ArmorPOINT RTD and Thermocouple Input Modules

Similar documents
Backlight Replacement

POINT I/O RTD and Isolated Thermocouple Input Modules

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

STBART0200K standard analog input kit STB - 2 I - 15 bits + sign

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

NI PXI/PXIe-2543 Specifications

Thermocouple and RTD Modules for Compact FieldPoint

SLC Channel Thermocouple/mV Input Module

llen-bradley 194R-HM4-NFPA3

DATA SHEET. The Advantys model STBDAI5260 Digital Input Module provides 2 isolated discrete input points that operate on a 115 VAC power source.

32 Channel CPCI Board User Manual

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

MicroLogix 1200 Thermocouple/mV Input Module

Advantys STB DATA SHEET. Advantys STB Output Module. Description. Features

Fibre Optic Modem ODW-622

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

Trusted 40 Channel 120 Vac Digital Input FTA

LONWORKS Fibre Optic Router

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated)

LONWORKS Fibre Optic Converter

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Fibre optic router for TP/FT-10 LRW-112PP

ODW-621. RS-232 Point-to-point applications

Fibre Optic Modem ODW-611

Trusted 40 Channel 120 Vac Digital Input FTA

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

GuardPLC Certified Function Blocks -- Basic Suite

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES

BL67 electronic module 2 analog inputs for thermoelements BL67-2AI-TC

FP-AI-112 and cfp-ai-112

BNC-2120 INSTALLATION GUIDE. Connector Accessory for Multifunction DAQ Devices

3500/42E Vibration Monitor

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

SignalOn Series. L-Band Power Inserter Module INSTALLATION & OPERATION MANUAL. 1.2 GHz. D3.

SEL-3405 High-Accuracy IRIG-B Fiber-Optic Transceiver

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

USB Contents. Definitions SPECIFICATIONS. RF Power Sensor Device

Filters for Power Lines (Low Leakage Current)

Trusted 40 Channel Analogue Input FTA

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Instructions. P MHz 1X/10X Passive Probe

Specifications. Reference Documentation. Performance Conditions

DVBus and Multiplexer and demultiplexer assemblies for video channels, with bidirectional audio and data USER MANUAL

FOREST SHUTTLE S / L / M RECEIVER

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

WVR500 Waveform/Vector Monitor

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Chromalog T. Technical Information. Paper recorder Mulit-channel strip chart recorder with digital measured value display

Operating instructions

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

PT9420 Cable Actuated Sensor Industrial ma 0..20mA

LC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A V AC 50/60 Hz coil

Industrial Monitor Update Kit

LC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

SIL-2 8-Ch Analog Input Series Thermocouple, High Level, Low Level

DS 400 P. Intelligent Electronic Pressure Switch in Hygienic Stainless Steel Ball Housing. on hygienic process connections

DMP 331 DMP 331. Industrial Pressure Transmitter. for Low Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial. tri-matic.

LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil

I/A Series Hardware Fiber Optic LAN Converter

LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil

R&S RT-Zxx High-Bandwidth Probes Specifications

Series CT7N Bimetallic Overload Relays

MultiView T4 / T5 Transmitter

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

LC1D65AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC 50/60 Hz coil

LC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil

DMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial

DCT 532. Industrial Pressure Transmitter with i²c interface. Stainless Steel Sensor

Digital Input Modules for Compact FieldPoint

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Single output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

LC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil

Installation Instructions Series 9000 DeviceNett PHOTOSWITCHr Photoelectric Sensors

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

Colour Explosion Proof Video Camera USER MANUAL VID-C

DISTRIBUTION AMPLIFIER

Agilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz

LC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil

Process Transmitter RMA 422

Signal Conditioners. Highlights. Battery powered. Line powered. Multi-purpose. Modular-style. Multi-channel. Charge & impedance converters

LC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V AC coil

LC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A V AC coil

Operation Manual for. SCU1 Signal Conditioning Unit

LC1D32P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A V AC 50/60 Hz coil

USER GUIDE. AXIS T8640 Ethernet Over Coax Adaptor PoE+ ENGLISH

Specifications MAV Series Matrix Switchers

LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC

Perle Fast Ethernet Fiber to Fiber Media Converter Module. Installation Guide. P/N (Rev D)

LC1D150G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 150 A V AC coil

- special pressure ranges - variety of electrical and mechanical. Characteristics. - other versions on request

DMP 339. Pressure Transmitter. with G ¼" flush diaphragm. Pressure Transmitter. Industrial. accuracy according to IEC 60770: 0.

HDBaseT Extender Set 100m User Guide

PRO-CoaxExt HDMI extender over Coaxial cable with bi-directional IR User s Guide

PRO-ScalerHD2V HDMI to VGA & Audio Scaler Converter. User s Guide. Made in Taiwan

ELECTRICAL. DATA AND INDEX Not all complements shown A shown for reference. Index A leads B, CW (from shaft end) TERMINAL CONNECTIONS COM VCC CASE

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

Model Number Structure

Transcription:

Installation Instructions ArmorPOINT RTD and Thermocouple Input Modules Catalog numbers 1738-IR2M12, 1738-IT2IM12, Series A Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 About the Module 4 Mount the I/O Base 5 Install the Module 6 Remove the Module from the Mounting Base 6 Wire the Module 7 Communicate with the Module 8 Interpret Status Indicators 10 Specifications 12

2 ArmorPOINT RTD and Thermocouple Input Modules Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences. SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product.

ArmorPOINT RTD and Thermocouple Input Modules 3 Environment and Enclosure ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances. This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications. In addition to this publication, see: Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements. NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Preventing Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available. Store the equipment in appropriate static-safe packaging when not in use.

4 ArmorPOINT RTD and Thermocouple Input Modules About the Module The ArmorPOINT I/O family consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. Note that environmental requirements other than IP67 may require an additional appropriate housing. I/O connectors are sealed M12 (micro) style. The mounting base ships with the module. The 1738-IR2M12 module is shown here. ArmorPOINT RTD and Thermocouple Input Module 1738-IR2M12/A RTD (Ohms) In 1 2 0 1 MOD NET RTD 0 3 RTD 1 43780 Description Description 1 Connector M12-A 3 LED indicators 2 Connector M12-B

Mount the I/O Base ArmorPOINT RTD and Thermocouple Input Modules 5 Mount the I/O base on a wall or panel, using the screw holes provided in the base. IMPORTANT The module must be mounted on a grounded metal mounting plate or other conductive surface. Mounting Diagram for ArmorPOINT Base with Adapter Millimeters 46.25 (1.8) 20.1 (0.8) 20.1 (0.8) (Inches) 51.9 (2) 51.9 (2) 51.9 (2) 102 (4.02) 56 (2.2) Adapter Follow the instructions to install the mounting base. 1. Lay out the required points as shown above in the drilling dimension diagram. 2. Drill the necessary holes for M4 (#8) machine or self-tapping screws. 3. Mount the base using M4 (#8) screws. 4. Ground the system using the ground lug connection. The ground lug connection is also a mounting hole. Mounting Base Keyswitch 43769 Ground lug connection Latching mechanism 43675

6 ArmorPOINT RTD and Thermocouple Input Modules Install the Module Follow the instructions to install the ArmorPOINT input module. 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 6 aligns with the notch in the base. 2. Position the module vertically above the mounting base. The module bridges two bases. Module bridges two bases. 1738-IR2M12/A RTD (Ohms) In 0 1 MOD NET RTD 0 RTD 1 43782 3. Push the module down until it engages the latching mechanism. You hear a clicking sound when the module is properly engaged. The locking mechanism locks the module to the base. Remove the Module from the Mounting Base Follow the instructions to remove the module from the mounting base. 1. Insert a flat blade screwdriver into the slot of the orange latching mechanism. 2. Push the screwdriver toward the I/O module to disengage the latch. The module lifts up off the base. 3. Pull the module off the base.

Wire the Module ArmorPOINT RTD and Thermocouple Input Modules 7 Follow the wiring instructions for the ArmorPOINT input modules. 1738-IR2M12 1 2 5 4 1738-IT2IM12 1 2 5 4 3 43664 3 43664 (View into connector) Pin 1 No connect Pin 2 Input 0A (M12-A) Input 1A (M12-B) Pin 3 Input 0C (M12-A) Input 1C (M12-B) Pin 4 Input 0B (M12-A) Input 1B (M12-B) Pin 5 No connect (View into connector) Pin 1 CJC + Pin 2 TC 0 + (M12-A) TC 1 + (M12-B) Pin 3 CJC - Pin 4 TC 0 - (M12-A) TC 1 - (M12-B) Pin 5 No connect IMPORTANT Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques. ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.

8 ArmorPOINT RTD and Thermocouple Input Modules Communicate with the Module I/O messages are sent to (consumed) and received from (produced) the ArmorPOINT I/O modules. These messages are mapped onto the processor s memory. The ArmorPOINT RTD I/O input module produces 6 Bytes of input data (scanner Rx status) and fault status data. The ArmorPOINT thermocouple I/O input module produces 8 Bytes of input data (scanner Rx status) and fault status data. They do not consume I/O data (scanner Tx). Default Data Map 1738-IR2M12 Message size: 6 Bytes 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Produces Input channel 0 high byte Input channel 0 low byte (scanner Rx) Input channel 1 high byte Input channel 1 low byte Status byte for channel 1 Status byte for channel 0 OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF Consumes No consumed data (scanner Tx) Where: OR = Overrange; 0 = No error, 1 = Fault UR = Underrange; 0 = No error, 1 = Fault HHA = High/High Alarm; 0 = No error, 1 = Fault LLA = Low/Low Alarm; 0 = No error, 1 = Fault HA = High Alarm; 0 = No error, 1 = Fault LA = Low Alarm; 0 = No error, 1 = Fault CM = Calibration Mode; 0 = Normal, 1 = Calibration mode CF = Channel Fault Status; 0 = No error, 1 = Fault

Default Data Map 1738-IT2IM12 Message size: 6 Bytes ArmorPOINT RTD and Thermocouple Input Modules 9 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Produces Input channel 0 high byte Input channel 0 low byte (scanner Rx) Input channel 1 high byte Input channel 1 low byte Status byte for channel 1 Status byte for channel 0 OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF OR UR Cold junction temperature (Selectable channel 0, channel 1, or average of both channels 0 and 1) Consumes No consumed data (scanner Tx) Where: OR = Overrange; 0 = No error, 1 = Fault UR = Underrange; 0 = No error, 1 = Fault HHA = High/High Alarm; 0 = No error, 1 = Fault LLA = Low/Low Alarm; 0 = No error, 1 = Fault HA = High Alarm; 0 = No error, 1 = Fault LA = Low Alarm; 0 = No error, 1 = Fault CM = Calibration Mode; 0 = Normal, 1 = Calibration mode CF = Channel Fault Status; 0 = No error, 1 = Fault

10 ArmorPOINT RTD and Thermocouple Input Modules Interpret Status Indicators This module has the following indicators: Adapter, DeviceNet and POINTBus status indicators System and Adapter power indicators Individual I/O status indicators for inputs and outputs 1738-IR2M12 1738-IR2M12/A RTD (Ohms) In 0 1 MOD NET Module status indicator Network status indicator RTD 0 RTD 1 I/O status indicator 43780 Indicator Status for Modules Status Description Module status Off No power applied to device. Green Device operating normally. Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration. Flashing red Recoverable fault. Red Unrecoverable fault may require device replacement. Flashing red/green Device is in self-test.

ArmorPOINT RTD and Thermocouple Input Modules 11 Indicator Status for Modules Status Description Network status Off Device is not online: - Device has not completed dup_mac-id test. - Device not powered check module status indicator. Flashing green Device is online but has no connections in the established state. Green Device is online and has connections in the established state. Flashing red One or more I/O connections are in timed-out state. Red Critical link failure failed communication device. Device detected error that prevents it from communicating on the network. Possible duplicate MAC ID or baud rate mismatch. Flashing red/green Communication faulted device the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request long protocol message. I/O status Off Module in CAL mode. Solid green Normal (channel scanning inputs). Flashing green Channel being calibrated. Solid red Major channel fault. Flashing red Channel at end of range (over or under).

12 ArmorPOINT RTD and Thermocouple Input Modules Specifications ArmorPOINT RTD and Thermocouple Input Modules 1738-IR2M12, 1738-IT2IM12 Attribute Value Inputs per module 1738-IR2M12 2 single-ended, nonisolated 1738-IT2IM12 2 differential, individually isolated Resolution 1738-IR2M12 16 bits, 9.5 mv/cnt, 0.03 C/cnt (Pt385 @ 25 ) 1738-IT2IM12 15 bits plus sign, 2.5 mv/cnt Thermocouple type (and 1738-IT2IM12 only resolution average over span) Sensor Range Resolution (average over span) Type B 30 1820 C 3 counts/ C Type C 0 2315 C 6 counts/ C Type E -270 1000 C 24 counts/ C Type J -210 1200 C 21 counts/ C Type K -270 1372 C 13 counts/ C Type N -270 1300 C 11 counts/ C Type R -50 1768.1 C 4 counts/ C Type S -50 1768.1 C 4 counts/ C Type T -270 400 C 15 counts/ C RTD sensors supported Cold junction compensation range Input range 1738-IR2M12 only 100 Ω Pt α = 0.00385 Euro (-200 870 C) 200 Ω Pt α = 0.00385 Euro (-200 630 C) 100 Ω Pt α = 0.003916 U.S. (-200 630 C) 200 Ω Pt α = 0.003916 U.S. (-200 630 C) 10 Ω Cu α = 0.00427 (-200 260 C) 100 Ω Ni α = 0.00618 (-60 250 C) 120 Ω Ni α = 0.00672 (-60 250 C) 120 Ω Ni α = 0.00618 (-60 250 C) 1738-IT2IM12 0 70 C 1738-IR2M12 0 600 Ω 1738-IT2IM12 ±75 mv Absolute accuracy (1) 0.1% full scale @ 25 C Accuracy drift w/temp 30 ppm/ C

ArmorPOINT RTD and Thermocouple Input Modules 13 ArmorPOINT RTD and Thermocouple Input Modules 1738-IR2M12, 1738-IT2IM12 Attribute Input update rate (per module) Step response (per channel) Input resistance Input impedance Conversion type Common mode rejection ratio Normal mode rejection ratio Data format Maximum overload Value 1738-IR2M12 40 ms @ Notch = 50 Hz 33 ms @ Notch = 60 Hz (default) 20 ms @ Notch = 100 Hz 17 ms @ Notch = 120 Hz 10 ms @ Notch = 200 Hz 8 ms @ Notch = 240 Hz 7 ms @ Notch = 300 Hz 5 ms @ Notch = 400 Hz 4 ms @ Notch = 480 Hz 60 ms @ Notch = 50 Hz 50 ms @ Notch = 60 Hz 30 ms @ Notch = 100 Hz 25 ms @ Notch = 120 Hz 15 ms @ Notch = 200 Hz 13 ms @ Notch = 240 Hz 10 ms @ Notch = 300 Hz 8 ms @ Notch = 400 Hz 6 ms @ Notch = 480 Hz 1738-IT2IM12 only 1 MΩ 1738-IT2IM12 only 100 KΩ Delta Sigma 120 db 100 db -3 db Notch filter 13.1 Hz @ Notch = 50 Hz 15.7 Hz @ Notch = 60 Hz 26.2 Hz @ Notch = 100 Hz 31.4 Hz @ Notch = 120 Hz 52.4 Hz @ Notch = 200 Hz 62.9 Hz @ Notch = 240 Hz 78.6 Hz @ Notch = 300 Hz 104.8 Hz @ Notch = 400 Hz 125.7 Hz @ Notch = 380 Hz Signed integer 1738-IR2M12 No input protection 1738-IT2IM12 Input not overvoltage protected 1738-IT2IM12 20 ms @ Notch = 50 Hz 17 ms @ Notch = 60 Hz (default) 10 ms @ Notch = 100 Hz 8 ms @ Notch = 120 Hz 5 ms @ Notch = 200 Hz 4 ms @ Notch = 240 Hz 3 ms @ Notch = 300 Hz 3 ms @ Notch = 400 Hz 2 ms @ Notch = 480 Hz (1) Includes offset, gain, non-linearity and repeatability error terms

14 ArmorPOINT RTD and Thermocouple Input Modules General Specifications Attribute Mounting base screw torque Calibration POINTBus current Power dissipation, max Thermal dissipation, max Isolation voltage Dielectric test External DC power LED indicators Dimensions, HxWxD Weight Enclosure type rating Wiring category (1) Keyswitch position 6 Value M4 (#8) screw, 0.85 Nm (7.5 lb-in.) in aluminum, 1.8 Nm (16 lb-in.) in steel Factory-calibrated 1738-IR2 220 ma @ 5V DC 1738-IT2I 175 ma @ 5V DC 1.0 W 3.3 BTU/hr Tested at 50V rms (1738-IT2I has isolation between individual channels) 1000V rms flash for 1s No external power required 1 green/red module status indicator, logic side 1 green/red network status indicator, logic side 2 green/red input status indicators, logic side 31.75 x 66.80 x 107.95 mm (1.25 x 2.63 x 4.25 in.) 0.289 kg (0.637 lb) Meets IP65/66/67 (when marked) 1 on signal ports (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Environmental Specifications Attribute Temperature, operating Temperature, storage Relative humidity Value IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20 60 C (-4 140 F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), -40 85 C (-40 185 F) IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 95% noncondensing

Environmental Specifications Attribute ArmorPOINT RTD and Thermocouple Input Modules 15 Value Vibration IEC60068-2-6 (Test Fc, Operating): 5 g @ 10 500 Hz Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g Emissions Emissions CSPR 11: Group 1, Class A ESD immunity IEC 61000-4-2: 6 kv contact discharges 8 kv air discharges Radiated RF immunity IEC 61000-4-3: 10V/m with 1 khz sine-wave 80% AM @ 30 MHz 1000 MHz 10V/m with 200 Hz 50% pulse 100% AM @ 900 Mhz EFT/B immunity IEC 61000-4-4: ±3 kv @ 5 khz on signal ports Surge transient immunity IEC 61000-4-5: ±2 kv line-earth(cm) on shielded ports Conducted RF immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80% AM @ 150 khz 80 MHz Certifications Certification (when product is marked) (1) c-ul-us CE C-Tick Value UL-listed Industrial Control Equipment, certified for US and Canada European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions (1) See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Outside United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Automation, ArmorPOINT, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Supersedes Publication 1738-IN005A-EN-E - June 2004 Copyright 2013 Rockwell Automation, Inc. All rights reserved.