Above Ground Cable Installation Systems Selection Guide

Similar documents
INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Signal Sighting and Position

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

Photovoltaic Module Installation Manual (IEC)

THE CABLE TRAY SYSTEM

Photovoltaic Module Installation Manual (IEC)

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.

ELECTRICAL SAFETY INSPECTION REPORT

Signalling Cable Equivalent Sizes

Engineering Instruction

SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

Signalling Cable Equivalent Sizes (formerly RT/E/C/11213)

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Trusted TMR I/O SmartSlot Slot Cables

Cable installation guidelines

Tab 10 - The NESC and Underground Applications. Restricted Siemens Industry, Inc All rights reserved.

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Laying of cables and lines in electrical installations and data networks

Register your product and get support at SDV5122/27. EN User manual

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

Amphenol. Amphenol-Tuchel Electronics GmbH. C 112 Series M12 - Connectors

Channel Cable Tray - Accessories

TRF STEP-DOWN TRANSFORMER USER MANUAL

XS_-EU. M8 and M12 Sensor Connectors. Ordering Information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

Description Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63

NetterVibrotron SRF. Operating Instructions for. Series SRF. These operating instructions apply to. Netter Static Adjustable Frequency Control

Effective earthing of screened cables

IndyGo Facility Upgrades Project 35671EE

CABLE CLEAT FAQs. Engineering Series. 1. What is a cable cleat?


INSTRUCTION MANUAL [J] [E] [C] [G] [B] [I] [H] [D] [F] [A] 0 INTRODUCTION 1 RECOMMENDATIONS 2 ACCESSORIES INCLUDED

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

Field Instruction. Any registered training organisation UETTDRCJ21A Lay ESI electrical cables. Before commencing work:

POLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES

INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN

CITOCUT Plasma inverter cutting range

Model Number Structure

KRF EMC Filters Installation, Operation and Maintenance Manual

HighBand 25. TrueNet Category 6 Solutions

01. Stay safe. Privacy information

Flygt Submersible Motor Cables

APPLICATION OF POWER SWITCHING FOR ALTERNATIVE LAND CABLE PROTECTION BETWEEN CABLE LANDING STATION AND BEACH MAN HOLE IN SUBMARINE NETWORKS

PEGAS 160 T PULSE HF PEGAS 200 T PULSE HF

Monochrome Video Monitors

Aerial Cable Installation Best Practices

CABLE TRAY MANUAL Based on the 2014 National Electrical Code

Identification - electrical services

SWA Cable - BS5467 Steel Wire Armoured PVC Eland Product Group A9S

I r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

In-Ceiling Electric Motorized Front Projection Screen Evanesce Series. User s Guide

Use of halogen-free cables and electrical wires at European XFEL

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL, RADIO FREQUENCY (SERIES SMA (CABLED) - PLUG, PIN CONTACT, CLASS 2)

STE Technic Project Engineering Services Trade Ltd. Co. General Information. Main Features. Proven Performance

Australian/New Zealand Standard

USERS GUIDE MCX-HTS. HDMI to 3G SDI Converter. Manual Number:

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Fiberglass - Technical Data

LED MODULES READYLINE DL

R87B. Box Fan. Comprehensive Lineup of Single, Double, and Triple Axial Fans with Easy One-step Mounting. Ordering Information. Model Number Structure

AMERICAN NATIONAL STANDARD

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

Ground Frames and Shunters Releases

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

CONTENTS. Table of Figures

Features. High Brightness SMD LED Light source

e-enterable Fiber Optic Splice Closure (Re-Enterable Aerial Closure for Access Service)

Inductive sensor NI3-EG08K-Y1-H1341

SPECIAL SPECIFICATION 2344 TMC Support Equipment

19" TiRAX cabinet system. from page 3. 19" NETcell cabinet system from page 31. Open 19" racks from page 43

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

SPECIAL SPECIFICATION 8540 Telecommunication Cable

Installation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.

8000 Plus Series Safety Light Curtain Installation Sheet ( CD206A/ CD206B )

Trusted 40 Channel Analogue Input FTA

OPTICAL FIBRE CABLE NETWORK 2004/1

/ PAT01 USER MANUAL

Trusted 40 Channel 120 Vac Digital Input FTA

Gigabit Multi-mode SX to Single Mode LX Converter. User s Manual NGF-728 Series. Warning COPYRIGHT

DISCLAIMER. This document is current at the date of downloading. Hunter Water may update this document at any time.

User Instructions. 16 SCB Sync Station.

MATERIAL SPECIFICATION FOR SIGNAL HEADS

HazLoc Essential Guides: Cable Glands

PERFORMANCE SPECIFICATION SHEET CONNECTORS, PLUGS, ELECTRICAL, COAXIAL RADIO FREQUENCY, (SERIES TNC (CABLED), PIN CONTACT, RIGHT ANGLE, CLASS 2)

ART 7 SERIES PROFESSIONAL ACTIVE SUBWOOFERS. a new generation of speakers is born and it s ready to rock audiences all over the world

Sample Test Project. District / Zonal Skill Competitions. Skill- Electrical Installation. Category: Construction and Building Technology

Soft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit

Signal Sighting Standard

PERFORMANCE SPECIFICATION SHEET

TECHNICAL MANUAL DRAW-WIRE DISPLACEMENT TRANSDUCER TYPE DWT

Transcription:

Discipline: Engineering (Electrical) Category: Standard Above Ground Cable Installation Systems Selection Guide PDS 13 Applicability ARTC Network Wide CRIA (NSW CRN) Primary Source RIC Standard EP 20 00 00 03 SP version 1.0 Document Status Version Date Reviewed Prepared by Reviewed by Endorsed Approved 1.3 1 September 2010 Standards National Bridges & Structures Eng / Mgr Standards Exec Manager SS&P 23/09/2010 CEO Amendment Record Version Date Reviewed Clause Description of Amendment 1.1 5 January 2005 Reformatted to ARTC Standard 1.2 11 March 2005 Disclaimer Minor editorial change 1.3 1 September 2010 2, 4.7.1, 5.4, 6.4 Replaced reference to superseded NSW Standard BSS 02 with applicable Australian Standard for tunnel fire safety Australian Rail Track Corporation Limited 2010 Disclaimer: This document has been prepared by ARTC for internal use and may not be relied on by any other party without ARTC s prior written consent. Use of this document shall be subject to the terms of the relevant contract with ARTC. ARTC and its employees shall have no liability to unauthorised users of the information for any loss, damage, cost or expense incurred or arising by reason of an unauthorised user using or relying upon the information in this document, whether caused by error, negligence, omission or misrepresentation in this document. This document is uncontrolled when printed. Authorised users of this document should visit ARTC s intranet or extranet (www.artc.com.au) to access the latest version of this document.

Contents Contents 1 Scope and Application... 4 2 References... 4 3 Definitions... 4 3.1 Cable Installation System... 4 3.2 Stray Traction Electrolysis Currents... 4 3.3 Touch Voltage... 5 3.4 Transferred Potentials... 5 4 General... 5 4.1 Strength... 5 4.2 Cable Support Points... 5 4.3 Joins and Couplings... 5 4.4 Radius of Bends... 5 4.5 Cable Rating... 6 4.6 Temperature Range... 6 4.7 Corrosion Resistance... 6 4.7.1 Rail Tunnels... 6 4.8 Vibration Resistance... 6 4.9 Electrical Discontinuities... 6 4.10 Cutting and Snagging Hazards... 7 4.11 Cable Joints... 7 5 Protection from Specific Hazards... 7 5.1 Work in the Vicinity of the Cable Route... 7 5.2 Falling Rocks, etc... 7 5.3 Wind Load... 7 5.4 Fire... 7 5.5 Vermin... 8 5.6 Moving Vehicles... 8 5.7 Water / Moisture... 8 5.8 Ultra-Violet (Solar) Radiation... 8 5.9 Vandalism... 8 6 Optional Features... 9 6.1 Restraint of cables... 9 6.2 Identification of cables installed... 9 6.3 Earthing... 9 Version 1.3 Date of last revision: 1 September 2010 Page 2 of 9

Contents 6.4 Combustion Products... 9 6.5 Aesthetics... 9 6.6 Segregation in Joint Use Situations... 9 Version 1.3 Date of last revision: 1 September 2010 Page 3 of 9

Scope and Application 1 Scope and Application This publication sets out the requirements for above ground cable installation systems for high voltage ac and 1500 volt dc traction cables including cable trays, cable ladders, ducts and conduits. This publication includes ground line troughing systems. Aerial and underground systems are excluded. It is intended that this standard be used in determining the suitability of proprietary cable installation systems for specific applications. The publication applies to outdoor and indoor situations, including tunnels. This standard is applicable to new works and for major rehabilitation of existing infrastructure. 2 References AS 1214:1983 Hot-dip galvanized coatings on threaded fasteners (ISO metric coarse thread series). AS/NZS4680:1999 Hot-dip galvanized (zinc) coatings on fabricated ferrous articles.as1397:2001 Sheet steel and strip Hot-dip zinc-coated or aluminium/zinc-coated. AS 1660.5.3:1998 Test methods for electric cables, cords and conduits Fire tests - Determination of the amount of halogen acid gas evolved during the combustion of polymeric materials taken from cables. AS 1939: 1990 Degree of protection provided by enclosures for electrical equipment (IP Code). AS/NZS 2053.1:2001 Conduits and fittings for electrical installations Part 1: General requirements AS/NZS 4296:1995 Cable trunking systems. AS/NZS 3000:2000 Electrical installations (known as Australian/New Zealand Wiring Rules). Applicable Australian Standard for tunnel fire safety SAA HB 29:2000 Communications Cabling Manual, Module 2: Communications Cabling Handbook. PCP 03 Cable Route Selection Guide. PDS 08 Low Voltage Installations Earthing. SCP 21 Construction of Cable Route and Associated Civil Works. C(b)2 1989 ESAA Guidelines for the Installation of Cables Underground. 3 Definitions 3.1 Cable Installation System A cable tray, cable ladder, duct or conduit and includes fasteners brackets and supporting structure(s) erected specifically for the cable installation system. Any cable restraints used to attach the cable to a cable ladder or similar shall be considered to be part of the cable installation system. 3.2 Stray Traction Electrolysis Currents In a DC electrified rail system, it is possible for some traction return current to leak from the rails and flow in an electrically parallel return path to the substation. This path may be along any continuous metallic item running geographically parallel to, or repeatedly crossing the rail corridor. This path may be along underground pipes, cable sheaths or along above ground paths such as metallic signal troughing and continuous fences. Where the current leaves this Version 1.3 Date of last revision: 1 September 2010 Page 4 of 9

General alternate metallic circuit to return to earth, the metal is lost through the electro-chemical process called electrolysis. 3.3 Touch Voltage The voltage which may appear between any point of contact with un-insulated metalwork located within 2400 mm of the ground and any point on the surface of the ground within a horizontal distance of one metre from the vertical projection of the point of contact with the uninsulated metalwork. 3.4 Transferred Potentials When an electrical fault to earth occurs the earth potential near the fault is different to the potential at a remote earth. The presence of a long conductive structure such as a metallic fence, metallic cable troughing, or the like near a fault can transfer the remote earth potential into the local area near the fault. Should a person then be able to bridge between these two potentials, the person may experience an electric shock. Similarly an electrical fault near a long conductive structure may transfer a local fault potential to a remote location, and a person remote to the actual fault may experience an electric shock. 4 General 4.1 Strength The cable installation system shall have adequate strength to: support the static weight of the cable, resist the handling forces that might reasonably be expected during installation or repair of the cable, resist the forces that may result from thermal expansion of the cable and/or cable installation system, and resist the electromagnetic forces that may result during an electrical fault. In some cases additional strength may be required due to local conditions; in particular see 5.1, 5.2 and AS/NZS 4296. 4.2 Cable Support Points If the cable installation system does not support the cable continuously, the spacing between support points shall be such that the cable does not sag more than the cable manufacturer s recommendation. The cable support points shall be smooth, rounded and of sufficient width so as not to subject the cable to damaging mechanical surface stress. 4.3 Joins and Couplings The cable installation system shall include appropriate means of joining lengths or modules together in a manner that does not compromise the continuity of support or protection requirements. If the cable installation system is intended for multiple cables, any Y or T couplings needed shall also meet this requirement. 4.4 Radius of Bends The cable installation system shall be able to accommodate the minimum bending radius prescribed by the cable supplier without the continuity of support or protection being compromised. Where the cable installation system is of a form that requires the cable to be drawn through a duct or conduit, the bend radius that the cables are subjected to shall not be less than the minimum bending radius as specified by the cable manufacturer. Version 1.3 Date of last revision: 1 September 2010 Page 5 of 9

General 4.5 Cable Rating Cable Installation System characteristics, such as shading, ventilation and heat dissipation, shall be assessed to ensure that the required cable capacity is achieved. The choice of cable size and cable installation system cannot be decided independently and shall be determined in combination. 4.6 Temperature Range The cable installation system shall maintain all aspects of its integrity whilst subject to frequent temperature cycles between the minimum expected ambient temperature and the greater of the maximum operating temperature of the cable and the maximum temperature of the cable or cable support system due to solar radiation. The minimum ambient temperature shall normally be taken to be -5 o C. 4.7 Corrosion Resistance The cable installation system shall have adequate corrosion resistance to ensure that the design life of the installation is achieved without significant loss of strength or the appearance of hazards such as sharp edges. In assessing the corrosion protection the following factors shall be taken into account: moisture electrolysis currents dissimilar metals in contact contaminants, both natural, eg salt, and man made pollutants. If components are galvanised to provide corrosion resistance, they shall be hot dip galvanised in accordance with AS/NZS 4680 and AS 1397. (Threaded fasteners shall be galvanised in accordance with AS 1214). 4.7.1 Rail Tunnels Galvanised steel components may be used in dry Rail Tunnels. In tunnels where sections of the cable installation system is exposed to water seepage marine grade aluminium shall be used. Stainless steel (grade 316) fasteners shall be used in conjunction with the marine grade aluminium components. The installation system shall comply the applicable Australian Standard for tunnel fire safety. 4.8 Vibration Resistance The cable installation system, including supporting structure(s), foundations and fasteners shall have adequate long term resistance to vibration from rail traffic and other sources. 4.9 Electrical Discontinuities In order to avoid problems with transferred earth potentials and electrolysis currents, metallic cable installation systems shall include provision for electrical discontinuities along the length of the cable installation system. Electrical discontinuities shall be achieved by the provision of an air gap of not less than 30 mm or by the use of a non-conductive insert. Where lids are provided, positive measures shall be taken to prevent the lids being replaced in a manner which short-circuits the electrical discontinuities. The maximum distance between discontinuities shall not exceed 300m. The distance between discontinuities shall be reduced if the cable installation system is erected where a touch voltage Version 1.3 Date of last revision: 1 September 2010 Page 6 of 9

Protection from Specific Hazards hazard may exist in relation to an overhead wiring structure or similar. These requirements are specified in PCP 03 Cable Route Selection Guide and SCP 21 Construction of Cable Route and Associated Civil Works. If the cable installation system is in close proximity to an overhead wiring structure, the discontinuities shall be located to prevent hazards due to touch potentials. See PDS 08 Low Voltage Installations Earthing and SCP 21 Construction of Cable Routes and Associated Civil Works. 4.10 Cutting and Snagging Hazards When assembled, the cable installation system shall be free from sharp edges, burrs, flashes and the like that may cause injury to persons installing or replacing the cable, injury to persons under any circumstances. 4.11 Cable Joints The cable installation system shall support and accommodate standard cable joints. The system shall also permit cable jointing operations without compromising the integrity of the cable installation system, the completed joint, the adjacent cable or the safety of the cable jointing personnel. 5 Protection from Specific Hazards Protection from the following hazards may be required in some circumstances. Where protection from a listed hazard is required, the cable installation system shall comply with the additional requirements listed under that hazard. 5.1 Work in the Vicinity of the Cable Route Where the cable route is near the track, or in another location where maintenance personnel and equipment are likely to be in the vicinity of the cable, the cable installation system shall provide protection for the cable from, and shall itself withstand, impacts that can reasonably be expected to result from such work. This protection shall include loads that may arise from persons standing or sitting on the cable support system, or placing material on or against it. Where the cable installation system is installed more than 2000 mm above ground this hazard can normally be disregarded. 5.2 Falling Rocks, etc Where the cable route is at the bottom of a cutting or embankment, the cable installation system shall be designed and positioned to minimise the risk exposure of the cable and the cable installation system from falling rocks and articles that may be illegally dumped such as motor vehicle tyres. The cable installation system shall have a heavy impact resistance in accordance with AS/NZS 4296. 5.3 Wind Load 5.4 Fire Where the cable route is exposed to strong winds or is near the track and subject to train induced wind, any removable lid required must be positively secured. Snap on lids are not acceptable in these situations. If the cable installation system is required to protect the cable against external fire, the cable installation system shall protect the cable from convected and radiated heat, and from burning particles that may fall, or be blown, onto the installation system. Version 1.3 Date of last revision: 1 September 2010 Page 7 of 9

Protection from Specific Hazards The cable installation system shall be designed to minimise the build-up of litter around the cable or cable installation system and to facilitate the easy removal of any accumulated litter or other fuel. Where the cable installation system is in a rail or pedestrian tunnel, it shall comply with the requirements of the applicable Australian Standard for tunnel fire safety. 5.5 Vermin If required to protect the cable from rats the cable installation system shall provide continuous enclosure of metallic or other suitably resistant material with a a rating of IP3X as specified in AS 1939. 5.6 Moving Vehicles If protection from de-railed trains is required the cable route shall be altered in accordance with PCP 03 Cable Route Selection Guide. If protection from motor vehicles and plant is required the preferred option is alteration of the cable route in accordance with PCP 03 Cable Route Selection Guide. If an alternative route is not feasible vehicle barriers independent of the cable installation system shall be provided. In circumstances where it is necessary for vehicular traffic to cross a ground line troughing route, load carrying plates shall be provided over the troughing route. Such load carrying plates shall be supported clear of, and independent of, the troughing. Alternatively, an underground system may be used. 5.7 Water / Moisture If required to protect the cable from water or moisture the cable installation system shall be classified and tested as a system for its level of protection against the ingress of water in accordance with AS 1939. 5.8 Ultra-Violet (Solar) Radiation If to be installed outdoors the cable installation system shall be sufficiently resistant to ultra violet solar radiation to ensure that the design life of the installation is achieved. If required to protect the cable from ultra-violet solar radiation the cable installation system shall provide the required level of protection over the full range of angles of incidence present at the location. 5.9 Vandalism Any cable installation system that is not in a secured area must be considered to be subject to vandalism. The degree of risk should be assessed on a case by case basis and protective measures taken accordingly. Any cable installation system that is not in a secured area must be tamper proof without the use of tools ie no snap on lids, etc. Resistance to graffiti may be appropriate in some circumstances in which case a graffiti removal system/plan must be available for the particular cable installation system prior to its selection being confirmed. Version 1.3 Date of last revision: 1 September 2010 Page 8 of 9

Optional Features 6 Optional Features 6.1 Restraint of cables Positive restraint of the cables may be required to ensure segregation of cables, for uniformity, to ensure adequate cooling or to maintain constant circuit impedance where three individual cables are used for a three phase circuit. If positive restraint of the cable is required (as opposed to reliance on gravity), the cable restraints used shall be spaced such that the cable does not deflect more than the cable manufacturer s recommendation between restraints as a result of gravitational, electromagnetic or other forces that the cable may be subjected to. Note that where cables are not resting on a continuous surface it shall be supported by a suitable means as required by AS/NZS 3000 (section 3..9.3)at intervals recommended by the cable manufacturer. 6.2 Identification of cables installed If the cable installation system fully encloses the cables, the cable installation system shall provide a suitable means of cable identification labelling. If the cable installation system does not fully enclose the cables the cable identification labelling may be direct on the cables. The means of cable identification labelling shall not compromise any other characteristics of the cable installation system and shall facilitate labelling at intervals of not more than 20m. The labelling shall include the words Danger - High voltage. 6.3 Earthing If the design, or the ARTC Earthing/Bonding/Electrolysis standards requires earthing of the cable support system, provision shall be made for earthing each component except where an assembly is classified as having electrical continuity, in which case provision shall be made for earthing each such assembly. An assembly classified as having electrical continuity for the purpose of earthing shall pass a test similar to that prescribed by AS/NZS 2053.1:1995 Appendix F. 6.4 Combustion Products If required not to emit toxic combustion products, the cable support system shall be classified as halogen free. When tested in accordance with AS 1660.5.3, halogen free fittings and materials shall evolve not more than the equivalent of 5 mg of hydrochloride-acid per gram of sample. Trunking or conduit systems in railway tunnels are to be low smoke, low toxicity and halogen free. 6.5 Aesthetics If the cable installation system is to be erected in station environs or in other places open to public view aesthetics must be considered. The cable installation system should be un-obtrusive. The need to match surface finish with other items should be checked. 6.6 Segregation in Joint Use Situations If the cable installation system is also to accommodate other cables of different systems the segregation requirements of each system must be met. In particular SAA HB 29 must be met for all communications cables. Other issues to be considered are electromagnetic coupling, under fault and normal conditions, cumulative thermal effects, and segregation of earthing systems. Version 1.3 Date of last revision: 1 September 2010 Page 9 of 9