EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

Similar documents
Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

EA350. Generator Automatic Voltage Regulator Operation Manual

EVC300i. Generator Automatic Voltage Regulator Operation Manual

EVC600i. Generator Automatic Voltage Regulator Operation Manual

EG4015. Digital Generator Governor Controller User Manual

ADVR-053. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

ADVR-08. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

www. ElectricalPartManuals. com l Basler Electric VOLTAGE REGULATOR FEATURES: CLASS 300 EQUIPMENT AVC63 4 FEATURES AND APPLICATIONS

multi-function meters

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25

AF-300 E11 Adjustable Frequency Drive

ORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA

DPS-250AB-18 E. 電氣規格 (Electrical Specification) REV. Description Date DESCRIPTION : MODEL NO. : Date Drawn Desing(EE) Design(ME) DOCUMENT NO. : REV.

Contactless encoder RI360P0-QR24M0-INCRX2-H1181

Catalogue Ignitors and power switches for HID

REGO Start&Go USER MANUAL

Figure 1: Device components

Gamma instabus. Technical product information

Contactless Encoder Incremental: ppr RI360P0-QR24M0- INCRX2-H1181

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

LED control gear Compact fixed output

LED Driver Linear / area fixed output

Series CT7N Bimetallic Overload Relays

MICROMASTER Encoder Module

LED Driver Compact fixed output

Telemetry Receiver Installation Guide

Contactless Encoder Analog RI360P0-QR24M0-ELIU5X2-H1151

RGB-3400-X RGB SEQUENCER / 3-CHANNEL UNIVERSAL LED DIMMER

Flat-Bed Module Recorders

LED Driver Compact fixed output

Electrical connection

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

LED Driver Compact dimming

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

3.5. Control Relays and Timers. Contents. 9575H Series 3000 Type AA, AC and DC. General Purpose Relays Type AA

T5, T8, TC-L. PC T5 PRO lp W V 50/60/0 Hz, HO. Electronic ballasts Linear lamps T5, T8 and compact lamps TC-L

Build A Video Switcher

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

LED Driver Compact fixed output

RADIO RECEIVER RGBW CONTROLLING LED STRIP COMMON ANODE

Contactless encoder Ri360P0-QR24M0-HESG25X3-H1181

KNX Dimmer RGBW - User Manual

Indoor Linear 80W Driver SI-C215280N2KR

COHERENCE ONE PREAMPLIFIER

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

Digital Economy Seven Programmer

1.5mm amplitude at 10 to 55Hz frequency in each X, Y, Z direction for 2 hours 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times

MclNTOSH MODEL C-4 and C-4P

DLP200M 2 Relay Module for Heating and Cooling Plants

Automatic Transfer Switch Control PLC Operator s Manual

RADIO RECEIVER RGB CONTROLLING LED COMMON KATHODE

INSTRUCTION & OPERATION MANUAL. MODEL MMW-05 (5kW) MUROMACHI MICROWAVE FIXATION SYSTEM

Australian Technical Production Services

Aspect 2 Circuit Digital Scene Control

12months. on-site warranty. DZE ELECTRONIC PRESSURE SWITCH for detection of overload per EN 81 2 featuring two adjustable switching points

TOSHIBA Industrial Magnetron E3328

CAMTO LTD. Arc detecting system DC/AC

Operating instructions Electronic preset counter Type series 717

DC Motors & Controls. DC2 DC Drives for 1/4 thru 2 Hp PMDC and Shunt Wound Motors. 1/4-2 Hp 115/230 VAC 1 Phase 50/60 Hz.

MATE3 Owner s Manual Addendum

1 Power Protection and Conditioning

15 Series - Dimmer

Electrical connection

Reproduce Amplifier Revision-D

Low-Cost, Single-CT, Automatic Power Factor Controller for Balanced Three-Phase Reactive Power Compensation User Manual

High performance circuit breakers

LINK-RAY TM MODULATORS FOR CONSTANT- VOLTAGE. LinkRay Modulators 12 V / 24 V Constant-voltage Applications MODULATORS

Single output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

I r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100

Model 1421 Distribution Amplifier

Dimmers SЕRIES. Kitchen light control. Bedroom light control. Living room light control

SINGLE ZONE CLIMATE ZONING SYSTEM. Technical Manual. Polyaire Pty Ltd

Contactless Encoder IO-Link Ri360P0-QR24M0-IOLX2-H1141

Revision 1.2d

Level Measurement silometer FMC 420, FMC 423

ABB i-bus EIB Universal dimmer 6155 EB for Installation

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

Description Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

Form C: Type Test Verification Report

DAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER. For the DAAB EP104 automatic control system with software version 4.

02/11/2015

HS-509 VIBRATION TRIP MODULE

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

Model Number Structure

DLP600M 6+1 Relay Module for Heating and Cooling Plants

Ordering details. Approval. Classification

CONSONANCE PREAMPLIFIER OWNER S MANUAL

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted.

SQM40/41 Actuators for air and gas dampers

MAP110 AC-DC Series Data Sheet

Type MG-6 Auxiliary Relay Class 1E

CPH-10 SUBWOOFER OWNERS MANUAL

Bulletin 190 IEC Modular Starter System

Transcription:

EA63-7D Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator SP POWERWORLD LTD Willows, Waterside, Ryhall, Stamford, Lincs, PE9 4EY, UK Tel: +44 1780 756872 - Email: info@sp-powerworld.com www.sp-powerworld.com

1. SPECIFICATION Sensing Input Voltage Frequency Power Input Voltage Frequency Output Voltage Current Resistance 220 / 440 VAC ± 10%, 1 phase / 60 Hz selectable 180~260 VAC ± 10%, 1phase 2wire / 60 Hz Max.63 VDC Continuous 7A Intermittent 15A for 10 sec Min. 6 ohm Max. 105 ohm Voltage Regulation < ± 1% ( with 4% engine governing ) Voltage Build-up Residual voltage at AVR terminal > 5 VAC Voltage Adjustable Range 180 ~ 277 VAC @220V 360 ~ 554 VAC @440V Thermal Drift 0.05% per C change in AVR ambient External Volts Adjustment ± 10% with 1K ohm 1 watt trimmer EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max. 20 watt Under Frequency Protection (Factory Setting) 60 Hz system presets knee point at 55 Hz Hz system presets knee point at 45 Hz Over Excitation Shutdown Field volts shut down after a time delay If exciter field volts exceed 65 ± 2 VDC Quadrature Droop Sensitivity 4%@ 2A, PF 0.7 Max. Input 5A Dimensions 140mm L * 125mm W * 79.4mm H Weight 680g ± 2% GENERATOR OUTPUT(%FROM NORMINAL) 100 90 80 HZ CURVE 60HZ CURVE 70 60 40 30 20 10 0 5 10 15 20 25 30 35 40 45 55 60 65 70 FREQUENCY (HZ) Figure 1 Frequency Compensation Curves FREQUENCY COMPENATION (See Figure 1) 1. The frequency compensation characteristic of Figure 1 used to improve system load pickup performance by restraining voltage recovery until frequency has also started to recover. 2. The regulator is shipped from the factory set at a 45 Hz corner frequency for Hz systems. For 60 Hz systems, a 55 Hz corner frequency is achieved by removing the - external link. 1000 TIME DELAY(SECONDS) 100 10 1 0.1 55 60 65 70 75 80 85 90 95 100 105 110 115 FIELD VOLTAGE-Vdc OVER-EXCITATION TIME DELAY If exciter voltage exceeds 65 ± 2 Vdc, the regulator automatically removes the field current, after a time delay. The time delay is inversely proportional to the magnitude of the detected field over voltage condition up to 120 ± 5 Vdc point. Beyond120 ± 5 Vdc, the field voltage is removed at a much faster rate. This shutdown function may be disabled for parallel operation by linking terminals N and D together. Figure 2 Typical Time Delay Characteristic Curve 2 EA63-7D

125mm(4.912") 77mm(3.02") 100mm(3.928") 17mm(0.667") ATTENTION 140mm(5.512") 115mm(4.528") - + 4 3 V Y X U Droop U/F VOLT STAB. C T D N Outline Drawing Figure 3 Q P B A 33mm(1.29") 1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will not affects operation. For dimension reference, please see Figure 3. 2. The ground terminal must be bonded either to a metal ground by the mounting screw or by means of a cable to the most suitable earthing point available close to the requlator. 2. WIRING 2.1 Exciter Fileld Power Circuit Connect AVR terminal + to field +, connect AVR terminal to the field. Refer to Figure 5. If the exciter field resistance is less than 6 ohms, and if the full-load field current does not exceed the maximum continuous current rating of the regulator ( 7 Adc), a resistor of sufficient wattage must be added in series with the field to bring the total resistance to 6 ohms. CAUTION! The DC resistance of the exciter field must be equal to or greater than 6 ohms and less than 100 ohms. 2.2 Power Input Connect wiring as shown in Figure 5. Power for the regulator is derived from the generator auxiliary winding, connected to wires 3 and 4. The operable power input range is 180 ~ 260 VAC. 2.3 Sensing Input For sensing, wires U and V are connected to the generator phase U and phase V respectively. Wires X and Y are connected to the opposite ends of the U and V phase coils, or commoned together at the Neutral (star) point. 2.4 Quadrature Droop Input Paralleling Provisions CT input for customer supplied 5 A nominal CT. Adjustable droop from 0 to 6% with 5 A input at 0.8 power factor. CT input burden is10 VA 2.5 Fuses It is recommended that a fuse or fuses with high interruption capability be installed per ther interconnection diagram. A suitable fuse type would be LittlefuseTM type 3AG, rated 2 VAC, 6,3 A, SLOBLO. Dimensions are 6.3 mm 32 mm (1 1/4 M 1/4 M ). NOTE : Fuse(s) MUST be installed per interconnection diagram to avoid interrupting field current directly. 2.6 Voltage Adjust Rheostat (V) An internal screw-driver pre-set (V) provides coarse adjustment of generator output voltage. Adjustment of V clockwise increases voltage. The voltage regulator is shipped from the factory with a link across terminals P and Q. If a remote voltage adjust rheostat is used, the link should be removed and the Rheostat connected to P and Q. A 1K ohm, 1W. Potentiometer will provide a fine voltage range adjustment of approximately ± 10% over most of the coarse range of adjustment. See Figure 4 interconnection diagram.. EA63-7D 3

2.7 V/Hz Corner Frequency Selection For Hz systems, the regulator is pre-set at the factory for a 45 Hz corner frequency, and a link fitted across terminals. If operation at 60 Hz is required, this link should be removed; the corner frequency is now set to 55 Hz. Do not operate the system at 60 Hz with the Hz link still in place. 2.8 Over-Excitation Shutdown Over-excitation shutdown is provided to remove output excitation should the regulator s output voltage exceeds 65 ± 2 Vdc for a sufficient time. The inverse-time delay curve is shown in Figure 1-2. For voltage above 120 ± 5 Vdc, there is a second and much shorter inverse time curve. After output power is removed, the regulator can be reset by decreasing the input voltage to less than 5 Vac for a minimum of 2 seconds; this may be.accomplished by stopping the prime mover or interrupting the regulator input by means of a reset switch. In cases where the generator is operating in a parallel mode, it is sometimes considered undesirable to allow the regulator to shut down, which may cause the generator to be motored. The regulator is provided with terminals N and D, which may be linked together to prevent over-excitation shutdown. Note however that continuous running at output levels greater than the continuous rating may result in eventual regulator failure, and that other means should be employed to protect the system. 3. OPERATION PROCEDURE 3.1 General The following system operation procedures provide instructions for adjusting the EA63-7D voltage regulator. Symptoms resulting form a faulty regulator and certain generator system problems are included, together with suggested remedies. Complete the following steps before proceeding with system start-up. CAUTION! Meggers and high-potential test equipment must not be used. Incorrect use of such equipment could damage the semiconductors used in the regulator. 3.2 Preliminary Set-Up Verity that the voltage regulator specifications conform with the generator system requirements. Ensure that the regulator links are fitted correctly where required, as follows: 1. If the remote voltage adjust rheostat is not required, ensure terminals P and Q are linked together. 2. If a 55 Hz corner frequency for 60 Hz systems desired, ensure the ~ link is removed. If a 45 Hz corner frequency for Hz systems is desired, ensure the ~ link is connected. 3. If the system is to be run in parallel, consider whether shutdown of the generator s excitation is acceptable. If not, ensure that the link between terminals N and D is in place. Ensure the voltage regulator is correctly connected to the generator system; F+ to field positive, F- to field negative, and terminals 3 and 4 to the auxiliary winding supply. It is vital that the sensing connections are correctly made to all 4 wires U, V, X, and Y. Ensure the metal ring tag at one mounting hole is bonded to ground via either a metal screw or shout length of cable. Install the fuses as per paragraph 2-5. Set the regulator and external voltage adjust, if used, as follows : Regulator Volts Adjust V Remote Volts Adjust Stability Adjust S 3.3 System Start-Up Fully CCW Centered Centered Perform preliminary set-up, per paragraph 3.2, checking wiring carefully. NOTE : All AC voltage readings are to be taken with an average reading voltmeter. Start Prime-mover and bring up to rated speed. RESULT : Voltage should build up to less than nominal value. If not, proceed to paragraph 3.4. 4 EA63-7D

Slowly adjust the regulator voltage adjust V until the generator output voltage reaches the nominal value. Should a low frequency oscillation or hunting be present on the generator output voltage, adjust stability control S to cause this to be damped out. In general, Clockwise increases the stability but in some cases, too far CW may start to reduce stability again, and will invariably slow the response of the generator to load changes. An optimum method of setting is to adjust S slowly CCW until the generator voltage just starts to become unstable, then up to 1/4 turn CW from that position. If used, adjust the external voltage adjust rheostat to fine trim the voltage to the exact value desired. RESULT : Voltage should now have built up and be stable at the desired value. If voltage does not build to rated value, check that there is no short circuit or excessive load present on the generator lines. If a minimum residual of 5 Vac is not present, perform field flashing per paragraph 3.4. Check regulator under normal operating and loading conditions. RESULT : Voltage regulation should be better than ± 1.0% no-load to full-load. If regulation is not within this range, check the following : 1. Voltage reduction under loads of cosθ > 0.0 may be due to speed reduction due to loading of the prime mover. This may be causing the frequency compensation (V/Hz) circuit to reduce voltage at a speed which is less than the corner frequency. 2. Replace voltage regulator. 3.4 Field Flashing When the regulator is operated with the generator for the first time, the polarity of residual magnetism may be reversed or too small to achieve the necessary build-up voltage for the regulator. If reversing the field connections does not induce build-up, and the residual voltage is less than the specified value of 5 Vac, shut down the Prime-mover and proceed with the following steps : With the Prime-mover at rest and the regulator s field output wires disconnected, apply a DC source ( NOT grounded ) of not more than 3~12 Vdc with Positive to F+ and Negative to F-, in series with a current-limiting resistor of 3~5 ohms 20 watt. (The set battery is a suitable source.) Allow approximately 3 seconds before removing the DC source. With the voltage regulator disconnected ( wires 3 and 4 ), start the prime mover and measure the residual voltage available at the auxiliary winding. If this voltage is greater than 5 Vac, reconnect voltage regulator, and voltage build-up should be successful. If less than 5 Vac is measured, repeat field flashing procedure. If repeating steps a. and b. does not result in generator voltage build-up, and residual is greater than 5 Vac, replace voltage regulator. AUXILIARY WINDING /60HZ GENERATOR U V W + FIELD - GROUND CONNECTION LINK FOR HZ EXT. VOLTS ADJUST C.T. (N:5A) N - + 4 3 Q VOLT 5A 240 V FUSE P STAB. B A V Y X U U/F Dp C T D N LINK IF EXT. VOLTS ADJUST NOT REQUIRED LINK FOR LARGER TIME CONSTANTS LINK TO DISABLE OVER-EXCITATION SHUTDOWN EA63-7D 5

Wiring Diagram Figure 5 6 EA63-7D