POLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES

Similar documents
Cold Shrink Straight Joint

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Quick Term III. 3M Cold Shrink 3 Core Indoor Termination. 3.3 kv mm 2

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

UNDERGROUND CONSTRUCTION MANUAL MATERIAL DATA

LEGEND POWER SYSTEMS

CLP s first 400kV XLPE cable application

EE028: Practical High Voltage Cable Jointing and Termination

Identification - electrical services

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

Identification of LV Cables

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Cable installation guidelines

ENERGY /// TRICKS OF THE TRADE TRICKS OF THE TRADE

3 SLiC Aerial Closure with Rubber End Seal

3M Cold Shrink Splice Kit QS-III 5416A

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7)

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

Instructions. Cable with Armor F CAUTION. October Rev A

ECS INSTALLATION OF SERVICE WAYS AND CABLES (SCHNEIDER ELECTRIC)

2178 Fiber Optic Splice Case and 2181 Cable Addition Kit

3M Cold Shrink Splice Kit QS-III 5515A

System 500. Non-fire-rated, mineral insulated copper sheathed wiring cable

Laying of cables and lines in electrical installations and data networks

SJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1

TERMINATIONS AND JOINTS FOR XLPE-INSULATED kv MEDIUM VOLTAGE CABLES

3 Cleaning. 4 Technical data

PEM1124ENG ENGLISH. STK TERMINATION KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv STKR TERMINATION KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv

3M Sensored Termination (15 kv) QX-T15I-vi1-E

Industrial Loadbreak Elbow

SWA Cable - BS5467 Steel Wire Armoured PVC Eland Product Group A9S

3M Cold Shrink Splice Kit QS-III 5514A


FIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays

Trends and Challenges of HV Cable Systems

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

2178-L/S Series Fiber Optic Splice Case with Gasket

Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex.

Signalling Cable Equivalent Sizes (formerly RT/E/C/11213)

3M Better Buried Closures

Fiberglass - Technical Data

HCS - HES Cabling Systems

AMERICAN NATIONAL STANDARD

Medium Voltage 12/20 (24)kV NF C cable system. Xavier Brosse Luanda May 2009

INSTALLATION INSTRUCTIONS

3M Better Buried Closure (with 3M Scotchlok Shield Bond Connector 4462-FN and 3M High Gel Re-enterable Encapsulant 8882)

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

Signalling Cable Equivalent Sizes

92-AK620-1/C 92-AK630-1/C 92-AK621-1/C 11kV 92-AS610-1/C 92-AS620-1/C STND. 93-AK621-1/C 93-AK630-1/C 22kV 93-AK631-1/C 93-AS620-1/C STND

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

Medium Box for Cable Termination

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR

Installation Manual SaVi Note Underwater LED Light

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF

3M Better Buried Compound Compression Closure System

HIGH VOLTAGE CABLE ACCESSORIES - Application, Design, Installation, Testing - Ivan Jovanovic G&W Electric Company

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series

LED control gear Compact fixed output

ELECTRICAL SAFETY INSPECTION REPORT

Contents. Track Circuit Rail Connection Components. Yellow Bonding Kits and T.P.W.S Joint and Termination Kits

Automatic Connector MHV Connectors MHV Introduction MHV series connectors Contents Polarized mating interfaces Anti-Rock mating interfaces

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

3 Foam Sealed Closure 2" (50 mm) with Compound Compression

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

Fixed Audio Output for the K2 Don Wilhelm (W3FPR) & Tom Hammond (NØSS) v August 2009

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

An introduction to Kabeldon cable accessories kv

Transmission Cables Overhead/Underground Guidance

3M Distribution Box (DDB)

INSTALLATION INSTRUCTION PEM1423ENG ENGLISH

Cold Shrink Silicone Rubber Termination QT-II

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

INSTALLATION INSTRUCTION PEM1368ENG ENGLISH

3M Fiber Optic Splice Closure 2178-XL & 2178-XL/FR 3M Cable Addition Kit 2181-XL and 2181-XL/FR

PEM1126ENG ENGLISH STPKR. TERMINATION KIT FOR PAPER CABLE WITH LEAD SHEATH 1 kv INSTALLATION INSTRUCTION

1 Inductive proximity switches. 5 Connecting cables. Highlights: New:

F CAUTION. Jacketed Concentric Neutral (JCN) Cable. Concentric Neutral (CN) Cable. IEEE Std. No. 48 Class 1 Termination 15 kv Class 110 kv BIL

Filters for Power Lines (Low Leakage Current)

EXPlora. Introduction

High Voltage Cables kv. Handling and Operating Instructions

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.

Trusted TMR I/O SmartSlot Slot Cables

OWNER'S MANUAL SIGNAL COMMANDER

podis CON Instructions podis CON Power Bus System Installation system for decentralized power distribution

Product Manual MNX10015 / REV C MODEL SB142, SB242. Dual Output Series Switch Boxes

LED Driver Compact fixed output

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

3M Fiber Optic Splice Closure 2178-XSB/XSB-FR & 2178-XLB/XLB-FR 3M Cable Addition Kit 2181-XB/XB-FR

GENUINE PARTS ! CAUTION

FIST-GCOG2-Dx6. Follow all local safety regulations related to optical fiber plant elements.

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers

Quick Term II. Cold Shrink Silicone Rubber Termination (With High-K Stress Relief) Instruction Sheet. Quick Term II. Silicone Rubber Termination Kits

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

Transcription:

1. SCOPE This document provides information and guidance on the application of polymeric cables on the SPEN 11kV network. Throughout this document, references to 11kV shall by inference also relate to 6kV and 6.6kV networks and equipment. 2. ISSUE RECORD This is a Reference document. The current version is held on the EN Document Library. It is your responsibility to ensure you work to the current version. Issue Date Issue No. Author Amendment Details Aug 2003 1 D.W. Naylor New Issue Nov 2003 2 J. Livie Issues Raised At Road Shows Dec 2012 3 C Sherry Significantly reduced in size because most of the previous information was about the transition period which finished a long time ago and most information is now referenced in new documents that have been created and are now referenced in this document. Dec 2017 4 C Sherry Reviewed and changed from a Controlled document to a Reference document in sections 2 and 4 3. ISSUE AUTHORITY Author Owner Issue Authority Clark Sherry Senior Eng, Engineering Design & Standards Frank Berry Circuits Manager Engineering Design & Standards Martin Hill Head of Engineering Design and Standards 4. REVIEW. Date:... This is a Reference document which has a 10 year retention period after which a reminder will be issued to review and extend retention or archive. DISTRIBUTION This document is not part of a Manual maintained by Document Control and does not have a maintained distribution list. SP Power Systems Limited Page 1 of 11

5. CONTENTS 1. SCOPE... 1 2. ISSUE RECORD... 1 3. ISSUE AUTHORITY... 1 4. REVIEW... 1 DISTRIBUTION... 1 5. CONTENTS... 2 6. REFERENCE DOCUMENTS... 3 7. POLICY... 3 8. COMPONENTS AND STOCK CODES... 6 9. CABLE RATINGS... 6 9.1 Special Installation requirements to achieve the Enhanced rating for 300mm2 3-core XLPE Cable... 6 9.2 Background... 6 9.3 Installation Method... 7 9.4 Recording... 7 10. PHOTOGRAPHS... 8 11. INSTALLATION PARAMETERS... 10 11.1 Bonding and Earthing... 10 11.1.1 Feeder cables... 10 11.1.2 Cables between switchgear and transformer... 10 11.2 Temporary Bonding of Cable Screens... 10 11.3 Insulation Testing of Polymeric Cables, and circuits comprising a mixture of cable types... 10 12. SOLUTIONS FOR CONNECTIONS TO LEGACY SWITCHGEAR... 11 13. OVERHEAD LINE TERMINATIONS... 11 SP Power Systems Limited Page 2 of 11

6. REFERENCE DOCUMENTS CAB-06-001 CAB-17-001 CAB-15-003 ESDD-02-007 SUB-02-613 Approved Equipment Register Cables Joint Kit Selector Handling and Installation of Cables up to and Including 33kV Equipment Ratings and Assessment of EHV/HV Systems Electrical Insulation Testing of HV Equipment up to 33kV 7. POLICY SPEN policy is for the exclusive use of polymeric cables in new construction, diversion and repair works. Single core and three core polymeric cables shall be used in accordance with the policies outlined in this section. Connections to legacy switchgear and transformers may require different approaches these are dealt with in later sections. Terminations onto switchgear and transformers shall use single core polymeric cables. Main cable runs shall be laid using three core polymeric cables. This includes sections of cable inserted into existing lengths of pilc or picas cable for reasons such as fault repair or cable route deviation. The transition between single core polymeric and three core cables shall be achieved by the use of trifurcating joints. These joints will also enable correct cable phasing to be achieved at switchgear and transformer terminations. Phasing will be achieved by crossing the single core cables before they enter the joint or cable box. Terminations onto overhead lines shall normally be via three core polymeric cables. Single core cable overhead terminations are also permitted in accordance with the requirements of the next paragraph. To avoid using two joints (a trifurcating joint and a straight joint) in close proximity on a short length of cable, in the following situations only it is permissible to lay three single core cables for the entire length of a cable connection: cable less than 25m length between switchgear and overhead line cable less than 25m length between transformer and overhead line cable less than 25m length between switchgear and switchgear cable less than 25m length between switchgear and transformer cable less than 25m length between switchgear and cable section cable less than 25m length between cable section and overhead line It should be noted that the 25m rule does not apply to 11kV single core runs between a Primary Transformer and the associated 11kV switchboard because it is not uncommon for these to be in excess of 25m. The earthing arrangements are also different. In all other situations, three-core cable shall be laid for the majority of the cable route connection with short lengths of single core cables being used for terminations as defined in the paragraphs above. When laying single core cables, three cables shall always be laid even if the application is only planned to be single phase. Examples of certain applications of this policy are shown on the following pages. SP Power Systems Limited Page 3 of 11

. Existing 11kV PICAS or PILC 3c cable Transition straight joint Abandoned section of 3 core cable Transition straight joint Cable Diversion or Fault repair New polymeric 3c cable Three polymeric single cores overhead termination 3 new single core polymeric cables laid entire length of connection Cable connection between overhead line and switchgear (less than 25m length). 3 core polymeric cable overhead termination Short single core tails for connection to switchgear Trifurcating transition joint 3 core polymeric cable for majority of route Cable connection between overhead line and switchgear (greater than 25m length). SP Power Systems Limited Page 4 of 11

Short single core polymeric tails for connection to switchgear Short single core polymeric tails for connection to switchgear Trifurcating transition joint Trifurcating transition joint Existing 11kV PICAS, PILC or polymeric 3c main New Substation to be connected (less than 25m from existing main). Trifurcating transition joint Short single core polymeric tails for connection to switchgear Short single core polymeric tails for connection to switchgear Trifurcating transition joint Transition straight joint New 11kV polymeric 3c main Existing 11kV PICAS, PILC or polymeric 3c main Transition straight joint New Substation to be connected (more than 25m from existing main). SP Power Systems Limited Page 5 of 11

8. COMPONENTS AND STOCK CODES All SAP numbers for cables, cable terminations, joints and any associated modules are all contained in the Approved Equipment Register Cables CAB-06-001. For specific joint or termination requirements to suit a range of different cables sizes refer to Joint Selector CAB-17-001. The specialised stripping tools and consumable items required to work on polymeric cables are listed below along with their corresponding SAP numbers. Tools SAP Number MDPE Sheath Stripper KMS type 30982573 PG3 stripping pliers 26-52mm dia cables - 2.8mm cutting wheels 30982574 PG4 stripping pliers 45-75mm dia cables- 2.8mm cutting wheels 30982575 Spare blade for PG pliers - circular cut - blade 20C 30982576 Spare blade for PG pliers - longitudinal cut - blade 20L 30982577 LHM1R adjustable screen scoring tool 14-40mm dia cables (easy strip) 30982578 Spare blade for easy strip screen stripping tool LHM1R 30982302 FBS 1714-1 Fully bonded semi-con removing tool 10-50mm dia cables 30982299 Spare blade for Fully bonded screen stripping tool FBS 1714-1 30982300 BRMrd1 insulation removing tool c/w depth stop 14-40mm dia cables 30982580 Spare blade for XLPE insulation stripping tool BRMrd1 30982304 Adjustable torque wrench 1/2" drive (Norbar) 40-200Nm 30982589 11/33kV Temporary Continuity Connector (TCC) 30980307 2M diameter tape 30982273 Magnetic Clip Holding Tool 30026495 Consumables Chinagraph pencil 30983010 P60 grade oxide cloth 25mm x 25m (For abrading outersheath) 30981644 P240 grade oxide cloth 25mm x 25m (For smoothing & polishing insulation surface) 30908291 P320 grade oxide cloth 25mm x 25m (For smoothing & polishing insulation surface) 30980913 P400 grade oxide cloth 25mm x 25m (For smoothing & polishing insulation surface) 2360902 Silicone grease (For lubricating stripping tools only) 30982202 CES4 Heatshrink gland 30982065 CES5 Heatshrink gland 30982066 9. CABLE RATINGS For cable ratings refer to ESDD-02-007 Equipment Ratings and Assessment of EHV/HV Systems 9.1 Special Installation requirements to achieve the Enhanced rating for 300mm2 3-core XLPE Cable Ratings for 11kV XLPE cables are given in ESDD-02-007 Equipment Ratings and Assessment of EHV/HV Systems. The installation method described below allow an enhanced rating for 3-core 300mm² XLPE cable to be achieved by laying a continuous separate earth wire along with the cable. 9.2 Background The SPEN assigned ratings for 3-core XLPE cables are limited by the company s onerous system earth fault requirements. The maximum operating temperature of the phase conductors is limited to a lower than maximum value to allow the cable s earth screen to start any fault carrying duty at a lower temperature. As a result, the theoretical maximum rating of the XLPE cable design is not achieved and by design under normal conditions, the ratings of the XLPE cable match those of the PICAS cables they replaced. SP Power Systems Limited Page 6 of 11

In some situations, the SPEN assigned rating for the 3-core 300mm² XLPE cable is slightly lower than customer requirements requiring a second cable to be laid to achieve a marginal increase in rating. The method described here allows a more cost effective approach whereby the cables earth screen is supplemented by a separate additional earth wire giving an improved earth fault capacity and enabling the power cable phase conductors to be operated at a higher temperature to achieve the enhanced rating given in ESDD-02-007. Critical factors in utilising this method include: Use of appropriate earth cable. Secure installation method for supplementary earth cable (avoidance of accidental damage). Method of connection of supplementary earth cable into power cable joints at each joint position without compromising the joint s moisture seals. Recording of the enhanced rating installation so that the purpose and significance of the supplementary earth conductor is clear to any party consulting the cable records in future. The enhanced rating given in ESDD 02 007 can only be achieved by rigorous application of the methods described here; the enhanced rating cannot be employed under any other circumstances. 9.3 Installation Method 1) The supplementary earth conductor shall be 32mm² copper (standard overhead line conductor). 2) The supplementary earth conductor shall be installed in a 32mm diameter duct to afford protection against 3 rd party damage. 3) The duct containing the supplementary earth conductor shall be laid beside and touching the power cable or the power cable duct. 4) The duct containing the supplementary earth conductor shall be bound to the power cable or power cable duct every metre using appropriate plastic cable ties. 5) The supplementary earth conductor shall be connected to the power cable earth screen at every joint position using only the materials and jointing instructions provided with the joint kit. 6) Connections between the supplementary earth cable and the power cable earth screen shall be installed only by jointers who have been trained to make these connections. 7) The supplementary earth conductor shall be connected to the substation earth at both ends of the circuit. 9.4 Recording Cable records shall be clearly and unambiguously marked to record: 1) That a supplementary earth conductor is installed adjacent to the power cable. 2) The enhanced and standard ratings for the circuit. The circuit shall revert to the standard rating should the supplementary earth conductor become damaged or disconnected. SP Power Systems Limited Page 7 of 11

10. PHOTOGRAPHS The photos below show a selection of polymeric cables and terminations. Single and three core polymeric cables SP Power Systems Limited Page 8 of 11

3 x single core overhead termination + earthing 3-core overhead termination + earthing 3 x single core switchgear termination. (L2 bushing boot left off for illustration purposes) SP Power Systems Limited Page 9 of 11

11. INSTALLATION PARAMETERS For all installation parameters, configurations and ducted installation requirements refer to CAB-15-003. 11.1 Bonding and Earthing 11.1.1 Feeder cables It is vital that the copper earth screen wires are bonded together and connected to the substation HV earth. The copper wires of each single core cable shall be gathered into individual brass shear bolt lugs. Most gland plates will incorporate a parking bar suitable for bolting the three lugs onto. A further fully rated connection is required from this parking bar to the substation HV earth. Gland plates shall be manufacture from a suitable non-ferrous material in order to eliminate eddy currents. 11.1.2 Cables between switchgear and transformer Alternating current in single core cables results in voltages being induced in the cable sheaths, the magnitude of the induced voltage depends upon the cable length, current magnitude and spacing of conductors. It is possible to keep these voltages within tolerable limits by bonding and earthing at both ends, unfortunately this gives rise to circulating currents in the cable sheaths which has the effect of de-rating the cables. Accordingly it has been practice normally only to bond and earth the screens of single core cables between switchgear and transformer at one end normally at the switchgear - typically up to 50m in length. This practice has normally only been applied to the 11kV tails of Primary transformers (the only previous application of 11kV single core cables) which carry high currents. For the application to connect cables between secondary switchgear and transformers the rating of the cable will remain adequate for the required duty. The copper screen wires shall be bonded and earthed at both the switchgear and transformer 11.2 Temporary Bonding of Cable Screens A screen bonding kit has been approved that will be used to bond the screens of cables which are to be jointed. This has a series of screw fastenings that can be fitted to the bunched screen wires to keep them at the same potential during jointing. 11.3 Insulation Testing of Polymeric Cables, and circuits comprising a mixture of cable types Cables shall be tested in accordance with the SPEN document SUB-02-613, Electrical Insulation Testing of HV Equipment up to 33kV. SP Power Systems Limited Page 10 of 11

12. SOLUTIONS FOR CONNECTIONS TO LEGACY SWITCHGEAR Work has progressed to engineer solutions that will enable polymeric cables to be terminated in a wide range of older switchgear that currently utilise a compound filled box and a PICAS termination. A variety of Guroflex resin filled terminations are now available for both 3-core and single core cable applications. These Guroflex kits and associated modules can be referenced in CAB-06-001 and CAB-17-001. However it is important to remember that not all legacy cable boxes are suitable. Clearance measurements from phase to phase and phase to earth must be able to be maintained. Some older sharp edged connections do not have the correct geometry for Guroflex to be effective. For example some 6.6kV boxes being used at 11kV will not have sufficient clearances and smooth enough geometry for a Guroflex termination solution to be a viable option. Also the pouring holes in some legacy switchgear cable boxes are quite small and not suitable for Guroflex which is more viscous than hot bitumen compound or G38 oil. Attempting to pour Guroflex into these unsuitable boxes which will create air voids and increased electrical stresses shall be avoided. 13. OVERHEAD LINE TERMINATIONS Two terminations will be available for one three core cable, or three single core cables. The choice of which termination to use depends upon the policy outlined in an earlier section of this guide. Many of the components are common between the terminations including the crucifix and surge divertor / insulators. Different cable cleats are required when used with single cores, which are specially shaped to hold the cores. Standard cable guards are still appropriate for use with polymeric cables, despite outer diameters being slightly different. SP Power Systems Limited Page 11 of 11