DSX-1 Cross-Connect Procedures

Similar documents
DS1 Cross-Aisle Panel

6000 Series Patch Panel Terminating Instructions

LCC (Little Coaxial Connector) Installation Instructions)

Traditional RF Splitter/Combiner and Directional Coupler User Manual

LGX Compatible (LSX) Connector Module) User Manual)

Traditional RF Splitter/Combiner and Directional Coupler User Manual

SECTION 7 -- CROSS-CONNECT SYSTEMS

Instructions. Cable with Armor F CAUTION. October Rev A

4320 SS-25 Self-Strip Terminating Block

Next Generation Frame (NGF) Fiber Combination Block (FCB) User Manual)

High Density Block BRCP. HD BRCP- 128/192/256 pair. Installation Instructions

FTC AGL System Controller Reference Manual Part Number

BCS 4R DSX-3 Connectivity System. Models , , and User Manual

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

VGA Extender over Cat 6 with Audio Support. Model Extend both video and audio up to 300 meters

CR-R880-BL: Indoor/Outdoor Proximity Reader with 10cm (4in) read range

Instruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER

Broadband Connectivity System II

Instruction Guide February 2017

STRUCTURED CABLE SYSTEM (SCS)

MARINE HORNS V-1030M - 5 WATT PAGING HORN AMPLIFIER ASSEMBLY V-1036M - 15 WATT PAGING HORN AMPLIFIER ASSEMBLY V-1048M - 45 OHM TALKBACK HORN

VGA Extender over Single CAT 6 Cable with Audio Support. Model Extend both video and audio up to 1000 feet

HighBand 25. TrueNet Category 6 Solutions

VALCOM HANDSFREE TALKBACK PAGING SYSTEM DESIGN/INFORMATION

Solutions for Electronic Specialty Markets (ESM)

3M Cold Shrink Splice Kit QS-III 5416A

Installation and Operation Manual. for the. SM-6 Programmable Stereo Mixer

TRIPLETT. PairMaster. Lan Cable Test Set. Instruction Manual

3M Coupling Tray FDTC-10S-COUPLINGTRAY

UTP ACTIVE TRANSCEIVER HUB

TAC1 Telephone Entry System

Fixed Audio Output for the K2 Don Wilhelm (W3FPR) & Tom Hammond (NØSS) v August 2009

Installation Manual SaVi Note Underwater LED Light

3M Distribution Box (DDB)

SECTION T -- SYNCHRONIZATION

autotwo Automatic Mixer Operation Manual

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

OptEnet OC48 Regenerator Module User Manual

LavryBlack Series Model AD10 Analog to Digital Converter

PREMIUM 5e F/UTP PRODUCTS

SECTION SYNCHRONIZATION

Installation and Operation Manual

4 Wiring Brochure Wiring and installation of specific control

DSX-1. Copper :: DS1 Series User Manual. Applys to : DS1 Series BATT RTN SGND MON OUT. T Out R T. Front Cross-Connect TL T R T R. Out.

Table of Contents. Introduction Pin Description Absolute Maximum Rating Electrical Specifications... 4

3M Sensored Termination (15 kv) QX-T15I-vi1-E

4, 8, 16 Port VGA/ Audio Extender / Splitter With Local Output with SPDIF Model #: VGA-C5SP-8

FOSC-450D. Fiber Optic Splice Closure. 1 Introduction. Content. 5 Cable termination. 6 Fiber routing. 2 General. 7 Installation of the gel block

VGA / Audio Extender Single CAT5 / CAT6 with RGB Delay Control & EQ

user guide SLX-111 also available: SLX-100, SLX-214 transmitter & receiver pair tel: +44 (0) ,

32 Channel CPCI Board User Manual

STANDARD FOR MULTI-DWELLING UNIT (MDU) OPTICAL FIBER CABLE. Publication S First Edition - June 2012

BNC-2090A QUICK START GUIDE. Rack-Mount Connector Accessory for E/M Series DAQ Devices

Shunt Resistor Measurement Lab. for DE July From. SoftBaugh. Custom Software, Firmware, Hardware, and Project Management Consulting

The tracer - A dual range tester for semiconductors and other components.

FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N

Modular DAA with 2/4 Wire Convertor. XE0002D Block Diagram

Low Profile Digital HDTV Over-the-Air Antenna CONTENTS

AT&T January, 2012 Revised December, 2018 TABLE OF CONTENTS SECTION 1--INTRODUCTION...1-1

ART2000i Digital Dimming System. Installation guide. Stock number *8200-

SmartLynx X+ Cat5 AV Extender

VGA Extender LR EXT-VGA-141LR. User s Manual

TECHNICAL SUPPORT , or FD151CV-LP Installation and Operation Manual 15.1 Low Profile LCD

Colour Explosion Proof Video Camera USER MANUAL VID-C

3M Cold Shrink Splice Kit QS-III 5514A

INSTALLATION INSTRUCTIONS WIRED REMOTE CONTROL USING TWISTED PAIR AND COAX CABLE U-WRC-U-x

3M Fiber Optic Splice Tray 2527 with 3M PLC Optical Splitter

Dynatel Advanced Cable Locator 2250

This Errata Sheet contains corrections or changes made after the publication of this manual.

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

Table 4-1: Rating Levels

AT&T CIB 3067 CALL ACCOUNTING SYSTEM (CAS) MODEL 100 (61370) ( )

INSTALLATION INSTRUCTIONS MODEL VSBX-236 LED 3 X 8 INDOOR SCOREBOARD

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

Low Profile Digital HDTV Over-the-Air Antenna CONTENTS

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

Built tough for long-term connections

1x4, 1x8, 1x12, 1x16 VGA Extender / Splitter over Single CAT5

Built tough for long-term connections

Sample Test Project. District / Zonal Skill Competitions. Skill- Electrical Installation. Category: Construction and Building Technology

User Manual rev: Made in Taiwan

Model Extend HDMI audio and video connections up to 300 feet. Add up to 8 additional receivers with a dedicated network switch

VGA Extender LR EXT-VGA-141LR. User s Manual

MX-VGA CABLE MX-2107 AND MX MDR Electronics

Example Transport Engineering Guide (TEG): DSX-1 Rear Cross Connect

VGA CAT-5 1:8 Distribution S VGA CAT-5 Distribution R. EXT-VGA-CAT5-148S EXT-VGA-CAT5-148R User Manual

Sections 1. Application Equipment 2. Cable Preparation 3. Assembly 4. Termination Procedure 5. Inspection 6. Repair 7.

American National Standard for Lamp Ballasts High Frequency Fluorescent Lamp Ballasts

HTP1502W1 Remote Controlled Multicolor Lighting System

3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes

Instruction Manual Model 5620 Power Controller

OWNER'S MANUAL SIGNAL COMMANDER

Installation Instructions

FOSC 450 C6 and D6 Closures

VGA & Audio over CAT5 Distribution Series

VideoSplitter HDMI 4K PT

INSTALLATION INSTRUCTIONS FOR. MODEL 2230LED

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF

SG4424 HDTV Slave Sync Generator User Guide

Transcription:

ADCP-80-348 DSX-1 Cross-Connect Procedures 4-12000-0069

DSX-1 CROSS-CONNECT PROCEDURES ADCP-80-348 Content Page 1. CROSS-CONNECT ROUTING RULE PARAMETERS... 1 2. CROSS-CONNECT CABLE TYPE, LENGTH, AND LEVELS... 2 3. DSX BAY ZONING AND CROSS-CONNECT GUIDELINES... 3 4. CROSS-CONNECT ROUTING RULES... 4 5. DSX-1 CROSS-CONNECT ROUTING PROCEDURE... 5 Disclaimer of Liability Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period. This publication may be verified at any time by contacting ADC s Technical Assistance Center at 1-800-366-3891, extension 3475 (in U.S.A. or Canada) or 612-946-3475 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc., Attn: Technical Assistance Center, Mail Station #77, 4900 West 78th Street, Minneapolis, MN 55435, U.S.A.

1. CROSS-CONNECT ROUTING RULE PARAMETERS ADCP-80-348 A. General Routing Rules 1.01 Several basic rules should be followed in routing cables to the DSX system: Input and output digital signals should always be in separate cables. DS1, DS1C, and DS2 cables should not be routed above bays or in a lineup associated with electromechanical or crossbar switching equipment. DS1, DS1C, and DS2 cables should not run parallel with power or ground cabling. C. Cross-Connect Types 1.03 The recommended types of cross-connect wire for each digital rate are: DSX-1 and DSX-1C non-shielded, tinned 24 AWG, twisted pair wire. DSX-2 Circuits Concentration Bay (CCB) type cross-connect cords for Bantam modules, and shielded pair 26 AWG wire with shield grounded at one end for Longframe (310) panels. B. Cross-Connect Lengths 1.02 The DSX cross-connect jumpers also add to digital signal-level losses depending on jumper length To assure reliable signal levels, maximum jumper lengths recommended for each DSX frame are: DSX-1 and DSX-1C: 85 feet (25.9 m). DSX-2: 15 feet (4.6 m). Page 1

ADCP-80-348 2. CROSS-CONNECT CABLE TYPE, LENGTH, AND LEVELS A. Cable Types 2.01 All DS1, DS1C, and DS2 cables should be shielded twisted pair with the shields grounded at one end only (preferably the equipment end). The recommended cable types are: DS1, 655 feet (200 m): AT&T 600C or equivalent. DS1, 450 feet (137 m): AT&T 1249 or equivalent. DS1C, 655 feet (200 m): AT&T 600C or equivalent. DS2, 1050 feet (320 m): AT&T 600C or equivalent. C. Signal Levels 2.03 Each DSX frame serves as an equal level transmission point, and all digital signals crossing a DSX frame must be maintained within a certain voltage range for each specific bit rate. The peak-tobase voltage ranges for DSX frames are: DSX-1: ± 2.4 to 3.6 volts (± 3.0 volts, nominal). DSX-1C: ± 2.3 to 4.2 volts (± 3.0 volts, nominal). DSX-2: ± 0.55 to 1.3 volts (± 1.0 volt, nominal). B. Cable Length and Gauge 2.02 The digital equipment terminated on the DSX frames have equalizers and/or pads which are adjusted for the particular cable lengths to maintain the proper transmission levels. The maximum cable length between digital equipment and DSX frames are governed by the specific items of equipment and cable gauges as follows: DS1 and DS-1C, 22 AWG: 655 feet (200 m). DS2, 22 AWG: 1050 feet (320 m). Page 2

3. DSX BAY ZONING AND CROSS-CONNECT GUIDELINES A. Cross-Connect Procedures ADCP-80-348 3.01 Figure 1 is a lineup of multiple DSX bays. Each bay is zoned in quadrants to provide the most efficient cross-connect scheme, maximizing the use of the vertical and horizontal wireways. When a cross-connect assignment is required, the following must be considered: If the originating equipment is in zone one or two, the cross-connect jumper(s) must route to the adjacent bay via the upper wireway. If the originating equipment is in zone three or four, the cross-connect jumper(s) must route to the adjacent bay via the lower wireway. Cross-connect jumper(s) must always be routed through vertical and horizontal wireways when crossing zones, except when cross-connecting within the same DSX panel. When cross-connecting within the same bay from zone one (upper left) to zone three (lower left), the cross-connect jumper(s) must transition through the vertical wireway only. HORIZONTAL VERTICAL HORIZONTAL ZONE ONE ZONE THREE BAY 1 BAY 2 BAY 3 ZONE TWO ZONE FOUR Figure1. DSX Bay Cross-Connect Scheme 5751-B Page 3

ADCP-80-348 4. CROSS-CONNECT ROUTING RULES A. Cross-Connect Cabling 4.01 Cross-connect jumpers should be routed as shown in Figure 2. Whenever a cross-connect changes direction, it should do so at a point where a ring, tray or fanning strip is placed. This allows the cross connect to be dressed neatly without strain or interference with any other portion of the bays. HORIZONTAL CROSS- CONNECT VERTICAL BAY 1 BAY 2 BAY 3 D E B A C C 4.02 All cross connect jumpers should use the horizontal cable ways between bays, and vertical cable ways within bays. To prevent unnecessary jumper buildup and congestion, all discontinued cross connects should be removed from the DSX cable ways. Jumpers should be sized to the proper length, including a maximum of 3 inches of slack at each end. Page 4 HORIZONTAL B D F A 1860-D ROUTING RULES A. All jumpers in the left-hand side of the cross-connect field should enter and leave the bay from the left vertical wireways. B. All jumpers in the right-hand side of the cross-connect field should enter and leave the bay from the right vertical wireways. C. All intrabay cross-connects should use the vertical rings except when terminations are in the same panel. D. All interbay cross-connects should use the horizontal wireways. E. All jumpers originating in the upper half of the cross-connect field should route via the upper horizontal wireways. F. All jumpers originating in the lower half of the cross-connect field should route via the lower horizontal wireways. Figure 2. Jumper Routing Rules

5. DSX-1 CROSS-CONNECT ROUTING PROCEDURE ADCP-80-348 5.01 Follow the standard operating procedures for the routing of cross-connects based on local practice. For DSX-1 Bays and Modules, ADC recommends the use of five conductor jumper wire consisting of two independently twisted pairs (Signal Transmission) and a binding wire (used for Tracer Lamp identification). (Refer to Section 1 Cross-Connect Routing Rule Parameters). 5.02 Follow the steps as defined in your local practice or those indicated below to run a DSX-1 Cross-Connect Jumper. 1. Once the equipment assignments have been determined, strip the open end of the jumper wire as it comes off the spool. Caution: After properly stripping jumper wires, inspect area to ensure the removed insulation and wire clippings did not fall or land in the confines of the DSX bay line up. 2. At the originating end of the cross-connect, terminate the jumper wires to the IN and OUT TN (tip normal) and RN (ring normal) wire wrap terminals respectively. Terminate the green jumper wire to the TL (tracer lamp) wire wrap terminal. Inspect the wire wrap connections (see Figure 3). TL TN OUT RN TN IN RN 5 CONDUCTOR WIRE CROSS-CONNECT TERMINAL BLOCKS TWISTED PAIRS (continued) Page 5 TL TN OUT RN TN IN RN Figure 3. DSX-1, DSX-1C Cross Connection 1418-A

ADCP-80-348 CONNECT ROUTING PROCEDURE, continued 3. Carefully route the cross-connect jumper wire towards the terminating equipment ensuring that the zoning and routing procedures are followed as defined in Section 3 and 4. Figure 4 provides a pictorial view of the paths to be followed when routing via the upper and lower wireways. 4. After the cross-connect has been properly routed, cut and strip the terminating end being careful to ensure the insulation and wire clippings do not fall into the DSX bays. 5. Repeat Step 2 for this end of cross-connect jumper. 6. Complete a final inspection of the cross-connect to ensure it is neat and properly placed within the wireways and the cable rings. BAY 1 BAY 2 BAY 3 BAY 4 5752-C Figure 4. Do not pull jumper too tight leave minimal slack and store evenly at each end (six inches total) Page 6

ADC Telecommunications, Inc. 4900 West 78th Street, Minneapolis, Minnesota 55435 In U.S.A. and Canada: 1-800-366-3891 Outside U.S.A. and Canada: (612) 946-3000 Fax: (612) 946-3293