Summary of Meeting and Actions

Similar documents
Expert Workgroup on Fast Fault Current Injection stage 1 Terms of Reference

Frequency changes during large system disturbances workgroup, phase 2 (GC0079)

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

GC0100/101/102 Code Administrator Consultation Responses. Rob Wilson. Grid Code Panel 8 th Feb 2018

FCP Project Summary report

South Australian Energy Transformation

Grid Code Review Panel Meeting

Laser Beam Analyser Laser Diagnos c System. If you can measure it, you can control it!

Stage 05: Draft Final Modification Report

ELIGIBLE INTERMITTENT RESOURCES PROTOCOL

Primary Frequency Response Ancillary Service Market Designs

May 26 th, Lynelle Briggs AO Chair Planning and Assessment Commission

Mitigation of Cascading Outages and Prevention of Blackouts:System-Wide Corrective Control

Hornsdale 2 Wind Farm. FCAS Capability Test Plan

The new BBC Scotland Channel: Proposed variation to Ofcom s Operating Licence for the BBC s public services. BBC Response

Real Time Monitoring for SMART Grid Initiatives Synchronized Measurement & Analysis in Real Time SMART program by

9I273 01/10/2012 COU-03/0 AUTOMATIC CHANGEOVER UNIT TO BACK-UP AMPLIFIER

TIME-COMPENSATED REMOTE PRODUCTION OVER IP

BBC Trust Changes to HD channels Assessment of significance

Form C: Type Test Verification Report

Form C: Type Test Verification Report

RX40_V1_0 Measurement Report F.Faccio

NERC Reliability Standard PRC-024 Generator Frequency and Voltage Protective Relay Settings

Notes Generator Verification SDT Project

Symmetrical Services Over HFC Networks. White Paper

w w w.w h y t e t e c h n o l o g i e s.c o m.

Using the MAX3656 Laser Driver to Transmit Serial Digital Video with Pathological Patterns

Market Index Definition Statement Review 2011 ISG Recommendations

University of Tennessee at Chattanooga Steady State and Step Response for Filter Wash Station ENGR 3280L By. Jonathan Cain. (Emily Stark, Jared Baker)

Flicker Caused by Operation of Industrial Technology

db Broadcast reflect on their role in the largest broadcasting engineering project ever undertaken in the UK Digital Switchover

Joint submission by BBC, ITV, Channel 4, Channel 5, S4C, Arqiva 1 and SDN to Culture Media and Sport Committee inquiry into Spectrum

The BBC s services: audiences in Northern Ireland

Advanced Coding and Modulation Schemes for Broadband Satellite Services. Commercial Requirements

Improved Synchronization System for Thermal Power Station

National Park Service Photo. Utah 400 Series 1. Digital Routing Switcher.

data and is used in digital networks and storage devices. CRC s are easy to implement in binary

Policy on the syndication of BBC on-demand content

PLANNING STUDIES INTO THE ALL-DIGITAL FUTURE AND DIGITAL SWITCH-OVER SCENARIOS

Grid Code Modification Register. March 2018

Broadcasting Order CRTC

ECE 5765 Modern Communication Fall 2005, UMD Experiment 10: PRBS Messages, Eye Patterns & Noise Simulation using PRBS

User Guide Stand-Alone Metering for OptiPlant

The Art of Low-Cost IoT Solutions

Digital noise floor monitoring (DNFM)

Sidney Myer Music Bowl Noise Management Plan. November 2016

Emerging Subsea Networks

AMEK SYSTEM 9098 DUAL MIC AMPLIFIER (DMA) by RUPERT NEVE the Designer

, Participant Code # Item Topic Lead Action Documents

NOTICE. The information contained in this document is subject to change without notice.

Appendix II Decisions on Recommendations Matrix for First Consultation Round

DIGITAL COMMUNICATION

DMX-LINK QUICK OPERATION

INTERIM ADVICE NOTE 109/08. Advice Regarding the Motorway Signal Mark 4 (MS4)

NOTIFICATION OF A PROPOSAL TO ISSUE A CERTIFICATION MEMORANDUM

Submission to: A Future for Public Service Television: Content and Platforms in a Digital World - A Public Inquiry: Chaired by Lord Puttnam

IT S ABOUT (PRECISION) TIME

MARKET OUTPERFORMERS CELERITAS INVESTMENTS

Licence for the transmission of digital terrestrial television multiplex service

Frequency Response Initiative Generator Event Survey. NERC Resources Subcommittee North American Generator Forum December 8, 2016

NH 67, Karur Trichy Highways, Puliyur C.F, Karur District UNIT-III SEQUENTIAL CIRCUITS

Capital Works process for Medium Works contracts

Name Initials Position

Prototyping an ASIC with FPGAs. By Rafey Mahmud, FAE at Synplicity.

Operating licence for the BBC s UK Public Services

PRACTICAL PERFORMANCE MEASUREMENTS OF LTE BROADCAST (EMBMS) FOR TV APPLICATIONS

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

R G Alcorn, W C Beattie. The Queen s University of Belfast

An Introduction to the Spectral Dynamics Rotating Machinery Analysis (RMA) package For PUMA and COUGAR

-Technical Specifications-

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

Practical Application of the Phased-Array Technology with Paint-Brush Evaluation for Seamless-Tube Testing

Simulation of DFIG and FSIG wind farms in. MATLAB SimPowerSystems. Industrial Electrical Engineering and Automation.

The BBC s services: audiences in Scotland

WINTER 15 EXAMINATION Model Answer

PSB Annual Report 2015 PSB Audience Opinion Annex. Published July 2015

D PSB Audience Impact. PSB Report 2011 Information pack June 2012

Reciprocating Machine Protection

Ofcom's proposed guidance on regional production and regional programming

Case Study Meeting Demand with Automation: Luminator Aerospace Ramps Up Backlit Sign Testing Using ProMetric Imaging Colorimeters

Digital Signal Processing

Signalling Cable Equivalent Sizes

Energy Efficiency Labelling for Televisions A guide to the Commission Delegated Regulation (EU) 1062/2010

In accordance with the Trust s Syndication Policy for BBC on-demand content. 2

Response to the "Consultation on Repurposing the 600 MHz Band" Canada Gazette, Part I SLPB December, Submitted By: Ontario Limited

ONE-WAY DATA TRANSMISSION FOR CABLE APPLICATIONS WEGENER COMMUNICATIONS, INC.

Vignana Bharathi Institute of Technology UNIT 4 DLD

Request for Proposals

COMMUNICATIONS OUTLOOK 1999

OPERATOR MANUAL OSD390 SERIES 4 CHANNEL VIDEO/AUDIO/DATA FIBER OPTIC TRANSMISSION SYSTEM

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

6.UAP Project. FunPlayer: A Real-Time Speed-Adjusting Music Accompaniment System. Daryl Neubieser. May 12, 2016

S4C Authority Bulletin - October 2004

International Civil Aviation Organization METEOROLOGY PANEL (METP) FIRST MEETING. Montréal, Canada, 20 to 24 April 2015

0.1. Outage Management Process Summary

MODE FIELD DIAMETER AND EFFECTIVE AREA MEASUREMENT OF DISPERSION COMPENSATION OPTICAL DEVICES

of New York, Inc. Original Sheet No. 81 SCHEDULE 3 Black Start Capability

BBC S RELEASE POLICY FOR SECONDARY TELEVISION AND COMMERCIAL VIDEO-ON-DEMAND PROGRAMMING IN THE UK

T ips in measuring and reducing monitor jitter

OTD-3000 FREQUENCY AGILE TELEVISION DEMODULATOR INSTRUCTION MANUAL

Transcription:

Meeting Name Frequency Response Working Group Meeting No. 9 Date of Meeting Wednesday, 28 th April 2010 Time Venue 10:00am 3:00pm Conference Room B2-1, National Grid House, Warwick This note outlines the key action points from the ninth meeting of the Frequency Response Working Group. 1) Apologies for Absence Apologies were received from John Welsh (Scottish Power Systems), Damien McCool (Scottish Power Renewables), Dan Jerwood (GDF SUEZ Energy UK), Bridget Morgan (Ofgem) and Mark Baker (Scottish Power). 2) Minutes from Previous Meeting The draft minutes of the Grid Code/BSSG Frequency Response Working Group meeting held on 15 th February 2010 were approved subject to some agreed amendments and will be accessible from the National Grid Code Website. TI also took away an action to contact Damien McCool to see if he would be continuing with the Working Group. 3) System Inertia ACTION: TI In previous meetings it had been discussed that many new and renewable generation technologies do not inherently contribute to system inertia which would result in an increased rate of change of system frequency following a generation loss. AJ added some depth to the subject with a presentation on System Inertia. He ran through a number of scenarios in which various amounts of generation were tripped off the system and the corresponding requirements for Frequency Response and System Inertia to maintain the frequency above 49.2 Hz were determined. He showed that by halving the inertia on the system you will need to increase the number of machines selected for Frequency Response (which increases overall system operating cost) otherwise the frequency will dip below the 49.2 Hz threshold. For a large system loss (e.g. 1800MW) the amount of frequency response required increases substantially as a result of the increased rate of change of frequency fall. AJ also noted that it would be possible for new and renewable generation technologies to be able to contribute to System Inertia by a modification to the control system. Three wind turbine manufacturers have published information on such systems and discussions are still on-going with other manufacturers. Since the control systems would rely on a df/dt control, which is a noise amplifying process, some consideration will need to be given to adequate filtering. It is suggested such a facility would only be applicable to plant operating in Limited Frequency Sensitive Mode and that a dead band be put in place around ±0.003 Hz/s to minimise wear on the generator, however this value is based on past experience and further evaluation is needed. It was also noted that Hydro Quebec specify the requirement for a equivalent inertia constant of 3.5s in their Transmission System Connection requirements. In addition, the proposed European Grid Code also includes requirements for the provision of synthetic inertia. AJ concluded that there needs to be coordination between requirements for inertia, delivery of primary response and delivery of secondary response. Issues such as control systems dynamics, dead band and complexity need to be taken into account when considering such a requirement. The group commented that there would need to be close liaison with the manufacturers and that they need to be clear about what they can do to help contribute towards system inertia. Page 1

After looking at the models it was questioned why the step change after tripping appeared to be the same regardless of the system inertia. AJ explained that the Digsilent Power Factory Model used in the examples shown during the presentation where based on synchronous generator models only where there is direct coupling between the mechanical turbine and. AJ further outlined that due to the conservation of energy, the total energy delivered to the system by the Synchronous Generation, at the instant of the Generation loss, must equal the instantaneous demand, which would take place irrespective of the inertia. Immediately after the generation loss, the mismatch in generation and demand will be reflected by a drop in speed, the rate of fall frequency fall being dependant upon the stored energy in the rotating mass, the size of which would be dependant upon the inertia. However, as the stored energy in the rotating mass is lower in the case with lower inertia, the speed falls more quickly which in turn results in a faster rate of change of system frequency and a larger reduction in demand. In summary, the supplied energy from the rotating masses is equal to the area under the power / time curve not the instantaneous power delivered at the time of the loss. It should also be noted that where the turbine is decoupled from the generator (eg via power electronics), such as in a doubly fed wind turbine or full converter wind turbine, then the active power output of the generator will not be affected by changes in the system frequency or deviations in system frequency, and hence the short term power injected into the network is zero unlike that of a synchronous machine. Whilst looking at the models the group also commented that it appeared inertia was required immediately at the inception of the generation loss. It was explained that system inertia affects the initial rate of change of frequency before slower acting primary response and secondary response act to subsequently contain and correct the frequency fall. It was also discussed that any solution developed should be tested against the frequency limit of 49.2 Hz and the df/dt limit based on the G/59 setting of 0.125 Hz/s as a starting point. 4) Future Response Market Options Matrix RT provided a matrix of possible solutions that the group went through and discussed the merits of each option to decide if it was feasible or not. The matrix had three ways of grouping frequency response, by generating unit, company portfolio and by technology. These groups were then compared with whether it would be feasible to trade capacity, delivery, both or neither within each of the three groups. This matrix was then considered from the perspective of the, and to determine which party should have the requirement to procure Frequency Response. Below is an initial summary of the matrix discussed: Capacity Delivery Both Neither Generating Unit Company Portfolio Technology Key Current Provision Feasible Option Non Feasible Option Option 1 The general response to the matrix was that there are options within all three groups that seem to have the possibility of offering a feasible solution. However, initial analysis Page 2

seemed to suggest that a number of portfolio or technology specific solutions, whilst technically feasible, may to be too impractical or costly to implement. It was commented by one member of the group that, allowing each technology to provide a level of Frequency Response best suited to it might be the most cost effective option, as it would not put expensive and uneconomical requirements on generators. However, it was also pointed out from a system security perspective that, if each technology only produced a level of Frequency Response in relation to its ability and not the requirements of the system, it could leave the system without adequate Frequency Response. In regards to the portfolio option it was noted that a portfolio could arguably be one unit or a number of units but when any company acquires new units it would alter its Frequency Response requirements and it could be a difficult and costly to setup and monitor. It was noted, mainly within the generating unit group of the matrix rather than company portfolio and technology, that there seemed some benefit in placing the obligation on s to procure Frequency Response in proportion to the amount of generation they needed to meet their expected demand. This would allow the correct amount of Frequency Response to be available for any given level of demand, as well as helping s to understand the benefits associated with services such as Frequency Response. The group also commented that demand is a useful and flexible way to respond to a frequency situation but in the past suppliers have not been able to actively participate to Frequency Response due to the technology. ACTION: TI clarify matrix In discussing the possibility of a Frequency Response market, one group member commented that a clearly defined obligation to provide Frequency Response is necessary and it has to be clearly stated. If a clear definition is not contained within the Grid Code it will make it very difficult for manufacturers to know what requirements they must apply when designing their generation units. A market would also need to give suitable signals far enough in advance in order to be effective as well as having a framework in place that makes it lucrative enough to attract investment. It was noted that a Cost Benefit Analysis (CBA) would need to be carried out on the various options that the group puts forward. The CBA would also need to take into account issues such a stress on turbines and that response might not be the 10% that currently stands. By carrying out a CBA for each of the options it will be possible to determine the best overall cost option for industry. 5) Options going forward After discussions around the Future Response Options Matrix, the group agreed on three main areas to investigate further: 1. A possible Grid Code obligation solution - Action on MA 2. a) A Frequency Response Market solution - Action on TI b) A Frequency Response Market for delivery - Action on RT 3. Economic Tests that would be applied to a solution - Action on RT These actions were taken away and progress will be reported at the next Working Group meeting. 6) Next Meeting The next two meetings of the Working Group are to be agreed via email, possible dates below. 1. 1 st June or 3 rd June [later confirmed as 1 st June 2010-10:30am start] 2. Between 6 th and 8th July [later confirmed as 8 th July 2010-10:00am start] All to be held at National Grid House, Gallows Hill, Warwick. Page 3

Page 4

Appendix 1 Working Group Attendance Members Present: Tom Ireland TI Working Group Chairperson Thomas Derry TD Technical Secretary Antony Johnson AJ National Grid Chris Hastings CH Scottish-Southern William Hung WH National Grid Stephen Curtis SC National Grid Bob Nicholls BN E.ON UK Claire Maxim CM E.ON UK Mike Chowns MC RWE Malcolm Arthur MA National Grid Francois Luciani FL British Energy Raoul Thulin RT RWE Chris Proudfoot CP Centrica Apologies: Mark Baker MB Scottish Power John Welsh JW Scottish Power (DNO Representative) Damian McCool DM Scottish Power Renewables Dan Jerwood DJ GDF SUEZ Energy UK Bridget Morgan BM Ofgem Page 5