Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Similar documents
UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

A. The requirements of Section govern the work specified in this section.

STRUCTURED CABLE SYSTEM (SCS)

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

Telecommunication Infrastructure Project September 20, 2002

UNM IT/Telecommunications Guide Specification Labeling 11/07/

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

SECTION COMMUNICATIONS HORIZONTAL CABLING

384A Adapter Installation Instructions

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Telecommunciations Infrastructure Project September 20, A. Broadband radio frequency active and passive components

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

SECTION 7 -- CROSS-CONNECT SYSTEMS

Section Communications Optical Fiber Backbone Cabling

IT/Telecommunications Technical and Wiring Standards. Phillips Exeter Academy

DESIGN!!GUIDELINES!!!!!

Information Technology Services DESIGN AND INSTALLATION STANDARDS

SECTION COMMUNICATIONS HORIZONTAL CABLING

SPECIAL SPECIFICATION 8540 Telecommunication Cable

CABLING STANDARDS FOR

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SECTION MASTER TELEVISION ANTENNA SYSTEM (MTAS)

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION FIBER OPTIC STATION CABLES

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

A. As defined in Section Telecommunications General Requirements

Mfgr. Berk Tek ea , Berk Tek ea , Berk Tek ea. Berk Tek ea ,350.

Request for Proposal (RFP)

What really changes with Category 6

Technical Specifications Florida Gulf Coast University

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

Target Interface / Construction Compliance Inspection Checklist

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

Bravo AV s Structured or Whole-House Wiring Approach

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

EXHIBIT BASIS OF DESIGN REPORT. Space Type: Space Usage: Off-center of room to match side screen. Location

EXHIBIT BASIS OF DESIGN REPORT. Space Type: Space Usage: Approx. 2,000 BTU each. Off-center of room to match side screen.

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

Review of the Comcast. Fort Collins Cable System. Technical Characteristics

The University of Texas at Austin September 30, 2011

APPENDIX A Verify All Part Numbers (Partial List of Approved Products)

SECTION TESTING OF COPPER CABLES

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0553 Identification for Communications Systems

STANDARDS SECTION (16651) COMMUNICATIONS DISTRIBUTION SYSTEM (Rev. Jun 2011)

Request for Quote E- Rate Eligible Services Scope of Work Network Infrastructure and Structured Cabling

CATEGORY 6A CABLING SOLUTIONS

Public Works Division Lighting District Fiber Optic Specifications April 2009

THE OHIO STATE UNIVERSITY COMMUNICATIONS WIRING STANDARD

Brown University. Communications Standard Parts List

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SECTION 683 VIDEO OPTICAL TRANSCEIVER WITH BI-DIRECTIONAL DATA CHANNEL DESCRIPTION

AMERICAN NATIONAL STANDARD

Drop Passives: Splitters, Couplers and Power Inserters

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING

SECTION COMMUNICATIONS HORIZONTAL CABLING

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

Preparing a home for TransACT fibre-to-the-premise (FTTP) services

CATEGORY 6A CABLING SOLUTIONS

March 4 th, Addendum No. 1. Brooklyn College Systems Integrator Broadcast Television Equipment Project No: BY019/

GENERAL COMMUNICATIONS REQUIREMENTS

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

GENERAL COMMUNICATIONS REQUIREMENTS

AMERICAN NATIONAL STANDARD

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

ANSI/TIA-PN D-R1. Broadband Coaxial Cabling and Components Standard Draft 2, March 8, 2017 TABLE OF CONTENTS

PLU-TV & AT&T CATV CLASSROOM/OFFICE BUILDING EQUIPMENT LISTS & DIAGRAMS CLT CATV.doc CENTER FOR LEARNING & TECHNOLOGY (CLT)

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

University Center AV Integration Construction Documents February 8, 2012

ANSI/TIA-PN D. Broadband Coaxial Cabling and Components Standard Draft 1, October 11, 2016 TABLE OF CONTENTS

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Project No. # Page 1

Follow The Leader In Shielded Technology

Spec Sheet. InterReach Fusion Wideband 2.5 GHz WiMAX. In-Building Wireless Networking System. Product Highlights

10 Mb/s Single Twisted Pair Ethernet Preliminary Cable Properties Steffen Graber Pepperl+Fuchs

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

Directional Couplers and Splitters

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)

LYNX ULTRA Series Hubs and Baluns

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

Effective earthing of screened cables

SECTION COMMUNICATIONS STRUCTURED CABLING

Test Procedure for Common Path Distortion (CPD)

Telecommunications Design Standards

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS

CASS COUNTY, MICHIGAN CASSOPOLIS, MI REQUEST FOR PROPOSAL SPECIFICATIONS

Transcription:

PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer (RCDD) or equivalent. C. Ten (10) years working experience within the telecommunications industry. D. Three (3) years working experience in the planning, design, engineering, installation, and testing of both outside plant and building cabling systems, to include copper twisted pair, fiber and 75 ohm coax, for use as a CATV system, in the campus environment. E. Ability to author detailed specifications. F. Ability to prepare detailed construction and as-built drawings. G. Ability to inspect and supervise the project. H. Provide references on three (3) projects of similar scope worked within the last five (5) years. 1.02 Telecommunications Contractor Minimum qualifications for Telecommunications Contractor are: A. Five (5) years experience in the telecommunications industry. B. Three (3) years working experience in installation and testing of both outside plant and building cabling systems, in the campus environment to include: 1. Placing, splicing, terminating and testing of inter-building backbone cables, to include up to 2400 pair copper twisted pair, 144 strand fiber and.5 inch and.75 inch 75 ohm coax. 2. Placing, terminating and testing of intra-building backbone cables, to include up to 1200 pair copper twisted pair, 96 strand fiber and.5 inch Design & Construction Standards, Revised December 14, 2001 17010-1

and.75 inch 75 ohm coax and horizontal distribution cables, to include Category 5e unshielded twisted-pair, 2 strand fiber and 75 ohm coax. C. Ability to read and interpret construction specifications and drawings. D. Ability to inspect and supervise the project. E. Ability to prepare cable records and record-drawings. F. Ability to prepare cable test records G. Familiarity with 110 Cross-Connect System, Ortronics Series II Outlets, and associated hardware. H. Provide references on three (3) projects of similar scope worked within the last five (5) years 1.03 The University shall review and approve the qualifications of all Telecommunications Engineers, Contractors and Sub-Contractors. 1.04 Minimum Required Telecommunications Drawings and Details Telecommunications drawings and details shall be provided; separate from other disciplines; placed within the Electrical section; and identified as Telecommunications System drawings. 1.05 Telecommunications Plan Drawings Telecommunications plan drawings shall be submitted in AutoCAD compatible drawing files scaled to the true dimensions of the building (AutoCAD latest release drawings are preferred, however a minimum of Release 13 will be accepted). Telecommunications plan drawings shall include separately developed layers identifying Telecommunications pathways and spaces and Telecommunications outlet/connector locations 1.06 Telecommunications plan drawings shall indicate: A. Location of all telecommunications rooms, closets and spaces. B. All conduits, raceways, cable trays, floor ducts, and pull boxes, and their means of support. C. Source and destination locations for all telecommunications outlets. Design & Construction Standards, Revised December 14, 2001 17010-2

1.07 Telecommunications Backbone Schematic (Riser) Diagrams Telecommunications backbone schematic diagrams shall be provided and shall indicate: A. Inter-Building Backbone pathway. B. Telecommunications service entrance. C. Splice locations with cable identifier and count. D. Protector locations with cable identifier and count. E. Telecommunications Bonding and Grounding System F. Intra-Building Backbone pathways. G. Intra-Building Backbone cable support systems. H. Cross-connect locations. I. Type, size, sheath, gauge and length of all Backbone cables. J. Schedule of major hardware components. 1.08 Telecommunications Room, Closet and Space Detail Drawings Telecommunications room, closet and space detail drawings, in both plan and elevation views, shall be provided and shall indicate location, with dimensions, of: A. Conduits, slots and sleeves. B. Cable ladder and hardware. C. Grounding Busbar. D. Backboards. E. Cross-connect hardware for backbone and horizontal cables of each media type. F. Splices with cable identifier and count. Design & Construction Standards, Revised December 14, 2001 17010-3

G. Protector frames with cable identifier and count. H. Equipment Racks. I. Enclosures. 1.09 Minimum Required Telecommunications Specifications Telecommunications specifications shall be provided; separate from other disciplines; placed within the Electrical section; and identified as Telecommunications System specifications. Editor Note: The intention was to have a Division 17 for all low voltage cabling systems. I this still the case? If so make changes to text. Telecommunications product specifications shall be submitted. These include, but are not limited to the following: A. Cable B. Cable support hardware to include: Cable ladder Cable tray J-hooks Conduit Pull-boxes Design & Construction Standards, Revised December 14, 2001 17010-4

C. Connecting hardware to include: Outlet/connectors Cross-connects Protector frames and protectors Splice cases and modules D. Enclosures Telecommunications execution specifications shall include guidelines for placement; termination; grounding; splicing; labeling; testing; documentation and commissioning of all telecommunications systems. Design Development Review Documents Preliminary Telecommunications plan drawings; Preliminary Telecommunications backbone schematic diagrams and Preliminary Telecommunications specifications shall be provided. Preliminary telecommunications plan drawings shall indicate: A. Location of all telecommunications rooms, closets and spaces. B. Source and destination locations for telecommunications outlets. Preliminary telecommunications backbone schematic diagrams shall indicate A. Telecommunications service entrance. B. Inter-Building Backbone pathways. 50% Construction Development Review Documents Telecommunications plan drawings; telecommunications backbone schematic diagrams and telecommunications specifications, to include comments submitted by the University at Design Development, shall be provided. Telecommunications plan drawings shall indicate: A. Location of all telecommunications rooms, closets and spaces. B. Source and destination locations for telecommunications outlets. Telecommunications schematic diagrams of: Design & Construction Standards, Revised December 14, 2001 17010-5

A. Telecommunications pathways and spaces B. Telecommunications inter-building backbone cables (distribution) C. Telecommunications intra-building backbone cables (riser) Telecommunications Product Schedules, symbol legend and all telecommunications details shall be provided. 95% Construction Development Review Documents Telecommunications plan drawings; telecommunications backbone schematic diagrams and telecommunications specifications, to include comments submitted by the University at 50% Construction Development Review, shall be provided. Included, for each media type, shall be the final tabulations indicating the size and number of horizontal cables and backbone cables to be terminated; a termination hardware component schedule for each telecommunications room, closet or space and a telecommunications outlet/connector schedule. PART 2: CABLING STANDARDS 2.01 Technical Considerations for CATV Cabling System General General network configuration shall be as dictated by accepted engineering practices, with passive devices located as required by network design and active components located in equipment spaces as indicated on the project drawings and dictated by network design. Each CATV outlet shall have a 75 ohm terminator installed. CATV System Performance Requirements CATV network bandwidth shall extend from 50 MHz to at least 860 MHz. Any channel at any point in the system shall exhibit the following characteristics Worst case carrier to noise ratio Worst case cross modulation Worst case 2nd order distortion Worst case composite triple beat Worst case hum modulation 49 db -55 db -67 db -54 db -59 db Design & Construction Standards, Revised December 14, 2001 17010-6

Each outlet in the system shall exhibit the following characteristics Minimum signal level, any channel + /- 0.0 dbmv Maximum signal level, any channel +8 dbmv Maximum adjacent channel variation in level 2 db Amplitude response variation across any 6 MHz channel +/- 1 db Maximum tilt, lowest level channel to highest level channel 6 db Design & Construction Standards, Revised December 14, 2001 17010-7

Component Requirements Passive Devices Trunk Feeder Minimum bandwidth - 1000 MHz Scientific Atlanta or equivalent Minimum bandwidth - 1000 MHz Scientific Atlanta or equivalent Active Devices Trunk Amplifiers C-COR Flexnet 900 series, or equivalent. Feeder Amplifiers C-COR Flexnet 900 series, or equivalent Component Requirements-Continued Cable Trunk cable Feeder cable Drop cable Comm/Scope.750 P3 Flooded cable or equivalent Comm/Scope.500 P3 Flooded cable or equivalent Comm/Scope RG-6 Quad shield, 90% braid, or equivalent CATV System Warranty The installation contractor shall provide written "proof-of performance" demonstrating that the installed system meets all of the above stated requirements as well as applicable FCC requirements for leakage and radiation. (100% testing of all the outlets is not required, but the report must include measurements at those points in the system where normal practice would predict the worst-case performance.) The installation contractor shall guarantee said performance for a period of not less than one year after acceptance by the University. The University will assume all responsibility for maintenance of these parameters after the initial warranty period. Design & Construction Standards, Revised December 14, 2001 17010-8

Telecommunications General Specification Cabling General The University prefers to have the minimum number of telecommunications rooms possible with accessible pathways throughout the building to facilitate additional cable placements during the life cycle of the building. It is most desirable that the building have all cabling terminated in the telecommunications service entrance, while maintaining a maximum cable length of 90 meters. OSP Copper Cable The University will provide and install a (tbd) pair OSP cable to the telecommunications service entrance. The University will splice to the 100 pair tails on the CIRCA 1880B1-100 protected termination blocks, or The University approved equivalent. CIRCA 1880B1-100 protected termination blocks to be provided by project. OSP Fiber Cable The University will provide and install a (tbd) strand 62.5/125 multi-mode fiber cable and a (tbd) strand single-mode fiber cable to telecommunications service entrance. OSP fiber cable and termination hardware to be provided and installed by UT. Telecommunications Grounding System A Telecommunications main grounding busbar shall be provided and installed at each telecommunications service entrance. A telecommunications grounding busbar shall be provided and installed in all telecommunication rooms. A bonding conductor for telecommunications shall be provided and installed from the service equipment in the electrical entrance facility to the telecommunication main grounding busbar. Engineer to specify conductor size based on 2000 circular mils per linear foot. A telecommunications bonding backbone shall be provided and installed from the telecommunications main grounding busbar to each telecommunications grounding busbar. Engineer to specify conductor size based on 2000 circular mils per linear foot. Design & Construction Standards, Revised December 14, 2001 17010-9

Intra-Building Backbone Copper Distribution Cable To be specified by Engineer. Intra-Building Backbone Fiber Distribution Cable To be specified by Engineer. Horizontal Distribution Cable To be specified by Engineer, with a minimum of three ANSI/TIA/EIA-568- B.1 category 5e cables installed to each outlet location (two for data and one for voice) and two outlet locations per work area. Work area outlets shall be Ortronics Series II telecommunications outlets. Network Implementation Equipment racks shall be provided and installed in the telecommunications service entrance and in each telecommunication room. A #6 AWG grounding conductor shall be provided and installed to bond the telecommunications grounding busbar to the equipment racks. (tbd) Category 5e patch cables shall be provided for installation by owner. (tbd) 62.5/125 multi-mode fiber patch cables shall be provided for installation by owner. PART 3: ROOM STANDARDS 1.General 1.1 The telecommunications room shall be designed to contain telecommunications equipment and cable terminations. 1.2 The telecommunications room shall not be shared with building or custodial services. The telecommunications room shall not be shared with building power other than a dedicated power panel installed to serve the telecommunications equipment in the room. 1.3 Piping, ductwork or distribution of electrical power to the building shall not be located in or pass through the telecommunications space. 2. Size The telecommunications room shall be sized to provide a minimum of 2 ft. of linear wall space for each usable 1,000 of usable floor space served. 3. Location Design & Construction Standards, Revised December 14, 2001 17010-10

3.1 The telecommunications room shall be located as close as practicable to the center of the area that it is intended to serve. 3.2 The telecommunications room shall be accessible from a hallway or other common area. 3.3 The telecommunications room shall be located in an area of the building with a minimum floor loading of 50 LB/ft. 2. 3.4 The telecommunications room shall be located away from any threat of flooding. 4. Provisioning 4.1 General The telecommunications room floors, walls and ceilings shall be treated to eliminate dust. Finishes shall be light in color to enhance room lighting 4.2 Power The telecommunications room shall have a minimum of two dedicated 20 A, 120V AC duplex non-switched electrical outlets for equipment power and a separate 120V AC duplex non-switched electrical outlet for tools and instruments. 4.3 Lighting The telecommunications room shall have a minimum equivalent of 50 footcandles measured 3 ft. above finished floor. Design & Construction Standards, Revised December 14, 2001 17010-11

4.4 Environmental control Heating ventilation and air-conditioning that will maintain 64 F to 75 F and 30% to 55% RH and maintain positive pressure with a minimum of one air change per hour shall be provided. 4.5 Fire protection If sprinkler heads are provided, wire cages shall be installed to prevent accidental operation. If a wet pipe system is present, drainage troughs under the piping shall be installed. 4.6 Ceiling The minimum ceiling height shall be 8 ft. 6 in. False ceilings shall not be provided. 4.7 Walls A minimum of two telecommunications room walls shall be covered with Trade Size 3/4 in. AC-grade plywood installed 8-ft high. The plywood shall be securely fastened to the supporting wall. 4.8 Doorways The telecommunications room shall have fully opening; lockable doors which are at least 36-in. wide and 80-in. tall. The door hardware shall be keyed to the Telecommunications Master and a passkey provided for the client's network manager. 4.9 Conduit, raceway and duct penetrations Sleeves or slots through the telecommunications room floor shall be located adjacent to or behind the door. Conduits, raceways and ducts shall penetrate the telecommunication room wall at a minimum of 8 ft. above finished floor. Editors Note: The following needs to be inserted but I am not certain where. Engineer shall contact The University Assignment Office at 471-7800 for numbering scheme for voice and data in each telecommunications room. Cabling terminations for voice shall be to be separated from cabling terminations for data in each telecommunications room. Testing deliverables shall include: Source---building and room number Outlet Number Destination---building and room number Length of the cable Type of cable---category Outlet Types Used Indication if cable is terminated on voice or data field in the telecommunications room Date of test Design & Construction Standards, Revised December 14, 2001 17010-12

Link to the preinstallation section-send to David Rea Design & Construction Standards, Revised December 14, 2001 17010-13