SIPROTEC 5 Application Note

Similar documents
Breaker-and-a-half Automatic reclosing and leader follower.

Line differential protection and TPZ class CT at one terminal.

Factory configured macros for the user logic

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

Medium and High Voltage Circuit Breakers Characteristic Time Quantities of the Circuit Breaker with Applications

SIPROTEC Fault Record Analysis SIGRA

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Specification. NGTS Issue 1 October 1993

REF620_NAFCCAC3FFxxxAx1xx SINGLE LINE DIAGRAM (TYPICAL) 1MAC DR. Bus 1 (Open Delta) (2)

Improved Synchronization System for Thermal Power Station

Gamma instabus. Technical product information

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry.

Implementation of a High-Speed Distribution Network Reconfiguration Scheme by Greg Hataway, Ted Warren, and Chris Stephens.

XJTAG DFT Assistant for

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

3AH3 Vacuum Circuit-Breakers

EE201: Transmission Line Protection

Logic Design. Flip Flops, Registers and Counters

Coherence Measurement between two Signals regarding Timing, Phase and Gain Application Note

SIMATIC. ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Preface. Properties 1. Parameters 2. Error and system messages 3

Function Manual SIMATIC HMI TP900. Operator Panel.

B. The specified product shall be manufactured by a firm whose quality system is in compliance with the I.S./ISO 9001/EN 29001, QUALITY SYSTEM.

)HDWXUHV Interlocking function available for a double circuit breaker arrangement Preconfigured and tested interlocking function

Turnout Decoder TD Maxi. User Manual - version 0.1.6

SIMOREG DC Master. Application SIMOREG 1Q-device, braking to defined speed using reversing. 6RA70 Series

Re:connect M 203. RS232 Interface Revox. Dominating Entertainment. Revox of Switzerland. E 2.03

MICROMASTER Encoder Module

Dimming actuators GDA-4K KNX GDA-8K KNX

M203 LG. Multiroom Planer V2.00. Introduction. New features from software V2.00

R&S RSC Step Attenuator Where precise signal levels count

of of Re:connect M 203 Pioneer Interface Dominating Entertainment. Revox of Switzerland. E 2.03

BUSES IN COMPUTER ARCHITECTURE

XJTAG DFT Assistant for

IQACO Changeover Switch

GuardPLC Certified Function Blocks -- Basic Suite

Identification - electrical services

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Start Up or Shut Down Hunting Function. Using the Receiver. If there is a short circuit in the cable, it will display as follows:

CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase)

POLARIS 4 ELECTRONIC CONTROL BOARD FOR SLIDING GATES MANUAL

Solis Export Power Manager

D-901 PC SOFTWARE Version 3

2-output DALI controller

XJTAG DFT Assistant for

BE3-GPR GENERATOR PROTECTIVE RELAY

Application on Control Technology

ADS Basic Automation solutions for the lighting industry

Dimming actuators of the FIX series DM 4-2 T, DM 8-2 T

2. Using LCD Digital Operator

XJTAG DFT Assistant for

Sentinel I24 Digital Input and Output Configuration

KNX 1-10V dimmer 4 channels

The outputs are formed by a combinational logic function of the inputs to the circuit or the values stored in the flip-flops (or both).

APPLICATION NOTE # Monitoring DTMF Digits Transmitted by a Phone

C-net WIND. User s Guide

INSTRUCTION MANUAL AUTORECLOSING RELAY GRR100 - B

Automation Interface Requirements for J602 Basic I/O Interface of a DPC 4 Welding System

4/2 Introduction. 4/4 5SV RCCBs. 4/10 5SM3 RCCBs. 4/13 SIQUENCE 5SM3/5SU1 universal current-sensitive RCCBs, type B and type B+

istep STEPPER MOTOR PUMP

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

Simple all-in-one design style with front stereo speakers and natural ventilation system

of Loewe E 2.10_m1 1

K9123, K9134, K9135 Remote Programming Instructions and Specifications

D Latch (Transparent Latch)

Siemens AG Safety along the complete line: SIRIUS 3SE7 cable-operated switches SIRIUS. Answers for industry.

Online data sheet SGS4-S108P3PS2W03 SLG SWITCHING AUTOMATION LIGHT GRIDS

Luminaire installation box Surface-mounted box Ceiling installation box

K-BUS Dimmer Module User manual-ver. 1

DEPARTMENT OF ELECTRICAL &ELECTRONICS ENGINEERING DIGITAL DESIGN

HS-509 VIBRATION TRIP MODULE

Removal of Decaying DC Component in Current Signal Using a ovel Estimation Algorithm

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

istep STEPPER MOTOR PUMP

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

CDV07. Analog video distribution amplifier(s)

Power Supply and Watchdog Timer Monitoring Circuit ADM9690

Siemens Industry Online Support

6.3 Sequential Circuits (plus a few Combinational)

Toronto Hydro - Electric System

Product Brochure Version R&S RSC Step Attenuator Where precise signal levels count

NT5723SDHD CAMERA-BACK TRANSMITTER Operation Manual

C O B A R 18R U s e r G u i d e P a g e 1. User Guide COBRA 18R. Wireless Firing System.

SIMATIC. ET 200S distributed I/O 2AO U HS analog electronic module (6ES7135-4FB52-0AB0) Preface. Properties 1. Parameters 2.

Computer Organization & Architecture Lecture #5

FACTORY AUTOMATION. MANUAL Software QuickTeach

Micro-DCI 53ML5100 Manual Loader

Operating instructions Electronic preset counter Type series 717

ASNT8140. ASNT8140-KMC DC-23Gbps PRBS Generator with the (x 7 + x + 1) Polynomial. vee. vcc qp. vcc. vcc qn. qxorp. qxorn. vee. vcc rstn_p.

C-net MULTI Operating Instructions MULTI. User s Guide

R&S NESTOR-FOR Crime Scene Investigation

TECHNICAL MANUAL. Cheetah VIDEO MATRIX ROUTERS 3G VIDEO INPUT CARD WITH AUDIO DE-EMBEDDING AND 3G VIDEO OUTPUT CARD WITH AUDIO EMBEDDING

MC54/74F568 MC54/74F569 4-BIT BIDIRECTIONAL COUNTERS (WITH 3-STATE OUTPUTS) 4-BIT BIDIRECTIONAL COUNTERS (WITH 3-STATE OUTPUTS)

APPLICATIONS. Automatic warehouse. Trasportation lines

Aurora Grid-Tie Installation Instructions (Model Number: PVI-3.0-OUTD-US-W) Revision 4.1

Protective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A

A MISSILE INSTRUMENTATION ENCODER

Multi-functional safety relay modules PROTECT SRB-E

multi-function meters

Final Exam review: chapter 4 and 5. Supplement 3 and 4

INSTRUCTION MANUAL BREAKER FAILURE RELAY GRC100

Transcription:

www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-018: Answers for infrastructure and cities.

SIPROTEC 5 - Application: SIP5-APN-018 Breaker-and-a-half Automatic reclosing and leader follower Content 1 Application: 3 1.1 Introduction 3 1.2 Overview 3 1.3 Automatic reclosing 5 1.4 Leader/Follower Logic 5 1.5 Conclusion 8 SIP5-APN-018 2

1 Application: Breaker-and-a-half Automatic reclosing and leader follower 1.1 Introduction This application note provides describes a simple Leader/Follower logic for a breaker-and-a-half application using SIPROTEC 5. Most of the logic described in this application note is preconfigured in the template 1 ½ Circuit Breaker. The applicable SIPROTEC 5 device Manual should be consulted for detailed information. The Help Function in DIGSI 5 as well as detailed application descriptions on various SIPROTEC 5 subjects can also be consulted. 1.2 Overview The breaker-and-a-half configuration requires special attention with regard to the connection of the current transformers and the automatic reclosing scheme. With SIPROTEC 5 this is a simple matter as the application of multiple measuring points and circuit breakers is an integral part of the configuration of each device. This is best described with an example as provide in this application note. BB1 CB1 VT1 Bus2 Line2 CT1 ISO1 Line1 CT2 VT2 Line3 CB2 ISO2 Feeder 2 CT3 VT3 CB3 BB2 VT4 Figure 1: Single line diagram of protected feeder 3 SIP5-APN-018

Figure 2: Allocation of CT s and VT s The Single Line Editor shown in Figure 2 above is a useful tool for graphic assignment of measuring points and switch gear. The applied configuration should be confirmed in the Function Group connections shown below: Figure 3: Allocation of measuring points to function groups A Sync Check voltage is shown in the diagram above. This is only the case if the relevant FG Circuit Breaker contains a sync check function. SIP5-APN-018 4

1.3 Automatic reclosing SIPROTEC 5 Application The automatic reclosing function is located in the circuit breaker function groups. The initiation (start) and optional blocking of the automatic reclosing (AR) function is selected under Circuit Breaker Interaction as shown in Figure 4 below. Figure 4: Circuit breaker interaction selection of start and block of AR In general all the selective protection functions will be configured to start the automatic reclosing function. In the example above the Switch onto fault function is selected to block the auto re-close function. This provides additional security against inadvertent re-closure following a switch onto fault condition. Automatic reclosing is not required following a trip by voltage or frequency protection. A start by these functions is therefore not selected. The selection for Circuit breaker 1 and 2 are identical. 1.4 Leader/Follower Logic In the breaker-and-a-half application there is often a need to select a Leader. The Leader will perform the reclose with the AR function using the set dead time. The Follower will only perform a re-close when the Leader indicates that its reclosing was successful. In this application a user defined Marker Command (CB1 is Leader) is provided to select which Circuit Breaker will assume the role of Leader. When the selection is CB1 is Leader = ON, the leader role will be taken on by Circuit Breaker 1. This can be reversed by executing a command via the Keypad, or other external source, to change to CB1 is Leader = OFF. Now the leader role will be taken on by Circuit Breaker 2. Figure 5: Marker Command CB1 is Leader for selection of Leader/Follower 5 SIP5-APN-018

After the initial start of the device the selection state of Marker Command CB1 is Leader is ON. The state may be changed at any time, e.g. by means of the Control Menu in the device display. The required AR response is defined in the table below. The Leader circuit breaker is the CB1 when the Marker Command CB1 is Leader is ON. When it is OFF CB2 will be leader. The other breaker is designated as Follower : Pre fault state Description AR response Leade Follower Leader Follower r Close d Closed Close d Open Normal Operation with both CB closed prior to fault The Follower is open prior to fault Open Closed Leader is open prior to fault Close d Table 1 Closed Normal Operation with both CB closed prior to fault AR not successful permanent fault Close with set dead time as Leader and then release Follower Close with set dead time as Leader and then release Follower AR detects CB open and does not start = no AR close Close with set dead time - Trip definite trip no further AR A simple logic is applied in the Function charts to achieve the above response: Run normal dead time then wait for release by Leader before AR close AR detects CB open and does not start = no AR close Close with set dead time as Leader does not block the Follower Run normal dead time then wait no release by Leader no AR and definite trip Figure 6: CFC Logic to delay Follower Re-Close command (CB1 is Leader) The above logic is implemented in the Function Charts. Shown is only the Logic that applies when CB1 is leader. A further logic with the same structure exists in parallel; it applies when CB2 is leader. In the above logic, the Flip-Flop can only be set when CB1 is Leader equals ON. If this is not the case the input X2 of OR10 is true and therefore the Flip-Flop has a permanent reset via OR10. The Flip-Flop is set as soon as the Leader (CB1) indicates that Auto re-close is in progress. The Flip-Flop output then activates the >Delay close cmd. in the follower. This is maintained until the leader can indicate that it has successfully re-closed. This indication is obtained via the Remote close signal from the leader which is routed to X1 of OR10. SIP5-APN-018 6

To allow the Follower to re-close with a normal dead time when the Leader is open or out of service the AR in progress signal is used. As the initiation of the AR function in both circuit breakers is at the same time from the same source (the protection functions in FG Line), the AR in progress of the leader is a clear indication that the leader is in service and taking the its role as leader. If the leader is open for maintenance or the AR function is selected Off, the AR in progress from the leader will not assert, thereby allowing the Follower to re-close with a normal dead time. When the Flip-flop is set, the output sets (via the Build SPS block) the signal Delay Close Command in the Follower. The AR function in the follower will go through all the normal states until the AR Close command is due. If the signal Delay Close Command is active the AR close will not be issued until this signal resets. If the maximum dead time extension (Setting Parameter) has expired before the release is given, the AR will be terminated with a definite trip. Figure 7: AR Function General Settings The General settings for the AR function in both circuit breakers can be the same. The Leader must have a set time for Send delay for remote close as this determines how long after the Leader close command the follower is released. As the Leader/Follower selection can be set via marker command in this application, the AR settings for both circuit breakers is identical. The Max. dead time extension must be set longer than the release delay from the leader as set above. In this case the follower is released 50ms after the successful re-close of the leader (Send delay for remote close). Single Pole Trip / Operate As the two circuit breakers execute their AR cycles independently, they can be individually set to trip and AR: 1-pol, 3-pol or 1- and 3-pol. Although any combination is theoretically possible, it is not recommended to have single pole re-close by the follower when the leader is doing only 3-pol AR cycles. 7 SIP5-APN-018

1.5 Conclusion The leader/follower operation of the auto re-close function in a breaker-and-a-half application with SIPROTEC5 can be achieved with the standard auto re-close functions. The full scope of single and three pole AR with multiple stages is therefore available. By means of a simple logic (included in the template for breaker-and-a-half) the leader follower logic is implemented. There is no need to change settings or setting groups when changing the Leader/Follower configuration this is done with a single marker command that can be changed by the operator at any time. SIP5-APN-018 8

9 SIP5-APN-018

Fehler! Verweisquelle konnte nicht gefunden werden. Published by and copyright 2013: Siemens AG Infrastructure & Cities Sector Smart Grid Division Humboldtstr. 59 90459 Nuremberg, Germany Siemens AG Infrastructure & Cities Sector Smart Grid Division Energy Automation Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/protection Printed on elementary chlorine-free bleached paper. All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. For more information, please contact our Customer Support Center. Tel.: +49 180 524 8437 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.ic@siemens.com Application note: SIP5-APN-018 SIP5-APN-018 10