ProVu PD6000 Process Meter

Similar documents
PROVU PD6262 Dual Analog Input Rate/Totalizer

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

LAUREL ELECTRONICS, INC.

263 Series LED Bargraph Indicator and Controllers

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

Model IQ4-PC User Manual Revision Date:

Precision Digital Corporation 233 South Street Hopkinton MA USA Tel (800) Fax (508)

SCALE & WEIGHT DISPLAYS

TEK-LCD 7801A. NEMA 4X Loop-Powered Feet and Inches Level Meter. ACCESSORIES. Technology Solutions

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

Modbus Register Tables for SITRANS RD300 & WI100

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

TABLE OF CONTENTS SPECIFICATIONS...1 MOUNTING...3 WIRING...4 THEORY OF OPERATION...6 MILIVOLT INPUT OPTION JUMPER SELECTIONS...7

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416

CARLO GAVAZZI Automation Components

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

SC26 Magnetic Field Cancelling System

EA402 SERIES ANALOG INPUT FLOW RATEMETER/TOTALIZER INSTALLATION & OPERATING INSTRUCTIONS West Stetson Avenue Hemet, CA USA

DCP100 Digital Control Programmer Specifications

Wall-/Pipe-Mount Level Indicator

TDEPD. Field-Programmable Pressure Switch/Transducer with Integrated LED Display. Programming Sequence Manual

K3NX Process Meter OPERATION MANUAL

Registers type ILR7XX and ILR7XXT

GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS

2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at

16-BIT LOAD CELL/DUAL STATUS INPUT

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

Operating instructions Electronic preset counter Type series 717

Part No. ENC-LAB01 Users Manual Introduction EncoderLAB

800 Displaying Series Flowmeter

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

Sensopress LCD Special English

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features

SPX-5600 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface SPX-5600MAN. Page 1 of 20

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

SC24 Magnetic Field Cancelling System

Automation Interface Requirements for J602 Basic I/O Interface of a DPC 4 Welding System

FIELD MOUNTED RATE TOTALISER MODEL 202D

DPM 942-FPSI 4-20mA Loop Meter with Programmable Backlighting

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

SC24 Magnetic Field Cancelling System

Electronic converter for level transmitters MT03L Instructions manual

ET BLU MIX RX-Condo-3

HS-509 VIBRATION TRIP MODULE

Instruction Manual Alpha ph 190 1/8 DIN ph/orp Controller Transmitter ph / mv / ºC

Set Point Controller OC557. Operator s Manual

Application Note 11 - Totalization

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

RD RACK MOUNT DIMMER OWNERS MANUAL VERSION /09/2011

American DJ. Show Designer. Software Revision 2.08

DSIM-GI Installation Guide Revision P

Troubleshooting CS800/LC900 Bikes

DPM OWNERS MANUAL Website: Phone: (800)

FlexiScan. Impro FlexiScan 4-Channel Controller INSTALLATION MANUAL

SCENEMASTER 3F QUICK OPERATION

Veeder-Root brand Series C628 Dual Preset Counter (C628-8XXX) Technical Manual

MT03A Electronic converter for flow rate transmitters

OWL micro+ WIRELESS ELECTRICITY MONITOR

For warranty service, please contact Microframe at: A technician will gladly assist you.

FACTORY AUTOMATION AS-INTERFACE MAINTENANCE AND TROUBLESHOOTING GUIDE

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

6-DIGIT FREQUENCY METER, TACHOMETER, RATE METER, TIMER, PULSE TOTALIZER, PROCESS METER & TOTALIZER WITH RS-232 PENTA P6000

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder.

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted.

Type AKS 4100/4100U Coaxial D14 version

FRQM-2 Frequency Counter & RF Multimeter

SIGNET 5500 Flow Monitor ENGLISH

ADX-2400N AUDIO DISTRIBUTION AND DELAY SYSTEM. (Analog I/O)

Model CMX3838A2 AV Matrix Switch with DSP audio (firmware 1.0)

SECU-16. Specifications Power: Input Voltage 9-12V DC or AC Input Current Max 200mA. 8 2-wire inputs, Analog (0 5VDC) or Supervised

Quick Setup Guide for IntelliAg Model CTA

Omega.com TM. DPS3100 & DPS3200 series Programmable Scanners

Smart-Encoder : Optical Incremental

VENUS X1PRO-E Quick Start

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

MONITOR POWER Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

Quick Setup Guide for IntelliAg Model NTA

USER & ENGINEER INSTRUCTION MANUAL

Kramer Electronics, Ltd. USER MANUAL. Models: VS-162AV, 16x16 Audio-Video Matrix Switcher VS-162AVRCA, 16x16 Audio-Video Matrix Switcher

OSD. EXECUTIVE / MiniDome USERS MANUAL. USING THE MOTOSAT DISH POINTING SYSTEM EXECUTIVE / MiniDome OSD

THE APOLLO INTELLIGENT METER SERIES MODEL IMH INSTRUCTION MANUAL

REMOTE DISPLAY WIRELESS DECODER MK II

EchoSpan Two-Wire Ultrasonic Level Transmitter Model LU81/83/84 Owner s Manual

Electronic Pulse Counter Combination device

Digital Video Recorder

IMP+ INSTRUCTION MANUAL

Receiver Customization

Operating Manual. Basic Control BC16. two-channel for eco moon

Operating Instructions

DPM-400 Loop-Powered Feet & Inches Meter Instruction Manual

WELDING CONTROL UNIT: TE 450 USER MANUAL

EchoSpan Two-Wire Ultrasonic Level Transmitter Model LU81/83/84 Owner s Manual

Transmitter Interface Program

CONTROL PANEL ENGLISH INSTRUCTIONS MOTORLINE MC 2 / SEAV LRS 2150 SET

application software

Transcription:

Congratulations on your purchase of the ProVu PD6000 process meter! This quick start guide will briefly describe some of the common setup procedures for this meter. This guide includes: Basic Wiring for ProVu Meter... 2 Program and Scale 4-20 ma Input... Program and Scale 0-10 V Input... 4 Program Relays for Automatic Reset... 5 Program Pump Alternation Control... 6 Program Custom Unit Tags... 7 Program 4-20 ma Analog Output... 8 Program Round Horizontal Tank... 9 Program Multi-Point Linearization... 10 Program Noise Filter... 11 Program Process Rounding... 11 Setup Password Protection... 12 Return Meter to Factory Defaults... 12 PR VU SERIES 2015 Precision Digital Corporation. All rights reserved. Menu Button Use this button to access Programming Mode and to return to Run Mode. Note: If you think you have made a mistake while programming the meter, use this button to return the meter to Run Mode without saving. Right/F1 Button Use this button to change the selected digit while inputting a numeric value in Programming Mode. Up/F2 Button Use this button to increment the selected digit while inputting a numeric value in Programming Mode. Enter/F Button Use this button to access or accept a menu item while in Programming Mode. For additional information about the ProVu PD6000 meter not covered in this quick start guide, please consult the instruction manual included on the CD or available at www.predig.com. 2 South Street Hopkinton MA 01748-2208 USA Tel. (508) 655-700 www.predig.com

Basic Wiring for ProVu Meter The connectors label, affixed to the top of the meter, shows the location of all available connectors. Connect your wires to the provided connectors and plug into the meter as indicated. 4-20 ma Input Wiring Wiring for a 4-20 ma input using either an external power supply or self powered transmitter. INPUT SIGNAL 4 5 6 - + External Power Supply + - 2-Wire 4-20 ma Transmitter INPUT SIGNAL 4 5 6 - + 2-Wire 4-20 ma Self-Powered Transmitter Wiring for a 4-20 ma input using internal power supply. INPUT SIGNAL 4 5 6 INPUT SIGNAL 4 5 6 4-20 ma Output Wiring 1 Active (Self-Powered) RELAY1 2 1 + 24 V MA OUT I- I+ R 2 1 4-20 ma Input Remote Display, Chart Recorder, Etc. Passive (Externally Powered) RELAY1 2 1 4-20 ma Input Meter Relay Connections 2 RELAY4 RELAY 6 5 4 2 1 NO NC C NO NC C - + - 24 V MA OUT I- I+ R 2 1 - + 12-5 VDC Power Supply RELAY2 RELAY1 6 5 4 2 1 NO NC C NO NC C + - 2-Wire 4-20 ma Transmitter 0-10 V Input Wiring + - -Wire 4-20 ma Transmitter Signal C R C R AC and DC Loads Protection Power Connection Low Voltage DC Loads Protection INPUT SIGNAL 4 5 6 INPUT SIGNAL 4 5 6 POWER + - F4 Digital Input Connection 2 - + Voltage Signal + - -Wire Voltage Transducer 4 5 6 Signal AC or DC POWER Required External Fuse: 5 A max, 250 V Slow Blow Consult the PD6000 instruction manual located on the included CD or available online at www.predig.com for additional wiring diagrams. 1 ProVu models with 4-20 ma output option (PD6000-XX/5/7) 2 ProVu models with relay option (PD6000-XX2/4/5/7)

Program and Scale 4-20 ma Input These instructions show you how to program the ProVu meter to accept a 4-20 ma input and display a value associated with that range. When the meter is receiving a 4 ma input, it will display the low end of the display range; when receiving a 20 ma input, it will display the high end of the display range. The input values (InP 1 & InP 2) can be changed if needed, but the steps to do this have been omitted for this quick start guide. For example: If the meter were used to display the level of a 100 ft tall tank, the transmitter should send a 4 ma signal when the tank is empty and a 20 ma signal when the tank is full. The meter should be programmed to interpret these inputs on a display range of 0-100, so that at 4 ma the meter will display 0.00 and at 20 ma the meter will display 100.00. press to SEtup (Setup) 4 accept nma (Milliamp) as the input type. 5 multiple times, until the dec pt (Decimal Point) menu is displayed and press 7 to InPut (Input) until the desired decimal point location is displayed and press 8 ProG (Program) SCALE (Scale) 9 10 three times, until dis 1 (Low Display Value) is displayed. Use which and the selected digit. to change to increment when done. d-scal (Dual Scale) menu, press to select yes or no, then press. Note: Most applications only require one scaling point (select no). 6 to accept. three times, until dis 2 (High Display Value) is displayed. change which the selected digit. when done. return to Run Mode.

Program and Scale 0-10 V Input These instructions show you how to program the ProVu meter to accept a 0-10 V input and display a value associated with that range. When the meter is receiving a 0 V input, it will display the low end of the display range; when receiving a 10 V input, it will display the high end of the display range. The input values (InP 1 & InP 2) can be changed if needed, but the steps to do this have been omitted for this quick start guide. For example: If the meter were used to display the level of a 100 ft tall tank, the transmitter should send a 0 V signal when the tank is empty and a 10 V signal when the tank is full. The meter should be programmed to interpret these inputs on a display range of 0-100, so that at 0 V the meter will display 0.00 and at 10 V the meter will display 100.00. press to SEtup (Setup) 4 until volt (Volt) is displayed and then press to accept as the input type. 5 multiple times, until the dec pt (Decimal Point) menu is displayed and press 7 4 to InPut (Input) until the desired decimal point location is displayed and press 8 ProG (Program) SCALE (Scale) 9 10 three times, until dis 1 (Low Display Value) is displayed. Use which and the selected digit. to change to increment when done. d-scal (Dual Scale) menu, press to select yes or no, then press. Note: Most applications only require one scaling point (select no). 6 to accept. three times, until dis 2 (High Display Value) is displayed. change which the selected digit. when done. return to Run Mode.

Program Relays for Automatic Reset These instructions show you how to program the ProVu meter to turn on the relays at programmable set points and turn off the relays at reset points. Note: If the set point is higher than the reset point, the relay will be a high alarm. If the set point is lower than the reset point, the relay will be a low alarm. press to SEtup (Setup) until the relay (Relay) menu is displayed and then press 4 until the appropriate relay number is displayed (rly 1-8) and then press Act (Relay Action) 5 accept Auto (Automatic Reset). Note: See PD6000 Instruction Manual for details on additional relay actions. 7 the selected digit. when done to accept the new set point value. 9 the selected digit. when done to accept the new set point value. return to Run Mode. 6 set (Relay Set Point) 8 rst (Relay Reset Point) Note: select a different relay during step. If you need to program more relays, simply repeat steps -9 for each additional relay. Up to eight (8) relays can be installed using the ProVu meter. Consult the ProVu PD6000 Instruction Manual for information on additional relay action types. 5

Program Pump Alternation Control These instructions show you how to program the ProVu meter to alternate between relays when the set point is reached. This relay action is most commonly used to alternate between primary and backup sump pumps so that they wear evenly over their life spans. Note: With pump alternation active, when the first set point is reached the meter will alternate between the relays set up with the altern relay action. The other relays will be activated in turn if the subsequent relay set points are reached. They will also be deactivated in turn as their reset points are reached. press to SEtup (Setup) 4 until the appropriate relay number is displayed (rly 1-8) and then press This will be the relay that will activate the primary sump pump. 5 until altern (Pump Alternation) is displayed and then press to accept. 7 8 the selected digit. when done to accept the new set point value. 9 10 the selected digit. when done to accept the new reset point value. 6 until the relay (Relay) menu is displayed and then press Act (Relay Action) 6 to set (Relay Set Point) to rst (Relay Reset Point) next relay (rly) This will be the relay that activates the backup sump pump.

11 (pump alt. cont.) Act (Relay Action) 1 until altern (Pump Alternation) is displayed and then press to accept. 14 set (Relay Set Point) the selected digit. when Note: The second relay set point must differ from the first relay set point value. done to accept the new set point value. 15 16 rst (Relay Reset Point) Note: The second relay reset point must differ from the first relay reset point value. 12 the selected digit. when done to accept the new set point value. return to Run Mode. Program Custom Unit Tags These instructions show you how to program the ProVu meter to display custom unit tags for the process value. The secondary (little) display shows this custom unit tag by default. Note: The custom unit tag has no bearing on the meter s operation or the process value. Displaying a custom unit tag is simply for ease of reading. press to SEtup (Setup) 4 The meter will display the default unit tag (ma). Notice here that the letter 'm' uses two 7 segment LEDs. This is true of the letter 'w' as well. until the units (Units) menu is displayed and then press letter is selected and to increment to the next letter. when done to accept the new custom unit tag. 7

Program 4-20 ma Analog Output These instructions show you how to program the ProVu meter to output an analog signal based on its display value. This signal is commonly output to a PLC or chart recorder. Note: The display values programmed for 4-20 analog output do not need to be the same as those programmed as input scale values, though they most commonly will be. until the aout (Analog Out) menu press to is displayed SEtup (Setup) and then press 4 dis 1 (Display #1) This is the display value at which the low range of the output will be transmitted. 5 Out 1 (Output #1) This is the output signal which represents dis 1. 7 dis 1 (Display #1) This is the display value at which the high range the selected digit. when of the output will be transmitted. done to accept the new display value. 9 10 Out 2 (Output #2) This is the output signal which represents dis 2. 8 the selected digit. when done to accept the new display value. 6 The default value of 04.000 (4.000 ma) should be sufficient for most applications. accept the default value. 8 The default value of 20.000 (20.000 ma) should be sufficient for most applications. accept the default value. return to Run Mode.

Program Round Horizontal Tank These instructions show you how to program the ProVu meter to display the volume of a cylindrical tank that is laid horizontally. In level applications, the Round Horizontal Tank feature will automatically account for the non-linear increase in volume as a function of tank height. Just provide the diameter and length of the tank and the meter will do the rest. and until hold for the SELEct five seconds (Select) menu to enter the is displayed Advanced Features Menu. and then press 4 Functn (Function) rth (Round Horizontal Tank) 5 6 select whether to use Inch (Inches) or Cnm dianmr (Diameter) (Centimeters) for the diameter and length measurements. Note: This selection will determine whether the volume is measured in gallons or liters and will set the unit tag accordingly. 7 8 length (Length) the selected digit. when done to accept the diameter measurement. 9 10 the selected digit. when done to accept the length measurement. multiple times, until SAvEd (Saved) is displayed. to return to Run Mode. 9

Program Multi-Point Linearization These instructions show you how to program the ProVu meter to linearize the display for non-linear signals such as those from level transmitters used to measure volume in odd-shaped tanks. Meters are set up with 2-point linearization by default (meaning that the measurement scale is completely linear). This is a more advanced version of the Round Horizontal Tank feature described on the previous page. and until hold for the SELEct five seconds (Select) menu to enter the is displayed Advanced Features Menu. and then press 4 Functn (Function) 5 6 to access the linear (Linearization) select no PtS (Number of Linearization Points) the number of linearization points (2-2) and then press. 7 8 SCALE (Scale) 9 10 twice, InP 1 (First Input Value) is displayed. This is the input value (in ma or V) which represents the lowest display value. Use and to change the value. when done. twice, dis 1 (First Display Value) is displayed. Use and to change the value. when done. 10 twice, InP 2 (Second Input Value) is displayed. Use and to change the value. when done.

11 12 twice. Use and to change the value. when done. twice. Use and to change the value. 1 14 twice. Use and to change the value. when done. Program Noise Filter These instructions show you how to program the noise filter on the ProVu meter in case you are experiencing an unusually noisy signal. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged. Setting the filter level to zero disables the filter function. and hold for five seconds to enter the Advanced Features Menu. the filter (filter) to enter the selected digit. when done to accept the new filter level. Program Process Rounding These instructions show you how to program the rounding feature on the ProVu meter. The rounding feature is used to give the user a steadier display with fluctuating signals and is used in addition to the filter function. This will cause the display to round to the nearest value according the selected rounding value. and hold for five seconds to enter the Advanced Features Menu. The meter will display saved (Saved). to return to Run Mode. until the round (Rounding) menu is displayed and then press when done. select the rounding factor and then press. 11

Setup Password Protection The ProVu meter can be protected against unauthorized changes with the use of three tier password protection. These steps show how to set up a password. press until the PASS (Password) menu is displayed and then press 4 and to increment the digit. select the type of password you would like to create. PASS 1: Allows use of function keys and digital inputs PASS 2: Allows use of function keys, digital inputs and editing set/reset points PASS : Restricts all programming, function keys, and digital inputs when done to accept the new password. The meter will display Locd (Locked). Note: In order to unlock the meter once it has been locked, press then and enter the password. In order to disable password protection, press then and enter the password. Then repeat the above steps and enter the password in the applicable password tier. This will remove password protection and allow programming of the meter. Consult instruction manual for additional information. Return Meter to Factory Defaults If a mistake has been made while programming the meter and it is unclear where the error occurred, the best option may be to perform a factory reset of the meter and begin again. These steps show how to perform a factory reset of the ProVu meter. and until hold for the diag (diagnostics) menu five seconds to enter the is displayed. Advanced Features Menu. 4 and hold until the meter flashes reset (reset). Immediately press factory defaults. to reset the meter to The meter will flash all of the LED segments and then display ProcES (Process). The meter has been reset to its defaults. 12 LIM6000QS_B - 10/15