Operating Instructions VEGAMET ma/hart signal conditioning instrument

Size: px
Start display at page:

Download "Operating Instructions VEGAMET ma/hart signal conditioning instrument"

Transcription

1 Operating Instructions VEGAMET ma/hart signal conditioning instrument Document ID: Signal conditioning instruments and communication

2 Contents Contents 1 About this document 1.1 Function Target group Symbolism used For your safety 2.1 Authorised personnel Appropriate use Warning about misuse General safety instructions Safety label on the instrument CE conformity Safety instructions for Ex areas Overfill protection according to WHG Environmental instructions Product description 3.1 Configuration Principle of operation Operation Packaging, transport and storage Mounting 4.1 General instructions Mounting instructions Connecting to power supply 5.1 Preparing the connection Connection procedure Wiring plan Setup with the integrated indicating and adjustment unit 6.1 Adjustment system Setup procedure Menu schematic Setup with PACTware 7.1 Connecting the PC Parameter adjustment with PACTware Setup web server/ , remote enquiry Application examples 8.1 Level measurement in a cylindrical tank with overfill protection/dry run protection Pump control 1/2 (running time controlled) Pump control 3/4 (sequentially controlled) Tendency recognition Flow measurement VEGAMET ma/hart signal conditioning instrument

3 Contents 9 Maintenance and fault rectification 9.1 Maintenance Rectify malfunctions Instrument repair Dismount 10.1 Dismounting steps Disposal Supplement 11.1 Technical data Overview applications/functionality Supplementary documentation Information: Supplementary documents appropriate to the ordered version come with the delivery. You can find them listed in chapter "Product description". VEGAMET ma/hart signal conditioning instrument 3

4 1 About this document 1 About this document 1.1 Function This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device. 1.2 Target group This operating instructions manual is directed to trained qualified personnel. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information. Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result. Ex applications This symbol indicates special instructions for Ex applications. l List The dot set in front indicates a list with no implied sequence. Action This arrow indicates a single action. 1 Sequence Numbers set in front indicate successive steps in a procedure. 4 VEGAMET ma/hart signal conditioning instrument

5 2 For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use VEGAMET 391 is a universal signal conditioning instrument and power supply unit for connection of a 4 20 ma/hart sensor. You can find detailed information on the application range in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions. For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden. 2.3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g. vessel overfill or damage to system components through incorrect mounting or adjustment. 2.4 General safety instructions This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the countryspecific installation standards as well as all prevailing safety regulations and accident prevention rules. The instrument must only be operated in a technically flawless and reliable condition. The operator is responsible for trouble-free operation of the instrument. During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations. VEGAMET ma/hart signal conditioning instrument 5

6 2 For your safety 2.5 Safety label on the instrument The safety approval markings and safety tips on the device must be observed. 2.6 CE conformity This device fulfills the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a confirmation of successful testing. You can find the CE conformity declaration in the download area of Safety instructions for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments. 2.8 Overfill protection according to WHG In Germany the WHG (Water Resource Act) stipulates an overfill protection for systems that deal with substances hazardous to water. An appropriately certified sensor is the prerequisite for such protection. The VEGAMET 391 fulfils the construction and testing principles for overfill protection systems. This is certified by the TÜV (Technical Control Board) statement "PP 5003/09". You can download this document from our homepage under "Downloads - Approvals - Signal conditioning instruments - Overfill protection". 2.9 Environmental instructions Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment management system is certified according to DIN EN ISO Please help us fulfil this obligation by observing the environmental instructions in this manual: l Chapter "Packaging, transport and storage" l Chapter "Disposal" 6 VEGAMET ma/hart signal conditioning instrument

7 3 Product description 3 Product description 3.1 Configuration Scope of delivery The scope of delivery encompasses: l VEGAMET 391 signal conditioning instrument l Two clamping elements for panel mounting l Ex separating wall l Mini-USB cable l RS232 modem connection cable (optional) l Documentation - this operating instructions manual - Supplementary instruction "RS232/Ethernet connection" (optional) - Supplementary instructions manual "Modbus-TCP, ASCII protocol" (optional) - Ex-specific "Safety instructions" (with Ex-version) - if necessary, further certificates Components VEGAMET on ESC OK 5 4 Fig. 1: VEGAMET Ex separating wall 2 Clamping element for panel mounting 3 Indicating and adjustment unit 4 RS232 or Ethernet interface (optional) 5 USB interface Type label The type label contains the most important data for identification and use of the instrument: l Article number l Serial number l Technical data l Article numbers, documentation VEGAMET ma/hart signal conditioning instrument 7

8 3 Product description The serial number allows you to access the delivery data of the instrument via "VEGA Tools" and "serial number search". 3.2 Principle of operation Application area VEGAMET 391 is a universal signal conditioning instrument for a number of applications such as level, gauge and process pressure measurement. At the same time, it can serve as power supply unit for connected sensors. VEGAMET 391 is designed for connection of any 4 20 ma/hart sensor. On instruments with one of the optional interfaces (RS232/Ethernet), the measured values can be retrieved via modem or network and displayed by means of a web browser or WEB-VV. It is also possible to send measured values and messages via /sms. The use of VEGAMET 391 is particularly suitable for stocktaking, VMI (Vendor Managed Inventory) and remote enquiry. Functional principle Power supply The VEGAMET 391 signal conditioning instrument can power the connected sensor and process its measurement signals. The requested parameter is shown on the display and also outputted to the integrated current output for further processing. The measurement signal can thus be transferred to a remote indication or a superordinate control system. Six level relays for control of pumps or other devices are also integrated. Wide-range power supply unit with V AC/DC for world-wide use. Detailed information about the power supply can be found in chapter "Technical data". 3.3 Operation The instrument can be adjusted with the following adjustment media: l With integrated indicating and adjustment unit l an adjustment software according to FDT/DTM standard, e.g. PACTware and a Windows PC The entered parameters are generally saved in VEGAMET 391, when used with PACTware and PC optionally also on the PC. Information: When using PACTware and the respective DTM, additional settings can be carried out which are not possible or only partly possible with the integrated indicating and adjustment unit. Communication is carried out via the integrated USB interface or one of the optional interfaces (RS232/Ethernet). 8 VEGAMET ma/hart signal conditioning instrument

9 3 Product description Further instructions for setting up the web server and functions are stated in the online help of PACTware or the VEGAMET 391 DTMs as well as the operating instructions manual "RS232/Ethernet connection". 3.4 Packaging, transport and storage Packaging Transport Transport inspection Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN The packaging of standard instruments consists of environmentfriendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies. Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device. The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with. Storage Storage and transport temperature Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside. Unless otherwise indicated, the packages must be stored only under the following conditions: l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration l Storage and transport temperature see chapter "Supplement - Technical data - Ambient conditions" l Relative humidity % VEGAMET ma/hart signal conditioning instrument 9

10 Mounting 4 Mounting 4.1 General instructions Installation possibilities The instrument is designed for recessed installation in a front panel, housing front plate or a switching cabinet door. The required cut-out is 92 x 92 mm according to EN When installed correctly, protection rating IP 65 is guaranteed. As an alternative, the instrument can be mounted into a switching cabinet or housing by means of four screws (fixed with screws on rear of housing). A VEGAMET 391 in Ex version is an auxiliary, intrinsically safe instrument and may not be installed in explosion-endangered areas. Before setup, the Ex separating wall must be attached with Ex versions. Safe operation can be only ensured if the operating instructions manual and the EG type approval certificate are observed. VEGAMET 391 must not be opened. 4.2 Mounting instructions Front panel mounting 1 Check the correct hold of the seal directly behind the front plate and shift the instrument from the front into the front panel cut-out. 2 Shift the two tensioning elements into the provided gaps. 3 Screw in the two screws of the tensioning elements steadily with a screwdriver on ESC OK Fig. 2: Front panel mounting 1 Front panel, front plate or switching cabinet door 2 Tensioning elements 3 Slotted screw 10 VEGAMET ma/hart signal conditioning instrument

11 4 Mounting Screw mounting Fasten the instrument by means of four screws (max. ø 4 mm) on the rear of teh housing or the mounting plate according to the following illustration. 1 86,5 mm (3.41") 73 mm (2.87") 2 Fig. 3: Screw mounting 1 Fixing screws 2 Rear of the housing or mounting plate VEGAMET ma/hart signal conditioning instrument 11

12 5 Connecting to power supply 5 Connecting to power supply 5.1 Preparing the connection Note safety instructions Always keep in mind the following safety instructions: l Connect only in the complete absence of line voltage l If overvoltages are expected, install overvoltage arresters Take note of safety instructions for Ex applications Select power supply Selecting connection cable Cable screening and grounding In hazardous areas you should take note of the appropriate regulations, conformity and type approval certificates of the sensors and power supply units. The voltage supply can be V AC/DC, 50/60 Hz. The operating voltage of VEGAMET 391 is connected with standard cable according to the national installation standards. Standard two-wire cable can be used for connecting the sensors. The screening is absolutely necessary to ensure interference-free operation with HART sensors. Connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the sensor housing must be connected to the potential equalisation (low impedance). If potential equalisation currents are expected, the screen connection on the side of VEGAMET 391 must be made via a ceramic capacitor (e. g. 1 nf, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective effect against high frequency interference signals remains. Select connection cable for Ex applications Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equalisation currents flow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation. 5.2 Connection procedure Move on to electrical connection and proceed as follows: 1 Mount the instrument as described in the previous chapter 2 Remove terminal strip 1 on the upper side of the instrument 3 Connect sensor cable to terminal 1/2 (active input) or 5/6 (passive input) 4 If necessary, connect digital inputs to Plug terminal strip 1 to the upper side of the instrument 6 Remove terminal strip 2 on the lower side of the instrument 12 VEGAMET ma/hart signal conditioning instrument

13 5 Connecting to power supply 7 Connect power supply (switched off) to terminal 13/14 8 If necessary, connect relays or other outputs 9 Plug in terminal strip 2 on the lower side of the instrument 10 For connection of additional relais to terminal strip 3, you have to proceed as described before The electrical connection is finished. Remember that with Ex applications, the Ex separating wall must be plugged onto the upper side of the instrument before setup. Information: l On the active input (terminal 1/2), VEGAMET 391 provides power for the connected sensors. Power supply and measurement data are transmitted over the same two-wire cable. This mode is provided for connection of measuring transducers without separate operating voltage (sensors in two-wire version). l On the passive input (terminals 5/6), the sensors are not supplied with energy - only the measured value is transmitted. This input is for sensors with their own separate operating voltage (sensors in four-wire version). On a VEGAMET 391 in Ex version, the passive input is not available due to approval/technical reasons. VEGAMET ma/hart signal conditioning instrument 13

14 5 Connecting to power supply Wiring plan for two-wire sensor 5.3 Wiring plan on ESC OK N- - + L Fig. 4: Terminal assignment with two-wire sensor 1 Operating relay 1 2 Operating relay 2 3 Operating relay 3 4 Operating relay 4 5 Operating relay 5 6 Operating relay 6 7 Current output 8 Operating voltage of the signal conditioning instrument 9 Measurement data input with sensor supply (active input) 10 Connection for HART modem for sensor parameter adjustment 11 Measurement data input (passive input), not with Ex-ia version 12 Digital input Common ground for digital input ma/hart sensor (two-wire version) 14 VEGAMET ma/hart signal conditioning instrument

15 5 Connecting to power supply Wiring plan for four-wire sensor on ESC OK N- - + L Fig. 5: Terminal assignment with four-wire sensor 1 Operating relay 1 2 Operating relay 2 3 Operating relay 3 4 Operating relay 4 5 Operating relay 5 6 Operating relay 6 7 Current output 8 Operating voltage of the signal conditioning instrument 9 Measurement data input with sensor supply (active input) 10 Connection for HART modem for sensor parameter adjustment 11 Measurement data input (passive input), not with Ex-ia version 12 Digital input Common ground for digital input ma/hart sensor (four-wire version) 15 Power supply for four-wire sensor VEGAMET ma/hart signal conditioning instrument 15

16 6 Setup with the integrated indicating and adjustment unit 6 Setup with the integrated indicating and adjustment unit 6.1 Adjustment system Function The integrated indicating and adjustment unit is used for measured value display, adjustment and diagnosis of VEGAMET 391. The indication and adjustment are carried out via four keys and a clear, graphic-capable display with background lighting. The adjustment menu with selectable language is clearly structured and enables easy setup. Certain adjustment options are not available or only partially available with the integrated indicating and adjustment unit, e.g. the settings for flow measurement. For such applications, the use of PACTware with appropriate DTMs is recommended. Indicating and adjustment elements VEGAMET on ESC OK 2 Fig. 6: Indicating and adjustment elements 1 LC display 2 Adjustment keys 3 Status indication operation 4 Status indication fail safe relay 5 Status indication operating relay 1 6 Key functions l [OK] key: - Move to the menu overview - Confirm selected menu - Edit parameter - Save value l [->] key to select: - menu change - list entry - Select editing position 16 VEGAMET ma/hart signal conditioning instrument

17 6 Setup with the integrated indicating and adjustment unit l [+] key: - Change value of the parameter l [ESC] key: - interrupt input - jump to the next higher menu Note: Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. 6.2 Setup procedure Parameter adjustment Through parameter adjustment, the instrument is adapted to the individual application conditions. Calibration of the measuring point is the most important step and should always be carried out. A scaling of the measured value to the desired physical variable and unit, possibly including a linearization curve, is often useful. The adaptation of the relay switching points or the setting of an integration time to smooth the measured value are further standard adjustment options. For instruments with Ethernet interface, the instrument must be provided with an IP address and subnet mask suitable for the instrument. As an alternative, addressing via DHCP and a host name is also possible. If necessary, the /webserver can be also configured with PACTware. A setup assistant is available for easy, convenient setup. It guides the user through the standard applications and settings step by step. Information: When using PACTware and the respective DTM, additional settings can be carried out which are not possible or only partly possible with the integrated indicating and adjustment unit. Communication is carried out via the integrated USB interface or one of the optional interfaces (RS232/Ethernet). Further instructions for setting up the web server and functions are stated in the online help of PACTware or the VEGAMET 391 DTMs as well as the supplementary instructions manual "RS232/Ethernet connection". Switch on phase After being switched on, VEGAMET 391 first of all carries out a short self-check. The following steps are carried out: l Internal check of the electronics l indication of the instrument type, firmware version as well as the instrument TAG (instrument name) l The output signals jump briefly to the set fault value VEGAMET ma/hart signal conditioning instrument 17

18 6 Setup with the integrated indicating and adjustment unit Then the current measured values will be displayed and outputted. Measured value indication The measured value indication shows the digital indication value, the measurement loop designation (measurement loop TAG) and the unit. An analogue bar graph can also be blended in. If flow measurement is activated, an additional indication window with totalizer is available. By pushing the [>] key you can move between the different indication options. By pushing [OK], you move from the measured value indication into the main menu. Here, you have the choice between the setup assistant for the most important settings or the complete classical menu. Main menu/setup assistant At the beginning of every setup or parameter adjustment, you have the choice of continuing with the setup assistant or the classic menu guidance. We recommend using the setup assistant for the initial setup. If later on individual settings should be corrected or added, the most expedient way to do this is via the classic menus. Select the menu item "Setup assistant" with [->] and confirm with [OK]. Setup assistant The setup assistant leads you step-by-step throught the standard settings. All steps must be passed completely, it is not possible to interrupt the procedure. Following the individiual steps which can be passed through with the assistant: l Device-TAG (individually adjustable instrument name) l Measurement loop TAG (individually adjustable measurement loop designation) l Type of input (4 20 ma or HART) l Measured variable (for example level or process pressure) l Adjustment unit (for example m or bar) l Min./Max. adjustment l Activation of the fail safe relay l Configuration of the relay outputs (e.g. setup of pump control or overfill protection) l Adjustment date/time l Network settings with option "Ethernet interface" 18 VEGAMET ma/hart signal conditioning instrument

19 6 Setup with the integrated indicating and adjustment unit When changing the measurement, the assistant can be opened any time. The subsequent steps can be also reached via the classical menu guidance. The description of the individual menu items is available in the classical menu guidance. In chapter "Application examples" you will find further information to the setup. Classical menu guidance/main menu The main menu is split into six areas with the following functions: l Device settings: Includes the device-tag, settings for network connection such as date/time setting, l Measurement loop: Includes settings for input selection, adjustment, damping, linearization, scaling, outputs, l Display: Includes settings to the displayed measured value, languafe setting und brightness of the background lighting l Diagnosis Includes information to the device status, error messages, input current, digital inputs l Further settings: Includes simulation, reset, PIN, sensor address, l Info: Shows serial number, software version, last change, instrument features, MAC addr., Select the requested menu item via the respective keys and confirm with [OK]. Device settings - Device- TAG You can assign an unambiguous name to VEGAMET 391 via the Device-TAG. This function is recommended when several instruments are implemented and a good documentation of larger systems is required. Carry out your settings via the respective keys and save with [OK]. Device settings - Host Name/IP addr. For instruments with Ethernet interface, the instrument must be provided with an IP address/subnet mask suitable for your network. Depending on the network, the adjustment of a gateway address is also necessary. As an alternative, addressing via DHCP and a host name is also possible. These specifications are available from your network administrator. Keep in mind that your settings are only effective after a restart of VEGAMET 391. Further information to these network parameters is available in the supplementary instructions manual "RS232/Ethernet connection" and in the online help of the corresponding DTMs. VEGAMET ma/hart signal conditioning instrument 19

20 6 Setup with the integrated indicating and adjustment unit Carry out your settings via the respective keys and save with [OK]. Carry out your settings via the appropriate keys and save with [OK]. Disconnect briefly the operating voltage so that the modified settings become effective. Device settings - Communication protocol For instruments with optional RS232 interface, you determine here which mode this serial interface should operate in. The following options are available: l VVO protocol: Direct standard connection between signal conditioning instrument and PC for parameter adjustment and enquiry (e.g. with PACTware and DTM) l PPP: Dial-up connection between signal conditioning instrument and modem for independent transmission of s (dial-out connection) or enquiry via web browser (dial-in connection) l ASCII protocol: Direct standard connection between signal conditioning instrument and PC for enquiry with terminal programs, e.g. Hyperterminal Carry out your settings via the respective keys and save with [OK]. Further information is available in the supplementary instructions manual "RS232/Ethernet connection" and the online help of the respective DTM. Device settings - Date/ Time For instruments with built-in RS232/Ethernet interface, you can enter in this menu item the date and time. In case of power loss, these time settings are backed up for a period of up to 10 years by a capacitor as well as a battery. Carry out your settings via the respective keys and save with [OK]. 20 VEGAMET ma/hart signal conditioning instrument

21 6 Setup with the integrated indicating and adjustment unit Measurement loop - Input The signal conditioning instrument can process the VEGAMET 391 can process measured values from 4 20 ma/hart sensors via analogue communication as well as via digital HART protocol. Analogue 4 20 ma transmission In the standard setting of VEGAMET 391 the measured value transmission is carried out via analogue 4 20 signal. An adjustment in the sensor influences directly the input variable of VEGAMET 391. Only carry out the adjustment on one instrument, either on VEGAMET 391 or on the sensor. The adjustment in VEGAMET 391 is always carried out in ma (analogue transmission). Digital HART transmission For transmission via HART, VEGAMET 391 must be informed which sensor value should be used for further processing. Depending on the sensor type, this can be distance, pressure or temperature. With all HART sensors, always the unchanged initial value of the sensor is transmitted to VEGAMET 391. Thus, the adjustment must always carried out on VEGAMET 391, never on the sensor. Different parameters and meas. units are available. When HART sensors from other manufacturers are connected, the options PV (Primary Value) and SV (Secondary Value) are available. The prerequisite for this is the support of the HART commands 0, 1, 3, and 15. This information and which measured values are transmitted can be found in the operating instructions manual of the respective sensor manufacturer. Carry out your settings via the respective keys and save with [OK]. Meas. loop - Parameter The measured variable defines the applicaton of the measurement loop, the following settings are available depending on the connected sensor: l Level l Process pressure l Universal l Temperature l Interface l Flow (only after activating via PACTware or DTM) Carry out your settings via the respective keys and save with [OK]. VEGAMET ma/hart signal conditioning instrument 21

22 6 Setup with the integrated indicating and adjustment unit Meas. loop - Adjustment Through the adjustment the input value of the connected sensor is converted into a percentage value. This conversion step allows any input value range to be depicted in a relative range (0 % up to 100 %). Before carrying out the adjustment, the requested adjustment unit can be selected. With the input selection "Analogue", the adjustment unit is always "ma". If the HART input is activated, the available unit depends on the sensor type. With radar, ultrasonic and guided microwave this is always "m(d)" or "ft(d)", and with pressure transmitters it is e.g. "bar" or "psi". The following illustrations and examples relate to the min./max. adjustment of a radar sensor with HART communication. With [OK] you prepare the percentage value for editing, with [->] you set the cursor to the requested position. Set the requested percentage value with [+] and save with [OK]. After entering the percentage value for the min. adjustment, the suitable distance value must be entered. If you want the use the currently measured distance value, select the menu item "Accept" (live adjustment or adjustment with medium). If the adjustment should be carried out independent of the measured level, then select the option "Edit". Enter now the distance value in m [m(d)] for the empty vessel that is suitable for the percentage value, e.g. distance from the sensor to the vessel bottom (dry adjustment or adjustment without medium). Save your settings with [OK] and move to "Max. adjustment" with [->]. As described previously, enter now the percentage value for max. adjustment and confirm with [OK]. After entering the percentage value for the max. adjustment, the suitable distance value must be entered. If you want the use the currently measured distance value, select the menu item "Accept" (live adjustment or adjustment with medium). If the adjustment should be carried out independent of the measured level, select the option "Edit". Enter now the distance value in m [m(d)] for the 22 VEGAMET ma/hart signal conditioning instrument

23 6 Setup with the integrated indicating and adjustment unit empty vessel that is suitable for the percentage value, e.g. distance from the sensor to the vessel bottom (dry adjustment or adjustment without medium). Keep in mind that the max. level must be below the radar antenna. Finally save your settings with [OK], the adjustment is finished. Meas. loop - Damping To suppress fluctuations in the measured value display, e.g. caused by an agitated product surface, an integration time can be set. This time can be between 0 and 999 seconds. Remember that the reaction time of the entire measurement will then be longer and the sensor will react to measured value changes with a delay. In general, a period of a few seconds is sufficient to smooth the measured value indication. Carry out your settings via the respective keys and save with [OK]. Meas. loop - Linearization curve A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level, e. g. with a cylindrical or spherical tank. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set. Carry out your settings via the respective keys and save with [OK]. Meas. loop - Scaling Scaling means converting the measured value into a certain parameter and unit. The linearized percentage value is the source signal which is used as basis for the scaling. The indication can then show the volume in litres e.g., instead of the percentage value. Indication values from max to are possible. Carry out your settings via the respective keys and save with [OK]. VEGAMET ma/hart signal conditioning instrument 23

24 6 Setup with the integrated indicating and adjustment unit Meas. loop - Meas. loop TAG In this menu item you can enter an unambiguous designation for each measurement loop, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular designation should be entered for exact identification of individual measurement points. Carry out your settings via the respective keys and save with [OK]. Meas. loop - Outputs - Relay outputs Under "Outputs", you find the relay outputs and the current output. With each relay output, first of all the requested mode ("Overfill protection/dry run protection" or "Pump control") must be selected. l Overfill protection: Relay is switched off when the max. level is exceeded (safe currentless condition), relay is switched on again when the level falls below the min. level (switch on point < switch off point) l Dry run protection: Relay is switched off when the level falls below the min. level (safe currentless condition), relay is switched on again when the max. level is exceeded (switch on point > switch off point) l Pump control: With several pumps having the same function, the pumps will be alternately switch on and off according to the adjustable criteria Additional modes such as "Switching window", "Flow" and "Tendency" can be only adjusted via PACTware and DTM. Relay 6 can be also configured as fail safe relay. The following example shows the adjustment of an overfill protection. Further information to pump control, tendency recognition or flow measurement are available in chapter "Application examples". Select the requested mode and save with [OK]. By pushing [->], you reach the next menu item. Now enter the reference value to which the relay switching points relate. By pushing [->], you reach the next menu item. 24 VEGAMET ma/hart signal conditioning instrument

25 6 Setup with the integrated indicating and adjustment unit Now enter the switching points for switching the relay on and off. In the following window the reaction of the relay in case of failure can be determined. Here you can define whether, in case of failure, the switching condition of the relay remains unchanged or the relay is switched off. Meas. loop - Outputs - Current output The current output is used to transfer the measured value to a superimposed system, for example to a PLC, a control system or a measured value indication. This is an active output, i.e. a current is provided actively. The processing must hence have a passive current input. The characteristics of the current output can be set to 0 20 ma, 4 20 ma or inverted. The reaction in case of failure can also be adapted to the requirements. The measured variable they refer to can also be selected. Carry out your settings via the respective keys and save with [OK]. Display - Displayed value In the menu item "Display - Indication value", you can set the requested indication value. The following options are available: l Percent: adjusted measured value without taking a probably stored linearization into account l Lin. percent: adjusted measured value including a possible linearization. VEGAMET ma/hart signal conditioning instrument 25

26 6 Setup with the integrated indicating and adjustment unit l Scaled: adjusted measured value by taking a probably stored linarization into account as well as the values entered under "Scaling" l Sensor value: Input value delivered by the sensor. The presentation is in the selected adjustment unit Carry out your settings via the respective keys and save with [OK]. Display - Language In the menu item "Display - Language" you can adjust the requested display language. The following languages are available: l Deutsch l English l French l Spanish l Russian l Italian l Dutch Carry out your settings via the respective keys and save with [OK]. Display - Brightness In the menu item "Display - Brightness" you can adjust the brightness of the background lighting. Carry out your settings via the respective keys and save with [OK]. Diagnostics If the instrument signals a fault, further information about the fault is available under the menu item "Diagnosis - Device status". In addition, the input current as well as the input status for the digital inputs can be displayed. 26 VEGAMET ma/hart signal conditioning instrument

27 6 Setup with the integrated indicating and adjustment unit Additional settings - Simulation The simulation of the measured value is used to check the outputs and connected components. It can be applied to the percentage value, the lin. percentage value and to the sensor value. Note: Please note that connected system parts (valves, pumps, motors, control systems) are influenced by the simulation, thus unintentional plant operating conditions can occur. The simulation is terminated automatically after approxminately 10 minutes. Carry out your settings via the respective keys and save with [OK]. Additional settings - Reset A reset to basic adjustment changes all settings (with only a few exceptions) back to factory default. Exceptions are: IP-addr., subnet mask, time, language. Additional settings - PIN The signal conditioning instrument can be locked with a PIN to protect the adjusted parameters against unauthorized modification. After activation, it is not possible to carry out a parameter adjustment via the built-in indicating and adjustment unit without entering the previously determined PIN. This locking does not apply to parameter adjustment with PACTware and the respective DTM. Additional settings - Sensor address With every 4 20 ma/hart sensor, the measured value can be transmitted via analog current signal or digital HART signal. This is regulated via the HART mode or the address. If a HART sensor is set to address 0, the sensor is in the standard mode. Here the measured value is transmitted digitally on the 4 20 ma cable. In mode HART Multidrop, an address from 1 15 is assigned to the sensor. By doing so, the current is fix limited to 4 ma and the measured value transmission is only made digitally. VEGAMET ma/hart signal conditioning instrument 27

28 6 Setup with the integrated indicating and adjustment unit Via the menu item "Sensor address", the address of the connected sensor can be modified. For this purpose, you have to enter the address of the connected sensor (default setting 0) and in the next window the new address. Info In the menu item "Info" the following information is available: l Sensor type and serial number l Date of manufacture and software version l Date of last change using PC l Features of VEGAMET 391 l MAC address (with interface option Ethernet) Optional settings Additional adjustment and diagnostics options are available via the Windows software PACTware and the suitable DTM. Connection can be made optionally via the built-in standard interface or one of the optionally offered interfaces (RS232/Ethernet). Further information is available in chapter "Parameter adjustment with PACTware", in the online help of PACTware or the DTM as well as in the operating instructions manual "RS232/Ethernet connection". An overview of the standard functions and their adjustment options can be found in chapter "Functional overview" in the "Supplement". 28 VEGAMET ma/hart signal conditioning instrument

29 6 Setup with the integrated indicating and adjustment unit 6.3 Menu schematic Information: Depending on the instrument version and application, the highlighted menu windows are not always available. Measured value indication Setup assistant VEGAMET ma/hart signal conditioning instrument 29

30 6 Setup with the integrated indicating and adjustment unit Device settings Measurement loop - Input Meas. loop - Parameter 30 VEGAMET ma/hart signal conditioning instrument

31 6 Setup with the integrated indicating and adjustment unit Meas. loop - Adjustment Meas. loop - Damping Meas. loop - Linearization curve VEGAMET ma/hart signal conditioning instrument 31

32 6 Setup with the integrated indicating and adjustment unit Meas. loop - Scaling Meas. loop - Meas. loop TAG Meas. loop - Outputs - Relay 32 VEGAMET ma/hart signal conditioning instrument

33 6 Setup with the integrated indicating and adjustment unit Meas. loop - Outputs - Current output Display Diagnostics VEGAMET ma/hart signal conditioning instrument 33

34 6 Setup with the integrated indicating and adjustment unit Additional settings - Simulation Additional settings - Reset Additional settings - PIN Additional settings - Change sensor address (only with option RS232/Ethernet interface) 34 VEGAMET ma/hart signal conditioning instrument

35 6 Setup with the integrated indicating and adjustment unit Info VEGAMET ma/hart signal conditioning instrument 35

36 7 Setup with PACTware 7 Setup with PACTware 7.1 Connecting the PC Connection of the PC via USB For a brief connection to the PC, for example for parameter adjustment, you should use the USB interface. The necessary connection socket is on the lower side of all instrument versions. Keep in mind that correct functioning of the USB interface is only guaranteed in the (limited) temperature range of 0 60 C. Note: The connection via USB requires a driver. First of all, install the driver before connecting VEGAMET 391 to the PC. The required USB driver is included on the CD "DTM Collection". You should always use the latest version to ensure support of all instrument functions. The system requirements for operation correspond to those of the "DTM Collection" or of PACTware. When installing the driver package "DTM for Communication", the suitable instrument driver is installed automatically. When connecting VEGAMET 391, the driver installation is finished automatically and is ready for operation without a restart Fig. 7: Connection of the PC via USB Connection of the PC via Ethernet With the Ethernet interface, the instrument can be connected directly to an existing PC network. Any standard patch cable can be used. A cross-over cable must be used when connecting the instrument directly to the PC. To reduce EMC interferences, the supplied split ferrite should be connected to the Ethernet cable. Each instrument then gets its own IP address under which it can be accessed from anywhere in the network. The parameter adjustment of the instrument via PACTware and DTM can be carried out from any PC. The measured values can be made available to individual users within the VEGAMET ma/hart signal conditioning instrument 36 USB interface of the PC Mini-USB connection cable (in the scope of delivery) USB interface of VEGAMET 391

37 7 Setup with PACTware company network as HTML chart. As an alternative, the independent, time or event-controlled transmission of measured values via is also possible. The measured values can also be called up via a visualisation software. Note: To contact the instrument, a corresponding IP address must be available in the instrument. Each instrument is preset to address Enter the address and subnet mask corresponding to your network directly via the keyboard. As an alternative, addressing is also possible via DHCP and a host name. Briefly interrupt the operating voltage after each modification, then the instrument is accessible via its IP address or host name everywhere in the network. In addition, these specifications must be entered in the DTM (see chapter "Parameter adjustment with PACTware") Fig. 8: Connection of the PC via Ethernet The RS232 interface is particularly suitable for easy modem connection. External analog, ISDN and GSM modems with standard interface can be used. The necessary RS232 modem connection cable is included with the delivery. To reduce EMC interference, you should mount the supplied ferrite bead on the RS232 modem connection cable. Via a visualisation software, measured values can be retrieved remotely and further processed. Alternatively, the autonomous time or event controlled transmission of measured values via is also possible. Remote parameter adjustment of the instrument and the connected sensors is also possible with PACTware. Connection of the modem via RS232 Ethernet interface of the PC Ethernet connection cable (Cross-Over cable) Ethernet interface VEGAMET ma/hart signal conditioning instrument 37

38 7 Setup with PACTware Fig. 9: Connection of the modem via RS Connection of the PC via RS232 Analogue, ISDN or GSM modem with RS232 interface RS232 modem connection cable (in the scope of delivery) RS232 interface Via the RS232 interface, direct parameter adjustment and measured value enquiry of the instrument can be carried out with PACTware. Use the RS232 modem connection cable supplied with the instrument and an additionally connected null modem cable (e.g. article no. LOG ). To reduce EMC interference, you should mount the supplied ferrite bead on the RS232 modem connection cable. If there is no RS232 interface available on the PC or if it is already occupied, you can also use a USB-RS232 adapter (e.g. article no ) Fig. 10: Connection of the PC via RS RS232 RS232 RS232 RS232 interface of the PC interlink cable (article no. LOG ) modem connection cable (in the scope of delivery) interface 38 VEGAMET ma/hart signal conditioning instrument

39 7 Setup with PACTware 7.2 Parameter adjustment with PACTware Prerequisites As an alternative to the integrated indicating and adjustment unit, the adjustment can be also carried out via a Windows PC. For this, the configuration software PACTware and a suitable instrument driver (DTM) according to the FDT standard are required. The actual PACTware version as well as all available DTMs are compiled in a DTM Collection. Furthermore, the DTMs can be integrated into other frame applications according to the FDT standard. Note: To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functions are included in older firmware versions. The latest instrument software can be also downloaded from our homepage. A description of the update procedure is also available in the Internet. Further setup steps are described in the operating instructions manual "DTM Collection/PACTware" attached to each DTM Collection and which can also be downloaded from the Internet. A detailed description is available in the online help of PACTware and the DTMs as well as in the supplementary instructions manual "RS232/Ethernet connection". Connection via USB When connecting via USB, the instrument serial number must be entered as address in the DTM during project setup without assistant (offline mode). To do this, click with the right mouse key in the project window on the USB-DTM and select "Additional functions - Change DTM addresses". Connection via Ethernet When connecting via Ethernet, VEGAMET 391 must be provided with a suitable IP address and subnet mask. If the project setup is carried out without assistant (online mode), IP address and subnet mask must be entered additionally in the DTM. Click in the project window with the right mouse key to the Ethernet DTM and choose "Add. functions - Modify DTM addresses". Standard/Full version All device DTMs are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistent for simple project configuration simplifies the adjustment considerably. Saving/printing the project as well as import/export functions are also part of the standard version. In the full version there is also an extended print function for complete project documentation as well as a save function for measured value and echo curves. In addition, there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves. VEGAMET ma/hart signal conditioning instrument 39

Operating Instructions VEGAMET ma/hart signal conditioning instrument

Operating Instructions VEGAMET ma/hart signal conditioning instrument Operating Instructions VEGAMET 391 4 20 ma/hart signal conditioning instrument Document ID: 36032 Signal conditioning instruments and communication Contents Contents 1 About this document 1.1 Function..................................

More information

Operating Instructions VEGAMET 625 Double channel HART signal conditioning instrument

Operating Instructions VEGAMET 625 Double channel HART signal conditioning instrument Operating Instructions VEGAMET 625 Double channel HART signal conditioning instrument Document ID: 28970 Signal conditioning instruments and communication Contents Contents 1 About this document 1.1 Function..................................

More information

Operating Instructions VEGAMET 625 Double channel Hart signal conditioning instrument

Operating Instructions VEGAMET 625 Double channel Hart signal conditioning instrument Operating Instructions VEGAMET 625 Double channel Hart signal conditioning instrument WE'VE GOT ABILITY in out Contents Contents 1 About this document 1.1 Function... 5 1.2 Target group... 5 1.3 Symbolism

More information

Operating Instructions 09/2013

Operating Instructions 09/2013 Guided Wave Radar SITRANS LG260 4 20 ma/hart two-wire Operating Instructions 09/2013 2 SITRANS LG260 - Operating Instructions PBD-51041057 Contents 1 About this document 1.1 Function... 5 1.2 Target group...

More information

Operating Instructions 09/2013

Operating Instructions 09/2013 Guided Wave Radar SITRANS LG250 4 20 ma/hart - two-wire Operating Instructions 09/2013 2 SITRANS LG250 - Operating Instructions PBD-51041047 Contents 1 About this document 1.1 Function... 5 1.2 Target

More information

Operating Instructions

Operating Instructions Operating Instructions LEVEL TRANSMITTER 8188 4 20 ma/hart two-wire Rod and cable probe 2 Contents Contents 1 About this document 1.1 Function... 4 1.2 Target group... 4 1.3 Symbols used... 4 2 For your

More information

Capacitance Level Measurement Electronic insert FEC 12

Capacitance Level Measurement Electronic insert FEC 12 Technical Information TI 50F/00/en Capacitance Level Measurement Electronic insert FEC Smart electronic inserts for Multicap probes DC..TE/TA and DC..E/A with HART protocol and integrated linearisation

More information

MS2540 Current Loop Receiver with RS485 Communication

MS2540 Current Loop Receiver with RS485 Communication MS2540 Current Loop Receiver with RS485 Communication User Manual Metal Samples Company A Division of Alabama Specialty Products, Inc. 152 Metal Samples Rd., Munford, AL 36268 Phone: (256) 358 4202 Fax:

More information

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids ma/hart - two-wire Rod and cable probe

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids ma/hart - two-wire Rod and cable probe Operating Instructions TDR sensor for continuous level and interface measurement of liquids VEGAFLEX 81 4 20 ma/hart - two-wire Rod and cable probe Document ID: 41824 2 Contents Contents 1 About this document...

More information

For installation queries contact Customer Services (0) TCR IP 4 Operating instructions

For installation queries contact Customer Services (0) TCR IP 4 Operating instructions For installation queries contact Customer Services +49 - (0)3 69 25-9 00 90 kundenservice@rutenbeck.de TCR IP 4 Operating instructions GB Device overview External buttons (for manual switching) Temperature

More information

Installation & Maintenance Instructions VEGAFLEX ma/hart - two-wire Rod and cable probe

Installation & Maintenance Instructions VEGAFLEX ma/hart - two-wire Rod and cable probe Installation & Maintenance Instructions VEGAFLEX 81 4 20 ma/hart - two-wire Rod and cable probe TDR sensor for continuous level and interface measurement of liquids Supplied by.com Call us on +44 (0)118

More information

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids. Profibus PA Rod and cable probe

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids. Profibus PA Rod and cable probe Operating Instructions TDR sensor for continuous level and interface measurement of liquids VEGAFLEX 81 Profibus PA Rod and cable probe Document ID: 44217 2 Contents Contents 1 About this document... 4

More information

Operating Instructions 09/2017

Operating Instructions 09/2017 Guided Wave Radar SITRANS LG250 4 20 ma/hart - two-wire Rod and cable probe With SIL qualification Operating Instructions 09/2017 2 SITRANS LG250 - Operating Instructions Contents 1 About this document...

More information

Signal conditioning instruments

Signal conditioning instruments Signal conditioning instruments Overview Page 242 VEGAMET Page 244 VEGASCAN Page 248 VEGASTAB Page 249 VEGATOR Page 250 ISO housing Page 258 Components Page 259 2 24 Signal conditioning instruments For

More information

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL www.prolight.co.uk TRANSCENSION 6-CHANNEL PACK (order code: BOTE40) USER MANUAL SAFETY WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! CAUTION! Keep this

More information

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500 Industriefunkuhren Technical Manual IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C37.118 / AFNOR NF S87-500 Module 7628 ENGLISH Version: 02.01-06.03.2013 2 / 20 7628 IRIG-B

More information

MT03A Electronic converter for flow rate transmitters

MT03A Electronic converter for flow rate transmitters Instructions manual MT03A Electronic converter for flow rate transmitters The art of measuring R-MI-MT03A Rev.: 0 English version PREFACE Thank you for choosing a Tecfluid S.A product. This instruction

More information

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual ORM0022 EHPC210 Universal Controller Operation Manual Revision 1 EHPC210 Universal Controller Operation Manual Associated Documentation... 4 Electrical Interface... 4 Power Supply... 4 Solenoid Outputs...

More information

TRF STEP-DOWN TRANSFORMER USER MANUAL

TRF STEP-DOWN TRANSFORMER USER MANUAL TRF STEP-DOWN TRANSFORMER USER MANUA www.ventilation-system.com 2013 ! WARNING The present operation manual consisting of the technical details, operating instructions and technical specification applies

More information

Electronic converter for level transmitters MT03L Instructions manual

Electronic converter for level transmitters MT03L Instructions manual Electronic converter for level transmitters MT03L Instructions manual R-MI-MT03L Rev.: 1 English version PREFACE Thank you for choosing the MT03L converter from MT03 series of Tecfluid S.A. This instruction

More information

AVS50 USER GUIDE. 2.4GHz Audio/Video Sender System - AVS50

AVS50 USER GUIDE. 2.4GHz Audio/Video Sender System - AVS50 2.4GHz Audio / Video Sender System AVS50 USER GUIDE 2.4GHz Audio/Video Sender System CONTENTS 1. Introduction... 2 2. Conformity of Use... 3 3. Controls and Connections... 4-5 4. Product Contents... 6

More information

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids. Foundation Fieldbus Rod and cable probe

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids. Foundation Fieldbus Rod and cable probe Operating Instructions TDR sensor for continuous level and interface measurement of liquids VEGAFLEX 81 Foundation Fieldbus Rod and cable probe Document ID: 44218 2 Contents Contents 1 About this document...

More information

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130 Operating Manual (Edition 04/2004) sinamics Line Reactors SINAMICS G130 Contents 1. Safety Information 2 2. General 5 3. Mechanical Installation 6 4. Electrical Installation 8 5. Technical Specifications

More information

Process transmitter RMA422

Process transmitter RMA422 Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set

More information

Advanced Digital Melting Point Apparatus

Advanced Digital Melting Point Apparatus Advanced Digital Melting Point Apparatus User Guide Version 1.1 Figure 1: Front view Sample heating block Power on/off (at rear) Printer output (at rear) LCD screen Viewer Capillary storage Control panel

More information

Tube Rotator. User Guide. Version 1.2

Tube Rotator. User Guide. Version 1.2 Tube Rotator User Guide Version 1.2 Figure 1: Fixed Speed Model Tube holder spindle Tilt adjustment wheel IEC power inlet socket (at rear) Power on/off switch Figure 2: Variable Speed Model Tube holder

More information

HD-CM HORIZON DIGITAL CABLE METER

HD-CM HORIZON DIGITAL CABLE METER HD-CM OFF! Max RF i/p = +17dBm 75Ω Max AC/DC i/p = 120Vrms MENU INPUT ON HORIZON DIGITAL CABLE METER Horizon Global Electronics Ltd. Unit 3, West Side Flex Meadow Harlow, Essex CM19 5SR Phone: +44(0) 1279

More information

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH Industriefunkuhren Technical Manual OEM Sync-Module FE1000 (IRIG-B) ENGLISH Version: 07.02-24.03.2014 2 / 19 FE1000 IRIG-B Synchronisation - V07.02 IMPORTANT NOTES Version Number (Firmware / Manual) THE

More information

NetterVibrotron SRF. Operating Instructions for. Series SRF. These operating instructions apply to. Netter Static Adjustable Frequency Control

NetterVibrotron SRF. Operating Instructions for. Series SRF. These operating instructions apply to. Netter Static Adjustable Frequency Control Operating Instructions for Netter Static Adjustable Frequency Control Series SRF July 2016 No.1451E Page 1/23 These operating instructions apply to Netter Static Adjustable Frequency Control NetterVibrotron

More information

Instruction manual. DALI Gateway art Installation manual

Instruction manual. DALI Gateway art Installation manual Instruction manual DALI Gateway art. 01544 Installation manual Contents GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 6 COMMUNICATION OBJECTS GENERAL

More information

RIA45. Technical Information. Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values

RIA45. Technical Information. Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values Technical Information RIA45 Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values Application Plant and apparatus engineering and construction Control

More information

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area Guide for installers METTLER TOLEDO MultiRange System solution analog Ex1 Hazardous area Safe area System solution analog Ex1 Contents Contents Page 1 Safety precautions... 2 2 System overview... 3 2.1

More information

RMA42. Technical Information

RMA42. Technical Information Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and

More information

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper

More information

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01

Instruction Manual. Universal Flow Controller Model 261 / 261-EC-01 Universal Flow Controller Model 261 / 261-EC-01 Instruction Manual Type ARS 261-EC 01 Art.-no: 82212264 Table of Contents 1. Safety Instructions 2. Product ID - Dimensions 3. Function Description 4. Installation

More information

Dimensions. Model Number. Electrical connection. Features. Pinout Product information. Indicators/operating means. LGS25 Serie.

Dimensions. Model Number. Electrical connection. Features. Pinout Product information. Indicators/operating means. LGS25 Serie. Q Dimensions Transmitter Detection field + 9. Detection field 7.8 n Beam. Beam Receiver III 0. 0 Fix H H H Fn Model Number Light grid with fixed cable with -pin, M x connector, and fixed cable with 8-pin,

More information

LCD Thermometer / Clock S No. 1253

LCD Thermometer / Clock S No. 1253 Installation and Operating Manual LCD Thermometer / Clock S No. 1253 The 3 fold thermometer with crystal clock is purpose build for the mounting in caravans, boats and intervention vehicles. Please read

More information

-TECH DIGITAL. Explore The High DefinitionWorld. Website: Hot Line: [US] USER MANUAL

-TECH DIGITAL. Explore The High DefinitionWorld. Website:  Hot Line: [US] USER MANUAL -TECH DIGITAL Explore The High DefinitionWorld Website: www.jtechdigital.com Hot Line: 1-888-610-2818[US] USER MANUAL J-Tech Digital ProAV H.264 Encoder/Decoder Many to Many HDMI Extender RoHS 1 Operating

More information

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT Universal Control Unit UC-1-E User Manual General Information Universal Control Unit UC-1 Of Central Lubrication CC DC 24 V 5A / M 15 SL /MK 31 M Z 30 General Information Contents Universal Control Unit

More information

O P E R A T I O N M A N U A L. RF-Reader. Stand-alone-Reader Leser 2plus with RS-232 interface

O P E R A T I O N M A N U A L. RF-Reader. Stand-alone-Reader Leser 2plus with RS-232 interface O P E R A T I O N M A N U A L Version 01/05 RF-Reader Stand-alone-Reader Leser 2plus with RS-232 interface Important! Read by all means! To maintain the perfect shipping conditions and to ensure safe operation

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process, Strain & Potentiometer Follower Signals Features Selectable ±0.2, ±2, ±20, ±200, ±300 & ±600 Vdc voltage ranges Selectable ±2, ±20, ±200

More information

Quick Start. RSHS1000 Series Handheld Digital Oscilloscope

Quick Start. RSHS1000 Series Handheld Digital Oscilloscope Quick Start RSHS1000 Series Handheld Digital Oscilloscope General Safety Summary Carefully read the following safety precautions to avoid personal injury and prevent damage to the instrument or any products

More information

Brief instructions Connection of analogue cameras to the PDM360 NG process and dialogue module in CODESYS

Brief instructions Connection of analogue cameras to the PDM360 NG process and dialogue module in CODESYS Brief instructions Connection of analogue cameras to the PDM360 NG process and dialogue module in CODESYS UK 7391015 / 00 04 / 2014 Content 1 Preliminary note.................................................

More information

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15 > 8 channels for 2-wire HART transmitters > Inputs for Ex nl, Ex na and Nonincendive > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit >

More information

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics Operating Instructions 07/2007 Edition SINAMICS G130/G150 Line harmonics filter sinamics s Safety information 1 General 2 SINAMICS SINAMICS G130/G150 Operating Instructions Mechanical installation 3 Electrical

More information

KACO-display. Wireless Solar Monitoring System. Operating Instructions KACO-display. full of energy...

KACO-display. Wireless Solar Monitoring System. Operating Instructions KACO-display. full of energy... Wireless Solar Monitoring System. Operating Instructions KACO-display full of energy... KACO-display provides high-technology monitoring of your valuable photovoltaic installation. It shows the desired

More information

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS USER MANUAL 27 Full HD Widescreen LED Monitor L27ADS TABLE OF CONTENTS 1 Getting Started 2 Control Panel/ Back Panel 3 On Screen Display 4 Technical Specs 5 Care & Maintenance 6 Troubleshooting 7 Safety

More information

GESTRA Steam Systems NRR 2-50 NRR English. Installation & Operating Manual Level Controller NRR 2-50 Level Controller NRR 2-51

GESTRA Steam Systems NRR 2-50 NRR English. Installation & Operating Manual Level Controller NRR 2-50 Level Controller NRR 2-51 GESTRA Steam Systems NRR 2-50 NRR 2-51 EN English Installation & Operating Manual 819180-03 Level Controller NRR 2-50 Level Controller NRR 2-51 1 Contents Important notes Page Intended use...4 Function...4

More information

CHECK LINE. Model LS-36-LED. Stationary Stroboscope. Operating Manual BY ELECTROMATIC

CHECK LINE. Model LS-36-LED. Stationary Stroboscope. Operating Manual BY ELECTROMATIC CHECK LINE BY ELECTROMATIC Stationary Stroboscope Model LS-36-LED Operating Manual Table of Contents 1.0 Introduction... 02 1.1 Unpacking 1.2 Optional Accessories 2.0 Safety Information... 3 3.0 Controls...

More information

DLP200M 2 Relay Module for Heating and Cooling Plants

DLP200M 2 Relay Module for Heating and Cooling Plants Product Sheet TH6.24 Thermostat Type DLP200M DLP200M 2 Relay Module for Heating and Cooling Plants The DLP 200 M is a relay module for activation of loads (namely thermal actuators or circulators) in wireless

More information

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4 UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

Dragonfly Quad. User Manual V1.4. Order code: EQLED101

Dragonfly Quad. User Manual V1.4. Order code: EQLED101 Dragonfly Quad User Manual V1.4 Order code: EQLED101 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please

More information

Tube Roller Shakers. User Guide. Version 1.2

Tube Roller Shakers. User Guide. Version 1.2 Tube Roller Shakers User Guide Version 1.2 Control panel Rollers Side retaining panels Analog models LED display Drip tray (not visible) Digital models Power On/Off and control dial Roller retaining panel

More information

Technical data. General specifications. Indicators/operating means

Technical data. General specifications. Indicators/operating means Model Number Single head system Features Sensor head bidirectional and rotatable Function indicators visible from all directions Quick mounting bracket Selectable sound lobe width Programmable Diagrams

More information

Process Transmitter RMA 422

Process Transmitter RMA 422 Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog

More information

Guided Wave Radar Level Meter

Guided Wave Radar Level Meter Guided Wave Radar Level Meter Guided Wave Radar Level Meter Instruction 1. Product Description 1.1 principle of measurement Guided Wave Radar is the measuring instruments that based on the time travel

More information

Tebis application software

Tebis application software Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF device WYC42xQ

More information

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS SINAMICS G130 / G150 Line harmonics filter Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 / G150 Operating Instructions Mechanical installation 3 Electrical

More information

Smart Control SC16 3-Channel for matrix

Smart Control SC16 3-Channel for matrix Operating Manual Smart Control SC16 3-Channel for matrix Dear Customer, Thank you for choosing a WALTRON daytime lighting controller. Your daytime lighting controller is a high-quality product that was

More information

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide GB05-7 Peak Atlas IT RJ45 Network Cable Analyser Model UTP05 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2001/2013 In the interests of development, information

More information

IRIG-B PTP Clock Converter Output Module Hardware Installation Manual

IRIG-B PTP Clock Converter Output Module Hardware Installation Manual IRIG-B PTP Clock Converter Output Module Hardware Installation Manual Kyland Technology Co., LTD. Publication Date: May 2012 Version: V1.2 Customer Service Hotline: (+8610) 88796676 FAX: (+8610) 88796678

More information

AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE

AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE Thank you for purchasing a TSI AeroTrak Model 9110 Portable Airborne Particle Counter (particle counter). This guide will help you

More information

Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex.

Guide for installers. METTLER TOLEDO MultiRange System solution Point Ex. Guide for installers METTLER TOLEDO MultiRange System solution Point Ex www.mt.com/support System solution Point Ex Contents Contents Page 1 Safety precautions... 4 2 System overview... 5 2.1 Using the

More information

VIDEO ALARM VERIFICATION UNIT VIVER

VIDEO ALARM VERIFICATION UNIT VIVER VIDEO ALARM VERIFICATION UNIT VIVER viver_en 09/08 The VIVER module provides remote video alarm verification, based on image sequences transmitted from cameras installed in the protected facility. The

More information

Solis Export Power Manager

Solis Export Power Manager Solis Export Power Manager Installation and Operation Manual Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 3572, P.R.China Tel: +86 (0)574

More information

Commander 384. w w w. p r o l i g h t. c o. u k U S E R M A N U A L

Commander 384. w w w. p r o l i g h t. c o. u k U S E R M A N U A L Commander 384 w w w. p r o l i g h t. c o. u k U S E R M A N U A L 1, Before you begin 1.1: Safety warnings...2 3 1.2: What is included...4 1.3: Unpacking instructions...4 2, Introduction 2.1: Features...4

More information

PLC Control Unit for a CSM-E Electrical Compact Clean Steam Generator

PLC Control Unit for a CSM-E Electrical Compact Clean Steam Generator 3.635.5275.254 IM-P486-18 CH Issue 3 PLC Control Unit for a CSM-E Electrical Compact Clean Steam Generator Installation, Start-up and Operation Manual 1. Safety information 2. General product information

More information

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704

USER MANUAL. WARNING Read the instructions before using the machine. EN (Original Instruction) / 1704 USER MANUAL European Models American Models 60/100/120 3/4/5 24/40/48 3/4/5 Read the instructions before using the machine. EN (Original Instruction) 9124097 / 1704 KEEP THIS USER MANUAL FOR FUTURE USE

More information

KHT 1000C HV-Probe Calibrator. Instruction Manual

KHT 1000C HV-Probe Calibrator. Instruction Manual KHT 1000C HV-Probe Calibrator Instruction Manual Copyright 2015 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications are subject

More information

MICROMASTER Encoder Module

MICROMASTER Encoder Module MICROMASTER Encoder Module Operating Instructions Issue 01/02 User Documentation Foreword Issue 01/02 1 Foreword Qualified Personnel For the purpose of this Instruction Manual and product labels, a Qualified

More information

Instructions Manual

Instructions Manual 15 19 22 26 32 42 46 55 65 Instructions Manual Table of Contents Safety Guidelines Safety Guidelines 3 Package Contents 4 Ports and Connectors 5 Technical Specifications 6 Installation Guidelines 7 Installation

More information

RIA46. Technical Information. Field meter Digital field meter with control unit for monitoring and visualizing analog measured values

RIA46. Technical Information. Field meter Digital field meter with control unit for monitoring and visualizing analog measured values Technical Information RIA46 Field meter Digital field meter with control unit for monitoring and visualizing analog measured values Application Process recording and supervision Process control Signal

More information

OPERATING MANUAL. DMX512 to DALI Dekoder 7044A-H Mk4

OPERATING MANUAL. DMX512 to DALI Dekoder 7044A-H Mk4 last edited: 2014-08-12 OPERATING MANUAL DMX512 to DALI Dekoder 7044A-H Mk4 (C) SOUNDLIGHT 1996-2015 * ALL RIGHTS RESERVED * NO PART OF THIS MANUAL MAY BE REPRODUCED, DUPLICATED OR USED COMMERCIALLY WITHOUT

More information

8000 Plus Series Safety Light Curtain Installation Sheet ( CD206A/ CD206B )

8000 Plus Series Safety Light Curtain Installation Sheet ( CD206A/ CD206B ) SMARTSCAN 8000 PLUS LIGHT CURTAIN 1 Unpacking 8000 Plus Series Safety Light Curtain Installation Sheet ( CD206A/0160306 CD206B160306 ) Remove all packaging material and retain it Locate and keep the delivery

More information

USER MANUAL. 27 Full HD Widescreen LED Monitor L270E

USER MANUAL. 27 Full HD Widescreen LED Monitor L270E USER MANUAL 27 Full HD Widescreen LED Monitor L270E TABLE OF CONTENTS 1 Getting Started 2 Control Panel/ Back Panel 3 On Screen Display 4 Technical Specs 5 Care & Maintenance 6 Troubleshooting 7 Safety

More information

KRF EMC Filters Installation, Operation and Maintenance Manual

KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC

More information

Single cable multiswich programmer PC102W

Single cable multiswich programmer PC102W Single cable multiswich programmer PC102W 1. Product description The PC102W - single cable multiswich programmer (in the text - programmer) is useful instrument while configuring and troubleshooting SAT

More information

Model KBF 115 Constant climate chambers with large temperature / humidity range

Model KBF 115 Constant climate chambers with large temperature / humidity range Model KBF 115 Constant climate chambers with large temperature / humidity range The BINDER KBF is the specialist for unconditionally reliable stability testing and precise maintenance of constant climate

More information

OM2000N INSTALLATION MANUAL

OM2000N INSTALLATION MANUAL OM2000N INSTALLATION MANUAL 2 1 Figure A 1 2 Laser Beam Output Window Power Cable 821001342 (Rev. B) DESCRIPTION The OM2000N oscillating mirror is an accessory for the 2000N family laser scanners: DS2100N,

More information

USER MANUAL. 22" Class Slim HD Widescreen Monitor L215DS

USER MANUAL. 22 Class Slim HD Widescreen Monitor L215DS USER MANUAL 22" Class Slim HD Widescreen Monitor L215DS TABLE OF CONTENTS 1 Getting Started Package Includes Installation 2 Control Panel / Back Panel Control Panel Back Panel 3 On Screen Display 4 Technical

More information

MICROSENS. Fast Ethernet Switch Modul 4x 10/100Base-TX, 1x 100Base-FX. Description. Features

MICROSENS. Fast Ethernet Switch Modul 4x 10/100Base-TX, 1x 100Base-FX. Description. Features Fast Ethernet Switch Modul 4x 10/100Base-TX, 1x 100Base-FX Description This Ethernet Switch Module has been designed with 4x10/100Base-TX ports and 1x100Base-FX fiber optic port for the interconnection

More information

Technical data. General specifications. 60 ma Power consumption P 0. 1 W Time delay before availability t v. 120 ms Interface. Protocol IO-Link V1.

Technical data. General specifications. 60 ma Power consumption P 0. 1 W Time delay before availability t v. 120 ms Interface. Protocol IO-Link V1. Model Number Single head system Features IO-link interface for service and process data Programmable via DTM with PACTWARE programmable switch outputs Selectable sound lobe width Synchronization options

More information

ArtNet-LED-Dimmer 6 ArtNet-LED-Dimmer 6R

ArtNet-LED-Dimmer 6 ArtNet-LED-Dimmer 6R ArtNet-LED-Dimmer 6 ArtNet-LED-Dimmer 6R User Manual Art-Net Designed by and Copyright Artistic Licence Holdings Ltd. ArtNet-LED Dimmer 6 / 6R 2 Description The ArtNet-LED Dimmer 6 / 6R is a compact LED

More information

Technical Information RIA45

Technical Information RIA45 TI00141R/09/EN/05.16 71315968 Products Solutions Services Technical Information RIA45 Panel meter Panel meter with control unit for monitoring and visualizing measured values Application Plant and apparatus

More information

USER MANUAL. 28" 4K Ultra HD Monitor L28TN4K

USER MANUAL. 28 4K Ultra HD Monitor L28TN4K USER MANUAL 28" 4K Ultra HD Monitor L28TN4K TABLE OF CONTENTS 1 Getting Started 2 Control Panel/ Back Panel 3 On Screen Display 4 Technical Specs 5 Care & Maintenance 6 Troubleshooting 7 Safety Info &

More information

PS600 Digital Visualizer. User Manual. English - 0

PS600 Digital Visualizer. User Manual. English - 0 PS600 Digital Visualizer User Manual English - 0 Table of Content COPYRIGHT INFORMATION... 3 CHAPTER 1 PRECAUTIONS... 4 SAFETY PRECAUTIONS... 5 FCC WARNING... 5 EN55022 (CE RADIATION) WARNING... 5 CHAPTER

More information

Function Manual SIMATIC HMI TP900. Operator Panel.

Function Manual SIMATIC HMI TP900. Operator Panel. Function Manual SIMATIC HMI TP900 Operator Panel Edition 10/2016 www.siemens.com Introduction 1 Safety notes 2 Medium-voltage converters SIMATIC Description 3 Screens 4 Installing software 5 Function

More information

Model KBF 1020 Constant climate chambers with large temperature / humidity range

Model KBF 1020 Constant climate chambers with large temperature / humidity range Model KBF 1020 Constant climate chambers with large temperature / humidity range The BINDER KBF is the specialist for unconditionally reliable stability testing and precise maintenance of constant climate

More information

VGA & RS232 Extender SET over Single CAT5 with RGB Delay Control

VGA & RS232 Extender SET over Single CAT5 with RGB Delay Control VGA & RS232 Extender SET over Single CAT5 with RGB Delay Control Model #: VGA-C5RS-SET 2010 Avenview Inc. All rights reserved. The contents of this document are provided in connection with Avenview Inc.

More information

TVAC20000 User manual

TVAC20000 User manual TVAC20000 User manual Version 01/2010 Original English user manual. Keep for future use. 10 Introduction Dear Customer, Thank you for purchasing this product. This product meets the requirements of the

More information

INFORMATION TO USER CAUTION RISK OF ELECTRIC SHOCK, DO NOT OPEN

INFORMATION TO USER CAUTION RISK OF ELECTRIC SHOCK, DO NOT OPEN INFORMATION TO USER CAUTION RISK OF ELECTRIC SHOCK, DO NOT OPEN! CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER (OR BACK). NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED

More information

1440/2880 HP RGB+WW+CW

1440/2880 HP RGB+WW+CW office Nano*Pix 1440/2880 HP RGB+WW+CW User Manual Rev 7/2014 V4.4 Specifications subject to change without notice. Seite 1 Product Description Thank you for choosing this LDDE Nano*Pix 1440 HP / 2880

More information

User Manual Entry Line Industrial Fast Ethernet Switch 4x 10/100Base-TX, 1x 100Base-X Fiber Port 4x PoE+ up to 30W

User Manual Entry Line Industrial Fast Ethernet Switch 4x 10/100Base-TX, 1x 100Base-X Fiber Port 4x PoE+ up to 30W User Manual Entry Line Industrial Fast Ethernet Switch 4x 10/100Base-TX, 1x 100Base-X Fiber Port 4x PoE+ up to 30W Entry Line Fast Ethernet Switch Fast Ethernet Switch with PoE+ for Industrial Use Page

More information

LINK-MI LM-WHD05B. Wireless HDMI AV Transmission System. User Manual

LINK-MI LM-WHD05B. Wireless HDMI AV Transmission System. User Manual LINK-MI LM-WHD05B Wireless HDMI AV Transmission System User Manual Table of Contents 1.Important Information... 3 1.1 Safety Precautions... 3 1.2 Declaration of Conformity... 4 1.3 Trademark Information...

More information

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach

More information

Owner s Manual. multiswitch Firmware-Version 1.06 OS- Version 1.02

Owner s Manual. multiswitch Firmware-Version 1.06 OS- Version 1.02 Owner s Manual multiswitch 1.41 Firmware-Version 1.06 OS- Version 1.02 The information contained in this manual is subject to change without prior notice. All rights reserved. Current as of: Juli 19 th

More information

Siteco Service Box User Manual 1/31

Siteco Service Box User Manual 1/31 Siteco Service Box User Manual 1/31 Contents Page I. References.......5 II. General Safety Recommendations..... 6 III. IV. Technical Details........ 7 Device Description...... 8 V. Definitions........9

More information

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical

More information

OPERATING MANUAL. DMX512 to DALI Dekoder 7044A-H Mk1

OPERATING MANUAL. DMX512 to DALI Dekoder 7044A-H Mk1 last edited: 2010-07-24 OPERATING MANUAL DMX512 to DALI Dekoder 7044A-H Mk1 (C) SOUNDLIGHT 1996-2010 * ALL RIGHTS RESERVED * NO PART OF THIS MANUAL MAY BE REPRODUCED, DUPLICATED OR USED COMMERCIALLY WITHOUT

More information

Operating Manual. Basic Control BC16. two-channel for eco moon

Operating Manual. Basic Control BC16. two-channel for eco moon Operating Manual Basic Control BC16 two-channel for eco moon Dear Customer, Thank you for choosing a WALTRON daytime lighting controller. Your daytime lighting controller is a high-quality product that

More information