you will get an electric shock. - 11 -

6.3.4 Model RE relay unit We recommend the use of our relay unit model RE. It is single level (alarm) and / or dual level (empty/fill control) relay. The latching (holding relay) feature allows pumps, valves and other devices to be turned on at one level and off at another. It also contribute to safety since it allows lower voltage and smaller currents to be used with sensor. Fig. 16 For the relay unit Model RE, refer to Instruction Manual. NOTE the following points: (1) Do not connect the plural relay unit to identical switch. Otherwise, the relay unit may be malfunction. Fig. 17-12 -

(2) Power supply must be connected in phase. Fig. 18 (3) To avoid malfunction, the wiring distance should be used within specifications. If the wring distance exceed specifications, the relay unit may be malfunction by stray capacitance between cables or noise. 7. TECHNICAL NOTE (1) This relay unit can not detect the level of non-conductive liquids, such as oil, gasoline, and distilled water. (2) Inside of level sensor and relay unit shall be kept free from rain, splashing water, liquid, dust, dirt, metallic substances, and any other foreign matter. (3) This products must be stored in a dry, warm place where condensation of humidity will not occur. 8. INSPECTION/MAINTENANCE The following annual servicing tasks should be carried out on the sensor and relay unit. (1) Remove the sensor from tank carefully. (2) Ensure there is no damage. (3) If sediment or other foreign matters are stained between electrodes, clean the electrode in detector. (4) Make contact between electrodes, and check the relay unit operation. (5) Spare parts should be ordered from NOHKEN Inc. whose address appears on the title page. - 13 -

9. TROUBLESHOOTING Use the following chart to troubleshoot a malfunctioning. Problems Possible causes Remedies Relay unit de-energize Setting for improper length of detectors Miswiring between sensor and relay unit Short-circuit between electrodes Insulation failure Affection by stray capacitance Loosing terminal screws Affection by deposit or oil film Install in improper stilling tube Set for improper select switch (SELECT. SW.) mode of relay unit Adjust the proper measuring length Ensure the wiring correctly Clean electrodes in detector Check the insulation Re-wire as short as possible Tighten terminal screws Clean electrodes in detector Drill vent holes in the stilling tube Change the select switch mode(h ON/L ON). Relay chatter Loosing terminal screws Tighten terminal screws Miswiring between sensor and relay Ensure the wiring correctly unit If above remedies are unsuccessful, ask NOHKEN Inc. to repair and replace. - 14 -

HEAD OFFICE : 15-29,Hiroshiba-cho,Suita-city,Osaka 564-0052,Japan. TEL:06-6386-8141 FAX:06-6386-8140 TOKYO BRANCH OFFICE : 67,Kandasakumagashi,Chiyoda-ku,Tokyo 101-0026,Japan. TEL:03-5835-3311 FAX:03-5835-3316 NAGOYA OFFICE : 3-10-17,Uchiyama,Chikusa-ku,Nagoya-city,Aichi 464-0075,Japan. TEL:052-731-5751 FAX:052-731-5780 KYUSHU OFFICE : 14-1,2-chome,Asano,Kokurakita-ku,Kitakyushu-city,Fukuoka 802-0001,Japan. TEL:093-521-9830 FAX:093-521-9834