Tech Support: Customer Service: General Tech Questions: Tech Docs:

Similar documents
Provides an activation of Relay 1 triggered by Input 1. The function also provides an option for reverse-logic on the activation of Input 1.

USER S GUIDE. 1 Description PROGRAMMABLE 3-RELAY LOGIC MODULE

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2

HS-509 VIBRATION TRIP MODULE

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at

Operating Instructions

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

KNX Dimmer RGBW - User Manual

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

RF Wireless Receiver (Model S4PU-DC-ANT3)

Colour Explosion Proof Video Camera USER MANUAL VID-C

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

RD RACK MOUNT DIMMER OWNERS MANUAL VERSION /09/2011

Model: LCD4WM 3.5 Window Mounted LCD Monitor User Manual Features

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

.Power Distribution Center. PD-1. Instruction Manual

MICROMASTER Encoder Module

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

Ambient Weather WS-01 Intelligent Color Changing Temperature Night Light with Ambient Backlight User Manual

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

CONTROL PANEL ENGLISH INSTRUCTIONS MOTORLINE MC 2 / SEAV LRS 2150 SET

Magnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A

Scale Track System. 21 Century y Signal System 2-Rail Manual

Standard signal metering in wall-mounting case

INSTALLATION AND OPERATION M

Aspect 2 Circuit Digital Scene Control

SECU-16. Specifications Power: Input Voltage 9-12V DC or AC Input Current Max 200mA. 8 2-wire inputs, Analog (0 5VDC) or Supervised

2x1 HDMI SWITCH. with Multiview and PIP Vanco Part Number: EVSW21MV

Electronic converter for level transmitters MT03L Instructions manual

Multi-functional safety relay modules PROTECT SRB-E

Solid-State Digital Timer

Safety Information. Camera System. If you back up while looking only at the monitor, you may cause damage or injury. Always back up slowly.

TUSKIN Equipment Corporation

M150SP USER S AND INSTALLER S MANUAL. v2.0 REV. 03/2017

MT03A Electronic converter for flow rate transmitters

4 Wiring Brochure Wiring and installation of specific control

Short Manual. ZX2 Short Manual.doc Page 1 of 12

Standard RS232 RS ma

Model Number Structure

FlexiScan. Impro FlexiScan 4-Channel Controller INSTALLATION MANUAL

Comfort System T-32-P Universal Thermostat. Operation Manual

RIGOL. Quick Guide DSA800E. DSA800E Series Spectrum Analyzer RIGOL TECHNOLOGIES, INC. All Rights Reserved.

SPX-5600 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface SPX-5600MAN. Page 1 of 20

Be sure to run the vehicle engine while using this unit to avoid battery exhaustion.

Multifunction Digital Timer

LIGHT COPILOT II. elationlighting.com Internet:

Dimming actuators GDA-4K KNX GDA-8K KNX

CHECK LINE. Model LS-36-LED. Stationary Stroboscope. Operating Manual BY ELECTROMATIC

PC-250. SMD Taped Parts Counter Operator s Manual. ISO 9001:2008 Certified. V-TEK, Incorporated 751 Summit Avenue Mankato, MN USA

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL

Ordering details. Approval. Classification

Operating instructions Electronic preset counter Type series 717

TAC1 Telephone Entry System

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

TRIPLETT. PairMaster. Lan Cable Test Set. Instruction Manual

MINI MCR-SL-F-UI-NC. Frequency transducers. Data sheet. 1 Description

Access Control Keypad for MK-DV, JB-DV

NAVIGATOR OWNER S MANUAL

HDMI WIRELESS EXTENDER/ RECEIVER. Vanco Part Number: HDWIRKIT HDWIR-RX. Technical Support

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

STX Stairs lighting controller.

User Manual. June 30, Copyright 2004 Canopus Co., Ltd. All rights reserved.

Assembly. Front view. LEDs. Parametrization interface. Power Bus

12months. on-site warranty. DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points

Radio receiver EXL. 4-channel / up to 1000 memory locations. Mounting and operating instructions for qualified electricians

User Guide. Centrex Recording Interface

PROXIMITY SWITCHES INDUCTIVE TUBULAR SENSOR M30 SERIES HIGHLIGHTS APPLICATIONS

3214NXT. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

TDEPD. Field-Programmable Pressure Switch/Transducer with Integrated LED Display. Programming Sequence Manual

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.0

HD Digital MPEG2 Encoder / QAM Modulator

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

Model IQ4-PC User Manual Revision Date:

Sentinel I24 Digital Input and Output Configuration

Gamma instabus. Technical product information

USER MANUAL. 22" Class Slim HD Widescreen Monitor L215DS

Sensor module. Safety instructions. Function Correct use. Product characteristics. Structure of the device. Operation. Ref.No.

AT450SAW Programmable Selective Amplifier

SATRI AMPLIFIER AMP-51R. Owner s Manual

RERUN ARCHITECTURAL DMX512 RECORDER OWNERS MANUAL

PQ-Box 100 Quick Start Instructions

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK

Owner s Manual. multiswitch Firmware-Version 1.06 OS- Version 1.02

MANUAL ENGLISH Core Club Ordercode: D2314

Installation and Operation Manual

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

GUIDE TO ASSEMBLY OF ERICA SYNTHS DELAY MODULE

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS

Installation Guide VL-MV10. Model No.

NEA WIRING CENTRE NEA HT 230V /24 V

XTM72 Exerciser Timer Module

APPLICATIONS. Automatic warehouse. Trasportation lines

POLARIS 4 ELECTRONIC CONTROL BOARD FOR SLIDING GATES MANUAL

INSTALLATION & OPERATING INSTRUCTIONS SINGLE/TWO CHANNEL 24HR/7 DAY TIMER. Cat No. TR671/TR672TOP

OWNERS MANUAL. Revision /01/ Lightronics Inc. 509 Central Drive Virginia Beach, VA Tel

16-BIT LOAD CELL/DUAL STATUS INPUT

AW900mT. User s Manual. Point-to-multipoint. Industrial-grade, ultra-long-range 900 MHz non-line-of-sight wireless Ethernet systems

Transcription:

Tech Support: 1-800-407-4545 Customer Service: 1-800-523-2462 General Tech Questions: Tech_Services@beainc.com Tech Docs: www.beasensors.com BR3-X Programmable 3 Relay Advanced Logic Module & Restroom Controller ENGLISH (US version) DESCRIPTION 8 1 2 3 4 7 5 6 1. WET input 2. DRY inputs 3. Relay outputs 4. Power input 5. AC/DC jumpers 6. WET/DRY jumpers 7. Programming buttons 8. 7-segment display ACCESSORIES 10RESTROOMKIT: Restroom Control Kit COMPONENT DESCRIPTION PART NUMBER Logic module Br3-X restroom controller 10BR3X Door position switch NO/NC magnetic door position switch 10SWITCH1084 Occupied indicator Lock status indicator with LED and sounder 10LEDSOUNDER "PUSH TO LOCK" Button Door lock actuator with LED 10PTLBUTTON 10EMERGENCYKIT: Emergency Add-On Kit COMPONENT DESCRIPTION PART NUMBER Assistance Required Signal Corridor LED with sounder 10ARS Emergency Signage Emergency instruction signage 70.5675 "PUSH FOR EMERGENCY ASSISTANCE" Button Emergency assistance request button with LED and sounder 10BUTTONCOMBO 75.5871.01 BR3-X 20160616 Page 1 of 12

The device should not be used for purposes other than its intended use. All other uses cannot be guaranteed by the manufacturer of the sensor. The installer of the door system is responsible for carrying out a risk assessment and installing the sensor and the door system in compliance with applicable national and international regulations and standards on door safety. The manufacturer of the sensor cannot be held responsible for incorrect installations or inappropriate adjustments of the sensor. PRECAUTIONS Shut off all power going to header before attempting any wiring procedures. Maintain a clean & safe environment when working in public areas. Constantly be aware of pedestrian traffic around the door area. Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door. ESD (electrostatic discharge): Circuit boards are vulnerable to damage by electrostatic discharge. Before handling any board ensure you dissipate your body s ESD charge. Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment. Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation. DO NOT attempt any internal repair of the components. All repairs and/or component replacements must be performed by BEA, Inc. Unauthorized disassembly or repair: 1. May jeopardize personal safety and may expose one to the risk of electrical shock. 2. May adversely affect the safe and reliable performance of the product resulting in a voided warranty. JUMPERS PRECAUTIONS TO OBSERVE WHEN USING A WET OUTPUT Never change the jumper settings when the module has power connected to it or when a load is applied. Never allow 2 different voltage sources to be connected to the load (electric strike for example) at the same time. This can result in serious damage to equipment. Always move both jumpers when changing a jumper set. If an EL device is being powered by a separate power source, DO NOT select the WET output option on the Br3-X. If WET is selected, the next activation of the module will send a voltage to the load and if there is already a voltage being applied from another source, the Br3-X and possibly the load will be permanently damaged. When using the WET output option on the Br3-X, set all desired switch positions ( WET DRY and AC DC) before the module is powered and before any loads are applied. When DC WET output is selected, COM terminal is positive(+) and the ground(-) is switched between NO and NC. Ensure there is no other voltage connected to the load. Whatever the Input voltage is at the Br3-X, the output will correspond. The following can also be observed: 1. If voltage Input at the Br3-X is AC, then output selection can be AC or DC. 2. If voltage Input at the Br3-X is DC, then output selection can only be DC. 3. The maximum load applied to Relay 1 should never exceed 1A. If more than one device is to be connected, add the consumption values together for a total value. If current is excessive, damage to equipment can result. 4. On the Br3-X, the WET output is only available at Relay 1. When supplying Br3-X with AC input voltage, and selecting WET output on relay with DC conversion, you actually get rectified AC voltage, which is identical to applying a bridge rectifier to any AC voltage. CAUTION: Relay 1 WET OPTION IS ACTIVE FOR ALL FUNCTIONS! RELAY 1 OUTPUT DRY/WET JUMPER 2 AC OUTPUT VOLTAGE 3 DC OUTPUT VOLTAGE 4 DRY both jumpers set to DRY N/A N/A WET 1 both jumpers set to WET both jumpers set to AC both jumpers set to DC NOTES: 1. WET output allows the Br3-X to supply a voltage output of up to 1 A on relay 1 for powering maglocks or electric strikes directly from the Br3-X. Rating of power supply powering the Br3-X must be at least 1 A. 2. Default jumper settings make relay 1 DRY. 3. AC voltage only available if Br3-X is powered by AC voltage. 4. DC voltage available if Br3-X is powered by AC or DC voltage. Page 2 of 12 75.5871.01 BR3-X 20160616

WIRING Each Br3-X function is wired differently. Please review and follow the appropriate wiring diagram shown for each function. FUNCTIONS FUNCTION DESCRIPTION LOGIC 10 timer activation of relay 1 via trigger of input 1 reverse logic available 11 ratchet / latching ratchet/latching of relay 1 via trigger of input 1 22 28 2-relay sequencer + inhibitor 2-relay sequencer + door position sequence of relay 1 and relay 2 with inhibiting of input 1 until input 2, input 3, or WET input is triggered activation of input 4 reinhibits input 1 sequence of relay 1 and relay 2 via trigger of input 1 or WET input input 2 allows delay to run when open but not when closed 29 deactivation timer sequence of relay 1 and relay 2 via trigger of input 1 or WET input input 2, once opened after sequence, allows relay 1 to deactivate input 2 allows delay to run when open but not when closed input 3 disables sequence, reverse logic available 36 37 3-relay sequencer + 1-shot 3-relay sequence with independent relay sequence of relay 1 and relay 2 and relay 3 via trigger of input 1 or WET input relay 1, relay 2, and relay 3 can be maintained or '1-shot' sequence of relay 1 and relay 2 and relay 3 via trigger of input 1 or WET input relay 1, relay 2, and relay 3 can be 'independent' or sequenced 50 interlock timer interlock of relay 1 and relay 2 via trigger of input 1 and input 2, respectively 55 interlock ratchet / latching interlock ratchet of relay 1 and relay 2 via trigger of input 1 and input 2, respectively 65 2-way 2-relay sequence sequence of relay 1 and relay 2 via trigger of input 1 sequence of relay 2 and relay 1 via trigger of input 2 input 3 triggers relay 1 individually, input 4 triggers relay 2 individually NL normally locked restroom sequence of relay 1 (lock), relay 2 (door), and relay 3 (occupied indicators) for normally locked, single occupancy restrooms NU normally unlocked restroom sequence of relay 1 (lock), relay 2 (door), and relay 3 (occupied indicators) for normally unlocked, single occupancy restrooms DN 3-relay sequencer + 'day / night (24 hr) mode' sequence of relay 1 and relay 2 and relay 3 via trigger of input 1 or WET input input 2 operation dependent upon input 4 ('day / night (24 hr) mode') 00 disable Br3-X disabled PARAMETERS PARAMETER DESCRIPTION LOGIC h1 h2 h3 d1 d2 rl relay 1 hold time relay 2 hold time relay 3 hold time delay between relay 1 & relay 2 delay between relay 1 & relay 3 reverse logic 00-60 seconds count down begins AFTER release of input 1 or WET input 00-60 seconds count down begins AFTER d1 (delay between relay 1 & relay 2) expires 00-60 seconds count down begins AFTER d2 (delay between relay 1 & relay 3) expires 00-60, _1 (1/4), _2 (1/2), _3 (3/4) seconds delay beings AT activation of input 1 or WET input 00-60, _1 (1/4), _2 (1/2), _3 (3/4) seconds delay beings AT activation of input 1 or WET input 00 = normal logic input 1 trigger must be NO and close its contact to trigger np no parameters no parameters available for selected function 01 = reverse logic input 1 trigger must be NC and open its contact to trigger 75.5871.01 BR3-X 20160616 Page 3 of 12

PROGRAMMING 1 2 3 Press and hold INCR + PARAM for 3 seconds. Display will toggle between FF and 00 for 5 seconds. Press INCR to cycle through functions. 4 5 6 Once desired function is selected, press PARAM to cycle through parameters. Display will toggle between parameter and its current value for 5 seconds. Press 3 INCR to cycle through parameter s values. 7 8 Repeat steps 4-7 until all function parameters are set. Wait 5 seconds for Br3-X to save and function to display. NOTES: 1. Function 00 disables the Br3-X. 2. np means no parameters are applicable for the selected function. 3. Pressing and holding INCR will rapid cycle. Page 4 of 12 75.5871.01 BR3-X 20160616

10 - timer rl - reverse logic FUNCTION 10 NOTE: Reverse logic allows for a Normally Closed (NC) INPUT 1. 11 - ratchet / latching NONE indefinitely. 2. Trigger INPUT 1. RELAY 1 will open. 22-2-relay sequencer + inhibitor h1 must be greater than d1 when using an electric lock 1. Trigger INPUT 2, 3, or 'WET'. FUNCTION 22 NOTE: Ensure INPUT 1 does not initiate the sequence and that INPUT 4 is closed when the door is closed. 75.5871.01 BR3-X 20160616 Page 5 of 12

28-2-relay sequencer + door position h1 must be greater than d1 when using an electric lock 1. Trigger INPUT 1 or 'WET'. for time h1. FUNCTION 28 NOTE: INPUT 2 allows the delay to run when the contact is open but triggers RELAY 2 immediately when the contact is closed. 29 - deactivation timer rl - reverse logic h1 must be greater than d1 when using an electric lock 1. Trigger INPUT 1 or 'WET'. for time h1. FUNCTION 29 NOTE: INPUT 2 deactivates RELAY 1 once INPUT 2 is opened (and after the sequence has run). INPUT 2 allows the delay to run when the contact is open but triggers RELAY 2 immediately when the contact is closed. INPUT 3 disables the sequence. Page 6 of 12 75.5871.01 BR3-X 20160616

36-3-relay sequencer + 1-shot h3 - relay 3 hold time d2 - delay between relays 1 & 3 h1 must be greater than d1 when using an electric lock 1. Trigger INPUT 1 or 'WET'. for time h1. RELAY 3 will close after time delay d2 and hold for time h3. FUNCTION 36 NOTE: If INPUT 1 or 'WET' is maintained, jumping INPUT 2, 3, and/or 4 will allow RELAY 1, 2, and/or 3 (respectively) to close, run the hold time and then open. If no jumpers are set, RELAYS 1, 2, and/or 3 will close, hold and not time out (open) until INPUT 1 or 'WET' is released. 37-3-relay sequence with independent relay h3 - relay 3 hold time d2 - delay between relays 1 & 3 h1 must be greater than d1 when using an electric lock 1. Trigger INPUT 1 or 'WET'. for time h1. RELAY 3 will close after time delay d2 and hold for time h3. 1. Trigger INPUT 2. for time h1. 1. Trigger INPUT 3. RELAY 2 will close and hold for time h2. 1. Trigger INPUT 4. RELAY 3 will close and hold for time h3. 75.5871.01 BR3-X 20160616 Page 7 of 12

50 - interlock timer 1. Trigger INPUT 2. RELAY 2 will close and hold for time h2. FUNCTION 50 NOTE: If INPUT 1 is triggered, INPUT 2 and RELAY 2 will be inhibited until INPUT 3 (door position switch) is closed. Conversely, if INPUT 2 is triggered, INPUT 1 and RELAY 1 will be inhibited until INPUT 4 (door position switch) is closed. 55 - interlock ratchet / latching NONE until indefinitely. 2. Trigger INPUT 1. RELAY 1 will open. 1. Trigger INPUT 2. RELAY 2 will close and hold indefinitely. 2. Trigger INPUT 2. RELAY 2 open. FUNCTION 55 NOTE: If INPUT 1 is triggered, INPUT 2 and RELAY 2 will be inhibited until INPUT 3 (door position switch) is closed. Conversely, if INPUT 2 is triggered, INPUT 1 and RELAY 1 will be inhibited until INPUT 4 (door position switch) is closed. Page 8 of 12 75.5871.01 BR3-X 20160616

65-2-way 2-relay sequence d2 - delay between relays 2 & 1 RELAY 2 will close after time delay d1 and hold for time h2. 1. Trigger INPUT 2. RELAY 2 will close and hold for time h2. RELAY 1 will close after time delay d2 and hold for time h1. 1. Trigger INPUT 3. 1. Trigger INPUT 4. RELAY 2 will close and hold for time h2. nl - normally locked restroom h1 must be greater than d1 RELAY 2 will close after time delay d1 and hold for time h2. 2. Trigger INPUT 3. RELAY 3 will close and INPUT 1 will be inhibited. 3. Trigger INPUT 2. RELAY 2 will close after time delay d1 and hold for time h2. RELAY 3 will open. FUNCTION nl NOTE: INPUT 3 will not function unless INPUT 4 is closed. INPUT 4 should be closed when door is closed. 75.5871.01 BR3-X 20160616 Page 9 of 12

nu - normally unlocked restroom RELAY 2 will close and hold for time h2. 2. Trigger INPUT 3. RELAY 1 and 3 will close and INPUT 1 will be inhibited. 3. Trigger INPUT 2. RELAY 1 will open. RELAY 3 will open. FUNCTION nu NOTE: INPUT 3 will not function unless INPUT 4 is closed. INPUT 4 should be closed when door is closed. dn - 3-relay sequence with 'day / night (24 hr) mode' h3 - relay 3 hold time d2 - delay between relays 1 & 3 1. Trigger INPUT 1, INPUT 2, or 'WET'. RELAY 3 will close after time delay d2 and hold for time h2. 1. Trigger INPUT 3. INPUT 2 will be uninhibited for 5 seconds. FUNCTION dn NOTE: INPUT 2 will only function if INPUT 4 is open. Page 10 of 12 75.5871.01 BR3-X 20160616

TEST Upon completion of jumper settings, wiring, and programming, test the Br3-X to ensure all function parameters are working correctly and as intended for the specific application. RELAY STATUS STATUS DESCRIPTION r1 relay 1 closed when wired NO or open when wired NC r2 relay 2 closed when wired NO or open when wired NC r3 relay 3 closed when wired NO or open when wired NC r- relay 1 and relay 2 closed when wired NO or open when wired NC r- relay 1 and relay 3 closed when wired NO or open when wired NC r= relay 1, relay 2, and relay 3 closed when wired NO or open when wired NC FUNCTION CROSS REFERENCE BR3 FUNCTION BR3-X FUNCTION 21 22 25 36 or 37 35 36 or 37 75 36 or 37 TROUBLESHOOTING Br3-X will not react to any inputs Incorrect power Verify power supply of 12 to 24 VAC/VDC +/-10% is wired to correct terminals Not programmed Incorrect wiring Defective Br3-X Ensure a function is programmed, Br3-X does not show 00, and all 'h' values are set to at least 01 Verify wiring is applied exactly as described for specific function programmed Replace Br3-X Br3-X has no output Incorrect output devices Ensure proper devices are connected to outputs for the specific function programmed Not programmed Incorrect wiring Incorrect jumper settings Defective Br3-X Ensure a function is programmed, Br3-X does not show 00, and all 'h' values are set to at least 01 Verify wiring is applied exactly as described for specific function programmed Ensure all jumpers are configured correctly for specific application Replace Br3-X E1, E2, E3, E4, E5 EEPROM error Reset Br3-X and reprogram 75.5871.01 BR3-X 20160616 Page 11 of 12

TECHNICAL SPECIFICATIONS Supply Voltage 12-24 VAC/VDC +/- 10% PLEASE KEEP FOR FURTHER USE - DESIGNED FOR COLOR PRINTING Current Consumption 30-130 ma (DRY output) Temperature Rating -15 to 150 F (-26 to 150 C) If powered by AC voltage and using WET output to convert to DC voltage and current draw of device is greater than 0.9 A, the upper temperature range is 130 F (54 C) Input Input 1, 2, 3, 4 WET input Contact Rating Relay 1 (DRY) Relay 1 (WET) Relay 2 Relay 3 Dimensions Housing Specifications are subject to change without prior notice. All values measured in specific conditions. DRY contact 5-24 VAC/VDC +/-10% 3 A @ 24 VAC or 30 VDC 1 A 3 A @ 24 VAC or 30 VDC 1 A @ 24 VAC or 30 VDC 5.2" x 2.2" x 1" (133 mm x 55 mm x 25 mm) ABS - white translucent BEA 75.5871.01 BR3-X 20160616 Original Instructions ANSI / AAADM Compliance Upon completion of the installation or service work, at a minimum, perform a daily safety check in accordance with the minimum inspection guidelines provided by AAADM. Provide each equipment owner with an owner s manual that includes a daily safety checklist and contains, at a minimum, the information recommended by AAADM. Offer an information session with the equipment owner explaining how to perform daily inspections and point out the location of power/operation switches to disable the equipment if a compliance issue is noted. The equipment should be inspected annually in accordance with the minimum inspection guidelines. A safety check that includes, at a minimum, the items listed on the safety information label must be performed during each service call. If you are not an AAADM certifi ed inspector, BEA strongly recommends you have an AAADM certifi ed inspector perform an AAADM inspection and place a valid inspection sticker below the safety information label prior to putting the equipment into operation. Tech Support: 1-800-407-4545 Customer Service: 1-800-523-2462 General Tech Questions: Tech_Services@beainc.com Tech Docs: www.beasensors.com Page 12 of 12 75.5871.01 BR3-X 20160616