REGO Start&Go USER MANUAL

Similar documents
Sensopress LCD Special English

DUCATI SISTEMI S. P. A. DUCA47-96 USER MANUAL

Dimming actuators GDA-4K KNX GDA-8K KNX

EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

multi-function meters

EVF 300 series. Controllers for electric bread and pizza ovens, with touch-keys, in split version and which can be integrated into the unit.

EA350. Generator Automatic Voltage Regulator Operation Manual

ACT 10 Digital Keypad Operating & Installation Instructions This manual is found at

Telemetry Receiver Installation Guide

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

Thank you for purchasing this product. If installing for someone else, please ensure that the instructions are handed to the householder.

Dimming actuators of the FIX series DM 4-2 T, DM 8-2 T

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Light Curtain Type LA

USER MANUAL. Compact dimensions 6 DIN modules, with 4 LED s display with 7 segments, for an excellent reading of the measurements

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

PQ-Box 100 Quick Start Instructions

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL

KNX Dimmer RGBW - User Manual

E R A I GATE OPENERS DEPARTMENT

Operating instructions Electronic preset counter Type series 717

INSTALLATION & USER GUIDE

Gamma instabus. Technical product information

Turnout Decoder TD Maxi. User Manual - version 0.1.6

"shell" digital storage oscilloscope (Beta)

MICROMASTER Encoder Module

Solis Export Power Manager

Low-Cost, Single-CT, Automatic Power Factor Controller for Balanced Three-Phase Reactive Power Compensation User Manual

Standard RS232 RS ma

PLC Control Unit for a CSM-E Electrical Compact Clean Steam Generator

Foreword: The purpose of this document is to describe how to install and configure Neets 4 relay box

POWER FACTOR REGULATOR

Parsic Italia Timer Relay Module (FRM01) User Manual

AT450SAW Programmable Selective Amplifier

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

Digital Economy Seven Programmer

Telemetry Receiver Installation Guide

2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES

MATE3 Owner s Manual Addendum

B. The specified product shall be manufactured by a firm whose quality system is in compliance with the I.S./ISO 9001/EN 29001, QUALITY SYSTEM.

Operating Manual RISH OPTIMA VAF

VLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216

02/11/2015

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

Dimensions. Model Number. Electrical connection. Features. Pinout Product information. Indicators/operating means. LGS25 Serie.

Operating Instructions

Electrical connection

Digital differential Pressure switch Model DPS Instruction manual

Model IQ4-PC User Manual Revision Date:

SignalTap Plus System Analyzer

Revision 1.2d

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

Capacitance Limit Detection nivotester FTC 420/421/422

The Art of Engineering

Figure 1: Device components

Standard signal metering in wall-mounting case

Automatic Transfer Switch Control PLC Operator s Manual

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

Special Applications Modules

User Manual M1. Direct current / Direct voltage signals 0-20 ma, 4-20 ma, 0-10 VDC. Technical features:

2 2 Relay outputs. M DIN W72 H7mm. LE7 Weekly/Yearly timer

ZN-PD. Smallest Air Particle Sensor in the Industry for In-line Measurement. Air Particle Sensor. Features

Ocean Sensor Systems, Inc. Wave Staff, OSSI F, Water Level Sensor With 0-5V, RS232 & Alarm Outputs, 1 to 20 Meter Staff

Timer Modules. MEU11 24 Hour Module, MEU17 7 Day Module (Without Housing)

AF-300 E11 Adjustable Frequency Drive

AES-404 Digital Audio Switcher/DA/Digital to Analog Converter

Digital differential pressure controller Model DPD Instruction manual

SU17 Series Fiber Optic Sensors

Satellite B or D. Satellite Inputs (LNB Trunk)

E6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm

PACSystems* RX3i. Isolated Thermocouple Input Module, 6 Channels, IC695ALG306-EB Isolated Thermocouple Input Module, 12 Channels, IC695ALG312-EB

CET DOUBLE COUNTER WITH TWO THRESHOLDS LBM62CD. Type: TECHNICAL FEATURES

Description. Specifications and Ordering Information 1900/27 Vibration Monitor

Weekly Time Switch. Rated time Time setting range Time division 24 hrs x 7 days 00:00 to 23:59 1min

FOM-9010, FOM-9011 and FOM-9012

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Smart-Encoder : Optical Incremental

LED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data

AT47SAW Programmable Selective Amplifier

User Manual M1. Thermocouple type K, B, S, N, E, T, R, L, J. Technical features:

AK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:

XTM72E & F Real-Time Clock Modules

Operating Manual. Basic Control BC16. two-channel for eco moon

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.

VISUALIZED DIGITAL TIMER

Electronic converter for level transmitters MT03L Instructions manual

Digital Differential Pressure Gauge Switch 0.1 : 0.5 BAR USER GUIDE

LDS Channel Ultra Low Dropout LED Driver FEATURES APPLICATION DESCRIPTION TYPICAL APPLICATION CIRCUIT

ATS50SAW Programmable Selective Amplifier

application software

END USER MANUAL DAS-M44HD-R

N3ZI Digital Dial Manual For kit with Serial LCD Rev 3.04 Aug 2012

DCP100 Digital Control Programmer Specifications

Z-D-IN. RS485 Modbus Module 5 Digital Inputs

Cronotermostato Digitale

Junior Max (JR Max ) Controller

Active FCB-EV-HD-SDI INTERFACE BOARD

24 Hour & 7 Day Digital Immersion Heater Timeswitch Article

Transcription:

REGO Start&Go USER MANUAL Version 0 Rev. B of 03/03/16 Page 1 of 15

Introduction The purpose of the manual is to describe all of the steps required to commission and correctly operate the REGO Start&Go automatic power factor correction regulator, installed in the DUCATI energia power factor correction equipment. Note that the regulator is an integral part of the equipment and is not sold separately; the configuration of the batteries was designed and implemented in DUCATI energia; the correct connection is represented by the varmetric insertion described below. 1. Connection mode of the device 1.1 Connection mode to the mains. Below is a description of the connection mode to the mains of the REGO Start&Go regulator in combination with the Ducati energia electric board. Only the standard Varmetric insertion is used, where the linked voltage used is, for example, between the S/L2 phase and the T/L3 phase, while the CT (current transformer) in the remaining R/L1 phase line. Figure 1 Connection mode to the mains, connection FF1 Note: If the three-phase network is 230V L-L DO NOT connect the 400V pin, but the 230V pin ATTENTION: This connection mode is UNIQUE therefore a different type of connection DOES NOT allow the instrument to operate correctly. The customer must install the CT on the phase that is NOT used to power the device, for example L1/R as in figure above Version 0 Rev. B of 03/03/16 Page 2 of 15

1.2 CT connection It is requested to connect only one C.T. in one of the positions marked as OK in the figure below. The positions marked as NO are forbidden. Connect S1 to pin L and S2 to pin K (see figure 3 to identify the pin names) OK OK NO NO Figure 2 Example of CT connections ATTENTION: Note that the CT is not supplied and that therefore the customer must independently install and connect the most suitable CT for the plant, being sure to connect it ONLY IN ONE of the allowed position (a) or (b) in the figure above. For the choice of C.T. to be connected to the regulator: - the dimensions must be such that the busbars or existing cables that compose the conductor of ONE phase can pass through. - The full scale current of the secondary must be 5A - The primary will have a full scale current 20% greater than the maximum current absorbable by the loads. - Precision class required for the CT must be less than class 1 Version 0 Rev. B of 03/03/16 Page 3 of 15

1.3 IN/OUT connector wiring The meaning of the pins of the removable terminal boards is illustrated below. Check the correct connection of the cables before switch it on for the first time. Note: for models with only 3 relays the terminals relative to relay 4 and Relay 5 will not be available. COMM Relay 1 Relay Relay 2 Relay 3 Relay 4 Relay 5 CT connection K L Power supply 0V 230V 400V Figure 3 Wiring of the board connectors 2. Self-diagnosis at start-up Every time the equipment is switched on, REGO Start&Go runs a self-diagnosis on the input voltage and current signals and on the equipment s capacitors batteries. The following are carried out in particular: Installation Tests on the CT: CT not found; CT in wrong PHASE; CT in wrong POSITION; if these tests provide negative results the regulator locks in error status (see chap. 6). Check that the mains voltage and current are within the specified range, otherwise the regulator locks in error status (see chap. 6). Automatic adaptation of the CT direction. Mains frequency reading. Check that the temperature of the electric board is within the admissible range. Version 0 Rev. B of 03/03/16 Page 4 of 15

Testing on battery failures and size and, in case of failure, checking restored operation by running 3 insertions of the failed battery. Batteries that are still found to be failed or a different size from expected are momentarily excluded from the power factor correction logic and re-tested the next time they are switched on. SW1 switch position reading (see Figure 4 below) for self-acquisition to check the request for a new battery acquisition made by the Customer (Chap. 3.2). Switch SW1 is positioned on the board inside the cabinet (Figure 4). (*) For the blocking tests REGO Start&Go shows the detected error code (see chap. 6) and it is accordingly necessary to switch the electric board off, perform the operations to remove the cause of the error and then switch the electric board back on again. For the duration of the tests the Run led flashes while the Status led remains orange until it turns green or red at the end of the test (see Table 1, Table 2 and Table 3). 3. Commissioning 3.1 Automatic battery acquisition In addition to running the self-diagnosis at start-up, as described in Chap.2, only at the first commissioning, the regulator runs an automatic battery acquisition. It is not necessary to set the CT value because REGO Start&Go acquires it autonomously through a cyclical battery reading. ATTENTION: Before proceeding with the steps described below check that the CT has been installed as shown in Figure 2. Also ensure that the connected load remains stable as long as the Status led is orange. ATTENTION: If there is an PHOTOVOLTAIC system, be sure to momentarily SWITCH IT OFF during commissioning, to run the plant check in the absorption dial ATTENTION: when commissioning the equipment, before it switches to the normal state of operation, it is necessary to wait for the REGO Start&Go regulator to finish the automatic battery acquisition Version 0 Rev. B of 03/03/16 Page 5 of 15

By powering the cabinet, and therefore the regulator, the self-diagnosis tests described in chap. 2 are always carried out; if the self-diagnosis has a positive outcome, only when commissioning the equipment the first time, the automatic acquisition procedure of all of the batteries is carried out in sequence: every battery is connected and disconnected 3 times in a row and the sequence is repeated 4 times, with 30 s breaks in between (required to completely discharge the condensers). Based on the regulator s status, the Status led (see Figure 5) is a different colour: Auto-diagnosis or Automatic battery acquisition in progress: steady orange Status led Auto-diagnosis ok or Correct operation without errors: steady green Status led Auto-diagnosis failed or Operation with errors: steady red Status led 3.2 Total Parameter Reset If, after servicing the cabinet to replace the board or to resolve operation anomalies, you intend to reset the parameters, do the following: 1. Disconnect the power supply to the cabinet and open it to access the Rego Start&Go regulator. 2. Change the position of SW1 (see Figure 4). If it was previously in position A, move it to position B and vice versa. At the end, leave the switch in the position it was left in (without having to change its position at the end of the operation) 3. Close the cabinet back up again and power it. 4. REGO Start&Go will now start back up again as set forth in Par.3.1 The Figure 4 below illustrates the location of the SW1 switch on the board. Figure 4 Switch SW1 for Automatic Battery Acquisition Version 0 Rev. B of 03/03/16 Page 6 of 15

4. Regulator operation 4.1 Indicator leds Status Led: Status of the device Run Led: flashing to report the vitality of the regulator Steps: when steady this means that the batteries are connected (led on) CodeError: when flashing they report the error code (see Error Code Table) Figure 5 - View panel CodeError/Steps: When the Status Led is steady red, the flashing Leds (Step1..Step5) report the current error code (see Table 4), while the steady Leds (Step1..Step5) report which batteries are connected (ex. Led1 Step1 steady on means that battery 1 is connected). Status: this reports the status of the regulator: Orange: this means that the self-diagnosis that begins at start-up and automatic battery acquisition are in progress Green: correct regulator operation (no errors) Red: there are errors Power: This means that the device is powered. Run: When flashing it reports the device s vitality 1 1 Correct execution of the power factor correction programme on the internal micro-controller Version 0 Rev. B of 03/03/16 Page 7 of 15

5. Led signals pertaining to the operating statuses Below are the various existing led signals based on the current status of Rego Start&Go. For all of the phases below, even if not described, the POWER led is always steady Green meaning that the board is powered. 5.1 Orange Status Led Below is a list of the situations in which the Status led is steady Orange. Self-diagnosis: this is always carried out - Flashing green Run led every time the equipment is switched on - Steady orange Status led - Step1.. Step5 leds stay off for at least 30s during testing, the same amount of time it takes for the batteries to discharge; when they are steady on red this means that the first battery is connected, to Automatic battery acquisition: This phase is carried out immediately following the phase described above and is only carried out at the time of the first start-up (par. 3.1.) or after resetting the parameters (par. 3.2). 5.2 Green Status Led continue with further tests. - Flashing green Run led - Steady orange Status led - Step1.. Step5 leds, with steady red leds, report the timed connection of the various batteries in sequence, starting from Step1 up to Step3 (or Step5 in 5-step models), running 4 complete cycles, with a break of approx. 30s between cycles. Table 1. Orange led status Below is a list of the situations in which the Status led is steady green. Correct regulating operation: Value - Flashing green Run led Measurement and Regulation Phase. No - Steady green Status led errors - Steady red Step1.. Step5 mean that the batteries are connected End of self-diagnosis with positive outcome End of automatic battery acquisition with positive outcome A situation of error is resolved. - Flashing green Run led - Steady green Status led - Step1.. Step5 leds off mean that no battery is connected Table 2. Green led status Version 0 Rev. B of 03/03/16 Page 8 of 15

5.3 Red Status Led Below is a list of the situations in which the. Error / alarm in progress: one or more - Flashing green Run led errors have been detected - Steady red Status led - Step1.. Step5 leds: every 5s they alternate between displaying steady Red leds (relative to the connected batteries) and displaying flashing Red leds (relative to the error code). If there are several errors, they are displayed in sequence every 5s. If the type of error requires disconnecting the batteries, then during the display phase of steady End of Start-up test with Negative outcome leds they remain off. - Flashing green Run led - Steady red Status led - Step1.. Step5 leds: every 5s they alternate between displaying the error code with flashing Red leds, If there are several errors, they are displayed in sequence every 5s If no batteries are connected, then during the display phase with steady leds they remain off. Table 3. Red led status Version 0 Rev. B of 03/03/16 Page 9 of 15

6. Errors/Alarms view 6.1 ERRORS/ALARMS code Below is a table stating the combination of leds associated with the error number and its meaning ATTENTION! THE LED CONFIGURATIONS ILLUSTRATED BELOW STAND FOR AN ERROR/ALARM ONLY IF THE LEDS ARE FLASHING Step1 Step2 Step3 Step4 Step5 error no. ERROR/ALARM DESCRIPTION 1 Current of secondary CT too low 2 Current of secondary CT too high 3 Internal temperature too high 4 Input voltage too high 5 Input voltage too low 11 Insufficient reactive power of equipment 12 No current from CT secondary 13 CT primary on wrong phase 14 CT in wrong position 15 Incorrect reactive power on condenser arrays Table 4. error codes Version 0 Rev. B of 03/03/16 Page 10 of 15

6.2 Error codes and actions taken by the regulator error no. 1 2 3 4 Type of detected error and list of taken actions Current too low: the Input current to the instrument is below the bottom limit of 100 ma. Step1..Step5 leds flash as set for error no. = 1 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the batteries in sequence. The batteries remain disconnected for at least 30 sec (battery discharge time) or at least as long as the error persists. The error is no longer reported when the error condition disappears. Current too high: the input current to the instrument is higher than the top limit of 5.1A. Step1..Step5 leds flash as set forth for error no. = 2 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the batteries in sequence. The batteries remain disconnected for at least 30 sec (battery discharge time) or at least as long as the error persists. The error is no longer reported when the error condition disappears. Internal temperature too high: the temperature reading on the board is greater than 60 C. Step1..Step5 leds flash as set forth for error no. = 3 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the Batteries in sequence. The error condition is resolved only if the temperature drops below 50 C, otherwise the state of alarm persists with the batteries disconnected. There is therefore a hysteresis from 60 C to 50 C. Voltage too high: the input voltage to the device is greater than the top limit of 460V Step1..Step5 leds flash as set forth for error no. = 4 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the Batteries in sequence. The error condition is resolved as soon as the voltage drops below this threshold. Voltage too low: the input voltage to the device is lower than the bottom limit of 340V 5 Step1..Step5 leds flash as set forth for error no. = 5 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the Batteries in sequence. The error condition is resolved only if the voltage value rises above this threshold. Insufficient reactive power of equipment: measured in cos(phi) it is below the threshold of 0.95 Step1..Step5 leds flash as set forth for error no. = 11 in Table 4 11 12 13 This error occurs when, due to an insufficiently sized cabinet, or not sufficient for the requirements of the plant (for example due to a failed battery), an unavailable battery would be necessary or you are in a situation where the smallest battery would place the plant in capacitative; in both cases the error only applies if the cosfi is below the 0.90-1 range. With this error no battery disconnecting action taken. The error is no longer reported when the error condition disappears. No current from CT secondary: the value of the input current reading to the instrument is zero. Step1..Step5 leds flash as set forth for error no. = 12 in Table 4 If the error persists for 10 sec Rego Start&Go disconnects the batteries in sequence. The batteries remain disconnected for at least 30 sec (battery discharge time) or at least as long as the error persists. This can happen even if the CT is set up in the wrong POSITION, for example in the POWER FACTOR CORRECTION branch. The error is no longer reported when the error condition disappears or, only in the case of CT in incorrect POSITION, it is resolved by switching off the system and removing the cause of the blocking error CT primary on wrong phase: Step1..Step5 leds flash as set forth for error no. = 13 in Table 4 This error occurs when the CT connection was set up incorrectly (the connection must be set up as shown in Figure 1) It is necessary to switch the cabinet off, check the connections, remove the cause of error and turn the system back on again. Version 0 Rev. B of 03/03/16 Page 11 of 15

CT in wrong CT position: 14 Step1..Step5 leds flash as set forth for error no. = 14 in Table 4 This error occurs when the CT connection was set up incorrectly (for example, it was connected as shown in position c or d of Figure 2) It is necessary to switch the cabinet off, check the connection, remove the cause of error and turn the system back on again. Incorrect reactive power on condenser arrays: 15 Step1..Step5 leds flash as set forth for error no. = 13 in Table 4 This error occurs when, following an automatic battery acquisition at start-up, the weights measured for the batteries do not match the nominal factory values. All errors relative to failed batteries will be reported as this type of error Turn the equipment off and back on again in the case of first automatic acquisition Switch it off, move the jumper and restart the equipment for automatic acquisitions after the first one Table 5. description of errors and relative corrective actions Version 0 Rev. B of 03/03/16 Page 12 of 15

7. Technical Features of the Rego Start&Go Board 3/5-Battery Rego Start&Go Power Supply Circuit Nominal Supply Voltage 400V ± 15% 230V ± 15% Frequency 50Hz or 60 Hz (read automatically by the instrument) Absorbed Power Protection Current input Nominal Current 5A Operating Range 0.10A 5.1A 7 VA max F1 Self-resetting ceramic resistor on the board (It is nevertheless advisable to install an external 200mA T fuse ) Measurement and Control Data Type of measurement Measurement of the reactive current at the voltage zero-crossing Relay Output Number of Outputs 3 or 5 Contact Status NA Type of contacts 6A - 250Vac 2A 400Vac Rated Voltage/Max for Operation 250Vac / 440Vac Interface for testing Type Ambient Operating Conditions Operating Temperature Storage Temperature Connections Terminal Type Conductor size Protection Degree of Protection of Board Installation Type of Installation Clamping to support Overall dimensions LxDxH (mm) TTL port for internal use 0 C +60 C -20 C +70 C with removable screw 2.5mm 2 max IP00 Installation on internal cabinet support 4 M4 clamping screws 780x500x1450 Version 0 Rev. B of 03/03/16 Page 13 of 15

8. Alarm thresholds and intervention times Alarm thresholds Minimum / Maximum Input Voltage 340V / 460V on input 400V 196V / 264V on input 230V Minimum / Maximum Input Current 0.10A / 5.1A Alarm/Hysteresis Temperature +60 C / Hysteresis between +50 C +60 C Intervention times Wait time for a battery to discharge Insertion time for battery connection or disconnection 30s 30s Version 0 Rev. B of 03/03/16 Page 14 of 15

Via M.E. Lepido, 182 40132 BOLOGNA - Italy Tel.: 0039 051 64 11 511 Fax.: 0039 051 64 11 690 www.ducatienergia.com Email: info@ducatienergia.com Version 0 Rev. B of 03/03/16 Page 15 of 15