Full Disclosure Monitoring

Similar documents
We ve got the best technology to fit your power monitoring needs. Scenario works on all!

PowerMonic. FAQs [2/12]

Oscilloscopes for field applications

Oscilloscopes for field applications

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION SECTION 16901

Selection Table. Ordering Information

EMS DATA ACQUISITION AND MANAGEMENT (LVDAM-EMS) MODEL 9062-C

Sources of Error in Time Interval Measurements

Project Summary EPRI Program 1: Power Quality

1 Power Protection and Conditioning

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

DIGITAL INSTRUMENTS S.R.L. SPM-ETH (Synchro Phasor Meter over ETH)

Electrical and Electronic Laboratory Faculty of Engineering Chulalongkorn University. Cathode-Ray Oscilloscope (CRO)

Event recording (or logging) with a Fluke 287/289 Digital Multimeter

Advanced Test Equipment Rentals ATEC (2832)

Zero Crossover Dynamic Power Synchronization Technology Overview


BER MEASUREMENT IN THE NOISY CHANNEL

Application Note AN-708 Vibration Measurements with the Vibration Synchronization Module

BTV Tuesday 21 November 2006

User Manual Power and Harmonics Analyzer Model PQ3350

Fluke 430 Series Three-Phase Power Quality Analyzers

Getting Started with the LabVIEW Sound and Vibration Toolkit

IQ Analyzer 6400/6600 Series. Cutler-Hammer Power Management Products High End Metering Capabilities

1C.5.1 Voltage Fluctuation and Flicker

LED driver architectures determine SSL Flicker,

G4500. Portable Power Quality Analyser. Energy Efficiency through power quality

Overall vibration, severity levels and crest factor plus

Operating Instructions

A MISSILE INSTRUMENTATION ENCODER

PA9PLUS Portable Power Quality Analyzer

PRELIMINARY INFORMATION. Professional Signal Generation and Monitoring Options for RIFEforLIFE Research Equipment

Overall vibration, severity levels and crest factor plus 3 CF+ White Paper

4. ANALOG TV SIGNALS MEASUREMENT

Experiment 7: Bit Error Rate (BER) Measurement in the Noisy Channel

Calibrating attenuators using the 9640A RF Reference

# Voltage Performance Monitor Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

MIE 402: WORKSHOP ON DATA ACQUISITION AND SIGNAL PROCESSING Spring 2003

An Introduction to the Spectral Dynamics Rotating Machinery Analysis (RMA) package For PUMA and COUGAR

Assessing and Measuring VCR Playback Image Quality, Part 1. Leo Backman/DigiOmmel & Co.

INSTRUCTION MANUAL POWER QUALITY ANALYZER

PRINCIPLES AND APPLICATIONS

COMPOSITE VIDEO LUMINANCE METER MODEL VLM-40 LUMINANCE MODEL VLM-40 NTSC TECHNICAL INSTRUCTION MANUAL

Chapter 5 Flip-Flops and Related Devices

The Measurement Tools and What They Do

MAX11503 BUFFER. Σ +6dB BUFFER GND *REMOVE AND SHORT FOR DC-COUPLED OPERATION

Operating Instructions

Digital Delay / Pulse Generator DG535 Digital delay and pulse generator (4-channel)

Benchtop Portability with ATE Performance

PicoScope 4000 Automotive PC Oscilloscopes

Toronto Hydro - Electric System

Troubleshooting Your Design with Tektronix MSO and DPO Series Oscilloscopes

Transmitter Calibration

Digital Audio Design Validation and Debugging Using PGY-I2C

ME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition

Virtual Vibration Analyzer

S op o e p C on o t n rol o s L arni n n i g n g O bj b e j ctiv i e v s

Simple motion control implementation

National Park Service Photo. Utah 400 Series 1. Digital Routing Switcher.

4.9 BEAM BLANKING AND PULSING OPTIONS

MINI PC SCOPE PCSU01. User manual. test leads software download USB cable design enclosure

Dac3 White Paper. These Dac3 goals where to be achieved through the application and use of optimum solutions for:

OSCILLOSCOPE AND DIGITAL MULTIMETER

Oscilloscope Guide Tektronix TDS3034B & TDS3052B

DP1 DYNAMIC PROCESSOR MODULE OPERATING INSTRUCTIONS

Certificate of Calibration

Laser Beam Analyser Laser Diagnos c System. If you can measure it, you can control it!

Logic Analysis Basics

User Manual. Power and Harmonics Analyzer Model PQ3350

Logic Analysis Basics

NAPIER. University School of Engineering. Advanced Communication Systems Module: SE Television Broadcast Signal.

Application Note 11 - Totalization

V6118 EM MICROELECTRONIC - MARIN SA. 2, 4 and 8 Mutiplex LCD Driver

Hello and welcome to this training module for the STM32L4 Liquid Crystal Display (LCD) controller. This controller can be used in a wide range of

APQ Series Type C Power Factor Correction Banks

Power Supply and Watchdog Timer Monitoring Circuit ADM9690

PDA 1252 Portable Analyzer High Performance Power Quality Analyzer

Model 5240 Digital to Analog Key Converter Data Pack

Choosing an Oscilloscope

PulseCounter Neutron & Gamma Spectrometry Software Manual

SWITCHED INFINITY: SUPPORTING AN INFINITE HD LINEUP WITH SDV

technical note flicker measurement display & lighting measurement

Evaluating Oscilloscope Mask Testing for Six Sigma Quality Standards

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA

Understanding the Limitations of Replaying Relay-Created COMTRADE Event Files Through Microprocessor-Based Relays

The BAT WAVE ANALYZER project

1. Abstract. Mixed Signal Oscilloscope Ideal For Debugging Embedded Systems DLM2000 Series

Model 5250 Five Channel Digital to Analog Video Converter Data Pack

Major Differences Between the DT9847 Series Modules

Using the new psychoacoustic tonality analyses Tonality (Hearing Model) 1

MAutoPitch. Presets button. Left arrow button. Right arrow button. Randomize button. Save button. Panic button. Settings button

Switching Solutions for Multi-Channel High Speed Serial Port Testing

Quick Reference Manual

imso-104 Manual Revised August 5, 2011

System Requirements SA0314 Spectrum analyzer:

SigPlay User s Guide

Getting Started. Connect green audio output of SpikerBox/SpikerShield using green cable to your headphones input on iphone/ipad.

16 th Annual PQSynergy International Conference and Exhibition 2016

Brief Description of Circuit Functions. The brief ckt. description of V20 107E5 17 Monitor

Transcription:

Full Disclosure Monitoring Power Quality Application Note Full Disclosure monitoring is the ability to measure all aspects of power quality, on every voltage cycle, and record them in appropriate detail over the duration of a power study. It delivers clear visibility into all characteristics of a power system that affect critical loads and gives high confidence regarding the relative health of your power system. A simple setup process makes it unlikely you will miss events or critical measurements. Complicated setup procedures are a consistent source of monitoring frustration; if you configure a power monitor for the wrong measurements, set thresholds or sampling rates incorrectly, the monitor will record no useful information. You end up having to repeat the power survey or, worse yet, miss a rare intermittent event. In either case, complex configuration can lead to wasted time and money. With many monitors, more frustration follows after you ve collected the data as you are then faced with the challenge of sorting through data, trying to interpret the information. When investigating a serious power problem, searching through piles of data does not help get the power system up and running again. This application note explains the technology of Full Disclosure monitoring - how it gives clear visibility into a power system, and how it overcomes common shortcomings of monitoring instruments. With this technology: The need for setting thresholds, ranges and sampling rates is eliminated. The power monitor measures and processes every cycle. You can analyze both slowlychanging trends and high-speed events captured by one power monitor during a single monitoring session Changes in critical parameters are recorded and may be plotted on power tolerance curves. You can generate comprehensive written reports automatically. Measurements and event capture Full Disclosure monitoring requires an instrument that can perform significant signal processing on multiple input channels, and be able to monitor and store events that last both hours and microseconds. Many measurements and evaluations should be performed in order to judge power quality. To achieve Full Disclosure, all of these measurements must be processed simultaneously and in real time. Critical parameters and events include: RMS voltage and current Power and power consumption: Watts, VA, VAR, Power Factor, Displacement Power Factor, Demand and KWH Voltage sags, swells and outages Voltage transients Voltage imbalance Flicker (periodic voltage fluctuations which cause annoying modulation in lighting) Ground current Harmonic distortion Cycle-by-cycle measurements Root mean square measurements are the basis for determining power levels and capturing events of one cycle or more. Voltage, current and real power are usually measured as rms values and from these VA, VAR, PF and DPF can be calculated. Capture of sags, swells and outages are based upon rms values. Some power monitors use analog RMS measurement techniques and average the RMS measurement over several cycles. In this case, cycleto-cycle variations get lost. From the Fluke Digital Library @ www.fluke.com/library

A better approach is to look at every cycle. Full disclosure monitors use digital signal processing to measure RMS and harmonic distortion (THD) on every cycle, on all voltage and current channels. Measurements such as Watts, VA, VAR, and PF are derived for every cycle and processed in real time. The accuracy of power consumption and harmonics measurements depends not only on sampling rates, but also on processing throughput. Some monitors may sample for a limited period and suspend monitoring while they perform the power and harmonics calculations. Full disclosure monitors employing digital signal processors have the computational power to measure every cycle, without blind spots. Capturing Sub-cycle Events The intermittent nature of voltage events like sags, swells, outages and transients make them difficult to capture. To achieve Full Disclosure is to be able to analyze both the 5-minute outage and the 200-microsecond transient using the same instrument, during the same monitoring session. You should also be able to track the associated current events, to get a sense for the source of the disturbance. The ability of any digital recorder to capture and display transients depends on sampling rates and the design of the sampling system. Monitors equipped with peak detect circuitry can capture amplitude and phase of transients, but cannot display the shape of the transient. Monitors with highspeed sampling systems can both capture transients and display their waveforms, similar to a digital oscilloscope. For example, a sampling rate of 8 khz permits capture of transients and impulses down to 130 microseconds duration. This is adequate for capturing power factor capacitor switching transients, but is not fast enough for recording high speed impulses that occur inside facilities due to loads such as motors and machines turning on and off. To reveal the impulse waveform (Figure 2) requires high-speed analogto-digital sampling techniques at rates of 1 MHz or more. Standard practice is to perform power surveys over one business cycle. For most sites this means monitoring for a week to see the effects of shift changes, maintenance procedures and other weekly occurrences that affect power usage. Every day 5,184,000 cycles of voltage and the same number of current cycles occur on every phase. Clearly, Full Disclosure requires that highspeed sampling must be combined with creative memory management to provide microsecond detail, singlecycle visibility, and daily trends to provide on-going power quality tracking. No limits, no thresholds At the outset of a power survey, you may not know what to expect, making it difficult to anticipate problems and set up a monitor. For example, to ensure a robot on a production line does not malfunction due to a voltage event, a monitor must be set up to record events. How do you establish the correct limits, and for what types of events? The amount, as well as the detail, of power quality information is dependent on the setting of limits or thresholds. Older technology monitors require users to program Figure 1. Peak detect impulse capture. Figure 2. High speed, 2 MHz sampling impulse capture. thresholds and restrict the information captured by the instrument. Setting threshold limits is a major source of frustration. If they are set too low, the instrument collects too much data and runs out of memory or paper. If they are set too high, the monitor may not record any significant events. Then there is always the nagging fear that there may be important information just below the thresholds. Full disclosure monitoring eliminates the threshold problem by taking advantage of large memory capacity to capture all events above low, adaptive thresholds. This allows the instrument to record all changes in critical parameters. Full Disclosure Monitoring Reliable Power Meters 2

Figure 3. Sampling system architecture An Architecture that Delivers Breadth and Depth The diagram in Figure 3 shows the architecture of a full disclosure monitor that uses an on board digital signal processor, an internal hard disk drive, and an embedded microprocessor, a floating-point coprocessor and 4 MB of RAM. The 8 KHz sample and hold circuit and 14- bit analog to digital converter takes a one cycle snapshot on four voltage and five current channels and provides 128 samples per cycle. A digital signal processor performs a Fourier Transform on the sampled waveform data to the 63rd harmonic in 100 microseconds. This process is repeated on every cycle. From the harmonics information all other parameters such as RMS, Watts, VA, VAR, PF, THD, etc. are also calculated on every cycle. These parameters are logged to provide long-term summary graphs with one cycle resolution; the cycle by cycle data is summarized to show the maximum and minimum values recorded on a single cycle, as well as average values. A parallel signal path leads high-frequency events toward a 2 Msample/sec analog-to-digital converter. Digitized transient data is stored in a cache memory and time-correlated with RMS and other cycle-by-cycle measurements Adaptive thresholds and event capture In order to determine what gets stored, the instrument must determine what constitutes an event. Low, sensitive thresholds would be ideal and would insure that every event is captured. However, the desire to capture every small change must be balanced against a finite memory size. This is a severe problem with some monitors that will completely fill memory within seconds and cease monitoring if thresholds are incorrect. The solution is adaptive thresholds. In a full disclosure monitor, thresholds start at very low values. If the rate of incoming events will cause the memory to overflow before the monitoring period is over, software internal to the monitor raises the thresholds in 0.125 volt increments on successive cycles to regulate the rate of capture. If event activity slows down, the thresholds begin to lower in 0.125 volt increments; the threshold levels are constantly readjusting to match the event activity and rate of capture to memory capacity. Adaptive thresholds manage the instrument memory without the operator needing to be present. They prevent the monitor from coming to a halt in noisy, high activity situations, and ensure that the recorder completes its monitoring cycle. Using adaptive thresholds, the monitor captures the worstcase, most severe events, but provides a continuous cycle by cycle record of RMS voltage and current history, plus power consumption for the entire monitoring period. Event capture operates by recording RMS on a cycle-bycycle basis and simultaneous high-speed sampling. If the Full Disclosure Monitoring Reliable Power Meters 3

RMS voltage changes by 2.4 volts RMS on two successive cycles, the monitor records both the AC waveform and RMS values until the voltage stabilizes for two successive cycles. Full Disclosure technology provides you with waveform detail at the most critical times, namely during changes in the power system. Concurrently, the monitor maintains a record of RMS min, max, and average and plots the trend so that even a singlecycle sag or swell is captured. Any high-frequency activity is recorded as a transient event. Figure 4 shows a voltage sag of 107 volts RMS. Before the sag, the voltage is at 120 volts RMS. The beginning of the first transition event is marked when the RMS changes by 2.4 volts and ends when the RMS voltage reaches 107 volts and ceases to change. The second transition from 107 to 120 volts is recorded the same way. The steady state event between the two transitions has a magnitude and a duration that can be plotted as a point against a tolerance curve. Plotting events against power tolerance curves Power tolerance curves provide an indication of the likelihood that an event will cause an equipment failure. The vertical axis represents the magnitude of the event and the horizontal axis the duration of the event. The longer the duration of the event, and the more extreme it is, the more likely it is to cause a problem. There are various curves which are used depending upon equipment sensitivity and monitoring point. The ANSI curve, defines the maximum excursions of voltage with respect to time that can be expected at the service entrance from a utility. The CBEMA curve (Figure 5) and the newer ITIC curve describe the sensitivity of electronic equipment. Power tolerance curves focus your attention on the worstcase events. When you click on an event on the power tolerance curve, the analysis software links the RMS and AC waveform information to provide a plot of the steady state event along with the two transition events. The transition events can be expanded for further detail. Instruments that require fixed thresholds effectively eliminate areas of a power tolerance curve. Obviously, events that almost exceed the threshold are ignored, so you will miss symptoms that may indicate problems but fall below the threshold. It is difficult to represent equipment susceptibility as a simple limit, even if you have detailed knowledge of the equipment. Not only do manual thresholds affect whether you capture and event, they also affect the recorded duration of the event. Capturing all the events in your system allows you to superimpose a power tolerance curve after the power survey data has been collected. You can even superimpose your own customized curve. Curve editing and full disclosure capture allow you to quickly and easily check that power delivery systems are well within your required tolerances. Automatic reports The comprehensive nature of Full Disclosure technology lends itself to easy, thorough reporting. An automatic report writer sorts through the entire volume of survey data and builds a complete report in Figure 4. Steady state and transition events. Figure 5. Events plotted against CBEMA curve. Microsoft Word with text and graphs in a few minutes. The report writer is organized into chapters that can be selected to create as broad or as focused a report as the user desires. An automatic report writer increases productivity and helps make sense of large volumes of data. The user may also program limits in the report writer to report on only those events outside the limits. Full disclosure monitoring allows the limits to be set after the fact to operate on the captured data, and gives the user the option of compiling another report with a new set of limits. Full Disclosure Monitoring Reliable Power Meters 4

Conclusion There are two major constraints with manually programmed monitors with respect to event capture. First, there is a practical limit to the number of events that can be captured due to memory size. The second, and more serious limitation, is the operational limit the user imposes by setting limits and thresholds, restricting not only the number of events captured, but also restricting how the events are captured and ultimately presented. Full disclosure monitoring has created a new paradigm in power monitoring technology by capturing all the information and recording all events above low thresholds, and allowing you to more efficiently and effectively monitor and control power quality. Full Disclosure monitoring is an integral part of these Fluke and RPM products: Fluke Power Recorder Three phase portable power analyzer RPM MultiPoint Installed power analyzer RPM InSite Installed power monitor Fluke. Keeping your world up and running. Fluke Corporation PO Box 9090, Everett, WA USA 98206 Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa (31 40) 2 675 200 or Fax (31 40) 2 675 222 In Canada (800) 36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com 2003 Fluke Corporation. All rights reserved. Printed in U.S.A. 7/2003 2100695 D-ENG-N Rev A