SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

Similar documents
SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Function Manual SIMATIC HMI TP900. Operator Panel.

MICROMASTER Encoder Module

KRF EMC Filters Installation, Operation and Maintenance Manual

Power Injector 1520 Series

LED MODULES READYLINE DL

Trusted 40 Channel 120 Vac Digital Input FTA

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

DVBus and Multiplexer and demultiplexer assemblies for video channels, with bidirectional audio and data USER MANUAL

Trusted 40 Channel 120 Vac Digital Input FTA

SIMATIC. ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Preface. Properties 1. Parameters 2. Error and system messages 3

Installation Manual Original Instructions - IW4001

Trusted 40 Channel Analogue Input FTA

Installation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.

Colour Explosion Proof Video Camera USER MANUAL VID-C

LXM23DU10M3X motion servo drive - Lexium 23 - single phase V - 1 kw - I/O

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

Slot-type Photomicrosensor with connector or pre-wired models (Non-modulated) *1. configuration. Dark-ON/Light-ON

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry.

LINK-RAY TM MODULATORS FOR CONSTANT- VOLTAGE. LinkRay Modulators 12 V / 24 V Constant-voltage Applications MODULATORS

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

3 Cleaning. 4 Technical data

Installation Guide VL-MV10. Model No.

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

DALI TOUCHPANEL BASIC TW. Operating and control unit

Operating Instructions Dimmer for V Incandescent Lamps

LED Driver Linear / area fixed output

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

3M Sensored Termination (15 kv) QX-T15I-vi1-E

SIMATIC. ET 200S distributed I/O 2AO U HS analog electronic module (6ES7135-4FB52-0AB0) Preface. Properties 1. Parameters 2.

Siemens AG Safety along the complete line: SIRIUS 3SE7 cable-operated switches SIRIUS. Answers for industry.

Backlight Replacement

Instructions. P MHz 1X/10X Passive Probe

NetterVibrotron SRF. Operating Instructions for. Series SRF. These operating instructions apply to. Netter Static Adjustable Frequency Control

llen-bradley 194R-HM4-NFPA3

Model Number Structure

3 line filters for converters and power electronics

Emergency lighting units EM powerled

Emergency lighting units EM powerled

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

Cisco Aironet 1520 Series Outdoor Mesh Access Point Power Injector Installation Instructions

4 Wiring Brochure Wiring and installation of specific control

Indoor Linear 80W Driver SI-C215280N2KR

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

USER S MANUAL. FX2N-8AD Analog input block

LITE-ON TECHNOLOGY CORPORATION

TRF STEP-DOWN TRANSFORMER USER MANUAL


Installation. SAPTF33xx-1xx in the Network. Standard Configuration

/ PAT01 USER MANUAL

Installation Operation Maintenance

LED Driver Compact dimming

DSP 18 Sub active subwoofer. user manual

Remote Voltage Detector - JET (RVD) Medium and High Voltage kV AC

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

American Power Design, Inc.

HID control gear Electronic. PCIS, PCS outdoor FOX B011 PCI outdoor. Ordering data. Circuit power1. tc/ta for 60,000 h For luminaires with 1 lamp

User Manual. AtlonA. Passive VGA Extender with Wall Plate or Box options up to 330ft over 1 x CAT5/6/7 Cable AT-VGA100-SR and AT-WPVGA-SR AT-WPVGA-SR

KHT 1000C HV-Probe Calibrator. Instruction Manual

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

USERS GUIDE MCX-HTS. HDMI to 3G SDI Converter. Manual Number:

T5, T8, TC-L. PC T5 PRO lp W V 50/60/0 Hz, HO. Electronic ballasts Linear lamps T5, T8 and compact lamps TC-L

Figure 1: Device components

DATA SHEET. The Advantys model STBDAI5260 Digital Input Module provides 2 isolated discrete input points that operate on a 115 VAC power source.

Solis Export Power Manager

Gamma instabus. Technical product information

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

USER MANUAL. DE-1 Police-light. CAUTION! Keep this device away from rain and moisture! Unplug mains lead before opening the housing!

Advantys STB DATA SHEET. Advantys STB Output Module. Description. Features

Photovoltaic Module Installation Manual (IEC)

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

E8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors

LED Driver Compact fixed output

PSM-003. Micro Polarization Controller/Scrambler. User Guide

GE Interlogix Fiber Options S700V & S702V. Instruction Manual FIBER-OPTIC VIDEO TRANSMISSION SYSTEM

Assembly. Front view. LEDs. Parametrization interface. Power Bus

SQM40/41 Actuators for air and gas dampers

Photovoltaic Module Installation Manual (IEC)

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

Generator protection relay

LTC 113x & LTC123x FlexiDome Series Fixed Dome Cameras

EGM Einthoven Goldberger Module Type 701

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment

Register your product and get support at SDV5122/27. EN User manual


User Instructions. 16 SCB Sync Station.

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

Trusted TMR I/O SmartSlot Slot Cables

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

LED DRIVERS. LQC4D-V1 4 channels. User Manual FEATURES

Through Hole Lamp Product Data Sheet LTW-2S3D7 Spec No.: DS Effective Date: 10/06/2012 LITE-ON DCC RELEASE

LED Driver Compact fixed output

Achat 115 Sub A active subwoofer. user manual

Operating instructions

Transcription:

SINAMICS G130 Operating Instructions 03/2013 SINAMICS s

dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical installation 4 Maintenance and servicing 5 Technical specifications 6 Control version V4.6 03/2013 A5E00692302A

Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: Trademarks WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recoended or approved by Siemens. Proper transport, storage, installation, assembly, coissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY A5E00692302A P 05/2013 Technical data subject to change Copyright Siemens AG 2005-2013. All rights reserved

Table of contents 1 Safety information... 5 1.1 Warnings...5 1.2 Safety and application instructions...6 1.3 Components that can be destroyed by electrostatic discharge (ESD)...7 2 General... 9 3 Mechanical installation... 15 4 Electrical installation... 21 5 Maintenance and servicing... 27 6 Technical specifications... 29 Operating Instructions, 03/2013, A5E00692302A 3

Table of contents 4 Operating Instructions, 03/2013, A5E00692302A

Safety information 1 1.1 Warnings WARNING Dangerous electrical voltage Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. These personnel must be thoroughly familiar with all the warnings and maintenance procedures described in these operating instructions. The successful and safe operation of this device is dependent on correct transport, proper storage and installation, as well as careful operation and maintenance. National safety guidelines must be observed. DANGER Five safety rules When carrying out any kind of work on electrical devices, the "five safety rules" according to EN 50110 must always be observed: 1. Disconnect the system. 2. Protect against reconnection. 3. Make sure that the equipment is de-energized. 4. Ground and short-circuit. 5. Cover or enclose adjacent components that are still live. Note Use of copper cables for a UL-approved system For a UL-approved system use 60/75 C copper conductors only. Operating Instructions, 03/2013, A5E00692302A 5

Safety information 1.2 Safety and application instructions 1.2 Safety and application instructions DANGER Dangerous electrical voltage This equipment is used in industrial high-voltage installations. During operation, this equipment contains live, bare parts. For this reason, they could cause severe injury or significant material damage if the required covers are removed, if they are used or operated incorrectly, or have not been properly maintained. When the machines are used in non-industrial areas, the installation location must be protected against unauthorized access (protective fencing, appropriate signs). Preconditions The persons responsible for the safety of the plant must ensure that the following conditions are met: Basic planning work for the system and all work relating to transportation, assembly, installation, coissioning, maintenance and repairs is carried out by qualified personnel and checked by responsible, suitably skilled personnel. The Operating Instructions and machine documentation are always available. The technical specifications regarding the applicable installation, connection, environmental, and operating conditions are always observed. The plant-specific assembly and safety guidelines are observed and personal protection equipment is used. Unqualified personnel are forbidden from using these machines and working near them. These Operating Instructions are intended for qualified personnel and only contain information and notes relating to the intended purpose of the machines. The Operating Instructions and machine documentation are written in different languages as specified in the delivery contracts. Note Support by SIEMENS service centers We recoend engaging the support and services of your local Siemens service center for all planning, installation, coissioning and maintenance work. 6 Operating Instructions, 03/2013, A5E00692302A

Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) 1.3 Components that can be destroyed by electrostatic discharge (ESD) CAUTION Components sensitive to electrostatic charge The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: You should only touch electronic boards if absolutely necessary. When you touch boards, however, your body must be electrically discharged beforehand. Boards must not come into contact with highly insulating materials (such as plastic parts, insulated desktops, articles of clothing manufactured from man-made fibers). Boards must only be placed on conductive surfaces. Boards and components should only be stored and transported in conductive packaging (such as metalized plastic boxes or metal containers). If the packaging material is not conductive, the boards must be wrapped with a conductive packaging material (such as conductive foam rubber or household aluminum foil). The necessary ESD protective measures are clearly illustrated in the following diagram: a = conductive floor surface b = ESD table c = ESD shoes d = ESD overall e = ESD wristband f = cabinet ground connection g = contact with conductive flooring b d d b d e e f f f f f g a c c a g c a Figure 1-1 ESD protective measures Operating Instructions, 03/2013, A5E00692302A 7

Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) 8 Operating Instructions, 03/2013, A5E00692302A

General 2 Description The dv/dt filter plus voltage peak limiter comprises two components: the dv/dt reactor and the Voltage Peak Limiter, which cuts off the voltage peaks and returns the energy to the DC link. The dv/dt filters plus Voltage Peak Limiter must be used for motors for which the proof voltage of the insulation system is unknown or insufficient. Dv/dt filters plus Voltage Peak Limiters limit the rate of voltage rise to values < 500 V/µs and the typical voltage peaks with rated line voltages to the values below: < 1000 V at Uline < 575 V < 1250 V at 660 V < Uline < 690 V. Assignment of and Power Module Table 2-1 Assignment of and Power Module Power Module Type rating of the Power Module Matching Line voltage 380 480 V 3 AC 6SL3310-1GE32-1AAx 110 6SL3000-2DE32-6AA0 6SL3310-1GE32-6AAx 132 6SL3000-2DE32-6AA0 6SL3310-1GE33-1AAx 160 6SL3000-2DE35-0AA0 6SL3310-1GE33-8AAx 200 6SL3000-2DE35-0AA0 6SL3310-1GE35-0AAx 250 6SL3000-2DE35-0AA0 6SL3310-1GE36-1AAx 315 6SL3000-2DE38-4AA0 6SL3310-1GE37-5AAx 400 6SL3000-2DE38-4AA0 6SL3310-1GE38-4AAx 450 6SL3000-2DE38-4AA0 6SL3310-1GE41-0AAx 560 6SL3000-2DE41-4AA0 Line voltage 500 600 V 3 AC 6SL3310-1GF31-8AAx 110 6SL3000-2DH32-2AA0 6SL3310-1GF32-2AAx 132 6SL3000-2DH32-2AA0 6SL3310-1GF32-6AAx 160 6SL3000-2DH33-3AA0 6SL3310-1GF33-3AAx 200 6SL3000-2DH33-3AA0 6SL3310-1GF34-1AAx 250 6SL3000-2DH34-1AA0 6SL3310-1GF34-7AAx 315 6SL3000-2DH35-8AA0 6SL3310-1GF35-8AAx 400 6SL3000-2DH35-8AA0 6SL3310-1GF37-4AAx 500 6SL3000-2DH38-1AA0 6SL3310-1GF38-1AAx 560 6SL3000-2DH38-1AA0 Operating Instructions, 03/2013, A5E00692302A 9

General Power Module Type rating of the Power Module Matching Line voltage 660 690 V 3 AC 6SL3310-1GH28-5AAx 75 6SL3000-2DH31-0AA0 6SL3310-1GH31-0AAx 90 6SL3000-2DH31-0AA0 6SL3310-1GH31-2AAx 110 6SL3000-2DH31-5AA0 6SL3310-1GH31-5AAx 132 6SL3000-2DH31-5AA0 6SL3310-1GH31-8AAx 160 6SL3000-2DH32-2AA0 6SL3310-1GH32-2AAx 200 6SL3000-2DH32-2AA0 6SL3310-1GH32-6AAx 250 6SL3000-2DH33-3AA0 6SL3310-1GH33-3AAx 315 6SL3000-2DH33-3AA0 6SL3310-1GH34-1AAx 400 6SL3000-2DH34-1AA0 6SL3310-1GH34-7AAx 450 6SL3000-2DH35-8AA0 6SL3310-1GH35-8AAx 560 6SL3000-2DH35-8AA0 6SL3310-1GH37-4AAx 710 6SL3000-2DH38-1AA0 6SL3310-1GH38-1AAx 800 6SL3000-2DH38-1AA0 NOTICE Cable lengths The 100 clearances above and below the components must be observed. NOTICE Do not interchange the I/Os The terminals on the voltage limiting network (Voltage Peak Limiter) must always be connected as follows: Cable from the DC link of the Power Module at DCPS, DCNS and Cable to the dv/dt reactor 1U2, 1V2, 1W2. Failure to connect the terminals correctly could damage the voltage peak limiter. NOTICE Use only approved dv/dt filters If dv/dt filters plus Voltage Peak Limiters are used that SIEMENS has not approved for SINAMICS, these dv/dt filters may be damaged. CAUTION Hot surfaces The surface temperature of the dv/dt reactors may exceed 80 C. 10 Operating Instructions, 03/2013, A5E00692302A

General WARNING Risk of destruction during operation with increased pulse frequency When a is used with SINAMICS G130, the pulse frequency of the Power Module must not exceed 2.5 khz/4 khz. Setting a higher pulse frequency can lead to destruction of the dv/dt filter. NOTICE No operation without connected motor When a is used, the drive must not be operated without a connected motor, otherwise the filter can be destroyed. NOTICE Activation during coissioning If a is connected to the Power Module, it is essential that it is activated during coissioning (p0230 = 2). NOTICE Maximum output frequency The maximum permissible output frequency when a dv/dt filter with Voltage Peak Limiter is used is 150 Hz. NOTICE Component cooling Provisions for component cooling must be made at the installation site. Power loss data is given in the technical specifications. Note Setting range for pulse frequencies It is permissible to set pulse frequencies in the range between the rated pulse frequency and the relevant maximum pulse frequency when a is used. When so doing, take into account the "Current derating as a function of the pulse frequency; see Technical data. Operating Instructions, 03/2013, A5E00692302A 11

General Table 2-2 Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 2 khz Order number 6SL3310-... Power [] Output current for a pulse frequency of 2 khz [A] Line voltage 380 V 480 V 3 AC Max. pulse frequency when a dv/dt filter is used 1GE32-1AAx 110 210 4 khz 1GE32-6AAx 132 260 4 khz 1GE33-1AAx 160 310 4 khz 1GE33-8AAx 200 380 4 khz 1GE35-0AAx 250 490 4 khz Table 2-3 Max. pulse frequency when a dv/dt filter is used in units with a rated pulse frequency of 1.25 khz Order number 6SL3310-... Power [] Output current for a pulse frequency of 1.25 khz [A] Line voltage 380 V 480 V 3 AC Max. pulse frequency when a dv/dt filter is used 1GE36-1AAx 315 605 2.5 khz 1GE37-5AAx 400 745 2.5 khz 1GE38-4AAx 450 840 2.5 khz 1GE41-0AAx 560 985 2.5 khz Line voltage 500 V 600 V 3 AC 1GF31-8AAx 110 175 2.5 khz 1GF32-2AAx 132 215 2.5 khz 1GF32-6AAx 160 260 2.5 khz 1GF33-3AAx 200 330 2.5 khz 1GF34-1AAx 250 410 2.5 khz 1GF34-7AAx 315 465 2.5 khz 1GF35-8AAx 400 575 2.5 khz 1GF37-4AAx 450 735 2.5 khz 1GF38-1AAx 560 810 2.5 khz Line voltage 660 V 690 V 3 AC 1GH28-5AAx 75 85 2.5 khz 1GH31-0AAx 90 100 2.5 khz 1GH31-2AAx 110 120 2.5 khz 1GH31-5AAx 132 150 2.5 khz 1GH31-8AAx 160 175 2.5 khz 1GH32-2AAx 200 215 2.5 khz 1GH32-6AAx 250 260 2.5 khz 1GH33-3AAx 315 330 2.5 khz 1GH34-1AAx 400 410 2.5 khz 1GH34-7AAx 450 465 2.5 khz 1GH35-8AAx 560 575 2.5 khz 1GH37-4AAx 710 735 2.5 khz 1GH38-1AAx 800 810 2.5 khz 12 Operating Instructions, 03/2013, A5E00692302A

General Components The order numbers of the individual components (dv/dt reactor and voltage peak limiter) are listed in the following table: Table 2-4, order numbers of the individual components dv/dt reactor Voltage Peak Limiter Line voltage 380 V 480 V 3 AC 6SL3000-2DE32-6AA0 6SL3000-2DE32-6CA0 6SL3000-2DE32-6BA0 6SL3000-2DE35-0AA0 6SL3000-2DE35-0CA0 6SL3000-2DE35-0BA0 6SL3000-2DE38-4AA0 6SL3000-2DE38-4CA0 6SL3000-2DE38-4BA0 6SL3000-2DE41-4AA0 2 x 6SL3000-2DE41-4DA0 6SL3000-2DE41-4BA0 Line voltage 500 V 600 V 3 AC and 660 V 690 V 3 AC 6SL3000-2DH31-0AA0 6SL3000-2DH31-0CA0 6SL3000-2DH31-0BA0 6SL3000-2DH31-5AA0 6SL3000-2DH31-5CA0 6SL3000-2DH31-5BA0 6SL3000-2DH32-2AA0 6SL3000-2DH32-2CA0 6SL3000-2DH32-2BA0 6SL3000-2DH33-3AA0 6SL3000-2DH33-3CA0 6SL3000-2DH33-3BA0 6SL3000-2DH34-1AA0 6SL3000-2DH34-1CA0 6SL3000-2DH34-1BA0 6SL3000-2DH35-8AA0 6SL3000-2DH35-8CA0 6SL3000-2DH35-8BA0 6SL3000-2DH38-1AA0 2 x 6SL3000-2DH38-1DA0 6SL3000-2DH38-1BA0 Limiting the rate of voltage rise and the voltage peaks by means of the motor reactor and dv/dt filter plus Voltage Peak Limiter IGBT converter switching frequencies result in high voltage gradients (dv/dt) at the converter output. If long motor cables are used, this leads to an additional current load on the converter due to capacitive charge/discharge currents. The high voltage gradients, and the resulting transients at the motor terminals, cause the motors' electrical winding load to increase as compared with direct on-line operation. Operating Instructions, 03/2013, A5E00692302A 13

General The limits the rate of voltage rise to values < 500 V/µs and the typical voltage peaks ÛLL to the following values (with motor cable lengths of 150 m): < 1000 V at Uline 575 V < 1250 V at 660 V Uline 690 V 6 6 5 5 4 4 3 3 2 2 1 1 0 0 100 200 m 300 0 0 100 200 m 300 Û LL /U N Û LL /U N Û LL /U N Figure 2-1 Limiting the rate of voltage rise and the voltage peaks by means of the motor reactor and 14 Operating Instructions, 03/2013, A5E00692302A

Mechanical installation 3 Dimension drawing When the is installed in a cabinet, it must be positioned near the Power Module. l 4 l 5 l 5 a 2 a 5 a 4 a 4 a 8 a 7 a 8 n 2 h 2 a 3 h 3 a 4 a 5 d 3 n 1 n 2 n 1 n 4 n 3 Figure 3-1 Dimension drawing, dv/dt reactor Operating Instructions, 03/2013, A5E00692302A 15

Mechanical installation Table 3-1 Dimensions of dv/dt reactor, 380 V - 480 V 3 AC (all values in ) 6SL3000-2DE32-6CA0 2DE35-0CA0 2DE38-4CA0 2DE41-4DA0 a2 25 30 40 60 a3 5 6 8 10 a4 14 17 22 19 a5 10.5 x 14 14 x 18 14 x 18 14 x 18 a6 7 9 11 11 a7 - - - 17 a8 - - - 26 I4 410 460 460 445 I5 135 152.5 152.5 145 hmax 370 370 385 385 h2 258 240 280 250 h3 76 83 78 121 n1 1) 141 182 212 212 n2 1) 316 356 356 341 n3 229 275 312 312 n4 72 71 78 78 d3 (12 x 18) (12 x 18) (15 x 22) (15 x 22) 1) Lengths n1 and n2 correspond to the drill hole spacing Table 3-2 Dimensions of dv/dt reactor, line voltage 500 V - 600 V 3 AC and 660 V - 690 V 3 AC, Part 1 (all values in ) 6SL3000-2DH31-0CA0 2DH31-5CA0 2DH32-2CA0 2DH33-3CA0 a2 25 25 25 25 a3 6 6 5 5 a4 14 14 14 14 a5 10.5 x 14 10.5 x 14 10.5 x 14 10.5 x 14 a6 7 7 7 9 a7 - - - - a8 - - - - I4 350 350 460 460 I5 120 120 152.5 152.5 hmax 320 320 360 360 h2 215 215 240 240 h3 70 70 86 86 n1 1) 138 138 155 212 n2 1) 264 264 356 356 n3 227 227 275 275 n4 74 74 101 42 d3 (15 x 22) (15 x 22) 1) Lengths n1 and n2 correspond to the drill hole spacing 16 Operating Instructions, 03/2013, A5E00692302A

Mechanical installation Table 3-3 Dimensions of dv/dt reactor, line voltage 500 V - 600 V 3 AC and 660 V - 690 V 3 AC, Part 2 (all values in ) 6SL3000-2DH34-1CA0 2DH35-8CA0 2DH38-1DA0 a2 30 40 50 a3 6 8 8 a4 17 22 16 a5 14 x 18 14 x 18 14 x 18 a6 11 11 11 a7 - - 14 a8 - - 22 I4 460 460 445 I5 152.5 152.5 145 hmax 385 385 385 h2 280 280 255 h3 83 78 114 n1 1) 212 212 212 n2 1) 356 356 341 n3 312 312 312 n4 78 78 78 d3 (15 x 22) (15 x 22) (15 x 22) 1) Lengths n1 and n2 correspond to the drill hole spacing Dimension drawing of the voltage peak limiter Table 3-4 Assigning voltage peak limiter to dimension drawings Voltage Peak Limiter Dimension drawing type Line voltage 380 V 480 V 3 AC 6SL3000-2DE32-6BA0 Type 1 6SL3000-2DE35-0BA0 Type 2 6SL3000-2DE38-4BA0 Type 3 6SL3000-2DE41-4BA0 Type 3 Line voltage 500 V 600 V 3 AC and 660 V 690 V 3 AC 6SL3000-2DH31-0BA0 Type 1 6SL3000-2DH31-5BA0 Type 1 6SL3000-2DH32-2BA0 Type 2 6SL3000-2DH33-3BA0 Type 2 6SL3000-2DH34-1BA0 Type 3 6SL3000-2DH35-8BA0 Type 3 6SL3000-2DH38-1BA0 Type 3 Operating Instructions, 03/2013, A5E00692302A 17

Mechanical installation Figure 3-2 Dimension drawing of the voltage peak limiter, type 1 Figure 3-3 Dimension drawing of the voltage peak limiter, type 2 18 Operating Instructions, 03/2013, A5E00692302A

Mechanical installation Figure 3-4 Dimension drawing of the voltage peak limiter, type 3 Operating Instructions, 03/2013, A5E00692302A 19

Mechanical installation 20 Operating Instructions, 03/2013, A5E00692302A

Electrical installation 4 Important safety precautions WARNING Dangerous electrical voltage The devices are operated with high voltages. All connection work must be carried out when the cabinet is de-energized. All work on the device must be carried out by trained personnel only. Death, serious injury, or substantial material damage can result if these warning notices are not observed. Work on an open device must be carried out with extreme caution because external supply voltages may be present. The power and control terminals may be live even when the motor is not running. Dangerously high voltage levels are still present in the cabinet up to 5 minutes after it has been disconnected due to the DC link capacitors on the Power Module. For this reason, the unit should not be opened until a reasonable period of time has elapsed. The operator is responsible for ensuring that the dv/dt filter with Voltage Peak Limiter and other components are installed and connected in accordance with the recognized technical rules in the country of installation and applicable regional guidelines. Special attention should be paid to cable dimensioning, fuses, grounding, shutdown, disconnection, and overcurrent protection. If an item of protective gear trips in a branch circuit, a fault current may have been disconnected. To reduce the risk of fire or an electric shock, the current-conducting parts and other components in the cabinet unit should be inspected and damaged parts replaced. When an item of protective gear trips, the cause of the trip must be identified and rectified. Operating Instructions, 03/2013, A5E00692302A 21

Electrical installation Interface overview Figure 4-1 Interface overview, voltage peak limiter, type 1 Figure 4-2 Interface overview, voltage peak limiter, type 2 22 Operating Instructions, 03/2013, A5E00692302A

Electrical installation Figure 4-3 Interface overview, voltage peak limiter, type 3 Operating Instructions, 03/2013, A5E00692302A 23

Electrical installation Connection When connecting the dv/dt reactor and Voltage Peak Limiter, you must take into account the following conditions to ensure that it functions correctly: Control cables must be routed separately from power cables. Power cables are the motor cable or the connecting cables from the DC link of the Power Module (terminals DCPS/DCNS) to the Voltage Peak Limiter. In particular, you must ensure that control cables and power cables are not routed in parallel in a joint cable raceway, even if all the cables are shielded. It is recoended to use shielded motor cables. If a shielded motor cable is used, its shield should be in face-to-face contact with the shield plate and motor housing. The ground wire for the motor must be fed directly back to the Power Module. Connection overview L 1 L 2 L 3 PE 1 U 1 1 U 2 U 1 V 1 U 2 V 2 1 V 1 1 V 2 U V W M W 1 W 2 1 W 1 1 W 2 ~ PE PE 1 PE 2 PE 1 U 2 1 V 2 1 W 2 Figure 4-4 Connecting a for versions with one dv/dt reactor 24 Operating Instructions, 03/2013, A5E00692302A

Electrical installation L 1 1 U 1 1 U 2 1 U 1 1 U 2 U 1 U 2 U L 2 1 V 1 1 V 2 1 V 1 1 V 2 V 1 V 2 V W L 3 1 W 1 1 W 2 1 W 1 1 W 2 W 1 W 2 M ~ PE PE PE 1 PE 2 PE 1 U 2 1 V 2 1 W 2 Figure 4-5 Connecting a for versions with two dv/dt reactors Cable cross-sections Table 4-1 Cable cross-sections for connections between the and Power Module dv/dt filter plus Voltage Peak Limiter Connection to the DC link (DCPS/DCNS) [²] Line voltage 380 V to 480 V 3 AC Connection between dv/dt reactor and voltage peak limiter (1U2, 1V2, 1W2) [²] 6SL3000-2DE32-6AA0 35 10 6SL3000-2DE35-0AA0 70 16 6SL3000-2DE38-4AA0 2 x 50 50 6SL3000-2DE41-4AA0 2 x 120 120 Line voltage 500 V to 600 V 3 AC and 660 V to 690 V 3 AC 6SL3000-2DH31-0AA0 16 6 6SL3000-2DH32-2AA0 16 6 6SL3000-2DH33-3AA0 70 16 6SL3000-2DH34-1AA0 120 35 6SL3000-2DH35-8AA0 120 35 6SL3000-2DH38-1AA0 2 x 70 70 Operating Instructions, 03/2013, A5E00692302A 25

Electrical installation WARNING Risk of fire and damage to equipment due to short-circuit/ground fault The cables to the DC link of the Power Modules must be routed so that a ground fault or short circuit can be ruled out. A ground fault can result in fire with the associated smoke. Protect the cables from mechanical damage. Comply with local installation regulations that enable this fault to be ruled out. In addition, apply one of the following measures: Use cables with double insulation. Maintain adequate clearance, using spacers, for example. Route the cables in separate cable ducts or pipes. Note Maximum cable lengths The connections should be kept as short as possible. The maximum cable length for the connections specified in the table above is 5 m. 26 Operating Instructions, 03/2013, A5E00692302A

Maintenance and servicing 5 Maintenance and servicing are not carried out for the dv/dt reactor and the Voltage Peak Limiter. In the case of an error, full replacement of the dv/dt filter is necessary. Operating Instructions, 03/2013, A5E00692302A 27

Maintenance and servicing 28 Operating Instructions, 03/2013, A5E00692302A

Technical specifications 6 General technical data Table 6-1 General technical data Output frequency 0 to 150 Hz Product standard EN 61800-5-1 Ambient conditions Storage Transport Operation Ambient temperature -25 to +70 C -25 to +70 C 0 to +50 C Relative air humidity 1) (condensation not permissible) corresponds to class 5 to 95% 1K4 acc. to EN 60721-3-1 5 to 95% at 40 C 2K3 acc. to EN 60721-3-2 5 to 95% 3K3 acc. to EN 60721-3-3 Mechanical strength Storage Transport Operation Vibrational load 1) - Displacement - Acceleration corresponds to class 1.5 at 5 to 9 Hz 5 m/s² at > 9 to 200 Hz 1M2 to EN 60721-3-1 3.5 at 5 to 9 Hz 10 m/s² at > 9 to 200 Hz 2M2 to EN 60721-3-2 0.075 at 10 to 58 Hz 10 m/s² at >58 to 200 Hz - Shock load 1) - Acceleration corresponds to class 40 m/s² at 22 ms 1M2 to EN 60721-3-1 100 m/s² at 11 ms 2M2 to EN 60721-3-2 100 m/s² at 11 ms 3M4 to EN 60721-3-3 Deviations from the specified classes are shown in italics. 1) The EN standards specified are the European editions of the international IEC standards with the same designations. Operating Instructions, 03/2013, A5E00692302A 29

Technical specifications Detailed technical data Table 6-2 Technical data for the, 380 V 480 V 3 AC, Part 1 Order number 6SL3000-2DE32-6AA0 2DE32-6AA0 2DE35-0AA0 2DE35-0AA0 Suitable for Power Module 6SL3310-1GE32-1AAx 1GE32-6AAx 1GE33-1AAx 1GE33-8AAx Type rating of the Power Module 110 132 160 200 Ithmax A 260 260 490 490 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.701 0.729 0.78 410 370 229 0.701 0.729 0.78 300 (shielded) 450 (unshielded) 0.874 0.904 0.963 Weight, approx. kg 66 66 122 122 Voltage Peak Limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.029 0.027 0.025 263 265 188 410 370 229 0.029 0.027 0.025 460 370 275 0.042 0.039 0.036 Terminal 70 ² Terminal 70 ² Terminal 35 ² 0.874 0.904 0.963 460 370 275 0.042 0.039 0.036 Terminal 70 ² Terminal 70 ² Terminal 35 ² Weight, approx. kg 6 6 16 16 263 265 188 392 285 210 392 285 210 30 Operating Instructions, 03/2013, A5E00692302A

Technical specifications Table 6-3 Technical data for the, 380 V 480 V 3 AC, Part 2 Order number 6SL3000-2DE35-0AA0 2DE38-4AA0 2DE38-4AA0 2DE38-4AA0 Suitable for Power Module 6SL3310-1GE35-0AAx 1GE36-1AAx 1GE37-5AAx 1GE38-4AAx Type rating of the Power Module 250 315 400 450 Ithmax A 490 840 840 840 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.874 0.904 0.963 460 370 275 1.106 1.115 1.226 300 (shielded) 450 (unshielded) 1.106 1.115 1.226 Weight, approx. kg 122 149 149 149 Voltage Peak Limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.042 0.039 0.036 Terminal 70 ² Terminal 70 ² Terminal 35 ² 392 285 210 460 385 312 0.077 0.072 0.066 309 1312.5 400 460 385 312 0.077 0.072 0.066 309 1312.5 400 Weight, approx. kg 16 48 48 48 1.106 1.115 1.226 460 385 312 0.077 0.072 0.066 309 1312.5 400 Operating Instructions, 03/2013, A5E00692302A 31

Technical specifications Table 6-4 Technical data for the, 380 V 480 V 3 AC, Part 3 Order number 6SL3000-2DE41-4AA0 1 Suitable for Power Module 6SL3310-1GE41-0AAx Type rating of the Power Module 560 Ithmax A 1405 Degree of protection IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 1.111 1.154 1.23 2 x 2 x 445 385 312 Weight, approx. kg 158 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.134 0.125 0.114 309 1312.5 400 300 (shielded) 450 (unshielded) Weight, approx. kg 72 1) Two dv/dt reactors are required for these dv/dt filters. The technical data provided applies to one dv/dt reactor. Note Cable lengths for versions with two dv/dt reactors For versions with two dv/dt reactors, the cable lengths specified in the table do not change. 32 Operating Instructions, 03/2013, A5E00692302A

Technical specifications Table 6-5 Technical specifications for the, 500 V 600 V 3 AC, Part 1 Order number 6SL3000-2DH32-2AA0 2DH32-2AA0 2DH33-3AA0 2DH33-3AA0 Suitable for Power Module 6SL3310-1GF31-8AAx 1GF32-2AAx 1GF32-6AAx 1GF33-3AAx Type rating of the Power Module 110 132 160 200 Ithmax A 215 215 330 330 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.578 0.604 0.645 460 360 275 0.578 0.604 0.645 300 (shielded) 450 (unshielded) 0.595 0.62 0.661 Weight, approx. kg 83 83 135 135 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.032 0.03 0.027 Terminal 70 ² Terminal 70 ² Terminal 35 ² 392 285 210 460 360 275 0.032 0.03 0.027 Terminal 70 ² Terminal 70 ² Terminal 35 ² 460 360 275 0.042 0.039 0.036 Terminal 70 ² Terminal 70 ² Terminal 35 ² 0.595 0.62 0.661 460 360 275 0.042 0.039 0.036 Terminal 70 ² Terminal 70 ² Terminal 35 ² Weight, approx. kg 16 16 16 16 392 285 210 392 285 210 392 285 210 Operating Instructions, 03/2013, A5E00692302A 33

Technical specifications Table 6-6 Technical specifications for the, 500 V 600 V 3 AC, Part 2 Order number 6SL3000-2DH34-1AA0 2DH35-8AA0 2DH35-8AA0 2DH38-1AA0 1 Suitable for Power Module 6SL3310-1GF34-1AAx 1GF34-7AAx 1GF35-8AAx 1GF37-4AAx Type rating of the Power Module 250 315 400 500 Ithmax A 410 575 575 810 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.786 0.826 0.884 460 385 312 0.862 0.902 0.964 460 385 312 300 (shielded) 450 (unshielded) 0.862 0.902 0.964 460 385 312 0.828 0.867 0.927 2 x 2 x Weight, approx. kg 147 172 172 160 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.051 0.048 0.043 309 1312.5 400 0.063 0.059 0.054 309 1312.5 400 0.063 0.059 0.054 309 1312.5 400 Weight, approx. kg 48 48 48 72 1) Two dv/dt reactors are required for these dv/dt filters. The technical data provided applies to one dv/dt reactor. 445 385 312 0.106 0.1 0.091 309 1312.5 400 Note Cable lengths for versions with two dv/dt reactors For versions with two dv/dt reactors, the cable lengths specified in the table do not change. 34 Operating Instructions, 03/2013, A5E00692302A

Technical specifications Table 6-7 Technical specifications for the, 500 V 600 V 3 AC, Part 3 Order number 6SL3000-2DH38-1AA0 1 Suitable for Power Module 6SL3310-1GF38-1AAx Type rating of the Power Module 560 Ithmax A 810 Degree of protection IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.828 0.867 0.927 2 x 2 x 445 385 312 Weight, approx. kg 160 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.106 0.1 0.091 309 1312.5 400 300 (shielded) 450 (unshielded) Weight, approx. kg 72 1) Two dv/dt reactors are required for these dv/dt filters. The technical data provided applies to one dv/dt reactor. Note Cable lengths for versions with two dv/dt reactors For versions with two dv/dt reactors, the cable lengths specified in the table do not change. Operating Instructions, 03/2013, A5E00692302A 35

Technical specifications Table 6-8 Technical specifications for the, 660 V 690 V 3 AC, Part 1 Order number 6SL3000-2DH31-0AA0 2DH31-0AA0 2DH31-5AA0 2DH31-5AA0 Suitable for Power Module 6SL3310-1GH28-5AAx 1GH31-0AAx 1GH31-2AAx 1GH31-5AAx Type rating of the Power Module 75 90 110 132 Ithmax A 100 100 150 150 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.49 0.508 0.541 350 320 227 0.49 0.508 0.541 300 (shielded) 450 (unshielded) 0.389 0.408 0.436 Weight, approx. kg 48 48 50 50 Voltage Peak Limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.016 0.015 0.013 263 265 188 350 320 227 0.016 0.015 0.013 350 320 227 0.020 0.019 0.018 Weight, approx. kg 6 6 6 6 263 265 188 263 265 188 0.389 0.408 0.436 350 320 227 0.020 0.019 0.018 263 265 188 36 Operating Instructions, 03/2013, A5E00692302A

Technical specifications Table 6-9 Technical specifications for the, 660 V 690 V 3 AC, Part 2 Order number 6SL3000-2DH32-2AA0 2DH32-2AA0 2DH33-3AA0 2DH33-3AA0 Suitable for Power Module 6SL3310-1GH31-8AAx 1GH32-2AAx 1GH32-6AAx 1GH33-3AAx Type rating of the Power Module 160 200 250 315 Ithmax A 215 215 330 330 Degree of protection IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.578 0.604 0.645 460 360 275 0.578 0.604 0.645 460 360 275 300 (shielded) 450 (unshielded) 0.595 0.62 0.661 Weight, approx. kg 83 83 135 135 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.032 0.03 0.027 Terminals: 70 ² 70 ² 35 ² 392 285 210 0.032 0.03 0.027 Terminals: 70 ² 70 ² 35 ² 460 360 275 0.042 0.039 0.036 Terminals: 70 ² 70 ² 35 ² 0.595 0.62 0.661 460 360 275 0.042 0.039 0.036 Terminals: 70 ² 70 ² 35 ² Weight, approx. kg 16 16 16 16 392 285 210 392 285 210 392 285 210 Operating Instructions, 03/2013, A5E00692302A 37

Technical specifications Table 6-10 Technical specifications for the, 660 V 690 V 3 AC, Part 3 Order number 6SL3000-2DH34-1AA0 2DH35-8AA0 2DH35-8AA0 2DH38-1AA0 1 Suitable for Power Module 6SL3310-1GH34-1AAx 1GH34-7AAx 1GH35-8AAx 1GH37-4AAx Type rating of the Power Module 400 450 560 710 Ithmax A 410 575 575 810 Degree of protection IP00 IP00 IP00 IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.786 0.826 0.884 460 385 312 0.862 0.902 0.964 460 385 312 300 (shielded) 450 (unshielded) 0.862 0.902 0.964 460 385 312 0.828 0.867 0.927 2 x 2 x Weight, approx. kg 147 172 172 160 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.051 0.048 0.043 309 1312.5 400 0.063 0.059 0.054 309 1312.5 400 0.063 0.059 0.054 309 1312.5 400 Weight, approx. kg 48 48 48 72 1) Two dv/dt reactors are required for these dv/dt filters. The technical data provided applies to one dv/dt reactor. 445 385 312 0.106 0.1 0.091 309 1312.5 400 Note Cable lengths for versions with two dv/dt reactors For versions with two dv/dt reactors, the cable lengths specified in the table do not change. 38 Operating Instructions, 03/2013, A5E00692302A

Technical specifications Table 6-11 Technical specifications for the, 660 V 690 V 3 AC, Part 4 Order number 6SL3000-2DH38-1AA0 1 Suitable for Power Module 6SL3310-1GH37-4AAx Type rating of the Power Module 800 Ithmax A 810 Degree of protection IP00 dv/dt reactor Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the Power Module - Load - PE Max. permissible cable length between dv/dt reactor and motor Dimensions Width Height Depth m 0.828 0.867 0.927 2 x 2 x 445 385 312 Weight, approx. kg 160 Voltage peak limiter Power loss - at 50 Hz - at 60 Hz - at 150 Hz Connections - to the dv/dt reactor - DC - PE Dimensions Width Height Depth 0.106 0.1 0.091 309 1312.5 400 300 (shielded) 450 (unshielded) Weight, approx. kg 72 1) Two dv/dt reactors are required for these dv/dt filters. The technical data provided applies to one dv/dt reactor. Note Cable lengths for versions with two dv/dt reactors For versions with two dv/dt reactors, the cable lengths specified in the table do not change. Operating Instructions, 03/2013, A5E00692302A 39

Technical specifications 40 Operating Instructions, 03/2013, A5E00692302A

Siemens AG Industry Sector Drive Technologies Large Drives P.O. Box 4743 90025 NUREMBERG GERMANY www.siemens.com/automation Subject to change without prior notice Siemens AG, 2005-2013