IQ Analyzer 6400/6600 Series Cutler-Hammer Power Management Products High End Metering Capabilities
New IQ Analyzer Available May 2000 6400/6600 Series 2
Power Quality Monitoring Over 150 metered parameters for comprehensive diagnostics Assess trends, harmonics and waveforms to prevent process disruptions and equipment damage Isolate and diagnose power quality problems by analyzing historical metered data Control energy usage and costs via measurement, on-board data storage and time-of-use registers IQ Analyzer 3
Overview Revenue metering accuracy ANSI C12.16 ( 1% ) ANSI C12.20 ( 0.5% ) IEC 687 / Canada ( 0.5% ) Independent certification Time Of Use Registers Expanded event storage UL/CUL/CE (CSA applied for) New Display & Faceplate 4 Custom Display Screens 4
IQ Analyzer Key Features High-speed waveform capture Programmable event triggers 2 cycles @ 128 samples/cycle & 8 cycles @ 32 samples/cycle 11 channels of voltage & current information are saved Local display of waveform (6600 series only) Measures current and voltage through 50th harmonic Display harmonic spectrum on local display (6600 series only) 5
IQ Analyzer Key Features CBEMA/ITIC event display via PowerNet dv/dt trigger captures subcycle voltage disturbances (6600 series only) Communication flexibility: INCOM via IPONI Ethernet via EPONI & EPONIF RS-232 via RS232PONI Modbus via MPONI (Coming Soon!) 6
IQ Analyzer Key Features The IQ Analyzer stores 44 different minimum & maximum values including: Current Voltage Power Power Factor Frequency THD 7
IQ Analyzer Key Features On-board event data logging Auxiliary I/O capabilities Analog Outputs (3) 0-20mA/4-20mA 1% accuracy Analog Input (1) 0-20mA/4-20mA 1% accuracy Digital Inputs (3) optically isolated +30Vdc Digital Outputs (4) Form C contacts 10A @ 240Vac 8
IQ Analyzer Key Features Monitors L-L, L-N, L-G and N-G voltage PT ratios from 1:1 to 5,000:1 Monitors phase, neutral and ground current CT ratios from 5:5 to 10,000:5 Up to 40A continuous, 300A for 1 second Measures % Total Harmonic Distortion (THD) for current and voltage 9
New Features New Trending Capabilities 4 Independent trends Up to 6 parameters per trend Can chose from over 94 parameters Total of 90K bytes of storage Single parameter every 15 min. for 234 days Independent memory allocation for each trend Used with PowerNet for CBEMA/ITIC curve plotting utility 10
CBEMA Curve Utility 11
New Features New Trending Capabilities Sampling rate can be set from 8 cycles to 5040 minutes (3 1/2 days) Trend 1-3 can save data on a discrete input Trend 4 can save data on an event If the time period is set for an integer divisor of 60 the period starts at the next full hour. 12
New Features Data Logging Features Time & Reason for last 504 Events Any meter event is saved New Status Change Indicators Time of Alarms Power Up Resets Setting Changes INCOM Connection 13
New Features In addition to the data logging of the last 504 events last 10 Waveform Events are also stored The real time clock can be synchronized to the line to correct for long term errors (w/o PowerNet) Programmable CT Polarity Setting Change CT polarity from calibration menu Last event under Power Factor 14
New Features Time Of Use (TOU) Energy Registers 32 Schedules 8 Weekday - 8 Holiday 8 Saturday - 8 Seasons 8 Sunday Each schedule can change 9 times a day 4 Different utility rates Watt-hours, VAR-hours, VA-hours recorded 15
New Features TOU Demands Amps, Watts, VARS & VA 16
New Case Improvements Polycarbonate for higher durability & temperature Rugged outer edge Reset button changed from red to blue New Display Reverse mode, LED backlit LCD Yellow on black High reliability 17
Improvements Custom Screen Enhancements Allows programming of 7 parameters per screen Now 4 custom screens List of programmable items extended Clock Min/Max Values since last trend Magnitude THD (V and A) Displays each screen for 5 seconds 18
New IQ Analyzer Old IQA6000/6200 catalog numbers replaced with new 6400/6600 series IQA6410 - Separate Source PS IQA6420 - DC PS IQA6430 - Self Powered Three Phase PS IQA6610 - Separate Source PS w/waveform IQA6620 - DC PS w/waveform IQA6630 - Three Phase PS w/waveform 19
Support Material Instruction book changes to TD 17530B New Technical Data available TD.17.02A.T.E New Color Brochure available B.17C.01.S.E 20
Literature/Sales Tools/Getting Help www.ch.cutler-hammer.com/pmp Power Management Applications Support 800.809.2772 Power Management Sales Managers CHESS Power Automation Specialists Product Guide - PG.17.01A.T.E 21
Wrap UP Product Feedback PMPC Support Questions & Answers Thank You! 22