multi-function meters eclipse 2 eclipse 7 installation and operating manual
1 GENERAL DESCRIPTION 2 INSTALLATION 3 WIRING INFORMATION 4 2 ECLIPSE 2 METERS 2.1 PROGRAMMING THE METER 5 2.2 INFORMATION 6 2.3 OPERATION 7 2.4 FUNCTION DISPLAYS 8 2.5 MAXIMUM DEMAND 9 3 ECLIPSE 7 METERS 3.1 PROGRAMMING THE METER 10 3.2 INFORMATION 11 3.3 OPERATION 12 3.4 FUNCTION DISPLAYS 13 3.5 MAXIMUM DEMAND 14 4 TRANSFORMER SELECTION 4.1 CT SELECTION 15 5 TECHNICAL INFORMATION 5.1 PERFORMANCE AND DATA 16 5.2 MAINTENANCE 16 5.3 FIELD SERVICE 17 5.4 PERFORMANCE 17 FIRST CHECK THE CONTENTS OF YOUR PACKAGE It should contain: 1. Meter 2. Fixing brackets with screws inserted (Quantity 2) 3. Installation and operation manual
1 D ESCRIPTION OVERVIEW OF THE UNITS Eclipse Series multi-function meters are designed to display various types of power measurement information. Eclipse meters are fitted with one factory programmable relay, volt-free normally open contacts. All the connections are captive screw terminals at the back of the meter. The Eclipse 2 front panel has a single line, 16 character display and a set of readout selection buttons. The Eclipse 7 has a 20 character, 4 line display and a set of readout selection buttons. Standard meters are factory programmed and provide a small range of functions which are programmable by the user. They are also supplied with CT Ratio Setting and CT Polarity Check available for user programming. PULSE OUTPUTS One voltage free output is factory fitted in the meter. The relay in Eclipse 2 is set to indicate kwh only. The Eclipse 7 can be programmed to indicate kwh, kvarh* or kvah* on request. The standard setting for the Eclipse 7 is kwh. Pulse value and duration are factory set at 1kWh per pulse 100ms duration. Function 60 enables the user to alter the value to suit individual requirements. The pulse status cycle (code 53) provides a visual indication for testing the meter from the front panel. *Eclipse 7 meters only Fully complies to European Electromagnetic Compatibility Conforms to IEC 1036 Section 4.6.1. Accuracy Class 1.0 Certificate No. 0275 2
INSTALLATION ECLIPSE 2/7 INSTALLATION OF THE METER Eclipse meters should be mounted so that the front panel is vertical. A typical panel would be a switchgear cabinet door. The meter requires a depth behind the panel of 100mm. A single square aperture 92mm wide x 92mm high should be prepared. LOCATION Meters should be mounted in a dry, dirt free environment, away from heat sources and very high electric fields. Temperatures should not exceed 70 o C or fall below -20 o C. POWER SUPPLY Standard 3 phase 4 wire Eclipse meters are powered by 230 volts AC (50 Hz) at 0.2 amps. The units can be powered from a dedicated fused feed, or they may be powered by the voltage source which they are monitoring provided that it is a 230 volt system. A removable protection fuse for the electronic power supply is fitted in the rear of the meter. ELECTRICAL CONNECTIONS 2.5 sq.mm wire is recommended for all electrical connections, subject to the distance between the meter and the current transformer. Phasing and polarity of the AC current and voltage inputs, and their relationship is critical to the correct operation of the unit. WIRING Electrical connections are made directly to the back of the meter. See diagram opposite. 92mm 3 100mm
WIRING INFORMATION ECLIPSE 2/7 ATTENTION: Never link the Secondary of the current transformers to earth Never create a common point between the current transformer Never place in series with other instruments Do not meggar test 4
2 E CLIPSE 2 METERS 2.1 E CLIPSE 2 PROGRAMMING PROGRAMME THE CT RATIO CODE 013 The Current Transformer Ratio must be programmed into this meter. Please follow these instructions precisely. 1. Press Function. Enter the code 013 where the asterisks are indicated. Three asterisks indicates it requires three numbers to be entered. 2. Enter Password. This is the serial number on the reverse side of the meter - six digits starting from the left hand side. SERIAL No. 200000 Password VOLTAGE TERMINALS BLUE PHASE YELLOW PHASE RED PHASE NEUTRAL 3. Enter the CT Ratio Key in the number with the first digit on the left e.g. 2500/5. Key 2 followed by 5 then 00. If the CT Ratio is required with less than four digits (e.g. 300/5 amp), start the sequence with 0, e.g 0300. 5
2.2 E CLIPSE 2 INFORMATION CHECK CT POLARITY 1. Press function. Enter the code where the asterisk indicated. Three asterisks indicates it requires three numbers entering. 2. Enter code 050 Display will show - The Plus mark + indicates the CT is correctly connected. If a negative mark - sign is displayed, this indicates the CT connection is incorrect. N.B. This is only available if power is flowing RESET MAXIMUM DEMANDS 1. Press function. Enter the code where the asterisk is indicated. Three asterisks indicates it requires three numbers entering. 2. Enter Code. 012. Display will show - 3. Press enter to reset Maximum Demand. PULSE STATUS CHECK 1. Press function. Enter the code where the asterisk is indicated. Three asterisks indicates it requires three numbers entering. 2. Enter Code 053. 3. Display will show Please note this display is common for all Eclipse 2 Meters. Three digits equal the relay count (resets to zero after 999) 6
2.3 E CLIPSE 2 OPERATION Once the meter is installed and the functions have been set, the only operation required is to take the readings from the front panel readout. INFORMATION When the information button is pressed, the display cycles through a sequence giving information about the meter as shown below. SEQUENCE OF INFORMATION READOUTS First Readout Sixth Readout pulse value setting Second Readout Seventh Readout meter number pulse relay closure time Third Readout Eighth Readout system configuration maximum demand reset code Fourth Readout Ninth Readout voltage setting current transformer polarity code Fifth Readout current ratio setting 7
2.4 E CLIPSE 2 FUNCTION D ISPLAYS FRONT PANEL The display is of the standard LCD reflective type 16 x 1 characters. Dimensions of the characters are 3-15mm wide x 5.5mm hig (5x7 dots). Expected lifetime under normal operating conditions is a minimum of 100,000 hours. SEQUENCE AMPS The Eclipse 2 is a two key operation device; to obtain information e.g. volts, press the VOLTS key. VOLTS By pressing one of the keys under the arrows it will display one of the following phase details e.g. By pressing the RED key the following is displayed. To obtain current values, press the AMPS key. The display will indicate three downward facing arrows as shown below. To select individual phase current press one of the keys marked RED, YELLOW or BLUE. For total current in all three phases press TOTAL This gives a readout between Red Phase and Neutral and Red Phase to Yellow Phase. To obtain information on Yellow Phase or Blue Phase, press VOLTS and the appropriate (Yellow or Blue key). If a phase has been selected, then only the phase colour key need be pressed. KWH IMPORT To obtain kwh, press the key marked KWH. The information displayed is the combined total energy of all three phases. FREQUENCY Press the key marked Hz. The display will be as shown below. It should be noted that the display will show only the system frequency. The numbers displayed are for indication only. POWER FACTOR To obtain power factor press key marked Power Factor. Numbers displayed above are for indication only. POWER WATTS To obtain instantaneous power, press the key marked POWER WATTS. 8
2.5 E CLIPSE 2 MAXIMUM DEMAND To obtain maximum demand or actual demand, press the key marked MAX DEMAND. This information is displayed over two screens. The first shows peak maximum demand as illustrated below. FUNCTION KEY The Function key allows for resetting and checking of the various parameters as indicated by pressing the information key. To enter values which will define the meter parameters it will be necessary to enter a password. When entered and validated, the meter can then be programmed. The second screen displays time into period and actual demand as shown below. One line of 16x1 LCD reflective characters Twelve sealed membrane keys activate function 349415.43 KWH> Pulse Indicator Infomation key indicates what the meter has been programmed to do Function Button to select special features which have been added Phase Selector buttons when pressed indicate individual phase readings 9
3 E CLIPSE 7 METERS 3.1 E CLIPSE 7 PROGRAMMING PROGRAMME THE CT RATIO CODE 013 The Current Transformer Ratio must be programmed into this meter. Please follow these instructions precisely. 1. Press Function. Enter the code 013 where the asterisks are indicated. Three asterisks indicates it requires three numbers to be entered. 2. Enter Password. This is the serial number on the reverse side of the meter - six digits starting from the left hand side. SERIAL No. 200000 Password VOLTAGE TERMINALS BLUE PHASE YELLOW PHASE RED PHASE NEUTRAL 3. Enter the CT Ratio Key in the number with the first digit on the left e.g. 2500/5. Key 2 followed by 5 then 00. If the CT Ratio is required with less than four digits (e.g. 300/5 amp), start the sequence with 0, e.g 0300. 11 10
3.2 E CLIPSE 7 INFORMATION CHECK CT POLARITY 1. Press function. Enter the code 050 where the asterisks are indicated. Three asterisks indicates it requires three numbers to be entered 2. The display will show + to indicate the CT is connected correctly. If a - sign is displayed, this indicates that the CT connection is incorrect. N.B. This is only available if power is flowing. RESET MAXIMUM DEMANDS 1. Press Function. Enter the code 012 where the asterisks are indicated. Three asterisks indicates it requires three numbers to be entered. 2. The display will show PRESS ENTER TO RESET MDs 3. Press enter to reset Maximum Demand. The display will show MEMORY UPDATED 11 11
3.3 E CLIPSE 7 OPERATION Once the meter is installed and the functions have been set, the only operation required is to take the readings from the front panel readout. INFORMATION When the information button is pressed, the display cycles through a sequence giving information about the meter as shown below. SEQUENCE OF INFORMATION READOUTS 12
3.4 E CLIPSE 7 FUNCTION D ISPLAYS DISPLAY The Eclipse 7 is fitted with a display of 20 characters in a 4 line configuration. Dimensions of the characters are 2.3mm wide by 4.03mm high (5 x 8 dots). Expected lifetime under normal operating conditions is a minimum of 100,000 hours. Note: Numbers in displays are for example only. INST kva SEQUENCE The Eclipse 7 is a single key operation device, to obtain information press appropriate key. VOLTS INST kvar AMPS ENERGY IMPORT POWER FACTOR ENERGY EXPORT INST kw Hz 13
3.5 E CLIPSE 7 MAXIMUM D EMAND To obtain the peak maximum demand or actual demand, press the corresponding key. ACT DEMAND FUNCTION KEY The Function key allows for resetting and checking of the various parameters as indicated by pressing the information key. To enter values which will define the meter parameters it will be necessary to enter a password. When entered and validated, the meter can then be programmed. MAX DEMAND Pulse Indicator Display of pulse output is indicated by double chevron flashing on Import Energy display. Display of 20 x 4 LCD characters fourteen sealed membrane keys activate function VOLTAGE R-N 230 V R-Y 400 V Y-N 230 V Y-Y 400 V B-N 230 V B-Y 400 V Infomation key indicates what the meter has been programmed to do Function Button to select special features which have been added 14
4 T RANSFORMER S ELECTION CURRENT TRANSFORMER SELECTION For accurate monitoring, correct selection of CTs is critical. The following paragraphs provide the information required to choose the correct CT. CT SELECTION Eclipse Series Meters use current transformers (CTs) to sense the current in each phase of the power feed. The selection of the CTs is important because it directly affects accuracy. The CT secondary rating depends on the current input option installed. The current input rating is 5 amps for the standard Eclipse Series meters The CT primary rating is normally selected to be equal to the current rating of the power feed protection device. However, if the peak anticipated load is much less than the rated system capacity, improved accuracy and resolution can be obtained by selecting a lower rated CT. In this case the CT should be the maximum expected peak current + 25%, rounded up to the nearest standard CT size. Other factors may affect CT accuracy. The length of the CT cabling should be minimised because long cabling will contribute to inaccuracies. Also, the CT burden rating must exceed the combined burden of the Eclipse Series meter, plus cabling, together with any other connected devices. Overall accuracy is dependent on the combined accuracies of the Eclipse Series meter and the CTs. 15
5 T ECHNICAL 5.1 P ERFORMANCE AND D ATA MEASUREMENT RANGES The unit is designed for measuring 3 phase in a 4 wire star/delta configuration Volts ± 10% nominal voltage Accuracy All energy measurements comply with EC 1036 section 4.6.1 Class 1.0 Burden Current burden less than 1VA Drift Negligible, self-compensating circuit Display (Eclipse 7) LCD display, 4 lines x 20 characters, wide temperature band (Eclipse 2) LCD display, single line x 16 characters, reflective image Operating temp -20 o C to +70 o C Storage temp -30 o C to +80 o C Membrane switch Operating force 100-500 crs. Switch life 8-10 million operations. IP65 sealed FUNCTIONS Supplied as standard Function 012 - Peak maximum demand reset Function 013 - Programmes CT setting Function 050 - CT polarity check Function 053 - Pulse status check Function 060 - Programmed details of pulse value Function 061 - Programme details of pulse time PHYSICAL Dimensions (mm) W96 x H96 x D100 Cutout: 92 x 92mm Weight: 1.25kg excluding any external transformers 5.2 M AINTENANCE Eclipse Series meters incorporates E2 PROM for memory back-up. Eclipse Series meters do not require any regular maintenance. OUTPUTS Eclipse 2 One volt free relay, factory set to kwh Eclipse 7 One volt free relay, factory set to kwh, Can be factory programmable kvarh or kvah output Pulse width Programmable, factory set to 100ms Pulse value Programmable, factory set to 1kWh Relay contacts: Maximum switching voltage 600 volt AC/DC Maximum switching current 100mA Resistance 50 ohms Optically isolated MOSFET switch 16
5.3 F IELD S ERVICE C ONSIDERATIONS In the unlikely event that a unit should fail, it will normally be serviced by exchanging the faulty unit with a replacement unit. The initial installation should be done in such a way which makes the replacement procedure as convenient as possible. 1. A Current Transformer shorting block should be provided so that the meter current inputs can be disconnected without open circuiting the CTs. The shorting block should be wired so that protective relays are not affected. 2. All wiring should be routed to allow easy removal of the connections to the terminals. 5.4 P ERFORMANCE C HARACTERISTICS CURVE WITH BALANCED LOAD AT 50 HZ Load curve with balanced load 1 0.8 PF 0.5 lag 0.6 PF 0.8 lead 0.4 PF 1.0 % Error 0.2 0 1 4-0.2-0.4-0.6 0.25 0.5 1.5 2 2.5 3 3.5 4.5 5-0.8-1 Amps 17 The attention of the specifier, purchaser, installer and/or user is drawn to special measures and limitations or use which must be observed when these products are taken into service to maintain compliance with the CE Directives. Details of these special measures and limitations of use are shown in the following publications available from HMSO. Ref: IEC 1000-5-1 (BS195/210788DC) IEC 1000-5-2 (BS195/214642DC) IEC 1000-5-6 (BS195/210789DC)
N OTES 18
DEDICATED CUSTOMER SERVICE Customer care is the cornerstone of Autometers success with a positive service policy observed throughout every specialist area of operation. The direct involvement of the directors at every level, a fully trained and highly motivated workforce and in-depth stock holding combine to provide a level of service and quality which has earned the appreciation of customers throughout the UK and overseas markets. Computerised distribution systems are programmed to provide consistent 24 hour despatch of products. In response to exceptionally urgent demand for small orders, it is possible to process the order and despatch product within 20 minutes. PRODUCT RANGE Metering and monitoring equipment ranges from single and three phase kwh electro-mechanical meters to a range of sophisticated, fully programmable information centres. The product range also includes: Electronic meters Panel mounted meters Maximum demand meters DIN rail meters Current transformers Product development is continuous and Autometers Ltd reserves the right to make alterations in specifications and manufacture without notice. Products as delivered may therefore differ from the description and illustrations in this publication. T HE METERING AND MONITORING SPECIALIST Autometers Ltd 4B Albany Road, Chorlton-cum-Hardy, Manchester M21 0AW Tel: +44 (0)161 861 9056 Fax: +44 (0)161 881 3745 email: sales@autometers.co.uk Publication No. Eclipse 2,7 012002 www.autometers.co.uk