DIN Power Module ow Capacity Phase Adaptive DIN Power Module - Phase Adaptive 369849a 1 08.06.15 The Phase Adaptive Power Module family is a group of modular products for the control of lighting loads. This product is compatible with utron guestroom systems only. IEC SEV / 132 ma Features eading-edge or trailing-edge dimming for incandescent / halogen, electronic / magnetic low voltage, and neon / cold cathode light sources. Controls dimmable CF / ED loads. Refer to www./edtool for compatibility with dimmable CF / ED light sources. RTISS Equipped technology compensates for incoming line-voltage variations (up to ± 2% change in frequency / second) such as changes in Root Mean Square (RMS) voltage, frequency shifts, harmonics and line noise. Integral protection for common temporary overcurrent and over-voltage conditions. SS7 Compliant Includes QS link for seamless integration of lights, motorized window treatments ( Plus only), and control stations. Provides 4 Power Draw Units (PDUs) to power QS devices on the QS link. EDs on the module provide diagnostic information. Buttons on module provide load override control. Power failure memory 120-240 V~ 50 / 60 Hz 4 A (shown) 120-240 V~ 1 A D1 D2 D3 D4 Models Available : 120 240 V~, 1 A per output, 4 outputs MQSE-3A1-D: 120 240 V~, 1 A per output, 3 outputs MQSE-2A1-D: 120 240 V~, 1 A per output, 2 outputs Specification Submittal Page
6.5 1 2 3 4 Assembled in U.S.A. 50015757 Rev. A 243C IND. CONT. EQ. IEC PEV /NEC Class 2 +1.800.523.9466 + 44.(0)20.7680.4481 6.5 1 2 3 4 DIN Power Module ow Capacity Phase Adaptive System Example - Prime Room Thermostat (R-HVAC-230-S) or 3rd Party Thermostat 369849a 2 08.06.15 CCO 3rd Party Magnetic Door Switch CCI GCU-HOSP (for setup only) Guestroom Control Unit GCU-HOSP Switching Power Module MQSE-4S1-D 100-240 V~ 50 / 60 Hz 4 A CCI CCI CCO N.O. CCO N.C. CCO 24 V IEC PEV / 132 ma 100-240 V~ 1 A M 120-240 V~ 1 AX, 1 FA / 6 RA 4,4 in-lb Cu Al 65 / 75 C 0,5 N m 1 2 3 4 Dimming Power Module QS ink 24 V IEC PEV / 132 ma QS Power Supply (optional) To additional QS devices 100-240 V~ 50 / 60 Hz 4 A 4,4 in-lb Cu Al 65 / 75 C 0,5 N m 100-240 V~ 1 A D1 D2 D3 D4 QS Sensor Module (QSM) Wireless Communication Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM) Pico Wireless Controller (up to 10 per QSM) Multiple QS Sensor Modules can be added to increase the number of wireless inputs and Pico wireless controllers. Specification Submittal Page
Assembled in U.S.A. 50015757 Rev. A 6.5 243C IND. CONT. EQ. IEC PEV/NEC Class 2 65 / 75 C +1.800.523.9466 + 44.(0)20.7680.4481 4,4 in-lb 0,5 N m IEC PEV / 132 ma 1 D1 2 D2 3 D3 4 D4 DIN Power Module ow Capacity Phase Adaptive System Example - Plus 369849a 3 08.06.15 Guestroom Control Unit Property Management System (PMS) Guestroom Control Unit GCU-HOSP Hotel Network utron Property Management System (PMS) Interface Software Building Management System (BMS) QS Power Supply (optional) Room Thermostat (R-HVAC-230-S) 100-240 V~ 50 / 60 Hz 4 A Cu Al 24 V 100-240 V~ 1 A Dimming Power Module QS Wallstation QS Wallstation QS Sensor Module (QSM) Wireless Communication PalladiomTM Thermostat Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM) Pico Wireless Controller (up to 10 per QSM) Multiple QS Sensor Modules can be added to increase the number of wireless inputs and Pico wireless controllers. To additional QS devices SivoiaR QS Motorized Shades Corridor I/O Specification Submittal Page Alena QS Motorized Drapery Door Chime Door Switch Contact Window Switch Contact
DIN Power Module ow Capacity Phase Adaptive Specifications Regulatory Approvals Complies with IEC/EN 60669 Complies with U 508 Complies with CSA C22.2, #14 Complies with NOM 003 utron Quality Systems registered to ISO 9001.2008 Power 120 240 V~ 50/60 Hz Single input feed 4 A maximum input current ightning strike protection meets ANSI/IEEE standard C62.41 and IEC 61000-4-5. Can withstand voltage surges of up to 6 000 V~ and current surges of up to 3 000 A. Standby power: <2 W (wired devices on QS link excluded) Provides 4 PDUs to power QS devices on QS link ESD protection exceeds agency requirements per IEC-61000-4-2 QS ink output: 369849a 4 08.06.15 Environment For thermal specifications, see Mounting section Relative humidity: less than 90% non-condensing For indoor use only Terminals Mains wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG) (single wire, solid or stranded) Zone wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG) (single wire, solid or stranded) QS ink: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG) (single wire, solid or stranded) Manual Mode Operation By default each zone is set to Auto Detect load type. Zone buttons on the unit can be used to: turn loads on and off. dim loads up and down. Specification Submittal Page
DIN Power Module ow Capacity Phase Adaptive Specifications (continued) Output Zone Ratings No Derating is required if all the conditions below are met: Calibration point maximum is 70 ºC Room ambient temperature is between 0 ºC and 40 ºC (32 ºF and 104 ºF). Panel ambient temperature, within 20 mm (0.80 in) of unit, is between 0 ºC and 50 ºC (32 ºF and 122 ºF). Each zone has a 5 W incandescent minimum load requirement. For ED compatibility details, see www./edtool Automatically selects leading-edge or trailing-edge dimming when configured to "Auto-detect". It can also be configured for a specific load type. Does not support non-dimming loads One load type per zone. Output should not be used to control general purpose receptacles. Intended for lighting loads only. Output must be directly connected to the load, outputs are not compatible with load side switching (i.e., breakers, switches, etc.). Each zone is rated for the following wattage and load types A : oad Type Zones 1 4 120 V~ 220 V~ 230 V~ 240 V~ Incandescent / Halogen 120 W 220 W 230 W 240 W Electronic ow Voltage 120 W 220 W 230 W 240 W Magnetic ow Voltage B Neon / Cold Cathode B 120 VA (90 W C ) 120 VA (90 W C ) 220 VA (165 W C ) 220 VA (165 W C ) 230 VA (172 W C ) 230 VA (172 W C ) 240 VA (180 W C ) 240 VA (180 W C ) A Refer to www. for compatibility with dimmable CF / ED light sources. B Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1. C Actual lamp wattage. 369849a 5 08.06.15 Run a separate neutral for each load circuit. A common neutral connection is not recommended. Unit may be powered by Ground Fault Interrupter (GFI) or Residual Current Circuit Breaker with Overload (RCBO) protected circuit if required. oad circuit wiring (from breaker to unit to load) must be run in its own non-metallic conduit, or nuisance tripping may occur. For applications requiring 0 10 V- control, use 10 V- Interface (GRX-TVI). For applications requiring higher wattage ratings, use a power booster (NGRX-PB, NGRX-EVI for 230 V~ or PHPM-PA for 120 V~). Maximum wire length between Phase Adaptive Power Module and the load must be less than 30.5 m (100 ft). Specification Submittal Page
DIN Power Module ow Capacity Phase Adaptive Mechanical Dimensions 369849a 6 08.06.15 120-240 V~ 50 / 60 Hz 4 A IEC SEV / 132 ma 120-240 V~ 1 A 89.7 mm (3.53 in) 60.6 mm (2.38 in) D1 D2 D3 D4 161.7 mm (6.37 in) Mounting Mount in IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail. For United States and Canada, use NEMA Type 1 minimum rated enclosure. Unit is 9 DIN modules (161.7 mm [6.37 in]) wide. Mount in an accessible and serviceable location. Unit may be mounted by pressing the unit onto the DIN rail with the clips locked. To remove the unit from the DIN rail, unlock the clips using a screwdriver. See utron P / N 048466 at www. for more information on mounting and installation in panels with integrated DIN rail. Mount the Power Module where audible noise is acceptable (internal relay click) Unit generates heat, maximum 35 BTUs/Hour. Mount unit such that all the conditions below are met: Room ambient temperature is between 0 ºC and 40 ºC (32 ºF and 104 ºF). Temperature inside mounting panel, within 20 mm (0.80 in) of unit, is between 0 ºC and 50 ºC (32 ºF and 122 ºF). Calibration point maximum: 70 ºC (158 ºF). Prog. Prog. Zn. 1 Zn. Zn. 12 1 Zn. Zn. 23 2 Zn. Zn. 34 3 Zn. Zn. 4 4 120-120 240 - V~ 240-50 V~ / 60 50 50 Hz / 60 / 60 4 Hz A Hz 4 4 A A +1.610.282.3800 IEC SEV IEC IEC / SEV / / NECR Class NECR 2 Class 2 2 24 132 ma V- 132 132 ma ma 120-240 120 120 V~ - 240-240 1 V~ A V~ 1 1 A A N N N N N NN NN N N N ND1 D2 D1 D3 D1 D2 D4 D2 D3 D3 D4 D4 Mounting clips (4) on unit ocked Unlocked Specification Submittal Page
DIN Power Module ow Capacity Phase Adaptive Wiring: Mains and Output Zones 369849a 7 08.06.15 Wiring from Distribution to Phase Adaptive Power Module Turn off all circuit breakers or isolators feeding the Phase Adaptive Power Module at the distribution panel. Run line / hot and neutral wires from a 120 240 V~ 50 / 60 Hz feed to the Phase Adaptive Power Module unit. Run a separate neutral for each load circuit. A common neutral connection is not recommended. Mains Wiring and IEC PEV / NEC Class 2 Separation Follow appropriate local and national codes to avoid violating required separation guidelines. IEC SEV / 132 ma 120-240 V~ 50 / 60 Hz 4 A 2 Zn. 3 Zn. 4 120-240 V~ 1 A D1 D2 D3 D4 IEC SEV / 132 ma D 50 / 60 Hz 4 A 10.282.3800 Mains Neutral Outputs 120-240 V~ 1 A 120-240 V N N N N D1 D2 D3 D4 D1 D2 D3 D4 Distribution Panel 120 240 V~ Hot/ine Neutral To additional modules Note: If feeding through utron modules using mains terminals, total current must be less than or equal to 15 A. Zone 1 Zone 2 Zone 3 Zone 4 Specification Submittal Page
DIN Power Module ow Capacity Phase Adaptive Wiring: QS ink IEC PEV/NEC Class 2 QS ink Wiring ink communicates using IEC PEV/NEC Class 2 wiring. Follow all applicable national and local codes for proper circuit separation and protection. Turn off all breakers or isolators feeding the Phase Adaptive Power Module before servicing. Wiring may be t-tapped or daisy-chained. Total length of QS link must not exceed 610 m (2 000 ft). For the utron All-In-One cable specification, see utron P / N 369596 or 369597 on www.. Control power link (, ) wiring: For lengths under 150 m (500 ft), use 1.0 mm 2 (18 AWG) conductors. 120 For lengths over 150 m (500 ft), use 4.0 mm 2-240 V~ 50 / 60 Hz 4 A (12 AWG) conductors. Data link (, ) wiring: Use one, twisted-shielded pair of 1.0 mm 2. Alternate data-only cable: use approved data link cable (0.5 mm 2 [22 AWG] twisted, shielded) from Prog. Zn. 1 Zn. 2 Zn. 3 Zn. 4 Belden, model #9461. Each QS link IEC PEV/NEC Class 2 terminal will accept up to two 1.0 mm 2 120-240 V~ 50 / 60 Hz 4 A (18 AWG) wires; two +1.610.282.3800 4.0 mm 2 (12 AWG) wires will not fit. If using two 4.0 mm 2 (12 AWG) wires, connect using appropriate wire connectors. Note: For more information on PDUs, refer to Power Draw Units on the QS ink document (utron P/N 369405). Control ink Data ink 1: 2: 3: 4: IEC SEV / 132 ma 369849a 8 08.06.15 120-240 V~ 1 A D1 D2 D3 D4 IEC SE NECR Specification Submittal Page