Airborne sound insulation between two cinemas

Similar documents
Is INTERNATIONAL STANDARD. Acoustics - Measurement of the in sifu sound attenuation of a removable screen

Acoustics of new and renovated chamber music halls in Russia

REPORT issued by an Accredited Testing Laboratory

Coopers Gap Wind Farm AGL Energy Ltd 23-Aug-2016 Doc No AC-RP-02- Facade Sound Insulation Test Report

CEA Bulletin. Home Theater Recommended Practice: Audio Design CEA/CEDIA-CEB22

ISO/IEC INTERNATIONAL STANDARD. Information technology Office equipment. Technologies de l'information Équipements de bureau

Sound Insulation Reporter

Acoustic concert halls (Statistical calculation, wave acoustic theory with reference to reconstruction of Saint- Petersburg Kapelle and philharmonic)

JOURNAL OF BUILDING ACOUSTICS. Volume 20 Number

ISO INTERNATIONAL STANDARD. Digital cinema (D-cinema) quality Part 1: Screen luminance level, chromaticity and uniformity

DIGITAL IMMERSIVE GIANT SCREEN SPECIFICATIONS (DIGSS) V 2.0 January 2018

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER Acoustical Design of New Concert Hall in Mariinsky Theatre, St.

REPORT NO CRT-001h SOUND OUTPUT MEASUREMENTS ON SIX INVERTER GENERATOR SAMPLES RENDERED TO

THE EFFECT OF PERFORMANCE STAGES ON SUBWOOFER POLAR AND FREQUENCY RESPONSES

The TASA Standard (Updated 2013)

CINEMA MARKET PROMO VERSION MARKET STATISTICS OF THE RUSSIAN FILM INDUSTRY BY NEVAFILM RESEARCH AND RUSSIAN FILM BUSINESS TODAY

Sound insulation of open Supply Air Windows, comparing laboratory and field measurements

Audio Engineering Society Conference Paper Presented at the 21st Conference 2002 June 1 3 St. Petersburg, Russia

Laminated Glass. Sound Control. Where glass becomes architecture Section Introduction

Preferred acoustical conditions for musicians on stage with orchestra shell in multi-purpose halls

A Real Word Case Study E- Trap by Bag End Ovasen Studios, New York City

A Real Word Case Study E- Trap by Bag End Ovasen Studios, New York City

FC Cincinnati Stadium Environmental Noise Model

CEA Standard. Standard Definition TV Analog Component Video Interface CEA D R-2012

BACHELOR THESIS. Placing of Subwoofers. Measurements of common setups with 2-4 subwoofers for an even sound

Comparison of Low Frequency Sound Insulation Field Measurement Methods

Noise evaluation based on loudness-perception characteristics of older adults

Calibration of auralisation presentations through loudspeakers

NOTICE. (Formulated under the cognizance of the CTA R4.8 DTV Interface Subcommittee.)

The influence of the stage layout on the acoustics of the auditorium of the Grand Theatre in Poznan

Investigation into Background Noise Conditions During Music Performance

Methods to measure stage acoustic parameters: overview and future research

INSTRUCTION SHEET FOR NOISE MEASUREMENT

Standard Definition. Commercial File Delivery. Technical Specifications

Statement Of Results For Sound Transmission Loss Tests Performed By Acoustics Laboratory At RMIT University On Behalf Of Polyphen.

Hybrid active noise barrier with sound masking

ROOM LOW-FREQUENCY RESPONSE ESTIMATION USING MICROPHONE AVERAGING

Theater Sound MAE 5083

MANAGING NOISE IMPACTS IN BRISBANE S FORTITUDE VALLEY ENTERTAINMENT PRECINCT

What is the minimum sound pressure level iphone or ipad can measure? What is the maximum sound pressure level iphone or ipad can measure?

Comparison between Opera houses: Italian and Japanese cases

Underwater Noise Levels

FAR Part 150 Noise Exposure Map Checklist

ISO The pros and cons in a nutshell. Iain Critchley MIOA

2.0 SOUND SOURCES AT PINE RIDGES INLAND CLAMSHELL OPERATION AREA

Why Movies Are Not Too Loud

Acoustics in wooden buildings Correlation analysis of subjective and objective parameters

Sidney Myer Music Bowl Noise Management Plan. November 2016

FCC Part 15 Subpart B Test Report. FCC PART 15 Subpart B Class B: 2014

2018 GUIDE Support for cinemas

FC Cincinnati Stadium Environmental Noise Model

Chapter 10. Lighting Lighting of Indoor Workplaces 180

SMPTE STANDARD Gb/s Signal/Data Serial Interface. Proposed SMPTE Standard for Television SMPTE 424M Date: < > TP Rev 0

INTERNATIONAL STANDARD

Binaural Measurement, Analysis and Playback

CLASSROOM ACOUSTICS OF MCNEESE STATE UNIVER- SITY

Trends in preference, programming and design of concert halls for symphonic music

FLOW INDUCED NOISE REDUCTION TECHNIQUES FOR MICROPHONES IN LOW SPEED WIND TUNNELS

INTERNATIONAL STANDARD

Concert halls conveyors of musical expressions

IS0 TR l TECHNICAL REPORT. Acoustics - Recommended practice for the design of low-noise machinery and equipment - Part 1: Planning

Procedia - Social and Behavioral Sciences 184 ( 2015 )

Music Source Separation

The z-cl6 Six-Channel Mastering Dynamics Processor

Early and Late Support over various distances: rehearsal rooms for wind orchestras

D. BARD, J. NEGREIRA DIVISION OF ENGINEERING ACOUSTICS, LUND UNIVERSITY

Sound Level Measurements at Dance Festivals in Belgium

StepArray+ Self-powered digitally steerable column loudspeakers

The acoustics of the Concert Hall and the Chinese Theatre in the Beijing National Grand Theatre of China

FOR IMMEDIATE RELEASE

Getting Started with the LabVIEW Sound and Vibration Toolkit

EXPLANATION OF MRL CATALOG NUMBERS

DSP Monitoring Systems. dsp GLM. AutoCal TM

Official Journal L 191, 23/07/2009 P

Mapping Document. Issue date: 27 February 2014

INTERNATIONAL STANDARD

Colour Matching Technology

THE RESEARCH COMMITTEE FOR TOTAL ENERGY THE ENERGY CONSERVATION STANDARDS WORKING GROUP SUMMARY OF FINAL CRITERIA

Project: IEEE P Working Group for Wireless Personal Area Networks (WPANs)

THOUGHTS ON EQUALIZATION

Visual Color Matching under Various Viewing Conditions

Loudness and Sharpness Calculation

Roadway/Structure Widening Project MP A30.30 to MP A Lansdale Montgomery County, PA NOISE ANALYSIS REPORT FINAL. August 2006.

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.


THE VIRTUAL RECONSTRUCTION OF THE ANCIENT ROMAN CONCERT HALL IN APHRODISIAS, TURKEY

AUDIO FOCUS We delve into the world of audio, with products and projects all featured in our first focus.

CHARACTERIZATION OF END-TO-END DELAYS IN HEAD-MOUNTED DISPLAY SYSTEMS

ISO INTERNATIONAL STANDARD. Digital cinema (D-cinema) packaging Part 4: MXF JPEG 2000 application

Acoustic Camera 2018

User Manual. Model 1372A and 1374A HDMI Switchers. 1T-SX-632 Model 1372A 2X1 Switcher. v1.3 2x1 SWITCHER. v1.3 INPUT ENHANCE POWER

Multiband Noise Reduction Component for PurePath Studio Portable Audio Devices

APPENDIX O RECOMMENDED GUIDELINES FOR AUDIO/VISUAL TECHNOLOGIES (AV TECHNOLOGY) TABLE OF CONTENTS E. CATV... 8 F. SECURITY SYSTEM...

A Matlab toolbox for. Characterisation Of Recorded Underwater Sound (CHORUS) USER S GUIDE

Transporting NV Standardized Testing from the Lab to the Production Environment

Experiments on tone adjustments

BUREAU OF ENERGY EFFICIENCY

The Bapo (horn) Show

MULTI-CHANNEL CALL RECORDING AND MONITORING SYSTEM

THE ACOUSTICS OF THE MUNICIPAL THEATRE IN MODENA

Transcription:

Airborne sound insulation between two cinemas Ilya Tsukernikov Research Institute of Building Physics (NIISF RAABS), Moscow, Russia. Alexander Fadeev Research Institute of Building Physics (NIISF RAABS), Moscow, Russia. Summary The number of cinemas has increased over the past 10-15 years in Russia. The main part of new cinemas is multiplex cinemas in the shopping and entertainment malls. It is mean that in multiplex two cinemas may show the movies at the same time. The problem of airborne sound isolating by a partition/slab between two multiplex cinemas halls is considered. The analysis of the regulatory and technical documents (the International Standard, and the national documents of the Russian Federation, as well as the corporative standards of international cameramen) is done. The levels of penetrating noise through a partition between two cinemas halls are measured for two cinemas. The discrepancy between the estimated sound insulation parameters and the requirements of the current regulatory documents are shown. PACS no. 43.50.Ba, 43.55.Ti 1. Introduction There are more than 4000 operating cinema halls on the territory of the Russian Federation in 2017. Most of them are part of multiplexes. This means that several rooms can be located in close proximity to each other. In the majority of multiplexes, the cinema halls are divided among themselves by a partition, less often by a slab. The acoustic system of the modern cinema hall is characterized by the ability to reproduce high levels in the low frequency range (octave bands with centre frequencies (f с ) 31.5, 63 and 125 Hz). At the same time, as is known from the theory and practice of building acoustics, the sound insulation of airborne noise by a barrier in the low frequency is less than in the middle and high frequencies. That s why operation of two cinemas halls can lead to penetration of the sound of one cinema hall into another, to cause complaints of cinema visitors to penetrating noise. These facts allow us to consider the task of airborne sound insulation of a barrier (partition or slab) between two cinemas in the low frequency as one of the actual problems of building acoustics. This article reviews the current national, international regulatory framework, as well as the standards of enterprises of leading cinema industry operators. The results of field acoustic measurements of the airborne sound insulation by a partition between two cinemas in Moscow are given. Deficit of airborne sound insulation by the partition with respect to the current normative and technical documents is shown, especially in the low-frequency range (octave bands with f c. = 31.5 250 Hz). 2. Regulation by normative and technical documents 2.1. National standards of the Russian Federation On the territory of the Russian Federation, there is the Code of Rules SP 51.13330.2011 [1], the main requirements of which are mandatory for implementation in accordance with the Decree of the Government of the Russian Federation No. 1521 of December 26, 2014 [2]. This document regulates airborne sound insulation between rooms of different purposes. But there is no cinema hall category in [1]. At the same time SP 51.13330.2011 regulates the permissible values of sound pressure levels of penetrating noise for cinemas with Dolby equipment. There are no cinema industry standards in the field of building acoustic today in Russia. We can note the Building Regulations and Rules SNiP II-L.15-68 [3] which was in force from 1968 to 1977. This document limits the levels of penetrating noise below 40 db in octave bands with f c. = 31.5 8000 Hz. However, the revolutionary changes in the cinema industry do not allow it to be used. The positions of [1] and [3] are given in Table I. Copyright 2018 EAA HELINA ISSN: 2226-5147 All rights reserved - 1695 -

Table I. Maximum permissible sound pressure levels of background noise in the cinema hall. Limit sound pressure level, db, in octave band with centre Normative document frequencies, Hz SP 51.13330-2011 [1] 72 55 44 35 29 25 22 20 18 SNiP II-L.15-68 [3] 40 40 40 40 40 40 40 40 40 IMAX [4] (ISO 9568: 1993 [5], SMPTE RP141-1995 [6]) 65 54 44 37 31 27 24 22 21 THX Standard [7] 69 57 48 42 35 31 29 28 27 Table II. Minimum NR levels between two cinema halls. Normative document NR level, db, in octave band with centre frequencies, Hz IMAX [4] 40 55 65 70 70 70 70 70 70 THX Standard [7] 38 48 52 54 66 66 66 66 66 2.2 International and cinema industry documents One of the leading operators of cinema hall industry is IMAX Corporation (Canada). IMAX has an internal document [4], which requires the levels of background noise (from all sources inside or outside the cinema hall), based on the requirements of the International Standard ISO 9568: 1993 [5] and the standard of the Society of Motion Picture and Television Engineers SMPTE RP141-1995 [6]. Document [4] also limits the requirements for minimum noise reduction levels (NR) penetrating to the IMAX cinema hall from another cinema hall. Lucasfilm LTD (USA) is another of leader of cinema hall industry. Lucasfilm LTD has an internal standard THX Standard [7], which regulates the maximum levels of background noise (NC - noise criteria) from all sources inside or outside the cinema hall as NC30 and limits the levels of NR too. The positions of documents [4-7] are given in Table I and minimum NR values are given in Table II. SP 51.13330-2011 [1] has the most stringent requirements for noise penetrating into the cinema hall in the middle and high frequency bands. IMAX document [4] and International Standard [5] and Standard [6] have the most stringent requirements for noise penetrating into the cinema hall in the low frequency bands. These documents have more stringer requirements for noise reduction between cinema halls than Standard [7]. SP 51.13330-2011 has no requirements for external noise reduction. 3. Field measurements of airborne sound insulation in the multiplex (Moscow) Acoustic measurements of airborne sound insulation between two cinema halls were made in August 2017. Considered a couple of cinema halls, separated by a partition. 3.1. Field measurement scheme On the multi-channel acoustic system of the source cinema hall was given a test signal ( pink noise). Sound pressure levels in both cinema halls were measured by sound level meter EKOFIZIKA- 110A (Russia). The sound level meter was installed at a height of 1,2 meter from the floor. Source cinema hall was cinema hall 3 for 207 visitors (volume is 5000 m 3 ). Microphone cinema hall was cinema hall 4 for 197 visitors (volume is 5000 m 3 ). Acoustic measurement scheme is shown in Figure 1. 3.2. Measurement results The measured values of sound pressure levels and normative curves according to Table I are shown in Figure 2. Noise penetrating in the cinema hall 4 exceeds the permissible values of normative technical documents. In the low frequencies range (octave bands with f c = 63 250 Hz) the penetrating noise exceeds the permissible values of all normative documents. In the middle and high frequencies ranges (octave bands with f c. = 500 4000 Hz) the penetrating noise exceeds the permissible values of normative documents [1, 4-6]. - 1696 -

Figure 1. Cinema halls 3 and 4 (situation plan). Figure 2. Sound pressure levels in cinema halls 3 and 4. 100 90 Sound pressure level, db 80 70 60 50 40 30 20 10 0 Octave band with centre frequency, Hz Sound pressure level in Cinema hall 3 Sound pressure level in Cinema hall 4 Background noise in Cinema hall 4 SP 51.13330-2011 [1] SNiP II-L.15-68 [3] IMAX [4] (ISO 9568: 1993 [5], SMPTE RP141-1995 [6]) THX Standard [7] - 1697 -

3.3 NR evaluation The noise reduction by the partition between the cinema halls is determined by the formula: NR = L m1 L m2, (1) where L m1, L m2 are the average values of sound pressure levels in source and microphone cinema halls, db. The results of calculations in octave bands are shown in Figure 3 and compared with the requirements of Table II. Noise reduction, db 80 70 60 50 40 30 20 10 0 Octave band with centre frequency, Hz IMAX Standard [4] THX Standard [7] Measured noise reduction by the partition between cinema halls 3 and 4 Figure 3. Measured noise reduction by the partition between cinema halls 3 and 4. Noise reduction by the partition between two cinema halls does not meet the requirements of IMAX Standard [4] in octave bands with f c = 31.5 8000 Hz. Noise reduction by the partition between two cinema halls meets the requirements of the THX Standard in only one octave band with f c = 8000 Hz. The worst sound insulation is observed in the low-frequency range (octave band with f c = 31.5-250 Hz), were the NR deficit exceeds 26 db in relation to the requirements of IMAX Standard [4] and 20 db in comparison with the requirements of the THX standard [7]. 4. Cinema hall field measurement (Saint Petersburg) The measurements were made in August 2017. The sound pressure levels were measured during the trailer was played (3-5 minutes) in the central part of the cinema hall with volume 1600 m 3. The sound level meter was installed at a height of 1,2 m from the floor. The measurement results are shown in Figure 4. Sound pressure level, db 100 95 90 85 80 75 70 65 60 55 50 31,5 63 125 250 500 1000 2000 4000 800 Figure 4. Measured sound pressure levels in cinema halls. Trailer sound has a pronounced low-frequency character. The sound pressure levels emitted by trailer in octave bands with f c = 31.5 and 63 Hz are more than pink noise signal used in section 3. This fact clearly demonstrates that there is airborne sound insulation deficit in the low-frequency range for this cinema hall too and there is the need to increase the soundproofing properties of the partitions, especially in the low-frequency range. 5. Conclusions Octave band with centre frequency, Hz Сinema hall in Saint Petersburg Cinema hall in Moscow The experimental studies have established deficit of airborne sound insulation by a partition between two cinema halls in relation to the current normative and technical documents. It is shown that the most problematic frequency range is the low-frequency range (octave bands with f c = 63-250 Hz). Field measurements of sound pressure levels in the cinema hall during the trailer sound reproduction confirmed the pronounced low-frequency nature of the emitted noise. This fact shows that increase airborne sound insulation in the low-frequency range by a partition between two cinema halls is actual task of building acoustics. - 1698 -

Acknowledgement The authors are grateful to the staff of the Acoustics Group Company Vokhmyanin M.A., Nechaev A.A. for the results of field measurements (section 3), to the employee of the Acoustics Group Company Karataev S.V. and Nevafilm Company for the possibility of field measurements (section 4), as well as to the management of the Acoustics Group Company for the provided measuring equipment. References [1] SP 51.13330-2011. Noise protection. Updated version of SNiP 23-03-2003, Minregion of Russia, 2010. [2] Decree of the Government of the Russian Federation No. 1521 of December 26, 2014, from http://docs. cntd.ru/document/420243891 [3] SNiP II-L.15-68. Motion Picture Theaters - Design standards, Publishing house of literature on construction, 1968, from http://meganorm.ru/ Index2/1/4294848/4294848810.htm [4] Requirements for monitoring acoustics and noise in IMAX theaters, IMAX Corporation Mississauga, Ontario, September 2002 [5] ISO 9568:1993 Cinematography - Background acoustic noise levels in theatres, review rooms and dubbing rooms, ISO, Geneva, Switzerland, 1993 [6] Society of Motion Picture and Television Engineers, SMPTE RP 141, Background Acoustic Noise Levels in Theatres and Review Rooms (1995) [7] THX tech pages. THX. (2012). Retrieved February 13, 2012, from http://www.cinemaequipmentsales. com/athx2.html - 1699 -

- 1700 -