PRESENTING A NEW METHOD TO ESTIMATE THE REMAINING LIFE OF AERIAL BUNDLED CABLE NETWORK

Similar documents
ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Condition Monitoring Program of HV Cable Systems

ENGINEERING COMMITTEE

640 kv XLPE HVDC cable system

CHAPTER 3. HV and EHV Cable System Aging and Testing Issues

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

Photovoltaic Module Installation Manual (IEC)

640 kv extruded HVDC cable system

HVDC cable accessories

3M Sensored Termination (15 kv) QX-T15I-vi1-E

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ANALYSIS OF FAILURE IN POWER CABLES FOR PREVENTING POWER OUTAGE IN ALEXANDRIA ELECTRICITY DISTRIBUTION COMPANY IN EGYPT

Photovoltaic Module Installation Manual (IEC)

Flygt Submersible Motor Cables

Cable Retention Force Testing of Trunk & Distribution Connectors

Cable installation guidelines

Instruction Manual MODEL RSP SANITARY ELECTRONIC PRESSURE TRANSMITTER

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

WELDING CONTROL UNIT: TE 450 USER MANUAL

Operating instructions

Lecture 18 Design For Test (DFT)

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SPECIAL SPECIFICATION 6559 Telecommunication Cable

INSULATION CONDITION OF DRY-CURED XLPE CABLES MEASURED OVER A PERIOD OF 13 YEARS

Instrumentation Cables

Highly Accelerated Stress Screening of the Atlas Liquid Argon Calorimeter Front End Boards

AMERICAN NATIONAL STANDARD

DEVELOPMENT OF A 270 kv XLPE CABLE SYSTEM FOR HVDC APPLICATION

AMERICAN NATIONAL STANDARD

Laying of cables and lines in electrical installations and data networks

How to Implement PoE in Your Harsh Industrial Environment

Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique

3M Super 23 Electrical Tape

C I R E D 19 th International Conference on Electricity Distribution Vienna, May Transition Joints Behaviour. Paper 457 INTRODUCTION

SnapStak Stackable Snap-In Cable Hanger Electrical and Mechanical Testing Performance

Introduction to Fiber Optic Cable Technology Jerry Bednarczyk, PE Course Content

LCS 2 RJ 45 Cat. 6A HD panels and units

Aging test: integrated vs. non-integrated splices shield continuity systems.

FLUID VIEW 12V LED TAPE LIGHT

THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS

EE028: Practical High Voltage Cable Jointing and Termination

ENGINEERING COMMITTEE Interface Practices Subcommittee. ANSI/SCTE (Formerly IPS SP 001)

Colour Explosion Proof Video Camera USER MANUAL VID-C

TRISHALA ELECTROLYTICS PVT LTD BANGALORE

How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997.

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN

Digital Indicating ORP Meter AER-101-ORP. Instruction Manual

ANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester

SPECIAL SPECIFICATION 2344 TMC Support Equipment

SATRI AMPLIFIER AMP-51R. Owner s Manual

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

SPECIAL SPECIFICATION 8540 Telecommunication Cable

LED Thunder S-150 Code 1097

Guidelines for Specification of LED Lighting Products 2010

Student Services & Classroom Addition

HDMI Demystified April 2011

Revision 1.2d

CPD LED Course Notes. LED Technology, Lifetime, Efficiency and Comparison

The use of an available Color Sensor for Burn-In of LED Products

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

BTC and SMT Rework Challenges

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

ACTIVE IF SPLITTER/COMBINER UHP-IFS

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

APPLICATION NOTE RAPID ELECTROCHEMICAL ASSESSMENT OF PAINT

Series CT7N Bimetallic Overload Relays

Wired Troubleshooting Manual

TEST WIRE FOR HIGH VOLTAGE POWER SUPPLY CROWBAR SYSTEM

GV2P05. Main. Device short name. Device application

3M Cold Shrink Splice Kit QS-III 5515A

T5, T8, TC-L. PC T5 PRO lp W V 50/60/0 Hz, HO. Electronic ballasts Linear lamps T5, T8 and compact lamps TC-L

PanelView 1400e CRT Maintenance

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

TeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40

USER MANUAL Table of Contents

POLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES

User Manual. 360W LED Moving Zoom KEEP THIS MANUAL FOR FUTURE NEEDS. 36pcs10W 4 in 1 RGBW LEDs

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 872 LIGHT EMITTING DIODE TRAFFIC SIGNAL LAMP UNITS JULY 19, 2002

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

LINK-RAY TM MODULATORS FOR CONSTANT- VOLTAGE. LinkRay Modulators 12 V / 24 V Constant-voltage Applications MODULATORS

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

High Voltage Cable Splicing Training

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7)

3M Cold Shrink Splice Kit QS-III 5514A

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

Installation of Optical Fiber

GV2ME. Main. Device short name. Device application

USER MANUAL Table of Contents

CR7000. CRT Analyzer & Restorer. Easily Test And Restore CRTs With The Most Complete Tests Available For Added Profit And Security.

Dimming actuators GDA-4K KNX GDA-8K KNX

LE062XF DCC Decoder for Atlas N Scale Locomotives

Transcription:

PRESENTING A NEW METHOD TO ESTIMATE THE REMAINING LIFE OF AERIAL BUNDLED CABLE NETWORK Azim NOWBAKHT Mehdi AHRARINOURI Mohammadreza MANSOURISABA Shiraz Electrical Dis.Co Iran Shiraz Electrical Dis.Co -Iran Shiraz Electrical Dis.Co -Iran F.nowbakht@gmail.com M_ahrarinouri@yahoo.com mansourisaba@yahoo.com ABSTRACT Today, the aerial bundled cables (ABC) are gradually finding their place in low voltage electrical network around the world and especially in the Middle East and respectfully Iran due to the benefits that are superior to the wired network. In recent years, around 70% of the low voltage power network in Iran has replaced by ABCs. This paper introduces a new method of ABC s life expectancy that can be useful for electrical network operators. They can be informed about the useful life of ABCs before serious damage happen and take remedial activities such as repair or replacement of the network. Firstly, the erosion processes in ABCs are introduced, and then using the factors of influence on the aging, and the math formula a chart for determine the remaining life of the ABC will be presented. INTRODUCTION During recent years, the process of changing bare copper wires to the aerial bundled cables (ABC) is accelerated so rapidly. Regarding the concern of ABC s lifetime, there is an important question among engineers and senior managers of the electrical distribution company that whether ABC is a good alternative for bare wire or not? Answering this question is highly related to determining the useful life of ABC as accurately as it could be. Obviously, due to the shorter lifetime of ABC insulator, this cable has a shorter lifetime than copper or aluminum wires. In order to find the true value of ABC s life, important factors and parameters in erosion should be recognized. Due to the growing use of ABC networks across the countries, poor information and maintenance instructions and procedures troubleshooting are highlighted. Based on the experience gained in the Shiraz Electricity Distribution Company (SHEDC) the most important factors in shortening the lifespan of the ABC network are not following the standard quality from the manufacturer and the use of nonstandard hardware and clamps. In return, correct maintenance and operation of the ABC network and unified set of instructions will be helpful [1]. To estimate the ABC life, it is required to specify the mechanisms that cause errors, failures and aging. It is possible that the cable insulator shield is corrupted during the construction, transportation or operation procedure, and so the insulator failure starting [2]. Partial discharge is another influencing factor that may results in breakdown. The main reasons of PD are built of voids and sharp electrodes [3, 4]. Water tree phenomenon is another aging mechanism in extruded cables [5].Besides, wrong cable operation and designing of cable size would be influential in life of cables. In the following sections the major influencing factors on aging are introduced. After that, by using the mathematical methods and experiments obtained in SHEDC a curve is proposed for life expectancy of ABC. 1. INFLUENCING FACTORS ON AERIAL BUNDLED CABLE LIFETIME REDUCTION Research shows that several factors are responsible of deterioration and reduction of the useful life of ABCs. Factors such as mechanical damage, moisture penetration to cable insulation which is caused by hardware installation, use of non-standard clamps and cultural factors of the area as well as weather conditions are the most important ones. Meantime, it is proven that the cable insulation play major role in cable useful life. As a result, the cable insulation is a good indicator for calculating the remaining life in the ABCs. So that it can be said that the determination of the time duration break down of the insulator in cable is equivalent to the remaining lifetime of ABCs. 2- AERIAL BUNDLED CABLE WITH POLY ETHYLENE CROSS LINKED INSULATOR Compared to the other cables, ABCs have better thermal specification, withstanding temperature, dielectric loss and installation cost. Cross linked cables are able to work up to 90 centigrade. Temperature increase has a great role in life time of insulator. The temperature increase affected by parameters such as the maximum working temperature allowed for cable, the environment temperature and cable insulation structure. Cable rated current must be designed to use throughout the year for the worst case and can withstand the highest temperature. With increasing temperature, the polymer material has major change in the chemical qualities which results in physical characteristics shifts. For this reason, protection the polymer used in cable especially at high temperatures to obtain the optimum time in operation is important. Due to the loss of the cable insulation at high temperatures, releasing of heat to the environment is an CIRED 2015 1/5

essential item. Moreover, the cable insulation must protect against the explosion of sunlight (UV). Research shows that black carbon is a good stabilizer for poly elfin. The presence of oxygen in the air causes rapid aging of the family of chemical compounds, polymers (including poly elfin) and factors such as temperature and light intensity this procedure [6]. The cross linking process is created by various conditions such as high temperature heating cable in the steam room. This process changes the chemical structure of PE that increases the threshold withstanding to heat. In relation (1) the chemical structure of XLPE insulator illustrated. ሻሺ + = = = ۶ = = ۶ Relation 1: Chemical structure of ABC insulator 3- FACTORS AFFECTING ABC LIFE TIME Research has shown that several factors affect the deterioration of aerial bundled cables network and reduce the useful life of them. Factors such as mechanical damage, scarring or penetration of moisture into the cable insulation through the fittings, use of non-standard clamps, cultural factors and weather conditions concerns. In this section, we mention a few effective indexes. 3-1 Cable Insulators There are several phenomena in nature that causes the loss of the cable insulation and the gradual deterioration of aerial bundled cables. Several factors such as clash of adjacent trees, dragging on the ground and on the sharp rocks, intentional injuring to catch unauthorized branching and non-implementation of standard clamps principally are make serious damage in cables. This eases the water penetration into the cable and creating the phenomenon of the water tree over time. In water tree phenomenon the water penetrates in the cable shell, and then converts to steam and causes the expansion [5]. This procedure causes small cracks in insulation layer and slowly grows so that the insulation properties decrease rapidly. Another influential parameter that creates the water tree is voltage. The initial water tree and its growth is a function of the electric voltage at that point. This voltage should be between conductor and insulation cable layer. The average voltage must be between 2 to 8 KV/mm and its frequency is 50 or 60 Hz. In figure (1) the water tree phenomenon is shown. Figure 1: The water tree phenomenon in PE cables Experimental results show that the cable insulating material has corrupted after 20 to 30 years of operation. Therefore, under the pressures, thermal and electrical stresses the XLPE insulator will be suffered greatly [8-10]. If there is no supervision on old cable insulation they are intended to absorb moisture and impurities much more than the new ones. So cable insulator is a good indicator for the remaining life of the cable. Another phenomenon which causes gradual loss of insulation is partial discharge, which is a critical process in cable lifetime. Usually partial discharge occurs in cable joints and terminal or the location of wounding the cables. It can be expanded with time and eventually lead to the defeat of the electrical insulation and collapse. Operators can reduce the cost of maintenance by determining the weak points and repairing or replacing it in wright time. So knowing the lifetime is essential. In general, determination of the duration left to the electrical breakup of cable insulation is called life estimation. Regular Service and maintenance would be very helpful in reliability and lifetime of cables. 3-2 Clamps One of the most influential factors in aging ABC is the use of nonstandard electrical connections. This may cause premature aging of the network. ABC insulator layer can be damaged by malfunction or mechanical pressure connectors and the rain water can easily penetrates through cable clamps. Therefore, the correct guidelines must comply with the implementation of the standard clamps and protect them against water penetration (such as placement of screw clamps to the top or use the rubber linings and grace in them). Notice that there is no permission to take off installing clamps from the network. The most common reasons for operation group rechecking are not tighten enough the closing screw clamps and not going down steel blade in the cable conductor. 3-3 Temperature Temperature plays a very prominent role in aging. In order to create the required temperature the electric current is used. Heat cycle can be 8-16 hours daily within a few days of the week. Average ambient temperature for each country and each region varies according to the region and weather conditions as well as the cable installation conditions. CIRED 2015 2/5

Maximum working temperature of cable in accordance with IEC287 standard for XLPE insulated cable is 90 degrees. Basically the length incensement due to short circuit currents causes expansion in cable conductor and creates problems such as longitudinal advance in multiwires cables or displacement. This is happen because of the effects of thermodynamic phenomena. This phenomenon creates electromagnetic force from short circuit currents in the cable that results in cable departure if the wires are not fasten tightly together, thus increasing the length of the cable with the temperature is inevitable. This increase will be more in aluminum than copper. The ABC cable characteristics necessitate length incensement during hot season even if short circuit not happens. Although cold weather of next year will partly compensate this length growth but over time the length of cable will get bigger. So cable length can be used as a marker for age detecting of cable. 4- MAKING ARTIFICIAL AGING IN LABORATORIES In order To create the sample ABCs with different lifetime in a laboratory an artificial aging is produced. This action can be done under the mechanical, thermal and electrical stresses which are caused by machines. In the lab to create the required temperatures a proper electrical current would pass through the cable in consecutive cyclic duration of 8 to 10 hours within a few days of the week. Basically, the large rise in the cable temperature resulting from short circuit currents are causing expansion of cable conductor. This expansion causes problems such as longitudinal advance or cable displacement. The increasing longitudinal property of cables can be used as an indicator for detection of the cable age. The aging action of one piece cable should be done according standard IEC811-1-2. To create lifetime of 5, 10 and 15 years the cable placed in an oven for a week and for 20 years of aging, the duration should be 2 weeks. The oven temperature should be changed so that it matches to natural conditions. In this test, three different temperatures of 60, 80 and 100 c is of interest, so that 50% of cable life is in temperature of 80 degrees, 25% at the temperature of 60 c and 25% of it spent in the fitted temperature to 100 degrees. To create erosion in wet environment, the cable can be put on the tank filled with water for a period of 4, 6 and 12 months. In Figure (2) this issue is illustrated. Voltage is the other affecting parameter in deterioration of the cable. At temperatures higher than 90 degrees, the crystals of insulation are melting and then oxidizing. This leads to the weakening insulation property of XLPE cable. To apply the electrical breakdown voltage (EBV) the needle test is used. This process is controlled by placing a needle into the cable insulation. The depth of the needle is variable and the duration of applied voltage determines the lifetime of cable. In figure (3) this subject is shown [12]. Figure 3: Electrical circuit diagram for breakdown voltage test 5- PRESENTING AGING FORMULA In this section by using the math functions and the introduced factors a formula for estimating the cable lifetime is presented. The age of the cable operation is modeled by a multi variable function with linear regression. In this function T is the age of cable in years and L is the increasing length and E is the electrical breakdown voltage (EBV). In formula (1), this function is shown. (1) ܧଷ + ܮଶ = ଵ + The a 1, a 2 and a 3 fixed constants and calculated by Eviews software which is one of the best among similar ones. This software calculates the constants by sum of squared residuals method. Putting them in formula (1) the relation (2) is reached. This relation hands out the estimation of cable lifetime. (2) ܧ 2.095 + ܮ 00435. 67.19 = According to results of needle tests, table (1) is calculated. In table (2) the lifetimes for different cables are calculated by relation (2). The actual data plots of cables length value and electrical breakdown voltage are shown in figure (3) and (4). Finally a comparison among EBV and cables length is done in figure (5). Table 1: The results of cable length increment and EBV Cable age (year) 0 5 10 15 20 Cable length increment (mm) EBV(kV) 1000 13.6 11000 11.6 1155 9.8 1270 8.8 1297 8.7 Figure 2: The water tank used in the laboratory CIRED 2015 3/5

Figure 3: Increasing the length of the cable according to the age of the cable. 6-CONCLUSION In this paper the calculation of remaining life of aerial bundled cables are addressed based on the research and experiences of other countries and leading distribution companies. Analysis the graphs of aging affecting factors in ABC network can produce suitable information for estimating the remaining lifetime. As a consequence, it is possible to answer the question that how long the ABC network will be work properly? It should be noted that other effective factors in deterioration of cable networks are the rate of unauthorized branches, intentional wounding and climate changing that has a great effect on grid collapse. Figure 4: Electrical breakdown voltage vs time. Figure 5: Comparing diagram of EBV and cables length according to the age of the cable. Cable age (year) 14 6 8 Table 2: The remaining life of cable EBV(kV) Cable Remaining length lifetime increment (year) (mm) 9.2 1250 4.97 7.8 1090 12.3 10.3 1150 13.4 REFERENCES [1] La Salvia, J.A., 2006, Technological Components for an Anti-Theft System in Overhead Networks Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES, Page(s): 1307 1314. [2] Ariffin, Mohd Faris, 2009, Development and improvement of medium voltage aerial bundled cable system design in TNB distribution network Tenaga Nasional Berhad Malaysia 8-11 June [3] IEC 60270, 2000, High-voltage test techniquespartial discharge measurement [4] Cheng Yonghong, Chen Xiaolin, Rong Mingzhe, and Yue Bo, 2003, Study on the Partial Discharge Characteristics of the XLPE Insulation Samples during Electrical Treeing Ageing Proceedings of the 7th International Conference on Progenies and Applications of Dielectric Materials June 1-5 Nagoya, pp:211-214 [5] Suh Joon Han.2012, Evaluation of semiconductive shields on wet agingperformance of solid dielectric insulated power cables Electrical Insulation and Dielectric Phenomena (CEIDP)2012, Page(s): 819-822 [6] Hossein Borsi, 2002, Long Term Behavior of Polymer Insulating Systems, lecture 2004, IRAN [7] S.B. Dalal, Prediction of Future Performance of In- Service Cross-Linked Polyethylene Cables Arizona Statement University [8]S.B. Dalal, 2004, A New Approach for Condition Assessment of Cross-Linked Polyethylene Insulated Distribution Cables Arizona Statement University [9] Bostorm, E Marsden, 2003, Electrical stress enhancement of contaminants in XLPE insulation used for power cables, IEEE electrical insulation magazine July/August Vol. 19, No.4 [10] Farad Shahnia, A. Mashhad Kashtiban, K. Roughen Milani, M. Trader Hague, 2006, Insulation Effects and Characteristics of XLPE Covered Overhead Conductors in Low and Medium Voltage Power Distribution systems in Iran Conference IEEE CIRED 2015 4/5

International Symposium on Electrical Insulation [11] Pablo A.S, 2005, Electric Power Distribution, 5th Edition, Tata McGraw-Hill, New Delhi [12]Kicker C.J., Reid G.D, 2009, Is broadband over power-lines dead? Telecommunication Networks and Applications Conference (ATNAC), 10- Australasian 12 Nov. [13]Melo Nobrega, Alencar de Queiroz, 2013 Investigation and analysis of electrical aging of XLPEinsulation for medium voltage covered conductors manufactured in Brazil Dielectrics and Electrical Insulation, IEEE Transactions on Volume: 20, Issue: 2, Page(s): 628 640. CIRED 2015 5/5