SONARtrac Technical Bulletin

Similar documents
MT03A Electronic converter for flow rate transmitters

Electronic converter for level transmitters MT03L Instructions manual

Troubleshooting CS800/LC900 Bikes

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Table of contents 1. INTRODUCTION GENERAL CONTENTS OF PACKAGE GENERAL USE OF THE EQUFLOW 6100 D/A CONVERTER STORAGE..

INSTALLATION AND OPERATION M

Registers type ILR7XX and ILR7XXT

Wired Troubleshooting Manual

Electronic converter for flowmeters MT03F Instructions manual

Aspect 2 Circuit Digital Scene Control

Model: LCD4WM 3.5 Window Mounted LCD Monitor User Manual Features

EA63-7D. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator

Transfer Switch. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Amperes. English Original Instructions (Issue 5)

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.0

EXA PH200/400 and EXA PH202/402 Troubleshooting and Error Code Guide

Remote Control. degraded, causing unreliable operation. The recommended effective distance for remote operation is about 16 feet (5 meters).

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Warranty Information

CONTROL PANEL ENGLISH INSTRUCTIONS MOTORLINE MC 2 / SEAV LRS 2150 SET

RoHS. Atma-Sphere Music Preamplifier. model P-2 OWNER'S MANUAL. Please study this document carefully before using equipment

Safety Information. Camera System. If you back up while looking only at the monitor, you may cause damage or injury. Always back up slowly.

Field Service Procedure Replacement GACP Control Panel Kit, ST24

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1

Quick Start. RSHS1000 Series Handheld Digital Oscilloscope

Digital differential Pressure switch Model DPS Instruction manual

SCALE & WEIGHT DISPLAYS

Operating instructions Electronic preset counter Type series 717

USER MANUAL MODEL 650. TWO-WIRE ph/orp TRANSMITTER. um

REGO Start&Go USER MANUAL

Litile34 OPERATION MANUAL

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

MICROMASTER Encoder Module

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK

Exercise 5-1. Troubleshooting Techniques EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Signal flow tracing

PLC Control Unit for a CSM-E Electrical Compact Clean Steam Generator

MiT. MOVING image TECHNOLOGIES INSTRUCTIONS FOR INSTALLATION, OPERATION, AND MAINTENANCE. M Series Dimmer. Manual Version 1.1

Working with a Tektronix TDS 3012B Oscilloscope EE 310: ELECTRONIC CIRCUIT DESIGN I

FACTORY AUTOMATION AS-INTERFACE MAINTENANCE AND TROUBLESHOOTING GUIDE

Operating instructions Capacitive level sensor KNQ

MS2540 Current Loop Receiver with RS485 Communication

Operating Instructions

Model 5250 Five Channel Digital to Analog Video Converter Data Pack

INDEP. QUARTZ MIN. - 1/2 MIN. AFNOR / IRIG B DHF / RADIO

USERS MANUAL GR ONE 300 GR ONE 700 GR ONE 1400

MINI PC SCOPE PCSU01. User manual. test leads software download USB cable design enclosure

Light Curtain Type LA

WaveRider Trouble Shooting Guide

MATE3 Owner s Manual Addendum

Sigma 1 - Axis Servo Motor and Cables - Troubleshooting Guide

Electronic Pulse Counter Combination device

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

LX3V-4AD User manual Website: Technical Support: Skype: Phone: QQ Group: Technical forum:

2002 Martin Professional A/S, Denmark.

C-net WIND. User s Guide

OPERATOR S GUIDE OPERATOR S GUIDE OPERATOR S GUIDE OPERATOR S GUIDE OPERATOR S GUIDE OPERATOR S GUIDE OPERATOR S GUIDE.

Element 78 MPE-200. by Summit Audio. Guide To Operations. for software version 1.23

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.

BooBox Flex. OPERATING MANUAL V1.1 (Feb 24, 2010) 6 Oakside Court Barrie, Ontario L4N 5V5 Tel: Fax:

Noise Detector ND-1 Operating Manual

INSTALLATION & USER GUIDE

USER GUIDE for the. HES92020, HES92021, HES92220 & HES92221 DIMMER Modules

Stevens SatComm FAQs For use with SatCommSet or Terminal Setup programs

FD104CV. Installation and Operation Manual 10.4 LCD MAN FD104CV. TECHNICAL SUPPORT , or Document Number: Rev:

AH-PMP-1DA & AH-1DA Operator's Manual

IMPORTANT SAFETY INSTRUCTIONS

Revision 1.2d

Wall-/Pipe-Mount Level Indicator

FRQM-2 Frequency Counter & RF Multimeter

VARIABLE SPEED USER MANUAL. Premium Efficiency Variable Speed Motor

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B

APM CALIBRATION PROCEDURE Rev. A June 3, 2015

C200H-AD002/DA002 Analog I/O Units Operation Guide

CELLO SETUP WITH WinGPS CelloSetup_WinGPS(15.9).doc September 17, Contents

Click Here To Start Demo

Exercise 5. Troubleshooting a QAM/DQAM Modem EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Signal flow tracing

Product Manual MNX10015 / REV C MODEL SB142, SB242. Dual Output Series Switch Boxes

ISC202 Quick Start Guide

MITSUBISHI ELECTRONICS AMERICA, INC.

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

GWL/ Power Group Technology Solutions Stay Powered for the Future

K3NX Process Meter OPERATION MANUAL

CDV07. Analog video distribution amplifier(s)

Junior Max (JR Max ) Controller

Operating Instructions

PQ-Box 100 Quick Start Instructions

RD RACK MOUNT DIMMER OWNERS MANUAL VERSION /09/2011

1440/2880 HP RGB+WW+CW

Application Notes on the ClearOne Beamforming Microphone Array

Introduction Display...1 Mounting...1 Firmware Version...2. ADL Operation... 3

USER MANUAL. 27" 2K QHD LED Monitor L27HAS2K

This document is a reference document that shows the menus in the 5500sc, 9610sc and 9611sc analyzers. There are 3 top-level menus:

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

A6 OPERATING INSTRUCTIONS

DISTRIBUTION AMPLIFIER

APOLLO DESIGN TECHNOLOGY 4130 Fourier Drive Fort Wayne, IN USA Phone: Fax:

SquareLED - Aura Bar & Matrix Beam Light 100

User interface. Abbreviations / Meanings

DSIM-GI Installation Guide Revision P

MOTION CONTROL SYSTEMS, MSC SERIES AUGUST 1998 EFC-240X ENCODER/FIBER OPTIC CONVERTER INSTRUCTION BOOK

User Manual. Digital Storage Oscilloscopes Models 2534, 2540 & General Safety Summary. Version 1.03

Transcription:

Page 1 of 14 Purpose: The purpose of this document is to formally release the SONARtrac TM Troubleshooting. The guide lists problems that may be encountered by personnel installing SONARtrac TM meters as well as actions to take to correct the problems. In the case where all troubleshooting techniques have been utilized, but the unit is still not working properly, please call CIDRA Technical Support at 203-626-3405 or after working hours call Pager # 203-766-4086. The guide will be incorporated into the next manual release. Contents Page# System Faults 2 Flow Meter Faults 8 GVF Meter Faults 13 Priority Code: 1 Safety issue or system will not function 2 Intermittent problem causing system crash 3 Erratic data/readings 4 Added product feature 5 Product enhancement CiDRA Corporation 50 Barnes Park rth Wallingford, CT 06492 Tel. 203-265-0035 Fax. 203-294-4211 www.cidra.com 2006, CiDRA Corporation, All rights reserved.

Page 2 of 14 System Faults: 1 System does not come on or was working and stopped working POSSIBLE CAUSE power to system Check input power with volt meter Check status of fuse(s) Is the green LED lit RESULT Yes - there is power and power is within system specs of 100-240 volt AC and 16 36 volt DC - power to system or power is below spec Fuse(s) bad Fuse(s) good Yes See Below Verify if there is power to Troubleshoot per item 1 system Yes Check external wiring / circuit breakers, etc. to ensure power and that power is within spec Connect to alternate power source Replace fuse(s) and see if blown fuse fault recurs. If problem recurs contact CiDRA Technical. Support. There is power to system but still does not come on Contact There is no power to the LED Contact 2 Screen is blank Screen is not working Screen is located in an area outside of the Is the ambient temperature Yes temperature specifications. below or above the Relocate transmitter. operating range of the screen (-20ºC to +85)? Are system signal outputs Yes continue to use Possible damaged or faulty screen. (4-20 ma, etc) in operation system with DCS output Contact and functional Contact

Page 3 of 14 System Faults: POSSIBLE CAUSE RESULT 3 The display has random lines or makes no sense BOOT and / or MAIN software is corrupt Display shows lines or random characters --- Contact 4 System keeps turning on and off Low or dirty power to system Poor connections at Power Input terminal block in transmitter Verify power source for transmitter is stable and within operating range of system Verify power connections to transmitter Power fluctuates Power is good and stable at between 100 240 volt AC or 18 36 volt DC Wire(s) not properly installed Wires installed properly Connect to stable power source Reconnect power cable Problem may be internal to transmitter. Contact 5 The system keeps rebooting on its own Poor power source for system System memory error or problem Verify power source for transmitter is stable and acceptable Run RAM TEST and DPRAM TEST in SELF TEST in S menu Power fluctuates Power is good and stable at between 100 240 volt AC or 18 36 volt DC Fail either or both RAM and DPRAM test Pass both RAM and DPRAM tests Connect to stable power source Faulty RAM/DPRAM. Contact contact

Page 4 of 14 System Faults: POSSIBLE CAUSE RESULT 6 Screen is light or dark in color Incorrect screen contrast setting Check screen setting in DISPLAY / CONTRAST in CUSTOMIZE menu. rmal setting is 170 the contrast setting is not 170 Yes contrast is set to 170 Adjust contrast setting up or down as necessary. If problem persists contact Try adjusting contrast. If this does not work contact Verify 4-20mA is wired to proper connector terminals in the transmitter (internal or external power) system is not connected to appropriate terminals yes Reconnect wires; refer to section 8 of Transmitter Installation Manual Incorrect wiring 7 The 4 20mA input on plant data system does not work Verify POWER SEL on 4-20mA CH1 (or 2) in OUTPUT CONFIG menu (internal or external) is set to correspond with the wiring option above incorrect Power Sel option. Yes Correct output option Broken lead between transmitter and plant data system or faulty 4-20mA supply Verify 4-20mA output on transmitter and at data system Select 4-20mA TEST under the menu to output discrete 4 through 20 ma signals. Yes, output from transmitter and input to plant system signal at plant data system signal from transmitter Wiring is good Suspect wiring problem Suspect faulty 4-20mA output. Acquire Snapshot, Upload to secure Website, and contact CiDRA Technical Support.

Page 5 of 14 System Faults: POSSIBLE CAUSE RESULT Wrong Range settings at transmitter or DCS Verify the range setting are the same Yes - Ranges of transmitter and DCS are the same range setting are different if problem persists Re-range the DCS or the transmitter 8 The 4 20mA display in control room does not match the flow rate on the meter The transmitter output trim needs to be adjusted Signal is being affected by PLC card Scroll to 4mA TRIM in the 4-20 ma CH 1(2) submenu under the OUTPUT CONFIG menu in order to access trim function. Press ENTER and follow instructions Disconnect input signal lines from PLC card. Connect current meter to leads. Output discrete ma signals using 4-20mA TEST under the menu. Yes the output is correct the output needs to be adjusted Yes the current meter readings match the transmitter output values the current readings do not match the transmitter values Input values per transmitter screen values. If problem persists see below A 4-20mA signal isolator may be required. Contact The 4-20mA values generated by the transmitter in 4-20mA Test do not match the signals seen at the end of the signal cable Connect current meter at the 4-20mA terminals in the transmitter and output discrete signals using 4-20mA Test Yes - The signals output from the transmitter match the current meter readings the output from the meter dos not match the current meter readings Plant wiring may have a problem. Verify integrity of signal wires. Contact

Page 6 of 14 System Faults: POSSIBLE CAUSE RESULT 9 The Display is Frozen (reads same value all the time) Transmitter left in Idle Mode Is Heart Beat Indicator Turning in Lower Right Corner Yes Heart Beat Indicator is Turning - Heart Beat Indicator is not turning Yes Display updates contact Cycle power to transmitter Meter is properly functioning Transmitter is hung up Cycle power to transmitter. Does the display update? Display is still frozen contact 10 The Display Reads Preamp Failure and there is no flow reading Possible faulty Preamp or bad connection Verify wiring and connectors are properly connected wiring / connector fault found Yes all wiring and connectors is correct Correct fault contact

Page 7 of 14 System Faults: POSSIBLE CAUSE RESULT 11 The display reads Invalid Mode Improper Op Mode selected or Display Settings selected Under Basic Menu, Verify Op Mode is set to FLOW for Flow Meter or GVF/SOS for Entrained Air Meter or FLOW/GVF/SOS for combined meter operation Under Customize Menu verify Display Line 1 set to Flow Rate for Flow Meter or GVF for Entrained Air Meter, etc Op Mode is not set to VF for Flow Meter or GVF for Entrained Air Meter Yes proper operating mode is selected Display Line 1 is not set to Flow Rate for Flow Meter or GVF for Entrained Air Meter,. Yes display is set correctly Reset to proper operating mode Change Display line 1 to appropriate mode contact 12 The signal output from the SONARtrac TM meter is noisy Need to use Damping or ise Reduction Filter See Filter Section of manual for more information on filtering Yes with filtering enabled, the signal is less noisy with filtering enabled, the signal is still noisy Employ filtering at the transmitter or at the DCS contact

Page 8 of 14 Flow Meter Faults POSSIBLE CAUSE RESULT 13 The signal output from the meter has spikes when the Flow starts or stops Need to use Spike Filter See Filter section of Manual in order to turn on filtering Yes With filtering Enabled, signal is less noisy With filtering enabled, signal is still noisy Use this as new transmitter configuration contact Improper pipe size entered Verify pipe size input in transmitter PIPE SIZE in BASIC CONFIG menu Yes correct size entered incorrect pipe size entered Re-enter correct pipe size 14 Flow does not seem correct Improper calibration coefficients entered Verify coefficients in transmitter CALIBRATION in BASIC CONFIG menu match sensor band coefficients (on label in transmitter or on sensor band cable) Yes correct values entered incorrect values entered Yes all sensors are on Re-enter correct coefficients All sensors are not turned on Verify sensors are turned on in SENSOR SETUP / ENABLE in CUSTOMIZE menu some or all are turned Off Turn on all sensors in Customize menu unless some were purposely turned off. If problem persists, Acquire Snapshot, Upload to secure Website, and contact CiDRA Technical Support.

Page 9 of 14 Flow Meter Faults POSSIBLE CAUSE RESULT Yes passes all tests Sensor to transmitter wiring may be faulty Run SENSOR CHECK in S menu fails one or more tests Verify and correct fault indicated on screen. If problem persists, Acquire Snapshot, Upload to secure Website, and contact CiDRA Technical Support. One or more sensors may be faulty Run SENSOR MAX/MIN in INFO menu Yes all sensors are within 30% of each other (process must be flowing at nominal flow rate) 14 Flow does not seem correct one or more sensors vary from the others by >30% Potential sensor failure. contact Incorrect viscosity or density settings Verify correct settings in BASIC CONFIG menu Yes the proper settings are input - the settings are not correct Correct inputs in BASIC CONFIG menu System is in Initialize Mode Is the system Heartbeat (indicated by a spinning \I/- ) on bottom right of screen active Yes System is operational and communicating with DSP. The system is designed to reset automatically after 30 minutes. If reset does not occur, cycle power to system. If this recurs, contact

Page 10 of 14 Flow Meter Faults 14 15 Flow does not seem correct The flow rate displayed is a series of dashes ( ------ ) POSSIBLE CAUSE A cable connection between the sensor and transmitter is cut or disconnected System Quality Metric is below set point Sensors are saturating Run SENSOR CHECK under menu RESULT Pass Fail Value is equal to or greater than 0.2 consistently The default value of VQ (if displayed on the transmitter front panel) is 0.2. Value is less than 0.2 Go to EVENT LOG in INFO menu and press ENTER Yes - A message of Sensor Over will be present if a sensor has been saturated message for Sensor Over This indicates all sensors are good and functional. 1. Verify wire connections in transmitter are all good. 2. Verify cable is not cut or damaged. 3. Verify cable connector on sensor head is connected. 4. Remove sensor head access panel per Installation Manual and ensure sensor to preamplifier connector is properly connected. 5. If system does not function, acquire Snapshot, upload to secure Website, and contact CiDRA Technical Support. Indicates system is above minimum threshold for making a reading Indicates system is below minimum threshold to make a reading. contact 1. Go to GAIN on S menu. 2. Press ENTER and scroll to AUTOSET GAIN and press ENTER 3. GAIN will be adjusted to proper level

Page 11 of 14 Flow Meter Faults POSSIBLE CAUSE RESULT 15 The flow rate displayed is a series of dashes ( ------ ) Undefined Process operating flow is less than the system programmed minimum flow setting Take s SNAPSHOT using StBasic or SONARstick Is the process flow rate < 3 ft/sec Post on secure Web site in Technical Support area Yes Contact CiDRA Technical Support. System normal specification is a low flow cutoff of 3 ft/sec Acquire Snapshot, Upload to secure Website, and contact 16 The flow rate displayed is > max flow Process operating flow is greater than the system programmed maximum flow setting Is the process flow rate > 30 ft/sec Yes System normal specification is a maximum flow cutoff of 30 ft/sec Acquire Snapshot, Upload to secure Website, and contact Sensors are saturating Select and run AUTOSET GAIN found in GAIN submenu of S menu Yes -The reading is less erratic. The reading is still erratic Use this as new transmitter configuration Acquire Snapshot, Upload to secure Website, and contact 17 The Flow Reading is erratic The flow is at or below min flow rate of the system Select LOW END under FLOW CUTOFF RANGE submenu of CUSTOMIZE menu and determine if that value is zero Yes the value is set to zero the value is not set to zero The operation may be outside the measurement capability of the meter. Contact CiDRA Technical Support. Lower the low end cutoff.

Page 12 of 14 Flow Meter Faults POSSIBLE CAUSE RESULT 18 The Flow Reading is erratic The meter is mounted too close to an elbow or obstruction If possible move meter to a straight run of process pipe. Yes The reading is less erratic The reading is still erratic. Acquire Snapshot, Upload to secure Website, and contact

Page 13 of 14 GVF Meter Faults: POSSIBLE CAUSE RESULT 19 The GVF Meter Displays dashes ----- The acoustics at the measurement location are too low Contact CiDRA Technical Support. 20 The GVF Reading is erratic Signals may be saturated Select and run AUTOSET GAIN found in GAIN submenu of S menu Yes this corrected the problem the problem persists Take Snapshot and send to Take Snapshot and send to 21 The GVF Meter always reads 50% GVF or some other value that is not correct Transmitter setup parameters are incorrect Verify setup parameters to ensure they are correct Yes the setup parameters are correct Yes the setup parameters are correct but the GVF is definitely incorrect the setup parameters are not correct The actual GVF of the fluid is >50% or what is indicated on the transmitter Take Snapshot and send to Correct transmitter input parameters in BASIC CONFIG menu

Date Revisio Changed By ECO # Description of Change n 11/20/06 01 R. Markoja E06-0104 Initial Release Page 14 of 14 Priority Code: 1 Safety issue or system will not function 2 Intermittent problem causing system crash 3 Erratic data/readings 4 Added product feature 5 Product enhancement CiDRA Corporation 50 Barnes Park rth Wallingford, CT 06492 Tel. 203-265-0035 Fax. 203-294-4211 www.cidra.com 2006, CiDRA Corporation, All rights reserved.