Failure Report. elbow near termination on bend. live-front

Size: px
Start display at page:

Download "Failure Report. elbow near termination on bend. live-front"

Transcription

1 Failure Report Circuit owner: Entergy (Gulf States) Segment: Work Order: Goslin Feeders (PO ) Termination 1: Gosling RD Termination 2: Woodlands DR/Gosling RD Failure type: Cable Termination Splice Other buried elbow near termination on bend Failure location & description live-front An Elastimold 35PCJ1P [14-10] splice failed on the B phase of the Goslin Feeder circuit at the second pit near the corner of Gosling and Woodlands. The splice joined a short segment of new EPR cable and a treated PE cable. The splice failed on the side adjacent to the EPR cable. The Elastimold splice body, a short section of EPR cable, a short section of treated PE cable, and the compression connector/injection adaptor assembly (hereafter the assembly ) were sent to Kent. Injected: May 12, 2008 Failed: May 23, 2008 at 5:30 A.M. Elapsed: 11 days Summary Figure 1 shows the sample components excluding the splice body as they were received. The cable was severed at the interface between the new EPR cable and the compression connector. Figure 2 shows a sectioned view of the splice body interior as it was received. The Elastimold splice body included a molding flaw at the interface between the EPDM insulation and the outer semiconducting shield. This flaw is visible in Figure 2 and enlarged in Figure 3. This flaw may have caused reliability issues had it remained in service, but its presence was in no way related to the failure. The inside of the splice body, enlarged in Figure 4, demonstrates extensive tracking along the entire 360 circumference of the interface between the EPR cable insulation and the EPDM insulation of the splice body. Within the splice body, the EPR experienced very high temperatures over a prolonged period of time, as the EPR is thinner and asymmetrical. This deformation was not present outside of the splice body. The asymmetry and the thinning of the insulation are illustrated in Figure 5, where the sample was cut at approximately 6 inch intervals to reveal the cable cross section. Figure 6 was prepared by cutting the Copyright 2008, Novinium, Inc. All rights reserved. Page 1 of 5

2 compression connector/injection adaptor assembly and a portion of the connected PE cable with an abrasive water jet to preserve internal features. Compression connector/injection adaptor assembly PE Cable EPR Cable Sample as received Figure 1. Internal components as received. Cable and assembly were severed. Index marks (each one inch apart) were added to the EPR cable starting with zero at the right cable end. The EPR cable was approximately 22.5 long. Molding flaw (see Fig. 3) 360 tracking (see Fig. 4) Figure 2. Splice body cut along an axis to allow inspection of the internal surfaces. Molding flaw increases local electrical stress and voids within flaw may create partial discharges Figure 3. Molding flaw unrelated to the failure of the splice may have created future reliability issues. The failure sample handling was not performed according to NRI 93. For example, solvents where used to clean portions of the sample prior to the sample being shipped to the Novinium laboratory. Improper sample handling may reduce the reliability of failure analysis. NRI-93 was first promulgated on May 25 th, two days after the failure and hence the injection team had not yet been exposed to the failure sample handling instructions. Copyright 2008, Novinium, Inc. All rights reserved. Page 2 of 5

3 Figure 4. Close-up of 360 tracking shows uniform and extensive damage. 240 mils 350 mils Figure 5. EPR cable in cross section approximately every 6 inches. From left to right, the cross sections are at 5.5, 11.5, 17.7 and 22.5 index marks respectively. Only the cable within the splice body was deformed indicating that the fault was the cause of the deformation. This deformation could only occur with prolonged temperatures well above 130 C Figure 6. An abrasive water jet was used to section the compression connector/injection adaptor assembly and the attached PE cable. Gaps in the assembly indicate improper craft work. Figure 6 is annotated with three gaps and the PE insulation cutback in red. The first 0.6 gap delineates the volume between the EPR strands and the water stop in the compression connector. There should be no Copyright 2008, Novinium, Inc. All rights reserved. Page 3 of 5

4 more than a 0.1 gap here. Installation instructions require that the strands touch the water stop. At least 0.5 of excess length was added to the assembly length by this craft error. This error would have been obvious if the installation template were used. The second 0.1 gap is the volume between the PE cable conductor strands and the compression connector water stop. This gap is within normal installation parameters and is created by differential elongation upon application of the swage. The third gap is the 0.2 between the injection adaptor shoulder stop and the compression connector. There should not be a gap here. In fact, when properly installed some aluminum from the compression connector extrudes past the shoulder. This error would have been obvious if the installation template were used. Finally, the cutback length of 2.7 is 0.2 greater than the required 2.5 and is the root cause of the aforementioned 0.2 gap. These errors together lengthened the assembly by about 0.7. When assembled correctly there is 0.61 of clearance within the conductive insert on each side or a total of At least 0.7 of that clearance was eliminated by improper assembly. A properly centered splice would have 0.52 of total clearance or 0.26 on either side. This is an unacceptably small margin even if the splice body were perfectly centered. The splice body was almost certainly not centered. The pattern of internal tracking around the entire inside circumference of the splice body suggests uniform encroachment by the compression connector past the conductive insert and into the insulation interface. The installer did not use a template and did not provide adequate permanent marks to center the splice. As seen in Figure 7, there may be some residual marking tape on one side of the splice, but it is not applied perpendicular to the axis. There is no evidence that marking tape was applied to the other side of the splice. Figure 7. Splice before removal Marking tape? Though probably not directly related to the fault, Figure 1 illustrates that the insulation shield cutbacks were incorrect on both cable ends. The installer clearly did not use the template for these cutbacks as such errors are obvious with even a cursory inspection. The individual (Mr. Gabe Durant) who installed this splice did not provide the following permanent marks, which are required by the Novinium NRIs: Copyright 2008, Novinium, Inc. All rights reserved. Page 4 of 5

5 1. There was no permanent tape or mark to demarcate a centered splice. See NRI 32, step 2 and There was no permanent tape or mark to demarcate the cleaned area of the insulation shield where a molded splice is parked. See NRI 32, step 2 and There was no permanent mark on the injection adaptor to indicate who performed the craftwork. See NRI 32, step There was no positioning line drawn on the insulation. See NRI 30, step 18 and NRI 32, step 4. Corrective Novinium has taken 1 the following case specific and general corrective actions to reduce the probability of a reoccurrence. Case Specific Corrective Actions Mr. Gabe Durant of Finway, Inc. has been decertified and will not be allowed to work for Novinium until he is recertified. Novinium recommends 3M splices and terminations. General Corrective Actions Asymmetrical splice templates (i.e. a splice with a single injection adaptor) are being redrafted to remove the unnecessary and excess gap between the insulation on the non-injected side and the compression connector. This change provides for a greater margin of craft error on assembly length and centering. For an Elastimold 35PCJ1P [14-10], the total margin is increased by about Proper failure handling instructions (NRI 93) are being pushed to all field injection personnel. Durable metallic craftsman tags are being distributed and will be attached to all compression connectors to document workmanship responsibility. Lead Investigator: Glen J. Bertini Date: August 9, In some cases the corrective actions require some developmental work and may not be fully implemented by the report date. Copyright 2008, Novinium, Inc. All rights reserved. Page 5 of 5

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 102 2010 Cable Retention Force Testing of Trunk & Distribution Connectors NOTICE The Society of Cable Telecommunications

More information

AMERICAN NATIONAL STANDARD

AMERICAN NATIONAL STANDARD Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 108 2018 Test Method for Dielectric Withstand of Coaxial Cable NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 SUMMARY A. Section includes cables and related cable splices, terminations, and accessories for mediumvoltage (2001 to 35,000 V) electrical distribution

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 CABLES SPLICES 1.0 SCOPE TABLE OF CONTENTS 2.0 CABLES SPLICES 2.1 Definitions 2.2 Scope of Specifications and Drawings 2.3 General Requirements 2.4 Routing Cables 2.5 Connectors 2.6 Conductor Connections 2.7 Heat Shrinkable

More information

SJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1

SJOF-BS604B. Fiber Optic Splice Closure User Manual Rev.1 Fiber Optic Splice Closure 1. Introduction 1.1 General SAMJIN s SJOF-BS604B protects fiber optic splicing point in various installation conditions such as aerial, manholes, ducts, wall and direct buried

More information

Cable Retention Force Testing of Trunk & Distribution Connectors

Cable Retention Force Testing of Trunk & Distribution Connectors ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 102 2016 Cable Retention Force Testing of Trunk & Distribution Connectors NOTICE The Society of Cable Telecommunications

More information

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes. SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of

More information

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN

COOPER POWER SERIES. 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions. Deadbreak Apparatus Connectors MN650017EN Deadbreak Apparatus Connectors MN650017EN Effective January 2016 Supersedes S600-46-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class DT625 T-body installation and cable preparation instructions DISCLAIMER

More information

Pivot Power RJ45 Modular Plug Connectors

Pivot Power RJ45 Modular Plug Connectors Pivot Power RJ45 Modular Plug Connectors Application Specification 114-32052 07 OCT 13 i All numerical values are in metric units [with U.S. customary units in brackets]. Dimensions are in millimeters

More information

VITALink Taped Splice Straight Through Crimp

VITALink Taped Splice Straight Through Crimp A Marmon Wire & Cable Berkshire Hathaway Company VITALink Taped Splice Straight Through Crimp 2 Hour Fire-Rated Splice VITALink MC Cables, UL FHIT 120 Installation Instructions Description The VITALink

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE Test Method for Cable Weld Integrity

ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE Test Method for Cable Weld Integrity ENGINEERING COMMITTEE Interface Practices Subcommittee SCTE 178 2011 Test Method for Cable Weld Integrity NOTICE The Society of Cable Telecommunications Engineers (SCTE) Standards are intended to serve

More information

Installation Manual SaVi Note Underwater LED Light

Installation Manual SaVi Note Underwater LED Light Installation Manual SaVi Note Underwater LED Light Model Numbers SAVI-NOTE7, SAVI-NOTE0 Table of Contents Safety Precautions...2 SaVi Note Install Instructions...3- M Instructions...- Warnings READ AND

More information

Preventing Fieldbus Physical Layer Problems

Preventing Fieldbus Physical Layer Problems Preventing Fieldbus Physical Layer Problems 1 Introduction Foundation Fieldbus is highly reliable when correctly installed and maintained. The key is in knowing what must be done to start with and to maintain

More information

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7)

TFT-150R-G. Tape Shield Cable (page 2) Suggested Installation Equipment (not supplied with kit) Wire Shield Cable (page 7) TFT-150R-G 5-15kV Cold Applied Indoor (5-8kV Indoor and Outdoor) Termination for Copper Tape, Wire Shield, Lead Sheath, and UniShield Cable Suggested Installation Equipment (not supplied with kit) Cable

More information

HEALTH AND SAFETY MANUAL

HEALTH AND SAFETY MANUAL HEALTH AND SAFETY MANUAL Title: Grounding Conductor Program Approved by: Greg Savoy Rev. 4/1/08 1 Purpose/Scope: The purpose of this program is to provide requirements to reduce employee potential for

More information

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40

3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40 3M Scotchcast Mine and Portable Cable Splice and Jacket Repair Kit M-40 Instructions 1 & 2 For Jacket Repair (pages 2 & 7) Supplemental Instructions for: Insulation Repair (page 12) Conductor Repair (page

More information

Jul03 Rev C EC

Jul03 Rev C EC Product Specification Coaxial BNC Solder Receptacle Connector 108-12079 10Jul03 Rev C EC 0990-0940-03 1. SCOPE 1.1. Content This specification covers the performance, tests and quality requirements for

More information

Industrial Loadbreak Elbow

Industrial Loadbreak Elbow Industrial Loadbreak Elbow 200 A 5, 8, and 15 kvclass 5810 Series Installation Instructions 1.0 General The 3M Industrial Loadbreak Elbow connector is a fullyshielded and insulated plug-in termination

More information

Spectra Batten (Order code: LEDJ95)

Spectra Batten (Order code: LEDJ95) www.prolight.co.uk Spectra Batten (Order code: LEDJ95) Safety WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! CAUTION! Keep this equipment away from rain,

More information

3M Motor Lead Inline Splice 5331, 5332, 5333 & 5334

3M Motor Lead Inline Splice 5331, 5332, 5333 & 5334 3M Motor Lead Inline Splice 5331, 5332, 5333 & 5334 for 5/8 kv Non-Shielded and Shielded Cables (Ribbon, Wire and UniShield Cables) Instructions Cable Size Range: Feeder: #8 AWG 500 kcmil Motor Lead: #10

More information

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series

3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series 3M Scotchcast Reenterable Signal and Control Cable Splicing Kits 78-R Series Instructions Voltage Rating: 1000 V, Temperature Rating: 90 C Kit Contents 78-R1 78-R2 78-R3 78-R4 78-R5 Sleeve Set 1 1 1 1

More information

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL

Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std kv Class 250 kv BIL Cold Shrink Three-Conductor Splice Kit QS-III for use on Armor and Non-Armor Cables Instructions IEEE Std. 404 35 kv Class 250 kv BIL Kit Number 5798A-MT Cable Range Requirements Cable Insulation O.D.

More information

Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles

Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles PV Wiring: Continuous Currents through Curious Cables by John Wiles When inspectors see a photovoltaic (PV) power system for the first time, they will usually be faced with a type of wiring method not

More information

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure The Case of the Energized Cable Cutting Incident How miscommunication leads to an electrical helper slicing through live 13.8kV cable and miraculously walking away to tell about it By Bob Huddleston, Eastman

More information

Colour Explosion Proof Video Camera USER MANUAL VID-C

Colour Explosion Proof Video Camera USER MANUAL VID-C Colour Explosion Proof Video Camera USER MANUAL VID-C Part Number: MAN-0036-00 Rev 4 Copyright 2002 Net Safety Monitoring Inc. Printed in Canada This manual is provided for informational purposes only.

More information

0.4 mm Pitch, Horizontal mating, Board- to-fine Coaxial Cable Connectors

0.4 mm Pitch, Horizontal mating, Board- to-fine Coaxial Cable Connectors 0.4 mm Pitch, Horizontal mating, Board- to-fine Coaxial Cable Connectors DF49 Series Reliable connection 0.7±0.1 (Mated height) (0.5) Effective mating length Figure. 1 Mis-insertion Prevention Features

More information

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT

3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT 3M Cold Shrink QS-III Silicone Rubber Splice Kit 5488A-TOW/WOT For Tape Over Wire (TOW) and Wire-Over-Tape (WOT) Shielded Cable For 250 2000 kcmil cable with 650-mil primary insulation thickness Instructions

More information

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK

ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK ECONOMICAL 36 kv CABLE SYSTEM FOR THE BELGIAN NETWORK J. Becker NEXANS BENELUX S.A. F. Musique ELECTRABEL S.A. ABSTRACT In order to tackle the deregulated market with confidence and in a realistic way,

More information

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-500-1000 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL F CAUTION Working around

More information

National Wire and Cable and National Cable Molding Headquarters Los Angeles California

National Wire and Cable and National Cable Molding Headquarters Los Angeles California National Wire and Cable and National Cable Molding Headquarters Los Angeles California CAPABILITIES Medical Business Machines Communications Equipment Computer Equipment Audio Systems General Instrumentation

More information

3M Cold Shrink Splice Kit QS-III 5416A

3M Cold Shrink Splice Kit QS-III 5416A 3M Cold Shrink Splice Kit QS-III 5416A for Jacketed Concentric Neutral (JCN) and Concentric Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL CAUTION Working around energized systems may

More information

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS

3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS 3M Cold Shrink QS4 Integrated Splice Kit QS4-35TS-350-1000 for Tape Shield, Wire Shield, UniShield, and Longitudinally Corrugated (LC) Cable Instructions IEEE Std. 404 35 kv Class 250 kv BIL F CAUTION

More information

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical

More information

3M Cold Shrink Splice Kit QS-III 5515A

3M Cold Shrink Splice Kit QS-III 5515A 3M Cold Shrink Splice Kit QS-III 5515A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric

More information

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd. ELECTRICAL SAFETY INSPECTION REPORT MTM Garments Ltd. 15934/16004, Chanpara, Medical Road, Uttarkhan, Dhaka, Bangladesh. Factory List MTM Garments Ltd. Inspected by: Hemlal Dahal Report Generated by: Hemlal

More information

HSK Mine and Portable Cable Splice

HSK Mine and Portable Cable Splice 8096-4-HSK Mine and Portable Cable Splice Instructions 5 and 8 kv rated cables; Type SHD-GC Size 2/0 4/0 (connector max. length 2 1/2") 8096-4-HSK Mine and Portable Cable Splice 78-8119-6296-4-A 1 1.0

More information

ELECTRICAL INCIDENT REPORT BUSHFIRE NEAR 22 NUKKLGUP LOOP YALLINGUP WESTERN AUSTRALIA 5 JANUARY Report prepared by: EnergySafety WA EIS

ELECTRICAL INCIDENT REPORT BUSHFIRE NEAR 22 NUKKLGUP LOOP YALLINGUP WESTERN AUSTRALIA 5 JANUARY Report prepared by: EnergySafety WA EIS ELECTRICAL INCIDENT REPORT BUSHFIRE NEAR 22 NUKKLGUP LOOP YALLINGUP WESTERN AUSTRALIA 5 JANUARY 2015 Report prepared by: EnergySafety WA EIS2015-0009 12 June 2015 TABLE OF CONTENTS 1. SUMMARY... 3 2. EXAMINATION...

More information

THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS

THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS THE EFFECT OF LOOSE CONNECTORS ON SHIELDING EFFECTIVENESS Asheridge Communications (A Teleste PLC Company) has undertaken a study to further understand the issues of RFI (Radio Frequency Interference)

More information

3M Cold Shrink Splice Kit QS-III 5514A

3M Cold Shrink Splice Kit QS-III 5514A 3M Cold Shrink Splice Kit QS-III 5514A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric

More information

0.3 mm Pitch, 1.5 mm Mated Height, Board- to-fine Coaxial Cable Connectors

0.3 mm Pitch, 1.5 mm Mated Height, Board- to-fine Coaxial Cable Connectors All non-rohs products have been discontinued, or will be discontinued soon. Please check the products status on the Hirose website RoHS search at www.hirose-connectors.com, or contact your Hirose sales

More information

Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98)

Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98) Mediacom Upgrade/Splicing Procedures (based on original document from Corporate dated 4/16/98) 1. Splicing specifications are provided by Mediacom, but due to resplice conditions, many locations become

More information

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF

3M Cold Shrink QS-III Splice Kit 5467A(S)-WF 3M Cold Shrink QS-III Splice Kit 5467A(S)-WF for Jacketed Concentric Neutral (JCN) Cable Instructions IEEE Std. 404 35 kv Class 250 kv BIL F CAUTION Working around energized systems may cause serious injury

More information

IPC-A-610F COMPONENT LEVEL ACCEPTANCE CRITERIA TRAINING CERTIFICATION EXAM (DVD-180C) v.1

IPC-A-610F COMPONENT LEVEL ACCEPTANCE CRITERIA TRAINING CERTIFICATION EXAM (DVD-180C) v.1 This test consists of twenty-five multiple-choice questions. All questions are from the video: IPC-A-610F Component Level Acceptance Criteria (DVD-180C). Use the supplied Answer Sheet and circle the letter

More information

Instructions. Cable with Armor F CAUTION. October Rev A

Instructions. Cable with Armor F CAUTION. October Rev A 3M Single Conductor Accessory Breakout Kits (BOK's) for use with 3M Cable Accessories (Terminations, T-Bodies and Push-On Elbows) For Use With Single Conductor Accessories On Three-Core Conductor Cables

More information

OPERATOR MANUAL OSD8865 DIGITAL TRIPLE VIDEO FIBER OPTIC RECEIVER

OPERATOR MANUAL OSD8865 DIGITAL TRIPLE VIDEO FIBER OPTIC RECEIVER OPERATOR MANUAL OSD8865 DIGITAL TRIPLE VIDEO FIBER OPTIC RECEIVER INDEX 1 1 TECHNICAL SUMMARY... 4 1.1 BRIEF DESCRIPTION... 4 1.1.1 OVERVIEW... 4 1.1.2 APPLICATIONS... 4 1.1.3 FEATURES AND BENEFITS...

More information

IndyGo Facility Upgrades Project 35671EE

IndyGo Facility Upgrades Project 35671EE SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for

More information

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 103 2018 Test Method for DC Contact Resistance, Drop cable to F connectors and F 81 Barrels NOTICE The Society of Cable Telecommunications

More information

Building a MidiBox LCD Cable

Building a MidiBox LCD Cable Building a MidiBox LCD Cable By Jim Henry, 3-Apr-2004 An LCD panel may be connected to the Core module by a 16 conductor flat ribbon cable. A 16 pin insulation displacement connector (IDC) terminates one

More information

MDA-2-HV. 1x2 Moblie Distribution Amplifier. Instruction Manual

MDA-2-HV. 1x2 Moblie Distribution Amplifier. Instruction Manual MDA-2-HV 1x2 Moblie Distribution Amplifier Instruction Manual Thank you for purchasing one of our products. Please read this manual before using this product. When using this product, always follow the

More information

CHAPTER 3. HV and EHV Cable System Aging and Testing Issues

CHAPTER 3. HV and EHV Cable System Aging and Testing Issues CHAPTER 3 HV and EHV Cable System Aging and Testing Issues Nigel Hampton 3-1 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES This document was prepared by Board of Regents of the University System

More information

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

High Temperature Operation of Extruded Distribution Cable Systems. White Paper High Temperature Operation of Extruded Distribution Cable Systems White Paper October 2018 NOTICE The information contained herein is, to our knowledge, accurate and reliable at the date of publication.

More information

Innovation in Magnetic Measuring Instruments. Operation Manual for. Mag648 and Mag649 Low Power Three-Axis Magnetic Field Sensors.

Innovation in Magnetic Measuring Instruments. Operation Manual for. Mag648 and Mag649 Low Power Three-Axis Magnetic Field Sensors. Innovation in Magnetic Measuring Instruments Operation Manual for Mag648 and Mag649 Low Power Three-Axis Magnetic Field Sensors www.bartington.com Table of Contents 1. Legal notices 3 1.1. Copyright 3

More information

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (8th) Factory Name Address Factory ID

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (8th) Factory Name Address Factory ID Factory Name Address Factory ID Shirir Chala, Bagherbazar 11705 Electrical Safety dates Initial Date 09/07/2014 30/10/2016 Date of 5 th Follow Up Report Received Date 24/08/2014 02/01/2017 Date of 6 th

More information

EAGLE RE-1 CONTROLLER

EAGLE RE-1 CONTROLLER EAGLE RE-1 CONTROLLER For Use On ALL MotoSAT Mounts Supported Systems HD SL5 DirecTV HD DP3 Dish Network HD SC2 SHAW HD DP3 BELL TV EXECUTIVE 18" DirecTV 101 Dish Network 119 MSC-60 SHAW MD-500 Dish Network

More information

ICS Digital Menu. Installation Guide Version 1.1

ICS Digital Menu. Installation Guide Version 1.1 ICS Digital Menu Installation Guide Version 1.1 Installation Overview This document was written to assist technicians and electricians in installing the ICS Digital Menu. A thorough understanding of electrical

More information

INSTALLATION INSTRUCTIONS FOR

INSTALLATION INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR MODEL 2240LED www.sportablescoreboards.com 1 Table of Contents 8 X 7 INDOOR SCOREBOARD... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:... 3 INSTRUCTIONS FOR

More information

MSF1000. MSF Radio Time Code Receiver. User Manual Version 1.1. World Time Solutions. World Time Solutions Limited

MSF1000. MSF Radio Time Code Receiver. User Manual Version 1.1. World Time Solutions. World Time Solutions Limited MSF1000 MSF Radio Time Code Receiver User Manual Version 1.1 World Time Solutions World Time Solutions Limited COPYRIGHT 2011-2014 World Time Solutions Limited. All Rights Reserved. All information contained

More information

Broadcast Interconnect Solutions CONNECTING INNOVATION TO APPLICATION

Broadcast Interconnect Solutions CONNECTING INNOVATION TO APPLICATION Broadcast Interconnect Solutions CONNECTING INNOVATION TO APPLICATION Contact Information NORTH AMERICA United States Winchester Electronics World Headquarters 62 Barnes Industrial Road North Wallingford,

More information

Sphinx II. Owner s Manual. Tube Hybrid Integrated Power Amplifier. Rogue Audio, Inc. 3 Marian Lane Brodheadsville, PA Issue date: 08/01/16

Sphinx II. Owner s Manual. Tube Hybrid Integrated Power Amplifier. Rogue Audio, Inc. 3 Marian Lane Brodheadsville, PA Issue date: 08/01/16 Sphinx II Tube Hybrid Integrated Power Amplifier Owner s Manual Rogue Audio, Inc. 3 Marian Lane Brodheadsville, PA 18322 Issue date: 08/01/16 TABLE OF CONTENTS 1) Introduction 2 2) Unpacking the Sphinx

More information

Profile 10F User Manual

Profile 10F User Manual Version 4.0 Profile 10F User Manual For Products: Vivid Wave Mini PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. INCORRECT INSTALLATION AND HANDLING CAN VOID YOUR WARRANTY. Table of Contents

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. Test Method for Moisture Inhibitor Corrosion Resistance

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. Test Method for Moisture Inhibitor Corrosion Resistance ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 69 2007 Test Method for Moisture Inhibitor Corrosion Resistance NOTICE The Society of Cable Telecommunications

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique

Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique Underground Cable Diagnostic Testing Utilizing Partial Discharge Technique (An Update to the April 29, 2001 Report) Potomac Electric Power Company Reliability Services (Asset Management) Mostafa Hassani,

More information

2179-CD Series Fiber Optic Splice Closure. Installation Instructions

2179-CD Series Fiber Optic Splice Closure. Installation Instructions 2179-CD Series Fiber Optic Splice Closure Installation Instructions 1.0 Product Introduction The new 3M TM 2179-CD Series Fiber Optic Splice Closure can be used in buried, underground, aerial, and pedestal

More information

Concert Series ORDERCODE D3470 ORDERCODE D3471 ORDERCODE D3472 D3470 D3471 D3472

Concert Series ORDERCODE D3470 ORDERCODE D3471 ORDERCODE D3472 D3470 D3471 D3472 Concert Series ORDERCODE D3470 ORDERCODE D3471 ORDERCODE D3472 D3470 D3471 D3472 Congratulations! You have bought a great, innovative product from DAP Audio. The DAP Audio Concert Series brings excitement

More information

UNSIGNED HARDCOPY NOT CONTROLLED

UNSIGNED HARDCOPY NOT CONTROLLED SUBJECT: APPROVED BY STATUS PURPOSE AFFECTED FUNCTIONS REFERENCES Cable and Harness Making Manager, Hardware Engineering Maintenance Revision Establishes requirements for the fabrication and inspection

More information

Effects of ESD and Cleaning on SFP Fiber Optic Transceivers

Effects of ESD and Cleaning on SFP Fiber Optic Transceivers Effects of ESD and Cleaning on SFP Fiber Optic Transceivers Field Service & GSC Training DOC1928793 MR Service Engineering Imagination at work Overview Optical Modules or SFP (small form-factor pluggable)

More information

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-2-4/0

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-2-4/0 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-2-4/0 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL F CAUTION Working around energized

More information

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK

POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK POET-1 P.O.E. TEST PORT MEASUREMENT TOOL INSTRUCTION BOOK IB6386-01 9-1-2015 TABLE OF CONTENTS DESCRIPTION 2 HOW TO CABLE THE POET-1 2 HOW TO TAKE A MEASUREMENT 3 EASE OF USE 3 APPLICATIONS 3 CARE AND

More information

F CAUTION. Jacketed Concentric Neutral (JCN) Cable. Concentric Neutral (CN) Cable. IEEE Std. No. 48 Class 1 Termination 15 kv Class 110 kv BIL

F CAUTION. Jacketed Concentric Neutral (JCN) Cable. Concentric Neutral (CN) Cable. IEEE Std. No. 48 Class 1 Termination 15 kv Class 110 kv BIL 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 7642-S-2 For Jacketed Concentric Neutral (JCN) and Concentric Neutral (CN) Cable Instructions IEEE Std. No. 48 Class

More information

ENGINEERING COMMITTEE

ENGINEERING COMMITTEE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 09 2016 Test Method for Cold Bend Title Table of Contents Page Number NOTICE 3 1. Scope 4 2. Compliance Notation

More information

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500

3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kv Class 150 kv BIL CAUTION Working around energized

More information

SPECIFICATION FOR FIBER OPTIC SPLICE CLOSURE

SPECIFICATION FOR FIBER OPTIC SPLICE CLOSURE SP-CTN-CT3000M,CT3000ML-00 ISSUED : 2015/02/11 PAGE : 8 SPECIFICATION FOR FIBER OPTIC SPLICE CLOSURE CT3000M/CT3000ML Fiber Optic Splice Closure 2 / 8 1. GENERAL This specification covers the standards

More information

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems

Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Revision of Qualification Procedures for High Voltage and Extra High Voltage AC Extruded Underground Cable Systems Tutorial vor the ICC Educational Session on November 11 2009 in Scottsdale, AZ by Wim

More information

NAVSEA STANDARD ITEM. 1.1 Title: Shipboard Electrical/Electronic Cable Procedure; accomplish

NAVSEA STANDARD ITEM. 1.1 Title: Shipboard Electrical/Electronic Cable Procedure; accomplish NAVSEA STANDARD ITEM FY-9 ITEM NO: 009-73 DATE: 0 OCT 07 CATEGORY: I. SCOPE:. Title: Shipboard Electrical/Electronic Cable Procedure; accomplish. REFERENCES:. Standard Items. MIL-STD-003, Electric Plant

More information

ConnectAnywhere Prep Kit OEM INSTALLATION MANUAL

ConnectAnywhere Prep Kit OEM INSTALLATION MANUAL Connectnywhere Prep Kit OEM INSTLLTION MNUL TBLE OF CONTENTS Introduction 2 Safety 2 Resources Required 3 Preparation 3 Installation 3 Notes 9 Introduction This document provides instructions for the installation

More information

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series

3M Scotchcast Flexible Power Cable Splice Kits 82-F Series 3M Scotchcast Flexible Power Cable Splice Kits 82-F Series For use in weather-exposed, direct burial or submerged locations. For making in-line splices on non-shielded portable power cables and cords rated

More information

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers

General Wiring and Installation Guidelines. Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers General Wiring and Installation Guidelines Typical Mounting Installations Electrical Connections General Guidelines Common Questions & Answers Congratulations on your purchase of a Dynapar brand encoder.

More information

SIMET AVIKO D INSTRUCTION MANUAL SORTING Solutions, Ltd.

SIMET AVIKO D INSTRUCTION MANUAL SORTING Solutions, Ltd. SIMET AVIKO D INSTRUCTION MANUAL 1870 SORTING Solutions, Ltd. 1. TABLE OF CONTENTS 1. TABLE OF CONTENTS...1 2. INTRODUCTION...2 2.1. Application...2 2.2. Operating Conditions...2 2.3. Electro - Optical

More information

Aging test: integrated vs. non-integrated splices shield continuity systems.

Aging test: integrated vs. non-integrated splices shield continuity systems. Aging test: integrated vs. non-integrated splices shield continuity systems. George Fofeldea Power Engineer, 3M Canada November 2018 Abstract To maximize long-term splice performance, the implications

More information

OCT 15 Rev B

OCT 15 Rev B AMP+ HVA280-3pxm XE High-Voltage Plug Connector with 1-Stage Latching Application Specification 114-32125 15 OCT 15 Rev B NOTE All numerical values are in metric units [with U.S. customary units in brackets].

More information

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX

220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX 220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED

More information

Practical Application of the Phased-Array Technology with Paint-Brush Evaluation for Seamless-Tube Testing

Practical Application of the Phased-Array Technology with Paint-Brush Evaluation for Seamless-Tube Testing ECNDT 2006 - Th.1.1.4 Practical Application of the Phased-Array Technology with Paint-Brush Evaluation for Seamless-Tube Testing R.H. PAWELLETZ, E. EUFRASIO, Vallourec & Mannesmann do Brazil, Belo Horizonte,

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

D-COAX, Inc. D-COAX d086 Series Cable Pair. High Frequency, Skew Matched, Phase Stable Cable Pair (65 GHz)

D-COAX, Inc. D-COAX d086 Series Cable Pair. High Frequency, Skew Matched, Phase Stable Cable Pair (65 GHz) D-COAX, Inc. D-COAX d086 Series Cable Pair High Frequency, Skew Matched, Phase Stable Cable Pair (65 GHz) D-COAX d086 Series Cable Pair consists of two skew matched (to 1ps) flexible cable assemblies with

More information

How to Implement PoE in Your Harsh Industrial Environment

How to Implement PoE in Your Harsh Industrial Environment Produced by: Engineering 360 Media Solutions July 2018 How to Implement PoE in Your Harsh Industrial Environment Sponsored by: Quabbin Wire & Cable Co., Inc. There is little doubt that the internet of

More information

Coaxial Cable Feedline Choke Kit - 50 Ω

Coaxial Cable Feedline Choke Kit - 50 Ω Coaxial Cable Feedline Choke Kit - 50 Ω COM-CFC-50K COM-CFC-50K-INS-Revision 2a COMTEK SYSTEMS 2013 P.O. Box 1491 - Akron, OH 44309-1491 USA Phone: (800) 777-0703 Technical Support and International: (330)

More information

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL

TRANSCENSION 6-CHANNEL DMX DIMMER PACK (order code: BOTE40) USER MANUAL www.prolight.co.uk TRANSCENSION 6-CHANNEL PACK (order code: BOTE40) USER MANUAL SAFETY WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! CAUTION! Keep this

More information

Safety Codes Council Conference Banff C Panel Discussion

Safety Codes Council Conference Banff C Panel Discussion Safety Codes Council Conference Banff 2014 90 C Panel Discussion Tim Driscoll OBIEC Consulting Ltd. George Morlidge Fluor Canada Ltd. Scott Basinger Eaton Canada René Leduc Marex Canada Limited Perspectives

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Jacketed Concentric Neutral (JCN) Cable and Concentric Neutral (CN) Cable 7652-S-4, 7652-S-4 (L), 7653-S-4, 7654-S-4,

More information

8900 Keystone Crossing, Suite 1220 Indianapolis, Indiana KLIPSCH

8900 Keystone Crossing, Suite 1220 Indianapolis, Indiana KLIPSCH 8900 Keystone Crossing, Suite 1220 Indianapolis, Indiana 46240 1. 800. KLIPSCH www.klipsch.com For your records: Make sure you return your warranty card so that we may keep you up-to-date on new Klipsch

More information

How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997.

How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997. How Wire Fails Originally presented to the Society of Motion Picture and Television Engineers Convention, Sydney, Australia, on Friday, July 4, 1997. ABSTRACT: By Stephen H. Lampen Technology Development

More information

Fieldbus Testing with Online Physical Layer Diagnostics

Fieldbus Testing with Online Physical Layer Diagnostics Technical White Paper Fieldbus Testing with Online Physical Layer Diagnostics The significant benefits realized by the latest fully automated fieldbus construction & pre-commissioning hardware, software

More information

EAGLE RE-1 CONTROLLER For Use On MotoSAT HD Mounts

EAGLE RE-1 CONTROLLER For Use On MotoSAT HD Mounts EAGLE RE-1 CONTROLLER For Use On MotoSAT HD Mounts Supported Systems HD SL5 DirecTV HD DP3 Dish Network HD SC2 SHAW HD DP3 BELL TV EXECUTIVE DirecTV 101 Dish Network 119 MSC-60 SHAW MD-500 Dish Network

More information

D-COAX, Inc. D-COAX Male-Female 1501 Series Cables and Cable Pairs. High Frequency, Skew Matched, Phase Stable Cable Pair (40 GHz)

D-COAX, Inc. D-COAX Male-Female 1501 Series Cables and Cable Pairs. High Frequency, Skew Matched, Phase Stable Cable Pair (40 GHz) D-COAX, Inc. D-COAX Male-Female Series Cables and Cable Pairs High Frequency, Skew Matched, Phase Stable Cable Pair ( GHz) D-COAX Series Cable Pair consists of two skew matched (to ps) flexible cable assemblies

More information

TIC TFS12 Stereo Outdoor Rock Speakers Feature

TIC TFS12 Stereo Outdoor Rock Speakers Feature TFS12 Stereo Outdoor Rock Speakers TIC TFS12 Stereo Outdoor Rock Speakers Feature Weatherproof Design Teflon sealed cabinetry Aluminum Grill Full range 200W speaker system 8 woofer driver 2x 1 aluminum

More information

3 Foam Sealed Closure 2" (50 mm) with Compound Compression

3 Foam Sealed Closure 2 (50 mm) with Compound Compression 3 Foam Sealed Closure 2" (50 mm) with Compound Compression Instructions 1.0 General 1.1 The 3M Foam Sealed Closure is designed to be used in the construction and maintenance of buried and underground PIC

More information

LITE-ON TECHNOLOGY CORPORATION

LITE-ON TECHNOLOGY CORPORATION Features * Lead (Pb) free product RoHS compliant. * Low power consumption. * High efficiency. * Versatile mounting on p.c. board or panel. * I.C. compatible/low current requirement. * Popular T-1 diameter.

More information

Winmate Communication INC.

Winmate Communication INC. 20.1 Military Grade Display Model: R20L100-RKA2ML User s Manual Winmate Communication INC. May, 2011 1 IMPORTANT SAFETY INSTRUCTIONS Please read these instructions carefully before using the product and

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information