SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

Similar documents
TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

SITE All work shall be performed at Center Park Substation (1895 Kernan Blvd, Jacksonville, Fl ). DATE: 04/03/2018

Student Services & Classroom Addition

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

SECTION COMMUNICATIONS HORIZONTAL CABLING

IndyGo Facility Upgrades Project 35671EE

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING

Public Works Division Lighting District Fiber Optic Specifications April 2009

STRUCTURED CABLE SYSTEM (SCS)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98)

Michigan State University Construction Standards EXTERIOR FIBER OPTIC CABLE SYSTEM PAGE

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

1. The contractor shall ensure that: c) Contractor or sub-contractor has at least 5 years experience

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

3M Sensored Termination (15 kv) QX-T15I-vi1-E

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Instructions. Cable with Armor F CAUTION. October Rev A

Three Phase - General Purpose. THREE PHASE: 3 kva - 9 kva Epoxy Encapsulated Series 76 ISO-Shield

CHAPTER 14 WIRING SIGNALS AND LIGHTING FIELD GUIDE Wiring Requirements WIRING

Operating Manual. Automated Gear. Apollo Design Technology, Inc Fourier Drive Fort Wayne, IN USA

SECTION TESTING OF COPPER CABLES

Section Communications Optical Fiber Backbone Cabling

AMERICAN NATIONAL STANDARD

HEALTH AND SAFETY MANUAL

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

HighBand 25. TrueNet Category 6 Solutions

ATTACHMENT 2: SPECIFICATION FOR SEWER CCTV VIDEO INSPECTION

UNSIGNED HARDCOPY NOT CONTROLLED

BROCHURE MC LUMINARY CABLES

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. July 19, 2013

SECTION FIBER OPTIC STATION CABLES

VITALink Taped Splice Straight Through Crimp

Aerial Cable Installation Best Practices

2016 Cable Splicing Courses

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Installation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

3M Cold Shrink Splice Kit QS-III 5416A

Instrukcja montażu. FLEX LED Neon Instalacja

3 Cleaning. 4 Technical data

Fiberglass - Technical Data

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles

SPECIFICATION NO NOTE

Linatron - M9 & M9A. Modular high-energy X-ray source. 2.0 Performance

Small System Packages. Strand Dimming Systems

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

3M Cold Shrink Splice Kit QS-III 5514A

Illustrated Feature. Options

LCS 2 RJ 45 Cat. 6A HD panels and units

3 Cold Shrink Products

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers

RESIDENTIAL SUBDIVISION BILL OF MATERIALS

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

Laying of cables and lines in electrical installations and data networks

Cable Installation Tips

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Cable Installation Tips

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

MICROMASTER Encoder Module

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

LIGHTING: ENCLOSED AND GASKETED AREA FLUORESCENT. Applications. Illustrated Feature. Certifications and Compliances

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM

Channel Cable Tray - Accessories

LED MODULES READYLINE DL

Underground Installation of Optical Fiber Cable by Pulling

SECTION COMMUNICATIONS HORIZONTAL CABLING

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment

SUMITOMO PRODUCT SPECIFICATION. FutureFLEX. TCxxMSOS DIELECTRIC HIGH PERFORMANCE OSP TUBE CABLE SERIES

Safety Codes Council Conference Banff C Panel Discussion

FLUID VIEW 12V LED TAPE LIGHT

lumenalpha spot Specification Sheet

Industrial Loadbreak Elbow

SECTION 7 -- CROSS-CONNECT SYSTEMS

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

CONSTRUCTION SPECIFICATION FOR TRAFFIC SIGNAL EQUIPMENT

PREMIUM 5e F/UTP PRODUCTS

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

Aging test: integrated vs. non-integrated splices shield continuity systems.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

AMERICAN NATIONAL STANDARD

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

Sumitomo Cable Specification SE-*RU. OFNP Rated Central Tube Cable with Optical Fibers. Issued: December 2014

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

Installation Guide VL-MV10. Model No.

3M Cold Shrink Splice Kit QS-III 5515A

SECTION 5900 TRAFFIC SIGNALS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

High Voltage Cable Splicing Training

Power Injector 1520 Series

Transcription:

SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of old cable is included in cable replacement work. B. Medium voltage cable, to be furnished by Stanford. The Contractor provides all other materials including all labor for a complete and fully functioning installation. C. Related Sections: 1. Section 33 71 19 Underground Ducts and Manholes. 2. Section 33 71 49 Medium Voltage Power Cable. 3. Section 26 12 19 Pad Mounted Transformers. 4. Sections 33 77 00.1, 33 77 00.2and 33 77 00.3 Pad Mounted and Submersible Switches and Fault Interrupters. 1.2 REFERENCES A. California Electrical Code, most recent edition. B. Cal/OSHA regulations, especially lock-out requirements and requirements for work in vaults and manholes. C. Code compliance is mandatory. Nothing in the Drawings and Specifications implies acceptance of work that does not comply with Codes. D. AEIC CG5 2005, Underground Extruded Power Cable Pulling Guide 1.3 CLOSEOUT SUBMITTALS A. Provide as-built drawings showing location of splices complete with updated manhole butterflies Section 33 71 19 Underground Ducts and Manholes. B. Provide Santa Clara County Permit with final sign-off date. 1.4 QUALIFICATIONS Cable splices and terminations shall be made by certified cable splicers with a minimum of five (5) years experience in splicing cables of the type being provided under the Contract. Provide qualifications to the Project Manager prior to splicing or termination February 2014 Page 1 of 5 2018 FDG Section 33 71 49.23

of cables. Splicing and terminating shall be in strict accordance with manufacturer's recommendations, utilizing factory furnished materials in kit form, or as specifically shown on the Drawings. 1.5 COORDINATION A. Contractor shall conform to the safety requirements in Stanford ESOP-1017and applicable OSHA/CalOSHA rules and regulations. B. Provide OSHA approved air monitor with current calibration sticker. C. All switching of Stanford circuits shall be performed by Stanford Utilities High-Volt Shop Electricians. High-Volt shop personnel, along with the Contractor, shall personally verify that circuits are de-energized and perform LOTO jointly with Stanford High-Volt Shop prior to work. D. All scheduled outages required to complete the work shall be arranged by the Project Manager and the High-Volt shop supervisor. PART 2 PRODUCTS 2.1 CABLE A. Unless otherwise noted, medium voltage cables are to be furnished by Stanford and be made available in the High-Volt Yard located at 506 Oak Road for pickup by the Contractor with prior notice. All cable reels picked up by the Contractor must be logged by Stanford High-Volt Shop personnel with initial footage and final footage, if any left, upon their return. B. Contractor to furnish and install 600 V THHN AWG # 4 ground conductor for 15 kv # 2 or 1/0 cables installations and 4/0 THHN for 15 kv 350 MCM or 500 MCM cable installations. C. Whenever old cables are pulled out, they shall be returned to the Stanford High-Yard for scrap, unless otherwise specified in the job scope. 2.2 TERMINATIONS A. Stress cone kits: Premolded, heatshrink, or cold shrink; Elastimold, Raychem or equal. B. Elbows: 200 Amp load-break and 600 Amp non load-break elbows shall be Elastimold, see Section 16122. 2.3 SPLICES A. Splices shall be made by pre-manufactured splicing kits. Splices shall be rated for continuous submersion in water. February 2014 Page 2 of 5 2018 FDG Section 33 71 49.23

B. Splices shall be made in strict compliance with the cable manufacturer s and the splicing materials manufacturer s instructions. All splicing materials shall be compatible with the cables. C. Use only copper compression sleeves for splicing copper cables. Do not use sleeves containing aluminum. 2. 4 CABLE RACKS AND SUPPORTS Provide galvanized steel racks with porcelain insulators or non-metallic racks. PART 3 EXECUTION 3.1 INSTALLATION OF MEDIUM VOLTAGE POWER CABLE: A. Test conduits with a mandrel and clean with a brush to remove foreign material prior to cable installation. B. Cable Pulling installation equipment shall be complete with instruments for reading pulling tension C. Pulling tensions and bending radii shall in no case exceed maximum values recommended by cable manufacturer. Long pulls require pulling tension calculations and measurement. Consult with Stanford High Volt Shop for details. D. Use only lubricants approved by the manufacturer for cable pulling. E. Install cables along those walls providing the longest route and the maximum spare cable lengths. The bending radius of trained cables shall be not less than twelve (12) times the outside diameter of the cable. F. Provide galvanized steel channels and brackets and porcelain blocks, Unistrut or approved equal, and support cable and splices on maximum 4-ft. centers. Use heavy duty plastic cable ties to secure cables to insulators. Approved non-metallic cable supports are acceptable 3.2 INSTALLATION OF GROUND CONDUCTORS A. Provide an insulated, 600-Volt THHN copper grounding conductor with all primary cable runs. B. Size shall be shown on drawings. C. Splice grounding conductor with T connectors and bond leg of T to ground bus in each manhole. DO NOT use manhole ground bus as a splice point. D. All equipment enclosures shall be grounded with code approved fittings. February 2014 Page 3 of 5 2018 FDG Section 33 71 49.23

3.3 CABLE SPLICES AND TERMINATIONS A. Materials and methods used shall conform to manufacturer s recommendations. B. Cable splices and terminations shall be completed without delay once the conductors and insulation are exposed to the atmosphere. C. The cable shall be installed with the minimum number of splices. Splices are permitted only in accessible locations. D. Ground the metallic cable shield at splices and terminations. 3.4 CABLES IN MANHOLES A. Support cables at 4-foot maximum intervals with galvanized steel racks and channels and porcelain insulators or nonmetallic cable racks. Fasten cables to supports with plastic cable ties. Do not allow cable weight to rest on the terminations. B. Ground metallic non-current carrying components such as cable racks, switches, and transformers. Use a #6 AWG solid copper conductor, minimum. 3.5 PHASING A. Verify by hot phase test that cables on loop and tie circuits are matched phase-to-phase at every splice or termination that occurs at an open point. Use an approved live-line phasing meter and follow safety and switching procedures. This test may only be performed by personnel experienced in and qualified for testing of energized circuits. Do not rely on color markings for assurance of proper phasing. B. Verify correct phase rotation when cables on radial circuits are replaced. Use approved secondary voltage rotation testers or verify that rotation of existing motors is correct. C. All hot phasing and Rotation testing shall be witnessed by Stanford High-Volt Shop personnel. D. Color marking for primary cables shall be: Phase A Yellow Phase B Red Phase C Blue E. Standard primary phase rotation is counterclockwise ACB. Changing the order of phases to accommodate desired building rotation will be done at the primary connection to the outdoor padmount transformer or to the indoor primary interrupter switch in the case of a unit substation. February 2014 Page 4 of 5 2018 FDG Section 33 71 49.23

3.6 PRIMARY VOLTAGE CABLE HIGH POTENTIAL TEST A. All primary cables shall be given D.C. high potential tests after installation. All tests shall be performed in the presence of the High-Volt shop s representatives and shall be performed to their complete satisfaction. Testing of cables shall be done after all splices and cable terminations are made, but before connections to equipment are made. Open cable ends shall be wrapped with plastic or provided with similar coronal protection. Test each cable with the shields and other cables grounded. A high potential test set shall be used to read the leakage current in microamperes in the cable at two-minute intervals during the test. B. When new cable segments are to be spliced to existing cable, the new segment shall be tested at the New Cable test value. After the final splice is complete, the entire segment shall be tested at the Existing Cable value. C. Raise the test voltage in 5 kv increments from zero (0) to the final test value over a minimum period of 10 minutes. Testing time shall be started when the voltage on the cable has attained final test value and shall be continued for at least 10 minutes thereafter. DC TEST VOLTAGE, FINAL TEST VALUE: Cable Type New Cable Existing Cable 5 kv 25 kv 10 kv 15 kv 50 kv 25 kv D. Results of the tests shall be plotted, current against voltage, at each 5 kv increment of rise after 2 minutes minimum or after value has been stabilized, to a maximum test value, and current against time for 10 minutes thereafter in one minute intervals on a separate sheet for each length of cable tests. Curves shall be identified with the cable to which they apply and shall be certified. Time of day, outside temperature and humidity at time of each test shall appear on each curve sheet. E. EXCEPTION: A go/no-go test at the proper test voltage may be accepted by the Project Manager for very short lengths of cable. END OF SECTION February 2014 Page 5 of 5 2018 FDG Section 33 71 49.23