Liquid Level Sensor AKS 4100U
|
|
- Godwin Flynn
- 5 years ago
- Views:
Transcription
1 MAKING MODERN LIVING POSSIBLE Technical brochure Liquid Level Sensor U
2 Liquid Level Sensor, U Contents Page Introduction...3 Features...3 Product concept...3 Cable Version Coaxial Version...3 Display interface (HMI)...5 Measuring principle...6 Material specification Approvals and certifications....6 Measuring range and installation information CABLE version...7 Measuring range and installation information COAXIAL version...8 Ordering U...9 Dimensions and weights Technical data Quick setup guide for CABLE version Quick setup guide for COAXIAL version Forcing ma output How to change the language setting Reset to factory setting Appendix1: Entering refrigerant dielectric gas constant Refrigerant saturated vapour dielectric constant DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
3 Liquid Level Sensor, U Introduction U liquid level sensor can be used to measure the liquid level of many different refrigerants in vessels, accumulators, receivers, level columns, etc. Cable Version Coaxial Version The U liquid level sensor is based on a proven techhology called Time Domain Reflectometry (TDR) or Guided Micro Wave. The electrical output is a 2-wired, loop powered 4-20 ma output signal, which is proportional to the refrigerant liquid level. Dust, foam, vapour, agitated surfaces, boiling surfaces, changes in density or in the dielectric constant, εr, for the liquid have no influence on the U performance. Oil accumulated in the bottom of a level column will not disturb the liquid level signal and it is not necessary to remove U for cleaning after oil has been drained out of the level column. Features One part number in the cable version is used for any probe length in the range of 31.5 in. to 197 in. (800 mm to 5000 mm) Cable version requires less top-end clearance for installation and service Proven operation with all refrigerants in combination with oil. No need to clean cable version when fully covered by oil. The cable version is very compact and easy to handle, ship, install and use with different lengths and refrigerants 2-wire loop powered Display interface units can be in mm, cm, m, ft, in. For further details regarding mechanical and electrical installation please refer to the product instructions PI.SC0.D (CABLE version) and PI.SC0.E (COAXIAL version). Product concept U is available in two different versions: Cable version Coaxial version The cable version is used for lengths from 31.5 in. (800 mm) and up to 197 in. (5000 mm) and is suitable for HCFC, Non flammable HFC and R717 (Ammonia). The U cable version should NOT be used for CO 2 or marine applications. The coaxial version of U is designed for use with R744 (CO 2 ), HCFC, Non flammable HFC and R717 (Ammonia). The U coaxial version should always be used for marine applications for all refrigerant types. Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H5916 3
4 Liquid Level Sensor, U Product concept (continued) Cable version U cable version must ALWAYS be installed in a level column. Danfoss M84H0001_1 Cable version The cable version consists of: Signal converter Mechanical process connection with 5 m (197 in.) ø2 mm (0.08 in.) stainless cable Counterweight Accessory bag comprising: 3 mm set screws Red cover to protect mechanical process connection prior to mounting signal converter. Setting label. Note: If the level column is not within 2" to 4" in size, the coaxial version should be used. Coaxial version Coaxial version can be installed in a level column (a) or directly in a vessel (b). a b Coaxial version The Coaxial version consists of: Signal Converter Mechanical process connection with 5 m (197 in.) Ø2 mm (0.08 in.) stainless steel wire Tube(s) depending on required length Accessory bag comprising: End Connector (incl. 3 mm (0.12 in.) set screws.) 3 mm (0.12 in.) set crews (1 set screw pr. tube) Red cover to protect mechanical process connection, before Signal Converter is mounted. Setting label. 4 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
5 Liquid Level Sensor, U Display interface (HMI) The HMI Service/Display unit is used for commissioning and quick on-site setup and is easily mounted on the U. The service unit supports mulitple languages in both SI and US units. * 4-20 ma output displayed as bar graph and in percentage [%] Measurement name (in this example, DISTANCE) Device tag name Measurement reading and unit Device status (markers) Marker 1, 2 and 3 (Error) Hardware problem; the Signal Converter hardware is defective. Contact Danfoss. Marker 4 and 5 (Notification) Depending on the level, the marker is ON or OFF. Used for Danfoss service information only. Keypad buttons Flashing star indicating unit in operation. Enter menu system Enter QUICK SETUP Unit change at distance/level readout: m, cm, mm, in, ft Change between: Distance* Level** Output (%)*** Output (ma)**** * If the display is set to DISTANCE then the value displayed will be the distance from the reference point (see diagram on p. 7 and 8) to the top surface of the liquid refrigerant. ** If the display is set to LEVEL then the value displayed will be the length of the probe length that is covered by the refrigerant (distance from bottom of level probe to the surface of the liquid refrigerant). See diagram on p. 7 and 8. *** If the display is set to OUTPUT (%) then the value displayed will be the % refrigerant level according to the 4 ma (0%) and 20 ma (100%) scale settings entered during setup. See diagram on p. 7 and 8. **** If the display is set to OUTPUT (ma) then the value displayed will be the ma output of the probe based on the refrigerant level and the 4 ma (0%) and 20 ma (100%) scale settings entered during setup. See diagram on p. 7 and 8. Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H5916 5
6 Liquid Level Sensor, U Measuring principle (Cable and Coaxial) 1. An electromagnetic (EM) pulse is transmitted by the signal converter 2. The pulse goes down the probe at the speed of light in air, V1 3. The pulse is reflected 4. The pulse goes up the probe at speed, V1 5. The converter receives the pulse and records the signal 6. The EM pulse moves at speed, V1 7. Transmitted EM pulse 8. Half of this time is equivalent to the distance from the reference point of the device (the flange facing) to the surface of the product 9. Received EM pulse The U electronic converter emits lowintensity, high frequency electromagnetic pulses with a width of approximately 1 nanosecond, which travel at the speed of light along the probe (wire or coaxial cable) down to the liquid surface. The pulses are reflected by the liquid surface, guided back along the probe, and received and analysed by the U electronic converter and then converted into a liquid level reading. This method is called time domain reflectometry (TDR) or guided microwave. The dielectric constant, εr, of the liquid is a key parameter and has a direct impact on the degree of reflection of the high frequency electromagnetic pulses. Liquids with high εr values, such as ammonia, produce strong reflections, while liquids with low εr values, such as CO2, produce weak reflections. As long as the εr value of the liquid refrigerant is higher than 1.2, U can detect the liquid level and level measurement accuracy is not affected. If the temperature condition in the level culomn/ vessel is known, a dielectric constant of the refrigerant gas can be entered in U (parameter GAS EPS.R), in order to improve the Dead Zone of probe. Refer to pages 7 to 8 for Measuring range of AKS 4100U - CABLE version and COAXIAL version. For details of gas constant values for different temperatures and refrigerants plus the procedure for entering these via the HMI, refer to pages 18 to 19. Material specification Housing Aluminium Coaxial (segmented) Standard: Stainless steel ( / 316L) Single cable Standard: Stainless steel ( / 316) Process fitting Standard: Stainless steel ( / 316L) Gaskets EPDM ( C / F) Cable gland Plastic (black) Approvals and certifications CE EMC LVD NAMUR This device fufills the statutory requirements of the EMC directives. The manufacturer certifies successful testing of the product by applying the CE mark. EMC Directives 2004 / 108 / EC and 93 / 68 / EEC in conjunction with EN (2006) and EN (2006). The device conforms to these standards if : - the device has a coaxial probe or - the device has a single probe that is installed in a metallic tank. Low-Voltage Directives 2006 / 95 / EC and 93 / 68 / EEC in conjunction with EN (2001) NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and Laboratory Control Equipment NAMUR NE 43 Standardization of the Signal Level for the Failure Information of Digital Transmitters 6 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
7 Liquid Level Sensor, U Measuring range and installation information CABLE version Because the cable version can be trimmed to the desired length during installation, it is required to record the following values on the setting label (included with probe) and stick the label on the signal converter for later use when programming: Probe length. The probe length can be trimmed to the desired length within the range of 31.5 in. and 197 in., but must allow a minimum clearance of 0.8 inches/20 mm from the bottom of the level column. Length to 4 ma setting. For a max. measuring range this length = Probe length bottom dead zone (given in tables) 1.3 inches/33 mm (counterweight height) Length to 20 ma setting. For the max. measuring range this length will be 4.7 inches/120 mm Note: The above lengths must be programmed into the U for the sensor to work. For most applications the bottom dead zone value can be taken from the table that is based on the factory setting for the dielectric constant, but if the refrigerant temperature is known, the dielectric constant can be changed to improve the measuring range (see appendix1 and table with improved bottom dead zone value). Bottom deadzone values based on the factory setting of dielectric constant Refrigerant Probe length range Bottom dead zone Ammonia, HFC, HCFC [in.] [mm] [in.] [mm] Improved Bottom dead zone value after the adjustment of dielectric constant Refrigerant Probe length range Bottom dead zone Ammonia, HFC, HCFC [in.] [mm] [in.] [mm] Top dead zones 4.7 in. (120 mm) Measuring range Standpipe diameter: 2-4 in. Reference point Probe length* 20 ma (100 %)* Surface level Distance 4 ma (0 %)* Inner length of the standpipe Bottom dead zone (see tables) Counterweight: 1.3 in. (33 mm) Min: 0.8 in. (20 mm) * Values to be entered into HMI Quick Setup menu and recorded on the setting label. Stick the setting label onto the Signal Converter either inside or outside. Danfoss M84H0063_1 Steel wire insertion length: 0.5 in. (12 mm) Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H5916 7
8 Liquid Level Sensor, U Measuring range and installation information COAXIAL version The coaxial version can be ordered in various predefined probe lengths but can be cut to a desired length during installation. Therefore, it is best to record the following values on the setting label (included with probe) and stick the label on the signal converter for later use when programming: Probe length. The probe length can be cut to the desired length but must be a min. length of 19.2 in./488 mm and allow a minimum clearance of 1.2 inches (30 mm) from the bottom of the level column. Dielectric constant only needs to be changed for CO 2 applications (see appendix1). For other refrigerants, the bottom dead zone can be taken from the table that is based on the factory setting of the dielectric constant. Length to 4 ma setting. For a max measuring range this length = Probe length bottom dead zone (given in the tables). Length to 20 ma setting. For the max measuring range this length will be 4.7 inches/ 120 mm. Note: The above lengths must be programmed into the U for the sensor to work. Please note: It is mandatory to input dielectric constant for CO 2 applications. U Dielectric Constant εr always set during Quick Setup Refrigerant Probe Length Bottom Bottom Dead Dead Zone Zone [in.] [in.] [mm] 19.2 CO * Values to be entered into HMI Quick Setup menu and recorded on the setting label. Stick the setting label onto the Signal Converter either inside or outside. Top dead zone 4.7 in. (120 mm) Reference point 20 ma (100 %)* Bottom dead zone values based on the factory setting of dielectric constant Refrigerant Probe Length Bottom Dead Zone Bottom Dead Zone [in.] [in.] [mm] Ammonia Bottom dead zone values based on the factory setting of dielectric constant Refrigerant Probe Length Bottom Dead Zone Bottom Dead Zone [in.] [in.] [mm] HCFC,HFC Measuring range Probe length* Surface level Distance 4 ma (0 %)* Inner length of the stand pipe Improved Bottom dead zone values after the adjustment of dielectric constant Refrigerant Probe Length Bottom Dead Zone Bottom Dead Zone [in.] [in.] [mm] 19.2 Ammonia Improved Bottom dead zone values after the adjustment of dielectric constant Refrigerant Probe Length Bottom Dead Zone Bottom Dead Zone [in.] [in.] [mm] 19.2 HCFC,HFC Bottom dead zone (see tables) Danfoss M84H0064_1 Min: 1.2 in. (30 mm) Ø0.08 in. (2 mm) stainless wire 8 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
9 Liquid Level Sensor, U Ordering U Cable verion: Standard version used for common refrigerants including R717 (ammonia), HCFC and HFC. Not for use with CO 2 or in marine applications. Description U with 196 in. insertion cable length which can be trimmed to desired length during installation within the range of 31.5 in. to 196 in. during installation. 3/4" NPT process connection. Code number With HMI Display 084H4521 Coaxial version: used for common refrigerants including R717 (ammonia), HCFC, HFC and CO 2. Can be used for marine applications Description Probe length Code number in. mm With HMI Display U - Coaxial version with 3/4" NPT process connection H4530 U - Coaxial version with 3/4" NPT process connection H4533 U - Coaxial version with 3/4" NPT process connection H4535 Spare parts and accessories Description U HMI Display Interface Code number 084H4548 Description U Signal Converter without HMI Display, excluding cable gland Code number 084H4541 Description Content Code number Cable and counterweight for U - CABLE version End connector incl screws for U - COAXIAL version Cable in. (5 m) Ø0.08 in. (Ø2 mm) Crimp Counterweight End connector (incl in. (3 mm) set screws) 084H H4549 Process connection, counterweight and 197 in. (5 m) Ø0.08 in. (Ø2 mm) cable for U - CABLE and COAXIAL version 3/4 in. NPT process connection Counterweight 084H4546 Description U Coaxial tube. Tube length : 26.8 in. (680 mm) U blank top cover for signal converter Code number 084H H4544 Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H5916 9
10 Liquid Level Sensor, U Dimensions and weights CABLE version Ø0.9 in. (Ø22 mm) Ø4.1 in. (Ø104 mm) Ø0.08 in. (Ø2 mm) 1.3 in. (33 mm) Ø3.6 in. (Ø92 mm) 5.6 in. (141.3 mm) 1.4 in. (34.2 mm) Probe length Weight: approx. 4.4 lbs (2.0 kg) COAXIAL version Ø4.1 in. (Ø104 mm) Ø0.6 in. (Ø14 mm) Ø0.8 in. (Ø21 mm) 5.6 in. (141.3 mm) 1.4 in. (34.2 mm) Probe length Weight: approx. 7.7 lbs (3.5 kg) 10 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
11 Liquid Level Sensor, U Technical data Measuring system Measuring principle 2-wire loop-powered level transmitter; Time Domain Reflectometry (TDR ) Refrigerants Primary measured value Secondary measured value Max. measuring range Level measurement of liquid refrigerants. Approved refrigerants: Halogen Free / Environmently friendly: R717 / NH3, R744 / CO2 HCFC: R22 HFC: R404A, R410A, R134A Time between the emitted and received signal Distance or level Coaxial version U: 19.2 in. to 85 in. Cable version U: 31.5 in to 197 in.) Dead zone This depends on the type of probe. (see pages 7 and 8) Liquid dielectric constant (εr) Enclosure IP66/67 ( NEMA type 4x) Cable version to be used in R717 / NH3, HCFC and HFC εr, liquid > 5.6 Coaxial version is mandatory for R744 / CO2 and marine applications εr, liquid > 1.3 Display and User interface (HMI) Display Interface languages Ambient temperature Storage temperature Refrigerant temperature ure Max. working pressure Other conditions Vibration resistance Protection category Process connections Single cable Ø2 mm / 0.08 Coaxial Integrated LCD display pixels in 8-step greyscale with 4-button keypad English (default), German, French, Spanish 40 F / +175 F ( 40 C / +80 C) without HMI display 4 F / +140 F ( 20 C / +60 C) with HMI display F / C The refrigerant temperature can be in the range of -76 F/ 212 F (-60 C/ 100 C), however, the accuracy may be affected if the temperature is not within the below temperature ranges based on the refrigerant. R717 / NH 3 40 F / +122 F ( 40 C / +50 C) R744 / CO 2 58 F / +59 F ( 50 C / +15 C) HCFC: R22 58 F / +118 F ( 50 C / +48 C) HFC: R404A 58 F / +59 F ( 50 C/ +15 C) R410A 58 F / +59 F ( 50 C /+15 C) R134A 40 F /+122 F ( 40 C /+50 C) 14.5 psig / 1450 psig ( 1 barg / 100 barg) EN (1...9 Hz: 3 mm / Hz:1g; 10g shock half-wave sinusoidal: 11 ms) IP 66/67 equivalent to NEMA type 4X (housing) and type 6P (probe) U: ¾ in. NPT U: ¾ in. NPT Electrical connections Power supply Current output load Cable gland Terminals output: V d.c. Min./Max. Value for an output of 22 ma at the terminal. Ambient temperature limitations: 40 F / +176 F ( 40 C/+80 C) : V d.c. 4 F / +176 F ( 20 C/+80 C) : V d.c. RL [Ω] ((Uext -14 V)/20 ma). Default (Error output set to 3.6 ma) RL [Ω] ((Uext -14 V)/22 ma). (Error output set to 22 ma) U: ½ in. NPT Cable entry capacity (terminal) ~20-15 AWG ( mm 2 ) Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H
12 Liquid Level Sensor, U Technical data (continued) Current output Output signal 4 20 ma or ma acc. to NAMUR NE 43 Resolution drift Error signal ±3 μa Typically 75 ppm/k High: 22 ma; Low: 3.6 ma acc. to NAMUR NE 43; Hold (frozen value - not available with NAMURNE 43 compliant output. Minimum power supply voltage Use this graph to find the minimum power supply voltage for a given current output load: Current output load R L [Ω] Power supply U [VDC] Minimum power supply voltage for an output of 22mA at the terminal U connected to PLC 24 V d.c. or 24 V a.c. 50/60 Hz EKC 347 /4100U + PLC Active Analog Input 4-20 ma V d.c. 1st generation ICAD motor for ICM p/n 027H12xx (discontinued Dec. 2009) 2nd generation ICAD motor for ICM p/n 027H9xxx. Introduced Jan Orange White Danfoss M84H0020_1 AKS 41U level probe (previous version) + Alarm relays U connected to EKC V d.c. power supply (customer supplied) (+) ( ) U ma Danfoss M84H0052_1 ICM/ICAD valve position feedback AKV, AKVA or solenoid for on-off control Controller powers the 24V a.c., Max. 20W coil Can also be a 24V a.c. relay to control a solenoid valve. 12 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
13 Technical brochure Liquid Level Sensor, U Quick setup guide for CABLE version Prior to programming the U the below values will be needed which should have been recorded on the setting label during installation and placed on U converter. For more information on these values, please see the measuring range and installation information on p. 7. Probe length Length to 4 ma setting Length to 20 ma setting Note: The signal converter can be programmed with or without mechanical process connector assembled. Steps for quick setup (all values below are only examples) 1. Make sure the power supply is connected to the U. The AKS 4100U can be programmed with or without the signal converter attached to the mechanical process connector. 2. The units in the display can be changed to any of the following: mm, in, ft, m, cm. If the current units do not match the recorded units, press as many times as needed to change to the desired units. For more information about the displayed values, please see display interface on p.5 3. Start quick setup for cable version 5. Enter length to 4 ma scale setting to enter the store/save screen SCALE 4 ma STORE NO in mm to change of SCALE 4 ma. to change the cursor position. to decrease the value or to to confirm and save setting. values to select STORE YES to confirm and store/save The quick setup is now complete and the default screen will be displayed. 6. Enter length to 20 ma scale setting SCALE 20 ma 8. Optional check of setting To check the settings, press mm in times. to change of SCALE 20 ma. to change the cursor position. to decrease the value or to to confirm and save setting. QUICK SETUP? YES NO to enter quick setup PROBE TYPE SINGLE CABLE twice. SINGLE CABLE (0%) 4 ma (100%) 20 ma default screen. 196mm in mm in in mm to return to 7. Store/Save entered values to select single cable version. The following should now be displayed after about 8 seconds: AKS QUICK QUICKSTART SETUP? 4. Enter probe length PROBE LENGTH mm in YES NO to change the PROBE LENGTH. to change the position of the cursor. to decrease the value or to to confirm and save setting Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H
14 Technical brochure Liquid Level Sensor, U Quick setup guide for COAXIAL version Prior to programming the U the below values will be needed which should have been recorded on the setting label during installation and placed on U converter. For more information on these values, please see the measuring range and installation information on p. 8. The units in the display can be changed to any of the following: mm, in, ft, m, cm. If the current units do not match the recorded units, press as many times as needed to change to the desired units. For more information about the displayed valves, please see display interface on p.5 Probe length Length to 4 ma setting Length to 20 ma setting Make sure the power supply is connected to the U. The U can be programmed with or without the signal converter attached to the mechanical process connector. Note: The signal converter can be programmed with or without mechanical process connector assembled. Quick Setup (all values below are only examples) When CO2 is used: Connect the device to the power supply (see the product instruction for detail on electrical installation/connection). 3 times. to change the PROBE LENGTH. to change the position of the cursor. to decrease the value or to QUICK SETUP? YES NO to enter quick setup. PROBE TYPE SINGLE CABLE PROBE LENGTH mm QUICK SETUP COMPLETED IN 8 Wait for QUICK SETUP to complete. Count down from 8 sec. AKS QUICK QUICKSTART SETUP? YES SCALE 4 ma mm to change of SCALE 4 ma. to change the cursor position. to decrease the value or to LIQUID CO2? YES NO (YES) to confirm or to select between STORE NO or STORE YES. Default screen appears: DISTANCE 5000 mm SCALE 20 ma GAS EPS R? mm to change GAS EPS.R. (Select the correct value from the tables on page 16) to change cursorposition. to decrease the value or to to change of SCALE 20 ma. to change the cursor position. to decrease the value or to Quick Setup completed You have the possibility of checking your settings by pressing twice. COAXIAL 2200 mm (0 %) 4 ma 1900 mm (100 %) 20 ma 70 mm 14 DKRCI.PD.SC0.C5.22 / 520H STORE NO to select COAXIAL. and press NO to return to default screen. Danfoss A/S (AC-SMC / MWA),
15 Liquid Level Sensor, U COAXIAL version (continued) Quick Setup (all values below are only examples) For all other refrigerants: Connect the device to the power supply press YES PROBE TYPE SINGLE CABLE 3 times. QUICK SETUP? NO to enter quick setup. to select COAXIAL and LIQUID CO2? YES (NO) to confirm PROBE LENGTH mm NO to change the PROBE LENGTH. to change the position of the cursor. to decrease the value or to SCALE 4 ma mm to change of SCALE 4 ma. to change the cursor position. to decrease the value or to SCALE 20 ma mm to change of SCALE 20 ma. to change the cursor position. to decrease the value or to Wait for QUICK SETUP to complete. Count down from 8 sec. QUICK SETUP COMPLETED IN STORE NO or to select between STORE NO or STORE YES. Default screen appears: DISTANCE QUICK START SETUP 5000 mm Quick Setup completed Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H
16 Liquid Level Sensor, U CABLE and COAXIAL version Forcing ma output (all values below are only examples) Default screen DISTANCE 5000 mm TESTS 4 times to return to default screen. Default screen appears: QUICK SETUP START SET OUTPUT DISTANCE 5000 mm Force ma completed and disabled SUPERVISOR SET OUTPUT 3.5 ma Enter password by pressing the following buttons: to decrease the value or to SET OUTPUT 8 ma INFORMATION 16 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
17 Technical brochure Liquid Level Sensor, U How to change the language setting (Default: English, others: German, French, Spanish) Default screen Enter password by pressing the following buttons: DISTANCE 5000 mm or to see the language possibilities INFORMATION AKS QUICK SETUP START? YES 6 times DISPLAY NO LANGUAGE STORE NO SUPERVISOR LANGUAGE times or to select between STORE NO or STORE YES. Select STORE YES by pressing Default screen appears: LANGUAGE ENGLISH DISTANCE 5000 mm Language setup completed Reset to factory setting Default screen Enter password by pressing the following buttons: RESET FACTORY NO DISTANCE 5000 mm once and SENSOR twice SERVICE twice CONFIG/RESET and confirm 3 times to return to default screen. Default screen appears: DISTANCE 5000 mm RESET FACTORY Danfoss A/S (AC-SMC / MWA), Select YES by pressing with DKRCI.PD.SC0.C4.22 / 520H5916 Factory reset completed 17
18 Liquid Level Sensor, U Appendix1: Dielectric constant (default factory setting = 1.066) The dielectric constant of the refrigerant gas will change based on the temperature in the level column. If the refrigerant temperature is known the corresponding dielectric constant from the tables on p. 19 can be entered into the AKS 4100U to improve the measuring range (see the measuring range and installation information on p. 7 and 8 for more info). For CO 2 (R744) this setting is mandatory in the quick setup procedure. It is optional for refrigerants other than CO 2 (R744). Entering refrigerant dielectric gas constant (all values below are only examples) Default screen DISTANCE inmm 4 times APLICATION GAS EPS. R QUICK START SETUP TRACING VEL. 3 times STORE NO SUPERVISOR Enter password by pressing the following buttons: INFORMATION 2 times GAS EPS. R to change GAS EPS.R. (Select the correct value from the tables on the next page) to change cursorposition. to decrease the value or to GAS EPS. R or to select between STORE NO or STORE YES. Select STORE YES by pressing Default screen appears: DISTANCE in mm Entering the dielectric constant of refrigerant gas completed 18 DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
19 Liquid Level Sensor, U Appendix1 (continued) Saturated vapour dielectric constant (default value: 1.066) R717 (NH 3 ) range: 76 F +122 F ( 60 C +50 C) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R R22 range: 76 F +118 F ( 60 C +48 C) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R R410A range: 85 F +59 F ( 65 C +15 C ) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R R744 (CO 2 ) range: 56 C +15 C ( 69 F +59 F) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R R134a range: 76 F +122 F( 60 C +50 C) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R R404A range: 76 F +59 F ( 60 C +15 C) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R Danfoss A/S (AC-SMC / MWA), DKRCI.PD.SC0.C4.22 / 520H
20 Liquid Level Sensor, U Appendix1 (continued) R507 range: 76 F +59 F ( 60 C +15 C) [ F] [ C] Dielectric constant of refrigerant gas Parameter GAS EPS.R DKRCI.PD.SC0.C5.22 / 520H5916 Danfoss A/S (AC-SMC / MWA),
Liquid Level Sensor Type AKS 4100U
Data sheet Liquid Level Sensor Type U U - Cable Version U - Coaxial Version The U liquid level sensor is designed specifically to measure liquid levels in a wide range of refrigeration applications. The
More informationLiquid Level Sensor AKS 4100U
MAKING MODERN LIVING POSSIBLE Technical brochure Liquid Level Sensor U U - Cable Version U - Coaxial Version The U liquid level sensor is designed specifically to measure liquid levels in a wide range
More informationLiquid Level Sensor Type AKS 4100/4100U
Data sheet Liquid Level Sensor Type /4100U /4100U - Cable Version /4100U - Coaxial Version The /4100U liquid level sensor is designed specifically measure liquid levels in a wide range of refrigeration
More informationLiquid Level Sensor AKS 4100/4100U
MAKING MODERN LIVING POSSIBLE Technical brochure Liquid Level Sens /4100U /4100U - Cable Version /4100U - Coaxial Version The /4100U liquid level sens is designed specifically measure liquid levels in
More informationType AKS 4100/4100U Coaxial D14 version
Instruction Type /4100U Coaxial D14 version Available lengths:, 500 mm, 800 mm, 1000 mm, 1200 mm, 1500 mm, 1700 mm, 2200 mm M84H0030_1 U, 19.2 in. U, 30 in. U, 45 in. U, 55 in. U, 65 in. U, 85 in. Push
More informationSITRANS F flowmeters SITRANS F M. Transmitter MAG 6000 I/6000 I Ex d e 4/43
Overview The MAG 6000 I/I Ex d transmitter is designed for the demands in the process industry. The robust die cast aluminium housing provides superb protection, even in the most harsh industrial environments.
More information2291 Guided Wave Radar Level Transmitter
2291 Guided Wave Radar Level Transmitter Product description / Function The 2291 Guided Wave Radar level transmitter is designed for continuous level measuring of conductive or non-conductive liquids,
More informationTEK-LCD 7801A. NEMA 4X Loop-Powered Feet and Inches Level Meter. ACCESSORIES. Technology Solutions
Technology Solutions TEK-LCD 7801A NEMA 4X Loop-Powered Feet and Inches Level Meter ACCESSORIES www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction The
More informationModular Lube Lubrication Systems System Controls
Model 84501 Program Timer Solid State Designed to control the lubrication cycle frequency of air-operated single-stroke pumps. Timer turns pump on/off at programmed intervals via a 3-way or 4-way air solenoid
More informationOPTIFLEX 1100 C Handbook
OPTIFLEX 1100 C Handbook Guided Radar (TDR) Level Meter Continuous level measurement of liquids and solids KROHNE : IMPRINT ::::::::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited
More informationMechanical flow switch for On/Off control
Mechanical flow switch for On/Off control Economic integration in pipe systems without any additional piping Magnetic measuring principle Mechanical adjustment of setpoint Type 8010 can be combined with...
More informationGuided Wave Radar Level Meter
Guided Wave Radar Level Meter Guided Wave Radar Level Meter Instruction 1. Product Description 1.1 principle of measurement Guided Wave Radar is the measuring instruments that based on the time travel
More informationLevel Measurement silometer FMC 420, FMC 423
Technical Information TI 077F/00/en Level Measurement silometer FMC 420, FMC 423 For connecting to capacitance probes or Deltapilot S hydrostatic probes Main applications The is used for continuous level
More informationAnalog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/
> 8 channels for 2-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit > Module
More informationSingle Point Flow Monitor SW118 SW119
SW8 SW9 SW8 SW9 Single point flow monitors with MIN/MAX monitoring function, suitable for water, oil, air and media with similar thermal conductivities (selectable by means of a medium switch). With either
More informationOPTIFLEX 2200 C/F Technical Datasheet
OPTIFLEX 2200 C/F Technical Datasheet Guided Radar (TDR) Level Transmitter for storage and process applications Modular design of housing and sensor ensures suitability for a variety of mounting positions
More informationCapacitance Level Measurement Electronic insert FEC 12
Technical Information TI 50F/00/en Capacitance Level Measurement Electronic insert FEC Smart electronic inserts for Multicap probes DC..TE/TA and DC..E/A with HART protocol and integrated linearisation
More informationAnalog Input Module HART Ex n Inputs, 8 Channels Series 9461/15
> 8 channels for 2-wire HART transmitters > Inputs for Ex nl, Ex na and Nonincendive > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit >
More informationProcess Transmitter RMA 422
Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog
More informationPanel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features
NEMA4X, IP65 Front Bezel Meter with Relays Option RELAY2 RELAY1 24V OUT POWER 4 3 2 1 6 5 2 1 2 1 NO NC COM NO NC COM RTD TC P P RTD 3 4 1 2 5 TC 6 SWITCH Rear View Gasket APM765 Panel Meter Description
More informationGuided Radar (TDR) Level Transmitter for storage and process applications
OPTIFLEX 2200 C/F Technical Datasheet Guided Radar (TDR) Level Transmitter for storage and process applications Modular design of housing and sensor ensures suitability for a variety of mounting positions
More informationFLOMAT Electromagnetic Insertion Flowmeter
LOMAT Electromagnetic Insertion lowmeter Working pressure manufacturing according to PED 97/23/CE (Lloyd s Register Certificate Nº 031) Introduction or use in large diameter pipes or open channels as an
More informationLevel Measurement Point level measurement - RF Capacitance switches
Overview Configuration Installation Standpipes 50 (2) 20 (0.79) max. is a compact, 2-wire, inverse frequency shift capacitance switch for level and material detection in constricted spaces, interfaces,
More informationRK-2 ENVIRONMENTAL DATA CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD. Main characteristics
RK-2 CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD (ANALOG OR START/STOP OUTPUT) Main characteristics Absolute transducer Strokes from 50 to 4000mm (RK-2- -N/E/S) Digital output
More information02/11/2015
DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage
More informationCapacitance Limit Detection nivotester FTC 420/421/422
Technical Information TI 127F/00/en Capacitance Limit Detection nivotester FTC 420/421/422 Limit switches in Minipac design for liquids and bulk solids Application Nivotester FTC 420...422 capacitive limit
More information48x24. Options ORDER NUMBER OF TYPE PFL B
Frequency metering (0.01 Hz 9999 Hz) with 2 setpoints Free scalable indication and setpoints from 0 up to +9999 Standard: min/max memory - option: analogue output Allow to be placed side by side in grid
More informationDissolved Oxygen Transmitter
3 YEAR SENSOR WARRANTY 5.4 We reserve the right to continuously improve our products and make any change in the stated specifications and dimensions without prior notice. General MJK Oxix s are designed
More informationTUC: Universal thermostat
Product data sheet 3.1 21.700 TUC: Universal thermostat How energy efficiency is improved Control, monitoring and limiting according to needs and with no auxiliary energy. Features Regulates and monitors
More informationTFRH Hygienic RTD temperature sensor. CombiTemp TM
Main features Pt100 sensor element, 2- or 4-wire uilt in graphical display, CombiView TM DFON optional Head mounted transmitter, FlexTop type 22xx HART, PA ATEX 3-A, FDA Programmable by touch screen Easy
More informationFLOMAT. Flowmeters. Electromagnetic Insertion Flowmeter: Series. Instrumentation for fluids
Flowmeters Instrumentation for fluids Series FLOMT FLOMT Electromagnetic Insertion Flowmeter: Introduction For use in large diameter pipes or open channels as an economical solution for liquid metering.
More informationGRUNDFOS alldos product information. The solution for complex dosing tasks
GRUNDFOS alldos product information The solution for complex dosing tasks Measurements Measurements a h d Electric actuator b Pneumatic actuator g e Ø 9mm k f i m 1 m 2 k j c n l 1 l 2 DMH model Measurements
More informationStandard RS232 RS ma
1 / 5 CONTROL AND VISUALIZATION OF AC CURRENT IN SINGLE PHASE LINES BY EXTERNAL SHUNT Function Operating mode Current control Frequency control DC component control Shunt Timer Resolution Current precision
More informationAF-300 E11 Adjustable Frequency Drive
AF-300 E11 Adjustable Frequency Drive The AF-300 E11 adjustable frequency drive is GE s new generation of micro drives. GE recognized your need for a high-performance, full-featured compact drive and designed
More informationDMP 335 DMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. Pressure Transmitter. Industrial
DMP 5 Industrial Pressure Transmitter Welded, Dry Stainless Steel Sensor accuracy according to IEC 60770: 0.5 % FSO Industrial Pressure Transmitter Nominal pressure from 0... 6 bar up to 0... 600 bar Output
More informationFlow Measurement SITRANS F M
Overview Limit switches and pulse output Batch control The MAG 6000 I/6000 I Ex is a microprocessorbased transmitter with a builtin alphanumeric display in several languages. The transmitters evaluate
More informationTFRN Industrial RTD temperature sensor. CombiTemp TM
Main features Pt100 sensor element, 2- or 4-wire HART uilt in graphical display, CombiView TM DFON optional Head mounted t ransmitter, FlexTop type 22xx ATEX Programmable by touch screen Easy and full
More informationDissolved Oxygen Transmitter
Data Sheet 3 YE A SEN R WAR SOR RAN TY 5.4 We reserve the right to continuously improve our products and make any change in the stated specifications and dimensions without prior notice. DK: NO: SE: NL:
More informationFlow Measurement SITRANS F M
Overview Design The transmitter is designed as either IP67 NEMA 4X/6 enclosure for compact or wall mounting or 19" version as a 19 insert as a base to be used in: 19" rack systems Panel mounting IP20/NEMA
More informationMagnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A
and 3DPT, 10 A UL Listed when used with proper Magnecraft s The 750R series octal base, plug-in relays offer clear or full-feature covers with multiple mounting options and accessories. 750R 750R Full-Feature
More informationInductive sensor. 2-wire, analog output BI8-M18-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M18 x 1 Chrome-plated brass 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection Wiring diagram Type code Ident no.
More informationDescription. Specifications and Ordering Information 1900/27 Vibration Monitor
R Specifications and Ordering Information 1900/27 Vibration Monitor Description The 1900/27 is a single-channel, stand-alone, locally mounted vibration monitor. It can be used as a stand-alone machinery
More informationLinear flow controls VFC Linear flow controls with actuator IFC
Linear flow controls VFC Linear flow controls with actuator Product brochure GB 3 Edition 01.16 Linear relationship between adjustment angle and flow rate Large control ratio of 25:1 Actuators IC 20 or
More informationFIELD MOUNTED RATE TOTALISER MODEL 202D
FIELD MOUNTED RATE TOTALISER MODEL 202D 16 June 2003 Introduction 1 1. INTRODUCTION The Model 202Di Rate Totaliser is a microprocessor based instrument which accepts a frequency or pulse input from
More information1.5mm amplitude at 10 to 55Hz frequency in each X, Y, Z direction for 2 hours 500m/s² (approx. 50G) in each X, Y, Z direction for 3 times
Color Mark Color Mark Feature Outstanding color matching accuracy - RGB light emitting diodes and 12-bit resolution - 2 detection modes (color only / color + intensity) - -step sensitivity adjustment for
More informationLinear flow control with actuator IFC
Linear flow control with actuator Product brochure GB 3 Edition 01.14 Linear relationship between adjustment angle and flow rate Large control ratio of 25:1 EC type-tested and certified Actuators IC 20
More informationMaterial: Weight: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:
Oil & Gas / Heavy Industry Type 2REX-H-SR EN 60079 Electrical Specifications Code: Resolution: Supply Voltage: Voltage: Current: Incremental 1 to 10,000 ppr (pulses per revolution) 4.5 Vdc min. to 30 Vdc
More informationSQM40/41 Actuators for air and gas dampers
SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The
More informationRIA46. Technical Information. Field meter Digital field meter with control unit for monitoring and visualizing analog measured values
Technical Information RIA46 Field meter Digital field meter with control unit for monitoring and visualizing analog measured values Application Process recording and supervision Process control Signal
More informationDMP 331i DMP 333i. Precision Pressure Transmitter. Stainless Steel Sensor. accuracy according to IEC 60770: 0.1 % FSO
DMP i DMP i Precision Pressure Transmitter Stainless Steel Sensor accuracy according to IEC 600: 0. % FSO from 0... 00 mbar up to 0... 600 bar Output signal wire:... 0 ma wire: 0 0 V others on request
More informationInductive sensor NI3-EG08K-Y1-H1341
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationDMP 335. Industrial Pressure Transmitter. Welded, Dry Stainless Steel Sensor. accuracy according to IEC 60770: 0.5 % FSO.
DMP 5 Industrial Pressure Transmitter Welded, Dry Stainless Steel Sensor accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 6 bar up to 0... 600 bar Output signals -wire: 4... 0 ma -wire:
More informationFTS84/85 Feature Application Field. Temperature & Humidity / Flow Measuring Specialist. Monitor gas and flow for industrial process
FTS84/8 Feature Application Field Capable of temperature compensation and linear adjustment Double line character : air velocity & temperature Switch for physical quantity:[m/s] [ft/s] [km/h] [mph] [knot]
More informationSmart-Encoder : Optical Incremental
1. Introduction The Smart-Encoder effectively eliminates multiple encoder part numbers by bringing intelligence and security to its design. In seconds, a four-digit LED display with two push-buttons enables
More informationRIA45. Technical Information. Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values
Technical Information RIA45 Panel meter Digital panel meter with control unit for monitoring and visualizing analog measured values Application Plant and apparatus engineering and construction Control
More informationInductive linear position sensor LI300P0-Q25LM0-LIU5X3-H1151
Rectangular, aluminium / plastic Versatile mounting possibilities LED indicates measuring range Immune to electromagnetic interferences Extremely short blind zones 12 bit resolution 4-wire, 15 30 VDC Analog
More informationDATA SHEET Panorama Rudder Indicator, TRI-2
DATA SHEET Panorama Rudder Indicator, TRI-2 Class 1 accuracy on CAN version Readable from up to 5 metres Single and dual CAN or analogue interface LED illumination DEIF A/S Frisenborgvej 33 DK-7800 Skive
More informationHygrotest 600. Instruction manual WH / WHT -20/+70 C DH / DHT -20/+70 C / DHT -20/+120 C PHT -20/+70 C / PHT -20/+120 C
Hygrotest 600 Instruction manual en WH / WHT -20/+70 C DH / DHT -20/+70 C / DHT -20/+120 C PHT -20/+70 C / PHT -20/+120 C Contents Introduction...2 Handling instructions...3 Dimensions of measuring instrument...3
More informationTFRN Industrial RTD temperature sensor. CombiTemp TM
Main features Pt100 sensor element, 2- or 4-wire HART, PA Built in graphical display, CombiView TM DFON optional Head mounted t ransmitter, FlexTop type 22xx ATEX Programmable by touch screen Easy and
More informationAK-PVE4 Operating Instructions. Measuring of norm signals in wall-type units. Performance:
AK-PVE4 Operating Instructions Measuring of norm signals in wall-type units 1 2 P Performance: Digit heights: 20 mm Colour: red Display range: -999 9999 Wall-type housing: light grey made of ABS-plastic
More informationLevel Measurement Point level measurement RF Capacitance switches
Siemens AG 2018 Overview Configuration Installation Standpipes 50 (2) 20 (0.79) max. is a compact, 2-wire, inverse frequency shift capacitance switch for level and material detection in constricted spaces,
More informationGenerator protection relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and
More informationPendant Light Fitting IEC Series 6470/2
> Available light sources high-pressure sodium lamps (HSE) metal halide lamps (HIE) halogen lamps (QT) > Versatile mounting methods > Enclosure made of saltwater-resistant aluminium www.stahl.de 11435E
More informationOperating Instructions 09/2013
Guided Wave Radar SITRANS LG250 4 20 ma/hart - two-wire Operating Instructions 09/2013 2 SITRANS LG250 - Operating Instructions PBD-51041047 Contents 1 About this document 1.1 Function... 5 1.2 Target
More informationMaterial: Weight: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:
Oil & Gas / Heavy Industry Type 2REX-H EN 60079 Electrical Specifications Code: Resolution: Supply Voltage: Voltage: Current: Incremental 1 to 10,000 ppr (pulses per revolution) 4.5 Vdc min. to 30 Vdc
More informationStandard signal metering in wall-mounting case
User manual AKV-2VR4C Standard signal metering in wall-mounting case Technical features: Digit height: 20 mm Colour: red Range of display: -999 9999 Wall-mounting case: black, made of ABS-plastic Protection
More informationMG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV
MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper
More informationSignet 2250 Hydrostatic Level Sensor
Signet 2250 Hydrostatic Sensor *32250.090* 32250.090 Rev. A 10/06 English English Safety Instructions 1. Prior to installation or removal: Depressurize and vent system Drain below sensor level 2. Confi
More informationInductive sensor BI1.5-EG08K-Y1
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationDMP 331i / DMP 333i LMP 331 i
DMP i / DMP i LMP i Precision Pressure Transmitter / Screwin transmitter Stainless Steel Sensor accuracy according to IEC 60770: 0. % FSO from 0... 00 mbar up to 0... 600 bar Output signal wire:... 0 ma
More informationAbsolute Encoders Multiturn
The Sendix 5863 and 5883 multiturn encoders with SSI or BiSS-C interface and optical sensor technology can achieve a resolution of max. 29 bits. A through hollow shaft up to 4 mm and a blind hollow shaft
More information7 Lighting Technology
7 Lighting Technology Floodlight 09676E00 explosion protected floodlight for use in explosive gas atmospheres of Zone 2 as well as in areas with combustibledust of Zone 21 and Zone 22. Explosion protection
More informationMTI-2100 FOTONIC SENSOR. High resolution, non-contact. measurement of vibration. and displacement
A worldwide leader in precision measurement solutions MTI-2100 FOTONIC SENSOR High resolution, non-contact measurement of vibration and displacement MTI-2100 Fotonic TM Sensor Unmatched Resolution and
More informationLMP 305. Slimline Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.
Slimline Probe Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO Nominal pressure from 0... mh 2 O up to 0... 250 mh 2 O Output signals 2-wire: 4... 20 ma
More informationWall-/Pipe-Mount Level Indicator
Data Sheet SS/_4 Wall-/Pipe-Mount Level Indicator High visibility 5-digit LED display clear multi-functional indication Analog and 2-relay outputs as standard high, low, latch and rate alarms, plus isolated
More informationDMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0,35 % FSO. Nominal pressure
DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0,5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity
More informationABB MEASUREMENT & ANALYTICS DATA SHEET. AZ100 series Zirconia oxygen analyzer for small boiler applications
ABB MEASUREMENT & ANALYTICS DATA SHEET AZ00 series Zirconia oxygen analyzer for small boiler applications AZ 00 SE RIE S Z I RCON I A OX YG EN ANALY ZE R FOR SMALL BOILE R APPLIC ATIONS DS/AZ00-E N RE
More informationSITRANS F M. Transmitter MAG 5000/6000 4/33
Siemens AG 2011 Flow Measurement Overview Design The transmitter is designed as either IP67 NEMA X/6 enclosure for compact or wall mounting or 19" version as a 19 insert as a base to be used in: 19" rack
More informationElectronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,
Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency, Temperature, RPM, Pressure, etc. LED/ LCD displays 1999 to 99999
More informationCoils for solenoid valves
MAKING MODERN LIVING POSSIBLE Technical leaflet Coils for solenoid valves www.danfoss.com B and A coils Encapsulated coils with long operating life, even under extreme conditions Standard coils for a.c.
More informationMT03A Electronic converter for flow rate transmitters
Instructions manual MT03A Electronic converter for flow rate transmitters The art of measuring R-MI-MT03A Rev.: 0 English version PREFACE Thank you for choosing a Tecfluid S.A product. This instruction
More informationE6CP-A. An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. Low-cost Encoder with Diameter of 50 mm
Low-cost Encoder with Diameter of 50 mm CSM DS_E An Absolute Encoder at About the Same Price as an Incremental Encoder. Ideal for robot limit signals. High-precision detection of automatic machine timing.
More informationInstallation and User Guide 458/CTR8 8-Channel Ballast Controller Module
Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach
More informationEA PROFIBUS SINGLETURN ABSOLUTE ENCODER PRESENTATION HARDWARE INSTALLATION DEVICE SINGLETURN ABSOLUTE ENCODERS EA PROFIBUS
EA PROFIBUS SINGLETURN ABSOLUTE ENCODER PRESENTATION The Eltra singleturn Pro bus encoder series (Identi cation Number 0x0599) is complying to the Pro bus DP standard as described on the European Standard
More informationOrdering details. Approval. Classification
Datasheet - SRB 301MC-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301MC Fit for signal evaluation
More informationDS 200 P DS 200 P. Electronic Pressure Switch with Flush Process Connection
with Flush Process Connection piezoresistive pressure sensor up to independent contacts, configurable optional: analogue output Exprotection (for wire) cooling element up to 00 C nominal pressure ranges
More informationENC - LKE51 - L I B
ENC-LKE51 Linear Magnetic Encoder FEATURES DESCRIPTION LKE51 ORDERING INFORMATION Resolutions: 5, 10, 25, and 50μm Linear Travel Speed: Up to 16m/s Standard Sensor for Linear and Rotary Axis Gap Clearance
More informationSHOWLINE SL BAR 640 LINEAR WASH LUMINAIRE SPECIFICATIONS.
GENERAL. A.) Overview. SHOWLINE SL BAR 640 LINEAR WASH LUMINAIRE SPECIFICATIONS. 1.) The luminaire shall be a color mixing luminaire employing twenty-four (24) red, green, blue, and white LED engines.
More informationUDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4
UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines
More informationBS36 Waveform TDR (Time Domain Reflectometry) Cable Fault Locator
BS36 Waveform TDR (Time Domain Reflectometry) Cable Fault Locator Prepared by Kit Page 1 of 10 BS36 Waveform Cable Fault Locator is highly accurate portable measuring instrument based on TDR (Time Domain
More informationElectromechanical Level Measurement Systems silopilot FMM 760, FMM 760 Z
Technical Information TI 280F/00/en Electromechanical Level Measurement Systems silopilot FMM 760, FMM 760 Z Level measurement system of high versatility for bulk solids and liquids Application The Silopilot
More informationAssembly. Front view. LEDs. Parametrization interface. Power Bus
otation Speed Monitor Features Assembly 1-channel signal conditioner 2 V DC supply Input for 2- or -wire sensors Input frequency 10 mhz... 50 khz elay contact output Start-up override and restart inhibit
More informationProcess transmitter RMA422
Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set
More informationOperating Instructions
CNTX Contrast sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target
More informationWeekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N
Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control
More informationFTS84/85 Feature Application Field. Temperature & Humidity / Flow Measuring Specialist. Monitor gas and flow for industrial process
FTS84/8 Feature Application Field Capable of temperature compensation and linear adjustment Double line character : air velocity & temperature Switch for physical quantity:[m/s] [ft/s] [km/h] [mph] [knot]
More informationMicro-DCI 53ML5100 Manual Loader
Micro-DCI 53ML5100 Manual Loader Two process variable inputs Two manually controlled current outputs Multiple Display Formats: Dual Channel Manual Loader, Single Channel Manual Loader, Manual Loader with
More informationAbsolute Rotary Encoder E6CP
Absolute Rotary Encoder Absolute Rotary Encoders with Gray Code Output Gray code output decreases output errors Lightweight plastic housing Used with Omron s H8PS Cam Positioner, this encoder detects the
More informationE8Y. Micropressure Sensor with Easy-to-Read Digital Display. Differential Pressure Sensor. Ordering Information. Sensors
Differential Sensor Micropressure Sensor with Easy-to-Read Digital Repeat accuracy of ±1% FS (setting resolution: 0.01 kpa), high-precision pressure control available. Compact design (31 mm) saves mounting
More informationLAUREL ELECTRONICS, INC.
LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process, Strain & Potentiometer Follower Signals Features Selectable ±0.2, ±2, ±20, ±200, ±300 & ±600 Vdc voltage ranges Selectable ±2, ±20, ±200
More information