Incorrect Temperature Measurements: The Importance of Transmissivity and IR Viewing Windows

Similar documents
Enhanced Diagnostics through Ultrasound Imaging

GESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE

Using Ultrasound and Infrared Technologies for Metal-Clad Switchgear Inspections

Methods of Inspection to Determine the Presence of Potential Arc Flash Incidents

BY ADRIAN MESSER, UE Systems, Inc.

ELECTRICAL SAFETY INSPECTION REPORT

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.

SPIRIT. SPIRIT Attendant. Communications System. User s Guide. Lucent Technologies Bell Labs Innovations

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

Corona and Tracking Conditions in Metal-clad Switchgear Case Studies

An Introduction to Vibration Analysis Theory and Practice

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

Take Control of Quality Assurance

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

Specification. NGTS Issue 1 October 1993

Auto classification and simulation of mask defects using SEM and CAD images

Meeting the Challenge of a Difficult Job Speciality Contractor ACE Awards

OPERATION AND MAINTENANCE MANUAL

EMERSON SMART WIRELESS RADIO SILENCE REPORT

HOME THEATER. HDMI Selector Switches. Vanco Part Numbers (5x1) (3x1) Technical Support

IR WINDOWS com. Supplied by. Call us on +44 (0)

Improving Lightning Protection of Power Systems with Externally Gapped Line Arresters (EGLA)

ANALYSIS OF FAILURE IN POWER CABLES FOR PREVENTING POWER OUTAGE IN ALEXANDRIA ELECTRICITY DISTRIBUTION COMPANY IN EGYPT

TC Mbps - 622Mbps FIBER OPTIC MODE CONVERTER/REPEATER (Rev A0.1) User's Manual

M4000 Diagnostic Test System For Power Apparatus Condition Assessment

Automatic Transfer Switch Control PLC Operator s Manual

New York MX700 Room. PWD-NY5-MX700-P60 List Price: $11, SLA Price: $1,100.00/year (Other options available See Appendix B)

ULTRA-TRAC APL INSTRUCTION MANUAL. Read and understand instructions before use. Patented. 851 Transport Drive Valparaiso, IN

CONTENTS. Troubleshooting 1

Safety FIND THE FEED CABLE IN YOUR ELECTRICITY METER (UK)

RECOGNITION OF PRIOR LEARNING CANDIDATE APPLICATION FORM UEE30811 CERTIFICATE III IN ELECTROTECHNOLOGY - ELECTRICIAN

Summary Project Specification Consultation Report

Series CT7N Bimetallic Overload Relays

Agilent 81600B Tunable Laser Source Family

A Study of Curriculum Design of Cable-TV to Promote College-Level Students Practical Competencies

Wired Troubleshooting Manual

Ecomind Electricity Monitor Kit EM422EM-E-KBTS EM422EM-E-KMTS. Installation Instructions

Aqua Turf International, Inc.

FA Cup Final Wembley Stadium London HA9 0WS 27th May 2017

User s Manual. Digital Media Converter Package Part #: DL-HDCAT

Model 1606 Super. User Manual

TEKTRONIX 2465B OSCILLOSCOPE: MAIN BOARD INTER-TRACK LEAKAGE.

FOGGY DOCSIS AN ENABLENCE ARTICLE WRITTEN BY JIM FARMER, CTO APRIL,

HDMI Extender over UTP Cable

SPECIAL SPECIFICATION 6735 Video Optical Transceiver

UTTR BEST TELEMETRY SOURCE SELECTOR

User s Manual. Digital Switch Part #: DL-HDS21 Part #: DL-HDS41

Agilent 81600B Tunable Laser Source Family Technical Specifications August New model: nm, low SSE output!

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

P 3. Thermal Imagers. Proven Practical Performance. Series

Room thermostat Instructions for Use. For the user. Instructions for Use. geotherm

SATRI AMPLIFIER AMP-51R. Owner s Manual

Condition Monitoring Program: A Need to Improve Performance of Machineries

USER MANUAL. 22" Class Slim HD Widescreen Monitor L215DS

MODEL PA II-R (1995-MSRP $549.00)

Model PSKIT-H540 Ultrasonic Power Supply Kit 40 khz 500 Watts

Design Issues Smart Camera to Measure Coil Diameter

Operation/Users Manual

Work no. 2. Doru TURCAN - dr.ing. SKF Romania Gabriel KRAFT - dr.ing. SKF Romania

VHF + UHF Amplified HDTV Antenna Model OA8000 & OA8001 Installation Instructions Reception Frequencies

SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment

A dedicated data acquisition system for ion velocity measurements of laser produced plasmas

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers

User Guide. Centrex Recording Interface

HOME THEATER. HDMI HDBaseT Lite Extenders. Vanco Part Number: Technical Support

Instruction Manual AVT-8710 Time Base Corrector

Avoiding False Pass or False Fail

FINAL REPORT LOAD SHEDDING IN TASMANIA ON 20 DECEMBER 2016 REVIEWABLE OPERATING INCIDENT REPORT FOR THE NATIONAL ELECTRICITY MARKET

REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA

Instructions. P MHz 1X/10X Passive Probe

HOW TO START A PREDICTIVE MAINTENANCE PROGRAM. Richard D. Hall. National Electrical Carbon Products

HOME THEATER. Super IR Accessories. Vanco Part Numbers. Technical Support

THE MINACK THEATRE. Notes for Playing Companies. Please note 2016 amendment to Section 5 - Public Liability & Employer Liability Insurance

US Army Corps of Engineers Visitor Center Evaluation Strategy

MTS/T-BERD 8000 Platform

Off Site Maintenance Goes Mobile Electronic Cellular Time Switch

FN:4181NX_M1.DOC MC4181NX MASTER CLOCK MC4181NX

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT

DEPARTMENT OF THE ARMY TECHNICAL BULLETIN CALIBRATION PROCEDURE FOR AUTOMATIC VIDEO CORRECTOR TEKTRONIX, MODEL 1440 (NSN )

MTS/T-BERD 8000 Platform Optical Spectrum Analyzer Modules

Toronto Hydro - Electric System

TRNSMT Festival Glasgow Green, Scotland. 29 th June 1 st July th July 8th July 2018

PRODUCT MANUAL : 1x8 Splitter/Extender : Receiver (Sold Separately)

EE028: Practical High Voltage Cable Jointing and Termination

Agilent N9355/6 Power Limiters 0.01 to 18, 26.5 and 50 GHz

Good Faith 14 THE FEED

Analog to Digital conversion of HD video. The HD-Now provides a simple method of upgrading ROVs for live HD. Keep existing infrastructure intact.

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (8th) Factory Name Address Factory ID

CITY OF LOS ANGELES CIVIL SERVICE COMMISSION CLASS SPECIFICATION POSTED JUNE VIDEO TECHNICIAN, 6145

Broken Wires Diagnosis Method Numerical Simulation Based on Smart Cable Structure

Concept of Operations (CONOPS)

FAQ FUJIFILM DIGITAL CAMERA RENTAL PROGRAM

Electric Motorized Projection Screen Spectrum Series

BUFORD COMMUNITY CENTER, TOWN PARK & THEATRE THEATRE AND STAGE RENTAL AGREEMENT

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

PHI 5000 VersaProbe TM Operator s Guide

INSTALLATION MANUAL FT-FOTR-1VDE-ST-S

Fluke 279 FC True-rms Thermal Multimeter

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12

Transcription:

Incorrect Temperature Measurements: The Importance of Transmissivity and IR Viewing Windows Abstract IR viewing windows save lives. Most Thermographers today are thankful to perform their scans without the danger and time of removing heavy panels. But just as the thermal imager is a tool - so is the IR Viewing Window. And as with any tool, it must be used correctly to get the desired results. Standardization is the key to getting repeatable results and accurate measurements. Many applications that benefit from infrared analysis do not require exact temperature measurements. For instance: Using thermography to conduct insulation surveys on building envelopes does not require concise temperature data; neither does locating a loose fuse clip. But when temperature is used as a criticality for major repairs (shut down required), it is imperative that your data is accurate.

Do you know your IR Viewing Windows Transmissivity rate? Perhaps a better question is: Have you calculated your IR viewing windows transmission with your camera? Though I had never measured, I knew my windows transmitted near 95%. That is what the salesman had said and, it s how it had always been done. This assumption likely put workers at risk and cost my customer money. This paper is comprised of my official report, the actions taken, and subsequent changes in plant policy to amend any missed opportunities. It is intended to educate thermographers and those whom they support on the importance of accurate temperature measurement through IR Viewing Windows. Official Report Excerpt: Summer 2009 At approximately 9:30AM on Monday morning, I began the quarterly inspection of the plants main switch gear (23KV incoming line, distribution switches). All Inspections on the main switch gear were made via 3 inch Calcium Fluoride (CaF2) Crystal Infrared Viewing Panes. The Imager used was a FLIR 695 with standard Emissivity set at 0.92. Upon completion, I was troubled to find a total of 3 anomalies (hot spots) in the switches. I captured my images and data and noted the Inspection point numbers. Upon completion of the inspection, I called the PdM Program Manager (PM) and briefed him on the unusual and serious nature of the findings. Seriousbecause company best practices for a 10 F ΔT (Differential temperature) or higher, on 23KV equipment is CRITICAL. And unusual- because the switchgear had been inspected by me approximately 3 months prior in the quarterly scan. I had used all of the same inspection points and had observed no anomalies. I reported the following to the PM: Isolation switch number one (Switch# 1) has a 30 F ΔT on the C phase Disconnect contact. Isolation Switch Number Two (Switch 2) has two hot spots: the first anomaly (21 F ΔT) on the Phase A Disconnect contact (Image 2). The second anomaly (30 F ΔT) on the phase C Disconnect contact (Image 1).

Image 2 Image 3 Image 4 Immediately following my phone call, I generated an official report, wrote the work orders, and entered all data into our system. I sent the report to all concerned parties and requested an immediate meeting. During the meeting it was decided to monitor all anomalies daily until a power outage could be scheduled. Since the substation was shared equipment; the city utilities bore some responsibility for the equipment as well as the repair. We decided the City Utilities would be called in to help assess the situation. As my schedule dictated, I was off site the following day. I was emailed a memo that stated City Utilities arrived around 9AM and conducted an IR scan with their own personnel and equipment. The Utility measured slightly above my measurements but the anomaly did not meet their criticality limits for repair (>50 F ΔT). They did not capture images thus I received a second hand report of their findings. If we wanted the anomaly corrected, we had to do it ourselves. Back on site Wednesday morning, I performed a complete scan of all incoming line switchgear. Though all anomalies were still present, I found that switch #1 s anomaly had doubled to >60 F ΔT!

A quick look at the production rate verified that the loading of the switch had not increased. Once again I generated a report and notified the PM. The Utility Company was contacted but not receptive. The next morning, Thursday, I came in early and scanned the equipment before sunrise. I found and reported that Switch No. 1 had increased to nearly 75 F ΔT. (Image 5) This anomaly had risen 150% in just 3 days! I captured the images and send out the report. In less than an hour a meeting was held. Reports were sent, calls were made, and the corporate office got involved. Management ordered a decrease in the production rate immediately. No one was willing to let a 75 F ΔT remain in the Incoming Power switch that fed half of the plant. Not on their watch. The plan was to take Switch #1 offline during a 2 hour power outage that evening. As is sometimes the case, paperwork and part acquisition delayed the repair. Finally, the switch was thrown around 2:00AM Friday morning. I arrived on site Friday morning just as the electricians were clearing locks and tags and preparing to bring the switch back on line. After the switch was loaded, I scanned the anomaly and reported that Switch #1 appeared to have no hot spots. Repairs, though costly, were successful.

I attended the post repair meeting on Friday. Everyone was in good spirits; Mission Accomplished seemed to be the theme. We had just discovered and repaired the most dangerous hot spot our Main Switchgear had ever seen. It was decided that the switch #2 hotspots would be monitored daily by the onsite technician s until a scheduled outage. A new policy was also adopted that put the Main Incoming Switch Yard on a monthly route versus the quarterly scan. (I recommend this to every plant I consult with now). In less than a month I had transferred up the chain of command. I made sure my replacement knew the history and the potential volatility of the Switch Yard. Switch #2 continued to be monitored on a daily basis. The temperatures rose and fell but never over 50 F ΔT; and definitely not the magical 75 F ΔT that had caused such a stir. I was given word that an emergency outage had given the electrician s time to repair Switch#2 a short time later. My contact at the site verified that all previous anomalies in the 23KV Main Incoming Switch Yard had been eliminated. Enlightened Some months later I read a surprising report, Titled: Transmission Stability and IR Viewing Windows: The Effects of Transmissivity on Data Accuracy. As I read his paper the above incident was the first thing on my mind. I had to wonder, had I given the most accurate information to my customer? It upset me to think I had reported incorrect data; I was responsible for the IR program and I should have known this information. According to the report, transmission rates are typically variable across the infrared spectrum (as shown in Madding, 2004 1), yet the manufacturer s specified transmission rate is generally relevant for a specific wavelength. So, while a Crystal may indeed have a 95% transmission rate in the short wave, most industrial IR camera operate in the long-(mid) wave or 8-14 μm. Transmission Curves for Barium Fluoride and Calcium Fluoride in micrometers After reading the report, I decide to put the Calcium Fluoride Crystal to the test. My test was somewhat like my daily camera calibration rudimentary but effective. *Side bar: I calibrate my IR camera each morning with a coworkers tear duct. I know human skin to be around.98 EM. If I get within +/-2% of 98.6 F (average human temperature), I trust my equipment to be calibrated to an effective degree.

To test my window in the office, I used a simple method known as the coffee cup test. I powered-up my imager and grabbed a 3 Calcium Fluoride IR viewing window. *Note: Polymer and Germanium windows will have some transmission loss as well. The transmissivity rate is not important (to a degree) as long as it is known and will not change. 1. Fill a cup with hot water, and place an Emissivity Label on it (No Emissivity target? use electrical tape) 2. Set the camera s Emissivity to 1.00 3. Measure the temperature of the target without the window (Temp= 160 F) 4. Then place the window (I used a 3 CaF2) in front of the camera and measure (Temp= 120 F) 5. Lower the camera s emissivity until the adjusted temperature is the same as the original temperature (.55 EM) 6. I recorded the new rate for future reference. I later estimated what my true temperatures were for the Main Switch Yard anomalies. Using the imager s software, I was able to change the flawed temperature readings I had collected by inputting the correction of.55 Emissivity. The results confirmed the coffee cup test and the fact that I had erred in my original calculations. Thermography software as well as many cameras themselves also provides a way to correct for transmission losses. For additional tips contact your window or camera manufacturer. Additional tips can also be found at http://www.pesd.com. Below are the switch #1 images after Emissivity correction.

Summary It was apparent to me that the Utility Co. should have aided in or completed this repair themselves. (I cannot imagine a 50 F ΔT, on 23kV switchgear being considered anything but CRITICAL. ) But I could not undo the past. I had erred in my own measurements and so had the utility. All anomalies were corrected and paid for by my customer. I felt obligated, however, to insure future scans (mine and my colleagues) did not suffer from the misinformation regarding transmission rates in IR viewing windows. Due to the incident being studied post repair, my experiment could not be considered scientific. I was unable to use the same crystal as the images were captured through. My crystal window was new. Though it was of the same brand, size, and model installed in the Switches, I was also unable to recreate any defects the window had due to age, high frequency, noise, vibration, moisture, etc. This paper should serve as a testament to the predictive maintenance strategies used in industry today. Though it was not the focal point of this particular paper, the use of Infrared Thermography and IR Viewing Windows saved my customer incalculable resources that day. When a Mega Plant loses its incoming line, everything stops. Tens of thousands of production dollars may be subtracted by the day, hour or even minute. And, I cannot speculate as to the toll on the plant s safety had an arc flash transpired. This problem was caught while in failure mode - very low on the P-F Curve. However, the system worked. The technology that the plant invested in paid for itself that day.