DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC Installation type Fixed Release system Thermomagnetic release Construction size NZM1 Number of poles 3 pole Standard equipment Box terminal Switching capacity 400/415 V 50 Hz I cu ka 36 Rated current = rated uninterrupted current Rated current = rated uninterrupted current I n = I u A 160 Setting range Overload trip I r A 125-160 Short-circuit releases Non-delayed I i = I n x 1280 A fixed Short-circuit releases max. A 1280 Technical data General Standards IEC/EN 60947 Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Ambient temperature, storage C - -40 - + 70 Operation C -25 - +70 Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 Safe isolation to EN 61140 g 20 (half-sinusoidal shock 20 ms) Between auxiliary contacts and main contacts V AC 500 between the auxiliary contacts V AC 300 Mounting position Vertical and 90 in all directions 08/26/2018 Eaton 283296 ED2018 V47.0 EN 1 / 9
With XFI earth-fault release: - NZM1, N1, NZM2, N2: vertical and 90 in all directions with plug-in unit - NZM1, N1, NZM2, N2: vertical, 90 right/left with withdrawable unit: - NZM3, N3: vertical, 90 right/left - NZM4, N4: vertical with remote operator: - NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90 in all directions Direction of incoming supply as required Degree of protection Device In the operating controls area: IP20 (basic degree of protection) Enclosures With insulating surround: IP40 With door coupling rotary handle: IP66 Terminations Tunnel terminal: IP10 Phase isolator and strip terminal: IP00 Other technical data (sheet catalogue) Temperature dependency, Derating Circuit-breakers Rated current = rated uninterrupted current I n = I u A 160 Rated surge voltage invariability U imp Main contacts V 6000 Auxiliary contacts V 6000 Rated operational voltage U e V AC 690 Overvoltage category/pollution degree III/3 Rated insulation voltage U i V 690 Use in unearthed supply systems V 690 Switching capacity Rated short-circuit making capacity I cm 240 V I cm ka 121 400/415 V I cm ka 76 440 V 50/60 Hz I cm ka 63 525 V 50/60 Hz I cm ka 24 690 V 50/60 H Ic ka 14 Rated short-circuit breaking capacity I cn I cn Icu to IEC/EN 60947 test cycle O-t-CO Icu ka 240 V 50/60 Hz I cu ka 55 400/415 V 50/60 Hz I cu ka 36 440 V 50/60 Hz I cu ka 30 525 V 50/60 Hz I cu ka 12 690 V 50/60 Hz I cu ka 8 Ics to IEC/EN 60947 test cycle O-t-CO-t-CO Ics ka 240 V 50/60 Hz I cs ka 55 400/415 V 50/60 Hz I cs ka 36 440 V 50/60 Hz I cs ka 22.5 525 V 50/60 Hz I cs ka 6 690 V 50/60 Hz I cs ka 4 Utilization category to IEC/EN 60947-2 A Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) Operations 20000 Lifespan, electrical AC-1 AC--3 400 V 50/60 Hz Operations 10000 415 V 50/60 Hz Operations 10000 690 V 50/60 Hz Operations 5000 Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker. 08/26/2018 Eaton 283296 ED2018 V47.0 EN 2 / 9
415 V 50/60 Hz Operations 7500 Max. operating frequency Ops/h 120 Total downtime in a short-circuit ms < 10 Terminal capacity Standard equipment Box terminal Optional accessories Screw connection Tunnel terminal connection on rear Round copper conductor Box terminal Solid 2 mm 1 x (10-16) 2 x (6-16) Stranded mm 2 1 x (10-70) 3) Tunnel terminal 2 x (6-25) Solid mm 2 1 x 16 Stranded 1-hole 2 mm 1 x (25-95) Bolt terminal and rear-side connection Direct on the switch Al circular conductor Solid 2 mm 1 x (10-16) 2 x (6-16) Stranded mm 2 1 x (10-70) 3) Tunnel terminal 3) Up to 95 mm² can be connected depending on the cable manufacturer. 2 x 25 Solid mm 2 1 x 16 Stranded Stranded 2 mm 1 x (25-95) Bolt terminal and rear-side connection Direct on the switch Solid 2 mm 1 x (10-16) 2 x (10-16) Stranded 2 mm 1 x (25-35) 2 x (25-35) Cu strip (number of segments x width x segment thickness) Box terminal Copper busbar (width x thickness) mm Bolt terminal and rear-side connection min. mm 2 x 9 x 0.8 max. mm 9 x 9 x 0.8 Screw connection M6 Direct on the switch Control cables min. mm 12 x 5 max. mm 16 x 5 3) Up to 95 mm² can be connected depending on the cable manufacturer. 2 mm 1 x (0.75-2.5) 2 x (0.75-1.5) Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation I n A 160 Equipment heat dissipation, current-dependent P vid W 36.1 Operating ambient temperature min. C -25 Operating ambient temperature max. C 70 IEC/EN 61439 design verification 08/26/2018 Eaton 283296 ED2018 V47.0 EN 3 / 9
10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. Technical data ETIM 6.0 Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation prot. (EC000228) Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kv) / Circuit breaker for power transformer, generator and system protection (ecl@ss8.1-27-37-04-09 [AJZ716010]) Rated permanent current Iu A 160 Rated voltage V 690-690 Rated short-circuit breaking capacity lcu at 400 V, 50 Hz ka 36 Overload release current setting A 125-160 Adjustment range short-term delayed short-circuit release A 0-0 Adjustment range undelayed short-circuit release A 960-1600 Integrated earth fault protection No Type of electrical connection of main circuit Frame clamp Device construction Built-in device fixed built-in technique Suitable for DIN rail (top hat rail) mounting No DIN rail (top hat rail) mounting optional Yes Number of auxiliary contacts as normally closed contact 0 Number of auxiliary contacts as normally open contact 0 Number of auxiliary contacts as change-over contact 0 Switched-off indicator available No With under voltage release No Number of poles 3 Position of connection for main current circuit Front side Type of control element Rocker lever Complete device with protection unit Yes Motor drive integrated No Motor drive optional No Degree of protection (IP) IP20 08/26/2018 Eaton 283296 ED2018 V47.0 EN 4 / 9
Characteristics 08/26/2018 Eaton 283296 ED2018 V47.0 EN 5 / 9
Let-through current 08/26/2018 Eaton 283296 ED2018 V47.0 EN 6 / 9
Let-through energy 08/26/2018 Eaton 283296 ED2018 V47.0 EN 7 / 9
Dimensions 1 Blow out area, minimum clearance to adjacent parts 08/26/2018 Eaton 283296 ED2018 V47.0 EN 8 / 9
Additional product information (links) IL01203004Z (AWA1230-1913) Circuit-breaker, Switch-Disconnector IL01203004Z (AWA1230-1913) Circuit-breaker, Switch-Disconnector Temperature dependency, Derating CurveSelect characteristics program ftp://ftp.moeller.net/documentation/awa_instructions/il01203004z2015_11.pdf http://ecat.moeller.net/flip-cat/?edition=hplen&startpage=17.172 http://www.eaton.eu/de/europe/electrical/customersupport/configurationtools/characteristicsprogram/index.htm 08/26/2018 Eaton Industries GmbH http://www.eaton.eu 08/2018 by Eaton Industries GmbH Eaton 283296 ED2018 V47.0 EN 9 / 9