Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual)

Similar documents
6000 Series Patch Panel Terminating Instructions

LGX Compatible (LSX) Connector Module) User Manual)

OptEnet OC48 Regenerator Module User Manual

24-Fiber LANLINXS (Model # ) 48-Fiber LANLINXS (Model # ) User Manual

OmniReach FTTX Solutions RealFlex DLX Universal Drop Cable Instruction Sheet

CONNECTING THE FUTURE 19" LINXS LIGHTWAVE INTEGRATED CROSS-CONNECT SYSTEM USER MANUAL

IP-LINX. Installation Guide

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

HCS - HES Cabling Systems

IP-LINX Fiber :: X-XXXX

ADC Passive Optical Network (PON) Test and Turn-Up Procedures

NGF optical distribution frame

Traditional RF Splitter/Combiner and Directional Coupler User Manual

3M Fiber Optic Wall Mount Enclosure 8430 Series

Traditional RF Splitter/Combiner and Directional Coupler User Manual

Optical Distribution Box 300 Installation Guide. Version : R0.0

FOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block

FIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays

Medium Box for Cable Termination

FOSC 450 C6 and D6 Closures

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

HD Flex Patch Panel. ASSEMBLY VIEW (FLEX1UPN** shown) FS128B. CONTENTS: (#) indicates FLEX4UPN** quantity

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR

FIST-GCOG2-Dx6. Follow all local safety regulations related to optical fiber plant elements.

3M Distribution Box (DDB)

3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket

SLiC Fiber Aerial Closure System

Ordering Guide of the Fiber-Optic Splice Closure (FOSC-400)

3M Coupling Tray FDTC-10S-COUPLINGTRAY

Clearview. Classic Cassettes. Installation Manual. Clearview Classic (HD) High Density. Part #: Rev: A Updated:

DSX-1 Cross-Connect Procedures

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR

Instructions. Cable with Armor F CAUTION. October Rev A

2178-L/S Series Fiber Optic Splice Case with Gasket

2.1 Kit Contents 2.2 Elements needed from the FIST installation kit 2.3 Tools 2.4 Cable preparation table

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR

LCC (Little Coaxial Connector) Installation Instructions)

Ordering Guide. for FIST-GSS2 product range

FACT Cable Termination Unit

4320 SS-25 Self-Strip Terminating Block

Section Communications Optical Fiber Backbone Cabling

INSTALLATION INSTRUCTIONS

Panduit Recommended Best Case Practice Split Fibre

COYOTE CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 22" 8.5" x 22" (15.24 cm x cm cm x cm)

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT

High Density Block BRCP. HD BRCP- 128/192/256 pair. Installation Instructions

WCH Slack Storage Housing (WCH-SSH-2 & WCH-SSH-4-12)

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box

ADF Module. Installation Guide. 1.1 Overview

Public Works Division Lighting District Fiber Optic Specifications April 2009

Crimp & Cleave Termination Instructions for SEL ST Connectors

Next Generation Frame (NGF) 600 mm Product Family Ordering Guide

18mm ECAM Cable Entry Port

OFDC-B8-72. Outdoor fiber distribution closure. 6 Closing. Content 1 Introduction. 7 Re-entry. 2 Kit content. 3 Closure preparation

Gel-sealed in-line fiber optic closure

FIST-GCO2-OTIAN I N S T A L L A T I O N I N S T R U C T I O N

A449-6S 70 CENTIMETER FM YAGI ANTENNA MHz

Installation Instructions

The FiberMark1 offers an ideal solution for

FIST-GCO2 GCO2-BC8 GCO2-BD8 GCO2-BE8 GCO2-BF8. 5 Heatshrink installation. 1 Introduction. Content. 6 Fiber routing. 2 General. 7 Fiber routing on tray

GF-KSW-48 Series of Fiber Optic Distribution Box. Instruction Manual

INSTALLATION INSTRUCTIONS

SJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1

FOSC 400. Ordering Guide For Closures and Accessories. Section I 3. Section II 5. Section III 9. Section IV 11. Section V 15

DS1 Cross-Aisle Panel

2178 L/S Series Fiber Optic Splice Cases and Accessories

A CENTIMETER FM YAGI ANTENNA MHz

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

3M Cold Shrink Splice Kit QS-III 5416A

3 SLiC Aerial Closure with Rubber End Seal

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

3M Fiber Optic Splice Closure 2178-L/S Series with Gasket

Water blocking tape. Locator ridge HPA-0486

Quante BPEO Splice-Protection Closure for Optical Fiber Cables. Features Advantages Benefits

Seal Kits for BUDI Enclosures

JACK Digital HDTV Over-the-Air Antenna

WaveTrax. Fiber Cable Management System

Aerospace Fiber Optics

Caution. Hanging the Screen:

3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter

NewScope-7A Operating Manual

SUBCARRIER TRANSFER FILTER INSTRUCTION BOOK IB622702

SPECIFICATION FIBER OPTIC SPLICE CLOSURE. Spec No : VSS-1007-BS403A-04A/SD. VSS-0107-BS403A-04A/SD R & D Center Manufacturing Division

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxMSOS DIELECTRIC HIGH PERFORMANCE OSP TUBE CABLE SERIES

3M Fiber Optic Closure System LL

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

ALTOS LITE Loose Tube, Gel-Free Cables with FastAccess Technology, Fibers

SECTION O FIBER OPTICS

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxMSOS-2 HIGH PERFORMANCE OSP TUBE CABLE SERIES WITH GALVANIZED STEEL INTERLOCKED ARMORING

3M Cold Shrink Splice Kit QS-III 5514A

3M Fiber Closures BPEO

SPECIFICATION FOR FIBER OPTIC SPLICE CLOSURE

3M Better Buried Closures

MiniXtend Cable with Binderless* FastAccess Technology Jacket and Buffer Tube Removal Procedures. 1. General. 2. Precautions

3M Cold Shrink Splice Kit QS-III 5515A

LTX Optical Distribution Panels. Ordering Guide

OA White OA Black. Owner s Manual. Low Profile Digital HDTV Over-the-Air Antenna. w/built-in KING SureLock Digital TV Signal Meter

JACK Digital HDTV Over-the-Air Antenna w/built-in SureLock Digital TV Signal Meter

Transcription:

Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual) Fiber Combination Block Content Page INTRODUCTION............................................................................. 2 Revision History........................................................................ 2 Trademark Information................................................................... 2 Related Publications..................................................................... 2 1 PRODUCT DESCRIPTION.................................................................. 3 1.1 General Description................................................................ 3 1.2 Main Components and Features....................................................... 4 1.3 Round Splice Tray................................................................. 6 2 SPECIFICATIONS........................................................................ 7 3 UNPACKING THE PRODUCT................................................................ 7 4 INSTALLATION OVERVIEW................................................................. 7 5 INSTALLING PIGTAILS.................................................................... 8 6 MOUNTING THE FCB ON THE RACK.......................................................... 10 7 INSTALLING CABLES.................................................................... 11 (continued) 1325817 Rev A Page 1

Content (continued) Page 7.1 Breaking Out the Cable............................................................ 11 7.2 Installing a Blocking Kit............................................................ 12 7.3 Installing a Cable Clamp........................................................... 12 8 LOADING THE ROUND SPLICE TRAY......................................................... 16 8.1 Standard Splice Configuration....................................................... 16 8.1.1 Breaking Out Cable Subunits and Pigtails......................................... 16 8.1.2 Left-Oriented FCBs (Clockwise Wind)............................................ 18 8.1.3 Right-Oriented FCBs (Counter-Clockwise Wind)..................................... 22 8.2 24-Fiber Heat-Shrink Configuration (144 FCB With LX.5 Only).................................. 26 8.2.1 Breaking Out Cable Subunits and Pigtails......................................... 26 8.2.2 Left-Oriented FCBs (Clockwise Wind)............................................ 28 8.2.3 Right-Oriented FCBs (Counter-Clockwise Wind)..................................... 32 9 SPLICING............................................................................ 36 10 INSTALLING PATCH CORDS............................................................... 36 11 CUSTOMER INFORMATION AND ASSISTANCE................................................... 38 INTRODUCTION This manual describes the Next Generation Frame (NGF) Fiber Combination Block (FCB), and provides instructions for installing this product. The FCB may be installed either on an NGF Slim Rack or on a Fiber Main Distribution Frame (FMDF). It may have been ordered empty or loaded with pre-terminated pigtails. This guide addresses all installation options, either by providing instructions or by referring to related publications sent with kits. Revision History ISSUE DATE REASON FOR CHANGE Issue 1 06/2001 Original. Issue 2 07/2001 Technical update to provide more thorough instructions. Issue 3 05/2005 Figure 6 corrected to show correct breakout point. Cover photo changed. Customer info updated. Trademark Information ADC is a registered trademark of ADC Telecommunications, Inc. Related Publications Title ADCP Number Next Generation Frame (NGF) Slim Rack Installation Manual 90-272 Fiber Main Distribution Frame (FMDF) Installation Manual 93-273 FMDF Patch Cord Cross-Connect and Interconnect Procedures 90-240 Page 2

1 PRODUCT DESCRIPTION 1.1 General Description The Fiber Combination Block (FCB) is a Next Generation Frame (NGF) equipment panel that provides a combination of splicing and termination functions. The FCB may be mounted on either a Fiber Main Distribution Frame (FMDF) or NGF Slim Rack. FCBs are available with different adapter types in block configurations of 48, 72, 96, or 144 (LX.5 only) positions. FCBs also have a left or right orientation for mounting on the left or right side of the rack. Figure 1 provides a functional overview of the FCB. Outside Plant (OSP) or Intrafacility (IFC) cables are brought in from above or below the FCB (called upward and downward exit, respectively). The cables are spliced to pigtails in the round splice trays in the bottom area of the FCB. The pigtails transition to the Fiber Termination Block (FTB), where they are terminated to adapter/connectors. Patch cords, routed through the NGF rack Z trough, are used to complete optic circuits or for patching and testing. FIBER TERMINATION BLOCK PIGTAILS NGF RACK "Z" TROUGH PATCH CORD 16692-A OSP OR IFC CABLE ROUND SPLICE TRAY Figure 1. Functional Overview of an FCB (Cable Downward Exit Shown) Page 3

1.2 Main Components and Features Figure 2 shows the main components and features of a Fiber Combination Block (in this case, the 72-position, left-oriented model). The FCB consists of an upper component called the Fiber Termination Block (FTB) and a lower component called the splice chassis. The FTB by itself is identical to FTBs sold (without splice chassis) as stand-alone units. 16691-ARM Figure 2. FCB Features (72-Position Left-Oriented Model) The splice chassis door provides entrance to the splice chassis. Round splice trays within the splice chassis hold splice chips and service coils for splices. Splice trays in the left-oriented version are numbered from left to right (when viewed from the front), with the number 1 tray adjacent to the splice chassis door, as shown. Page 4

The FCB is also available in a right-oriented model. Splice trays in the right-oriented model are also numbered from left to right. This places the splice trays in a reverse sequence with respect to the module features, with the number 6 splice tray adjacent to the splice chassis door, as shown in Figure 3. 16690-A SPLICE TRAY 1 SPLICE TRAY 6 Figure 3. Right-Oriented CFB (72-Position Model Shown) Radius-limiting spools guide pigtails from splice trays to their point of termination in the FTB. Strain reliefs and cable tie-down locations are used to secure the OSP or IFC cable being routed to the round splice trays. The FCB is shipped with a cable clamp kit that is installed on the rack adjacent to the FCB. The kit includes ground fittings for OSP cable. The upper component, the FTB, has a front and side cover. The side cover provides access to the area where pigtails are routed into the termination block. The FTB uses sliding adapter packs to provide termination locations for patch cords. Page 5

Front edge protectors in the FTB are used to guide patch cords to the NGF rack Z trough, through which they are routed to other FTBs or to fiber optic equipment. Either an interconnect or cross-connect configuration may be used. 1.3 Round Splice Tray The round splice tray is the component mounted in the splice chassis to provide a protected surface and service loop storage for splicing. Figure 4 shows its main features. TOP COVER SPLICE CHIPS (2) TRANSITION OPENING (2 PLACES) SPLICE TRAY (TOP SIDE) TIE-DOWN POINT (4 PLACES) BOTTOM COVER 14317-A Figure 4. Round Splice Tray As shown, the tray has a removable top cover, a removable bottom cover, and a splice tray. Cable subunits and pigtails are wound in the same direction around the splice tray and secured at the four tie-down points. Transition openings in two locations are used to route pigtails from the top to bottom of the splice tray, or vice versa. The direction of wind is clockwise for trays mounted in a left-oriented FCB; the direction of wind is counter-clockwise for the right-oriented FCB. The fibers being spliced are routed through the transition openings on either side of the tray and spliced on the splice chips. Each tray accommodates up to 12 splices (stranded or ribbon) using a standard splice configuration or up to 24 splices (LX.5 only) using a 24-fiber heat shrink configuration. Page 6

2 SPECIFICATIONS Table 1 lists specifications for the Fiber Combination Block and round splice tray. Table 1. Fiber Combination Block and Round Splice Tray Specifications ITEM Fiber Combination Block Dimensions (H W D) Weight Capacity Round Splice Tray DESCRIPTION 21.5 in. (54.6 cm) 18.6 in. (47.2 cm) 6.5 in. (16.5 cm) 36.67 lbs (16.68 kg) Available with 48, 72, 96 termination positions; or with 144 termination positions using LX.5 connectors 12 splices per tray; or 24 splices per tray using LX.5 connectors 3 UNPACKING THE PRODUCT Unpack and inspect the Fiber Combination Block as follows: 1. Inspect the exterior of the shipping container for evidence of rough handling that may have damaged the contents of the container. 2. Unpack the FCB and check for possible damage. 3. If damage is detected or if parts are missing, file a claim with the commercial carrier and then notify ADC Customer Service. Save damaged carton for inspection by the carrier. 4. Refer to Section 11 for repair, replacement, and warranty information. 5. Save the shipping container for use if equipment requires shipment at a future date. 4 INSTALLATION OVERVIEW Installation of the Fiber Combination Block involves the following main tasks: 1. Installing Pigtails If your FCB was shipped without pre-loaded pigtails, this will be your first task. This involves stripping back the yellow outer wall of the pigtail bundle (in conformance with the breakout diagram provided) and terminating the connector end of the pigtails at the Fiber Termination Block. For details, refer to Section 5, below. 2. Mounting the FCB on the Rack This consists of aligning the FCB correctly and securing it with the screws provided. For details, refer to Section 6. 3. Installing Outside Plant This consists of three procedures: breaking out the cable (subsection 7.1); installing a blocking kit (subsection 7.2); installing a cable clamp (subsection 7.3). 4. Loading Round Splice Trays This involves removing the round splice trays one by one to a work surface, measuring and breaking out the IFC or OSP cable subunits and pigtails, and routing them into the round splice tray. Details are provided in Section 8. Page 7

5. Splicing to Pigtails This procedure is also done using a work area adjacent to the rack. Guidelines are provided in Section 9. 6. Installing Patch Cords Patch cords may be used in either a cross-connect or interconnect configuration. Guidelines are provided in Section 10. 5 INSTALLING PIGTAILS If the FCB was shipped empty, so pigtails need to be installed, refer to the following instructions to install the pigtails before mounting the FCB on the rack. If pigtails are already present, skip to Section 6 to install the FCB on the rack. Install the pigtails as follows: Warning: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the optical adapter of an operational transmitter or into the launching (output) end of an active fiber. A clean, protective cap MUST be immediately placed over any radiating optical receptacle or optical fiber connector to avoid exposure to potentially dangerous amounts of radiation. This practice also helps prevent contamination of connectors. 1. Place the FCB on a flat work area immediately in front of the rack. 2. Lay the pigtail bundle on the work surface and strip back the outer wall of the pigtail bundle corresponding to breakout dimensions provided in Figure 5. YELLOW JACKET 33 IN. (83.8 CM) 16693-A Figure 5. Pigtail Breakout Dimensions Page 8

3. Secure the pigtail bundle to the FCB at the breakout point shown in Figure 6. BREAKOUT POINT OUT FROM SPLICE TRAY 16416-C Figure 6. Correct Pigtail Routing on the CFB 4. In the Fiber Termination Block, pull out the sliding adapters one row at a time and connect the terminated end of the pigtails to the bulkhead adapters. Note: Devise an orderly scheme for dividing the 12 connectors in the pigtail bundle with the number of adapters in the adapter packs (there may be 6, 8, or 12 adapters per pack). 5. Route the fibers around the edge protectors and spools as shown in Figure 6. 6. Remove the round splice tray from the splice tray compartment and set it beside the FCB. 7. Route the pigtails in the route shown through the splice tray compartment and out to the round splice tray. 8. Remove splice tray covers. 9. Wind up pigtails within round splice tray. Use a clockwise wind for left-oriented FCB and a counter-clockwise wind for right-oriented FCB. Do not trim pigtails at this time. 10. Replace splice tray cover and return round splice tray to FCB. Page 9

6 MOUNTING THE FCB ON THE RACK Use the following procedure to mount the Fiber Combination Block on a FMDF or Slim Rack: 1. Ensure that the block is upright as shown in Figure 7. 2. Align the guides on the top of the FCB with the top of the rack mounting bracket as shown in Figure 7. Figure 7. Aligning the Guides 3. Slide the FCB into position as shown in Figure 8. Figure 8. Sliding the FTB Into Position Page 10

4. Secure the FCB to the frame using four #12 screws provided, as shown in Figure 9. Figure 9. Securing the FCB on the Rack 7 INSTALLING CABLES The cable being installed may be either Outside Plant (OSP) or Intrafacility Cable (IFC). 7.1 Breaking Out the Cable Break out the cable corresponding to Figure 10 below. 14 FT. MINIMUM (4.27 M) CABLE CABLE CLAMP LOCATION BLOCKING KIT LOCATION (OSP ONLY) 16694-A Figure 10. Cable Breakout Page 11

7.2 Installing a Blocking Kit If installing OSP cable, install a blocking kit prior to clamping the cable. The blocking kit must be ordered separately. Figure 11 shows an example. Follow the instructions in the kit. CINTAS DE FIBRA VISTA FINAL DEL CABLE AGUJEROS DE ACCESO PARA OBTURACIÓN CAVIDAD DEL TUBO DILATADO TAPA DEL TUBO DILATADO TUBO PROTECTOR VISTA FINAL DEL TUBO DILATADO 2538-C Figure 11. Blocking Kit Example 7.3 Installing a Cable Clamp A cable clamp is provided with the FCB. Figure 12 provides an exploded view. MOUNTING BRACKET DOWNWARD CABLE EXIT POSITION OSP CABLE FIBERS RUBBER GROMMET CLAMP PLATE SCREW OSP CABLE RUBBER YOKE UPWARD CABLE EXIT POSITION 16725-A Figure 12. Cable Clamp Kit Exploded View Page 12

1. Select a cable clamp position on the rack based on whether the cable will exit upward or downward from the FCB, as shown in Figure 13. Note: If the FCB occupies the top position on the rack, install the clamp at the vertical cable guide located midway between the two vertical cable guides called out in Figure 13. UPWARD EXIT ROUTE CLAMP VERTICAL CABLE GUIDE RACK OSP CABLE DOWNWARD EXIT ROUTE 16750-A-RM-REV CLAMP VERTICAL CABLE GUIDE Figure 13. Selecting Cable Clamp Position on Rack 2. Remove the vertical cable guide at the location where you intend to install the cable clamp. 3. Install the cable clamp mounting bracket inside the vertical cable guide as shown in Figure 14. Page 13

RACK 16751-A VERTICAL CABLE GUIDE CABLE CLAMP MOUNTING BRACKET Figure 14. Installing the Cable Clamp Mounting Bracket 4. Stack the clamp plate and one rubber yoke on the two screws provided. Refer to the exploded view provided in Figure 12. 5. Install a rubber grommet on the cable. If the cable has been fitted with a blocking kit, the grommet should be placed just before the blocking kit and cable breakout (refer to Figure 10). The cable should fit snugly within the grommet. Page 14

6. Position the cable and grommet within the first rubber yoke (already stacked on the screws); place another rubber yoke on the screws on the other side of the grommet; and fasten the screws to the mounting bracket. Refer to Figure 15. 7. If the cable being installed has a metallic strength member, ground the cable using an alligator connector or split bolt connector (provided in the kit) as shown in Figure 15. 16726-A WITHOUT GROUND WITH ALLIGATOR CONNECTOR WITH SPLIT BOLT CONNECTOR Figure 15. Cable Clamp Grounding Options (Downward Exit Shown) 8. Loop the cable up over the spools to prevent it from being damaged, and proceed to load the round splice trays. Note: If you won t be loading the round splice trays at this time, route the fibers to the appropriate round splice tray and wrap them around the splice tray to protect them from damage. Wrap them in the same direction as the already installed pigtails. Page 15

8 LOADING THE ROUND SPLICE TRAY Different procedures are provided within this section for standard and 24-fiber heat-shrink splice configurations, and for left-oriented and right-oriented FCBs. Note: The 24-fiber heat shrink configuration may be used in LX.5 applications only. Select from the procedures based on the following guidelines: 1. Refer to Table 2 below to determine whether you are doing a standard or 24-fiber heatshrink splice configuration. 2. Find the corresponding subsection in the following pages. 3. Break out the cable subunits and pigtails using the first procedure in that subsection. 4. Select either of the remaining subsections depending on whether you are loading a leftoriented or right-oriented FCB. Table 2. Round Splice Tray Procedures SPLICE CONFIGURATION DESCRIPTION PROCEDURES Standard 24-Fiber Heat Shrink (LX.5 Only) Use when doing: 12 or fewer splices using heat shrink chip; three or fewer splices using ribbon mass fusion; 24 or fewer splices using bare fusion chip or swiss ant chip. Use for 24-fiber heat shrink splice chips only (LX.5). 8.1.1, Breaking Out Cable Subunits and Pigtails 8.1.2, Left-Oriented FCBs (Clockwise Wind) 8.1.3, Right-Oriented FCBs (Counter-Clockwise Wind) 8.2.1, Breaking Out Cable Subunits and Pigtails 8.2.2, Left-Oriented FCBs (Clockwise Wind) 8.2.3, Right-Oriented FCBs (Counter-Clockwise Wind) 8.1 Standard Splice Configuration If doing a standard splice, first break out the cable subunits and pigtails as described in 8.1.1, Breaking Out Cable Subunits and Pigtails below, then perform a clockwise or counterclockwise load as described in either 8.1.2, Left-Oriented FCBs (Clockwise Wind) or 8.1.3, Right-Oriented FCBs (Counter-Clockwise Wind) on the following pages. 8.1.1 Breaking Out Cable Subunits and Pigtails To be wound correctly into the round splice tray, the cable subunits and pigtails must be the same length; therefore, they should be measured and broken out side by side. Page 16

To break out the cable subunits and pigtails, perform the following steps: 1. Unwind the round splice tray to a flat surface in front of the rack. 2. Pull out the cable subunits and pigtails in a straight line directly in front of the rack as shown in Figure 16 below. 3. Break out the cable subunits and pigtails corresponding to Table 3 below, measuring from the point where the cable subunits and pigtails exit from the splice chassis. Note: The cut length for the cable subunits and pigtails must be the same for them to be wound into the splice tray correctly. ROUND SPLICE TRAY PIGTAIL BREAKOUT LENGTH PIGTAIL OSP OR IFC CABLE OSP OR IFC CABLE CUT LENGTH CABLE SUBUNIT BREAKOUT LENGTH 16695-A Figure 16. Breakout Lengths for Cables and Pigtails Table 3. Breakout Lengths for Standard Splice CUT LENGTH* BREAKOUT LENGTH Pigtail 68 in. (minimum) to 146 in. (maximum) 48 in. +1.0 in/ 0.0 in. 172.7 cm (minimum) to 370.8 cm (maximum) 121.9 cm +2.5 cm/ 0.0 cm Cable Subunit Same length as above 37 in. +1.0 in./ 0.0 in. 94 cm +2.5 cm/ 0.0 cm Note: It is recommended to use the maximum cut length of 146 in. (370.8 cm) to achieve maximum distance from FCB for splicing. Note: The cut length for the cable subunits and pigtails must be the same for them to be wound into the splice tray correctly. Page 17

8.1.2 Left-Oriented FCBs (Clockwise Wind) Use this procedure for an FCB that is mounted on the left side of the rack. In this case, you wind the pigtail in a clockwise direction. 1. Start with the fiber breakout positioned at the transition point from top to bottom, as shown in Figure 17. Route and tie down the pigtail as shown in Figure 17. TIE DOWN POINTS TRANSITION POINT FROM TOP TO BOTTOM PIGTAIL BUNDLE (YELLOW JACKET) PIGTAIL BREAKOUT POINT START FROM FIBER TERMINATION BLOCK ROUTE TO BOTTOM SIDE TOP SIDE 16709-A Figure 17. Starting Pigtails 2. Flip the tray over and route the pigtail around the spools and back to the top side of the splice tray as shown in Figure 18. Page 18

MAKE SURE TO ROUTE FIBERS ON OUTSIDE OF TAB TRANSITION POINT PIGTAIL BREAKOUT POINT PIGTAILS ROUTE TO TOP SIDE BOTTOM SIDE BOTTOM COVER 16710-A Figure 18. Routing Pigtails on Bottom of Tray 3. Flip the tray over to the top side and route the pigtail to the splice chip area as shown in Figure 19. Page 19

TRANSITION POINT FROM BOTTOM SIDE TOP SIDE ROUTE PIGTAILS 1.5 TIMES AROUND INSIDE OF TRAY START (PIGTAILS FROM BOTTOM SIDE) 16711-A Figure 19. Completing Pigtail Winding Page 20

4. Route in the IFC or OSP cable subunits as shown in Figure 20. FIBER BREAKOUT POINT OSP OR IFC SUBUNIT PIGTAIL BUNDLE ROUTE TO INSIDE OF TRAY 16712-A TOP SIDE TIE DOWN POINTS Figure 20. Correct Routing for OSP or IFC Subunit Page 21

8.1.3 Right-Oriented FCBs (Counter-Clockwise Wind) Use this procedure for an FCB that is mounted on the right side of the rack. In this case, you wind up the pigtail in a counter-clockwise direction. 1. Start with the fiber breakout positioned at the transition point from top to bottom, as shown in Figure 21. Route and tie down the pigtail as shown in Figure 21. TIE DOWN POINTS TRANSITION POINT FROM TOP TO BOTTOM PIGTAIL BREAKOUT POINT PIGTAIL BUNDLE (YELLOW JACKET) START FROM FIBER TERMINATION BLOCK ROUTE TO BOTTOM SIDE TOP SIDE 16713-A Figure 21. Starting Pigtails 2. Flip the tray over and route the pigtail around the spools and back to the top side of the splice tray as shown in Figure 22. Page 22

TRANSITION POINT PIGTAIL BREAKOUT POINT ROUTE TO TOP SIDE PIGTAILS BOTTOM SIDE BOTTOM COVER 16714-A Figure 22. Routing Pigtails on Bottom of Tray 3. Flip the tray over to the top side and route the pigtail to the splice tray area as shown in Figure 23. Page 23

TRANSITION POINT FROM BOTTOM SIDE TOP SIDE ROUTE PIGTAILS 1.5 TIMES AROUND INSIDE OF TRAY TRSTART (PIGTAILS FROM BOTTOM SIDE) 16715-A Figure 23. Completing Pigtail Winding Page 24

4. Route in the IFC or OSP cable subunits as shown in Figure 24. FIBER BREAKOUT POINT OSP OR IFC SUBUNIT PIGTAIL BUNDLE ROUTE TO INSIDE OF TRAY TIE DOWN POINTS TOP SIDE 16716-A Figure 24. Correct Routing for OSP or IFC Subunit Page 25

8.2 24-Fiber Heat-Shrink Configuration (144 FCB With LX.5 Only) If doing a 24-fiber heat-shrink splice (LX.5 only), first break out the cable subunits and pigtails as described in 8.2.1, Breaking Out Cable Subunits and Pigtails below, then perform a clockwise or a counter-clockwise load as described in either 8.2.2, Left-Oriented FCBs (Clockwise Wind) or 8.2.3, Right-Oriented FCBs (Counter-Clockwise Wind) on the following pages. 8.2.1 Breaking Out Cable Subunits and Pigtails To be wound correctly into the round splice tray, the cable subunits and pigtails must be the same length; therefore, they should be measured and broken out side by side. To break out the cable subunits and pigtails, perform the following steps: 1. Unwind the round splice tray to a flat surface in front of the rack. 2. Pull out the cable subunits and pigtails in a straight line directly in front of the rack as shown in Figure 25. 3. Break out the fibers and pigtails corresponding to Table 4 below the figure. Note: Typically, two pigtail bundles and two cable subunits are routed to each round splice tray in this configuration, with the first and second of each having different breakout dimensions, as indicated in Table 4. If possible, use the maximum cut length of 96 inches (243.8 cm) for the first cable subunit. Shorter lengths may be necessary for larger cable counts and larger cable diameters. Page 26

ROUND SPLICE TRAY PIGTAIL BREAKOUT LENGTH PIGTAIL OSP OR IFC CABLE OSP OR IFC CABLE CUT LENGTH CABLE SUBUNIT BREAKOUT LENGTH 16695-A Figure 25. Breakout Parameters for Cables and Pigtails Table 4. Breakout Lengths for 24-Fiber Heat-Shrink Splice (LX.5 Only) CUT LENGTH BREAKOUT LENGTH First Pigtail* 68 in. (minimum) to 96 in. (maximum) 48 in. +1.0 in./ 0.0 in. 172.7 cm (minimum) to 243.8 cm (maximum) 121.9 cm +2.5 cm/ 0.0 cm Second Pigtail* 8 in. (20.3 cm) shorter than first pigtail 40 in. +1.0 in./ 0.0 in. 102 cm +2.5 cm/ 0.0 cm First Cable Subunit Same length as first pigtail 37 in. +1.0 in./ 0.0 in. 94 cm +2.5 cm/ 0.0 cm Second Cable Subunit Same length as second pigtail 29 in. +1.0 in./ 0.0 in. 73.7 cm +2.5 cm./ 0.0 cm *Two pigtails per round splice tray Page 27

8.2.2 Left-Oriented FCBs (Clockwise Wind) Use this procedure for an FCB that is mounted on the left side of the rack. In this case, you wind up the pigtail in a clockwise direction. 1. Start with the fiber breakout positioned at the transition point from top to bottom, as shown in Figure 26. Route and tie down both the pigtails as shown in Figure 26. TIE DOWN POINTS TRANSITION POINT FROM TOP TO BOTTOM BOTH PIGTAIL BUNDLES PIGTAIL BREAKOUT POINT START FROM FIBER TERMINATION BLOCK ROUTE TO BOTTOM SIDE TOP SIDE 16717-A Figure 26. Starting Pigtails 2. Flip the tray over and route the pigtails around the spools and back to the top side of the splice tray as shown in Figure 27. Page 28

TRANSITION POINT FROM TOP SIDE BREAKOUT POINT (BOTH PIGTAIL BUNDLES) PIGTAILS ROUTE BACK TO TOP SIDE BOTTOM SIDE BOTTOM COVER 16718-A Figure 27. Routing Pigtails on Bottom of Tray 3. Flip the tray over to the top side and route the pigtails and cable subunits to the splice tray area as shown in Figure 28 and Figure 29 below. Page 29

FIRST PIGTAIL ROUTE 1.5 TIMES AROUND INSIDE OF TRAY START END TOP SIDE SECOND PIGTAIL ROUTE ONE TIME AROUND INSIDE OF TRAY START END TOP SIDE 16719-A Figure 28. Completing Pigtail Winding Page 30

FIRST CABLE SUBUNIT ROUTE 2 TIMES AROUND INSIDE OF TRAY FIRST CABLE SUBUNIT END START BREAKOUT POINT TOP SIDE TIE DOWN POINTS SECOND CABLE SUBUNIT ROUTE 1.5 TIMES AROUND INSIDE OF TRAY SECOND CABLE SUBUNIT START END BREAKOUT POINT TIE DOWN POINTS (SAME AS ABOVE) TOP SIDE 16720-A Figure 29. Correct Routing for OSP or IFC Subunits Page 31

8.2.3 Right-Oriented FCBs (Counter-Clockwise Wind) Use this procedure for an FCB that is mounted on the right side of the rack. In this case, you wind up the pigtail in a counter-clockwise direction. 1. Start with the fiber breakout positioned at the transition point from top to bottom, as shown in. Route and tie down both the pigtails as shown in Figure 30. TIE DOWN POINTS TRANSITION POINT FROM TOP TO BOTTOM PIGTAIL BUNDLE (YELLOW JACKET) PIGTAIL BREAKOUT POINT START FROM FIBER COMBINATION BLOCK PIGTAILS 16721-A TOP SIDE Figure 30. Starting Pigtails 2. Flip the tray over and route the pigtails around the spools and back to the top side of the splice tray as shown in Figure 31. Page 32

TRANSITION POINT FROM TOP SIDE PIGTAIL BREAKOUT POINT ROUTE BACK TO TOP SIDE PIGTAILS BOTTOM SIDE BOTTOM COVER 16722-A Figure 31. Routing Pigtails on Bottom of Tray 3. Flip the tray over to the top side and route the pigtails and cable subunits to the splice tray area as shown in Figure 32 and Figure 33 below. Page 33

FIRST PIGTAIL ROUTE 1.5 TIMES AROUND INSIDE OF TRAY START END TOP SIDE SECOND PIGTAIL ROUTE ONE TIME AROUND INSIDE OF TRAY START END TOP SIDE 16723-A Figure 32. Completing Pigtail Winding Page 34

FIRST CABLE SUBUNIT ROUTE 2 TIMES AROUND INSIDE OF TRAY END START BREAKOUT POINT TOP SIDE TIE DOWN POINTS SECOND CABLE SUBUNIT ROUTE 1.5 TIMES AROUND INSIDE OF TRAY START END BREAKOUT POINT TOP SIDE TIE DOWN POINTS 16724-A Figure 33. Correct Routing for OSP or IFC Subunits Page 35

ADCP-90-279 Issue 3 May 2005 9 SPLICING After installing the cable subunits and pigtails in the round splice tray, you can proceed to perform splices following local procedure. If splices will not be performed at once, return the round splice trays to the splice chassis. 10 INSTALLING PATCH CORDS Patch cords are installed on the front of the Fiber Termination Block to complete optic circuits or for patching or testing. Figure 34 provides a side view of correctly routed patch cords. Figure 35 gives an oblique view. Install patch cords using the following procedure: Figure 34. Correctly Routed Patch Cords (Side View) 1. Stand in front of the FCB and open the door to the Fiber Termination Block. 2. Identify the adapter pack at which you want to terminate patch cords and slide out the adapter pack toward you. Danger: Never look directly into an uncovered adapter for an active optic circuit. Laser light can cause serious damage to your eyes. 3. Remove the dust covers from the adapter and clean the adapters per local guidelines. 4. Terminate the patch cord connectors at the appropriate adapters. Page 36

5. Route the patch cords forward from the adapters and over the front edge protectors. Be careful not to kink or sharply bend the patch cords. 6. Route the patch cords down into the NGF Z trough and through the trough to the back of the FMDF or Slim Rack. Refer to Figure 34 and Figure 35. 7. Route the patch cords up or down through the rack vertical cable guides to the assigned termination point. Note: For a thorough description of patch cord routing on the rack, refer to the patch cord routing procedures listed under Related Publications in the front matter of this manual. 8. Record the use of each patch cord using the designation label on the side of the FTB. Figure 35. Correctly Routed Patch Cords (Oblique View) Page 37

11 CUSTOMER INFORMATION AND ASSISTANCE PHONE: EUROPE Sales Administration: +32-2-712-65 00 Technical Assistance: +32-2-712-65 42 EUROPEAN TOLL FREE NUMBERS Germany: 0180 2232923 UK: 0800 960236 Spain: 900 983291 France: 0800 914032 Italy: 0800 782374 U.S.A. OR CANADA Sales: 1-800-366-3891 Extension 73000 Technical Assistance: 1-800-366-3891 Connectivity Extension 73475 Wireless Extension 73476 ASIA/PACIFIC Sales Administration: +65-6294-9948 Technical Assistance: +65-6393-0739 ELSEW Sales Administration: +1-952-938-8080 Technical Assistance: +1-952-917-3475 WRITE: ADC TELECOMMUNICATIONS, INC PO BOX 1101, MINNEAPOLIS, MN 55440-1101, USA ADC TELECOMMUNICATIONS (S'PORE) PTE. LTD. 100 BEACH ROAD, #18-01, SHAW TOWERS. SINGAPORE 189702. ADC EUROPEAN CUSTOMER SERVICE, INC BELGICASTRAAT 2, 1930 ZAVENTEM, BELGIUM PRODUCT INFORMATION AND TECHNICAL ASSISTANCE: connectivity.tac@adc.com wireless.tac@adc.com euro.tac@adc.com asiapacific.tac@adc.com 13944-M Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be verified at any time by contacting ADC's Technical Assistance Center. All Rights Reserved Printed in U.S.A Page 38