3933 US ROUTE 11, CORTLND, NEW YORK 1345 Phone Number: 1-8-345-3851 Fax Number: 67-758-3648 PROJECT NO.: 3138572-311 REVISED DTE: December 13, 27 TEST REPORT NO.: 3138572CRT-1b RENDERED TO: Superior Essex 15 Interstate North Pkwy Suite 3 tlanta, G 3339 Network Solutions 2222 222nd SE Bothell, W 9821 TEST: Performance testing of the cabling configurations as defined in and to the requirements of TI/EI-568-B.2-1 draft 9., Transmission Performance ification for 4 Pair Ω ugmented Category 6 Cabling. STTEMENT OF LIMITTIONS: t the client's request, the purpose of this report is to provide electrical performance data on the test sample. It is not valid to use this report for any other purpose. STNDRDS USED: STM D4566-98, Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable, dated December 1, 1998 TI/EI-568-B.2-1 draft 9., Transmission Performance ifications for 4 Pair, Ω ugmented Category 6 Cabling, dated September 26, 27 UTHORIZTION: The project was authorized by, Gayle Watson, representing the client, Superior Essex, with purchase order No. 14722 DTE OF TEST: December 6, 27 n independent organization testing for safety, performance, and certification. Page 1 of 3 This report is for the exclusive use of Intertek's and is provided pursuant to the agreement between Intertek and its. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the is authorized to copy or distribute this report and then only in its entirety. ny use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Test.: 3138572CRT-1b Revised date: December 13, 27 TEST REPORT REVISION HISTORY: First issue: December 7, 27 Original Document Second issue: December 13, 27 Name change to Network Solutions, consolidate appendixes SMPLE DESCRIPTION: (4 Connectors Channel, bundled in a 6 around 1 configuration) Component ID Manufacturer Part Number 1 6S1-7S Equipment Cord 2 6S1-1S Equipment Cord 2 611G Wall Outlet 4 Superior Essex 4PR 22WG 1GIN CMP CT 6 Page 2 of 3 Horizontal Cable 5 41B6-1F4 Cat. 6 11 connecting block The samples were received on November 19, 27 and were in good condition. ll samples were supplied by the client. EQUIPMENT LIST: The following equipment was employed in conducting the tests. Model Equipment Used Number Serial Number Calibration Date Hewlett Packard utomatic Cable Test System HP46152 393U3 3/7/7 PROCEDURE: The testing was performed in accordance with the measurements and calculations list below. Measurements: ttenuation (Insertion Loss): STM D4566-98 Paragraph 26 Near End Cross Talk (NEXT): STM D4566-98 Paragraph 24 Far End Cross Talk (FEXT): STM D4566-98 Paragraph 25 Return Loss: STM D4566-98 Paragraph 45.3 Transverse Conversion Loss (TCL): TI/EI-568-B.2-1 draft 9. Paragraph 7.6.1 Transverse Conversion Transfer Loss (TCTL): TI/EI-568-B.2-1 draft 9. Paragraph 7.6.2 lien Near End Cross Talk and lien Far End Cross Talk (NEXT and FEXT): TI/EI-568-B.2-1 draft 9. nnex D Calculations: Power Sum NEXT (PSNEXT): STM D4566-98 Paragraph 26 and TI/EI-568-B.2-1 draft 9. Paragraph 7.2.2 ttenuation to Crosstalk Ratio Far End (CRF): STM D4566-98 Paragraph 25 and TI/EI-568- B.2-1 draft 9. Paragraph 7.3
Test.: 3138572CRT-1b Revised date: December 13, 27 Power Sum ttenuation to Crosstalk ratio Far End (PSCRF): STM D4566-98 Paragraph 25 and TI/EI-568-B.2-1 draft 9. Paragraph 7.3.3 ttenuation to Cross Talk Ratio (CR): ttenuation to Cross Talk Ratio was determined by subtracting the ttenuation from the NEXT Power Sum CR (PSCR): The Power Sum CR was determined using the same procedure as CR except that the Power Sum NEXT was used in the computation in lieu of the NEXT Propagation Delay and Delay Skew: TI/EI-568-B.2-1 draft 9. Paragraph 7.5 Equal Level Transverse Conversion Transfer Loss (ELTCTL): TI/EI-568-B.2-1 draft 9. Paragraph 7.6.2.3 lien Power Sum NEXT (PSNEXT): STM D4566-98 Paragraph 26 and TI/EI-568-B.2-1 draft 9. Paragraph 7.8 Power Sum ttenuation to lien Crosstalk Ratio Far End (PSCRF): STM D4566-98 Paragraph 25 and TI/EI-568-B.2-1 draft 9. Paragraph 7.9 REQUIREMENTS: The testing requirements were computed with the measurements and calculation list below. Measurements: Insertion Loss (ttenuation): TI/EI-568-B.2-1 draft 9. Paragraph 7.3 Near End Cross Talk (NEXT): TI/EI-568-B.2-1 draft 9. Paragraph 7.2.4 Return Loss: the TI/EI-568-B.2-1 draft 9. Paragraph 7.5 Calculations: Power Sum NEXT (PSNEXT): TI/EI-568-B.2-1 draft 9. Paragraph 7.2.2.2 ttenuation to Crosstalk Ratio Far End (CRF): TI/EI-568-B.2-1 draft 9. Paragraph 7.3.2 Power Sum ttenuation to Crosstalk Ratio Far End (PSCRF): TI/EI-568-B.2-1 draft 9. Paragraph 7.3.3.2 Propagation Delay: TI/EI-568-B.2-1 draft 9. Paragraph 7.5.2 Delay Skew: TI/EI-568-B.2-1 draft 9. Paragraph 7.5.4 Transverse Conversion Loss (TCL): TI/EI-568-B.2-1 draft 9. Paragraph 7.5.4 Equal Level Transverse Conversion Transverse Loss (ELTCTL): TI/EI-568-B.2-1 draft 9. Paragraph 7.6.2.3 Power Sum lien Near End Crosstalk (PSNEXT): TI/EI-568-B.2-1 draft 9. Paragraph 7.3 Power Sum ttenuation to lien Crosstalk Ratio Far-End (PSCRF): TI/EI-568-B.2-1 draft 9. Paragraph 7.9.3 RESULTS: See appendix for test results. CONCLUSION: The channel configurations, as previously described and supplied by the client, were tested in accordance with the procedures contained herein, and did comply with the indicated applicable transmission requirements. The testing was performed at Intertek ETL SEMKO located in Cortland, New York. These procedures and requirements were taken from the standards referred to on page Reviewed and pproved By: ntoine Pelletier Engineer Global Cabling Products Testing Global Cabling Products Testing Kathy Heath Project Coordinator Global Cabling Products Testing Page 3 of 3
Test.: 3138572CRT-1b Revised date: December 13, 27 ppendix Test results ny data reported above 5 MHz is for indication only. This appendix contains 5 pages.
ification TI 568B2-1 - ugmented Cat 6 Draft 9_ 5Mhz(Channel) 12/4/27 9:39:14 M Temperature Superior Essex with [Param7] 3138572CRT-1 2 C Limit Margin :.433 @ 312 MHz Insertion Loss Insertion Loss -1-3 -5-6 8 3.6 5.1 5.7 7.2 1 9.1 2 16 17 3.6 45.5 53.8 8 3.5 9 5.5 7. 7.8 7 9.8 11 1 29.4 43.5 5.6 2.3 2 5.8 6.5 2 9.2 3 15 4 9 33.9 49.4 uency (MHz) : (Blue - WorstCase, Green - ) Limit Margin : 775 @ 495.338 MHz Return Loss Return Loss -1-3 -5-6 37.2 29.8 26.8 22 27 3 27 39.1 22.7 33.4 22. 13.8 15.7 45.3 33 36.8 35.7 35.1 32.4 42.5 46.3 4.6 4.8 3.8 19.9 22 19. 19. 19. 19. 1 17.5 17. 5 1 12. 6. uency (MHz) : (Blue - WorstCase, Green - ) Page 1
ification TI 568B2-1 - ugmented Cat 6 Draft 9_ 5Mhz(Channel) 12/4/27 9:39:14 M Temperature Superior Essex with [Param7] 3138572CRT-1 2 C Limit Margin : 3.176 @ 47388 MHz NEXT NEXT -1-3 -5-7 -9-11 83.9 74 7.3 69.5 66.1 65.1 64 56.4 52.9 49.6 45 35. 34 99 82.7 76.2 76.8 72 72.2 7.8 7.3 62.6 51 53 43.2 4.2 65. 63. 52 56.6 53.2 56 5. 44 43.4 39.9 33.1 26.1 uency (MHz) : (Blue - WorstCase, Green - ) Limit Margin : 5.462 @ 47793 MHz PSNEXT PSNEXT -1-3 -5-7 -9 8 77 65.3 66.4 63.9 62. 59.4 55.9 56 47.6 43.8 33.3 29.6 89 75.5 69.3 69.5 67.3 65. 6 62 56. 54 46.4 36.4 38 62. 6.6 55.6 5 5.6 49. 47.3 45.7 4.6 37.1 3.2 23.2 uency (MHz) : (Blue - WorstCase, Green - ) Page 2
ification TI 568B2-1 - ugmented Cat 6 Draft 9_ 5Mhz(Channel) 12/4/27 9:39:14 M Temperature Superior Essex with [Param7] 3138572CRT-1 2 C Limit Margin : 7.344 @ 47.982 MHz CR CR 8 6 4 2 82.1 7.8 65.2 63.8 59 57.2 52.3 46.4 33 3 14-6 -22.4 9.1 79.1 71 72 61 68 6.2 41 39.6 21-4 -16 7. 59. 52.4 5.2 45.1 42.6 39.9 37. 27.1 19.2 -.7-23.2 uency (MHz) : (Blue - WorstCase, Green - ) Limit Margin : 9.6 @ 6.589 MHz PSCR PSCR 8 6 4 2 79.3 62 6.3 6.8 56.7 51 5.6 45.9 37.2 29.1 13.8-19 -22 83.1 72. 63 63.8 6.2 57. 55. 52 46 33. 3-1 -19.7 67.6 56.5 49.9 47.6 42.5 39.9 37.2 33 23 3-3.6-26.1 uency (MHz) : (Blue - WorstCase, Green - ) Page 3
ification TI 568B2-1 - ugmented Cat 6 Draft 9_ 5Mhz(Channel) 12/4/27 9:39:14 M Temperature Superior Essex with [Param7] 3138572CRT-1 2 C Limit Margin : 516 @ 17.994 MHz CRF CRF -6-8 - 76.9 69 59.7 58 56.9 55.8 56 52.2 32 4.4 32.9 27 24 83.7 72.2 66.6 65.2 62.4 67 63.2 52 4 49. 33 3.9 32.1 62.7 52 45.2 43.3 39.2 37.2 35.3 33.4 27.3 23.3 15.3 9.3 uency (MHz) : (Blue - WorstCase, Green - ) Limit Margin : 12.322 @ 62.23 MHz PSCRF PSCRF -6-8 - 73 62.9 57.6 56.4 51 53.5 52.7 5. 36.8 38 32 9 23. 76.7 65.2 59.7 54 55.9 55.6 55.7 52.2 4.4 42.3 39 23.7 1 59.7 42 42.2 4.3 36.2 32 32.3 3.4 23 3 12.3 6.3 uency (MHz) : (Blue - WorstCase, Green - ) Page 4
ification TI 568B2-1 - ugmented Cat 6 Draft 9_ 5Mhz(Channel) 12/4/27 9:39:14 M Temperature Superior Essex with [Param7] 3138572CRT-1 2 C Limit Margin :.32 @ 352.448 MHz PSNEXT PSNEXT -5-6 -7-8 -9 87.6 85.4 79.6 76 77 75.7 72.9 77 67.1 65.3 6. 56.5 55.2 86 86.5 83.3 82. 79. 77. 76.2 73.9 7.1 68 61 59.6 56.2 66. 65.1 62. 6. 5 49.5 uency (MHz) : (Blue - WorstCase, Green - ) Limit Margin : 2 @ 496.962 MHz PSCRF PSCRF -1-3 -5-7 -9 89 72. 66.4 65 6.4 53 56.4 54 4 44 35.7 26.1 12 83.7 73.5 67.7 65.9 68 59.8 5 56.2 5. 46.2 37.5 28 27 65. 59 57. 52.9 5 49. 47.1 41 37. 29. 23. uency (MHz) : (Blue - WorstCase, Green - ) Page 5