ISO/IEC testing LC to LC (Duplex Multimode) DTX-MFM

Similar documents
The need for Encircled Flux, real or imaginary?

The Road to Single Mode: Direction for choosing, installing and testing single mode fiber

Excel recommends Fluke Networks, this section is written around the use of this range of test equipment.

RCIT Cable Certification Testing Revised 10/2017

Instalaciones de fibra optica en entornos de centro de datos y campus para suportar 40, 100G y mas

DTX. Users Manual. Fiber Test Kit

OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide

Fiber Optic Testing. The FOA Reference for Fiber Optics Fiber Optic Testing. Rev. 1/31/17 Page 1 of 12

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Datasheet: MultiFiber Pro Update

CC-Link IE Controller Network Compatible. CC-Link IE Controller Network Recommended Network Wiring Parts Test Specifications

Datasheet: CertiFiber Pro Optical Loss Test Set

Mar11 Rev E

Versiv makes you money every time you use it.

A guide to Woolworths Limited additional requirements. for the testing of twisted pair and fibre installation.

Selection of a cable depends on functions such as The material Singlemode or multimode Step or graded index Wave length of the transmitter

Datasheet: CertiFiber Pro Optical Loss Test Set

Datasheet: CertiFiber Pro Optical Loss Test Set

SimpliFiber Pro. Users Manual. Optical Power Meter and Fiber Test Kits

Advanced Test Equipment Rentals ATEC (2832)

RFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH

Crimplok. Connectors. 3M Crimplok ST* Connector Multimode 1. 3M Crimplok SC Connector Single-mode 2

OPERATIONS GUIDE OWL

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Datasheet: SimpliFiber Pro

RFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH

We will look first at the cable, and then the transceivers (which act as both transmitter and receiver on each end of the fiber cable).

Optical Design Manufacturing, Inc. Sprint 2.5. Alcatel-Lucent (ALU) Fiber Inspection and Testing Procedures. Technical Support Document

Datasheet: MultiFiber Pro

The current state of multimode OTDR and Light Source and Power Meter (LSPM) Insertion Loss (IL) testing is as follows:

40G SWDM4 MSA Technical Specifications Optical Specifications

FIBER QUICKMAP. Users Manual. Multimode Troubleshooter

RFP LC Uniboot to RFP LC Uniboot Patch cord, 2 fibres, Interconnect tight-buffered cable, LSZH

SLS-50 Stabilized Laser Source. User s Manual. Shineway Technologies, Inc. All rights reserved.

For latest revision, visit our website at For Regional Customer Service, visit our website at

Cable Jacket - The outermost layer of the fiber cable. Application: Types Single mode Multi mode. Simplex or Duplex available

Fiber Meter. Specification & User Manual

Pluggable Transceivers Installation Guide

40G SWDM4 MSA Technical Specifications Optical Specifications

User Manual CXE Rev (12) CXX Series. User Manual. Teleste Corporation CXE810. Fibre optic receiver

Viavi T-BERD 5800 CPRI Testing Guide with ALU BBU Emulation

Fibre Channel Fiber-to-Fiber Media Converters

SSA Fibre-Optic Extender 160 Fibre Installation Guidelines Version 1.2

Aerospace Fiber Optics

User Manual CXE800. Fibre Optic Receiver. CXX Series. Teleste Corporation

U SER S G UIDE. TS2002A Fiber Optic Test Kit

INSTALLATION GUIDE. LANmark-OF Zone Distribution Box

OPERATOR MANUAL OSD351 FIBRE OPTIC CCTV TRANSMITTER CARD

INSTALLATION MANUAL FT-FOTR-8VD-ST-S. 8-Channel Digital Duplex Baseband Video Transmitter and Receiver With Reverse Data Transmission for PTZ Cameras

400G-FR4 Technical Specification

Light Source. Specification & User Manual

Scope: Using Wave Division Multiplexing (WDM) for the Protection Data Interface (PDI) of the 7SD5 / 7SD61.

Fiber Optic Meter Fiber Optic Source

FTK200. Users Guide. Optical Fiber Test Kit

IQORXD Dual-Channel Multimode Fibre Optic Receiver for SDI

Specification of Fusion Splice Loss - FIA TSD Mike Gilmore FIA Technical Director

MT-RJ SECURE Product Expansion Now 10 Variants of the MT-RJ SECURE Products

40GBASE-ER4 optical budget

DisplayPort Extender over 2 LC Fibers

SECTION 4 TABLE OF CONTENTS

Installation. SAPTF33xx-1xx in the Network. Standard Configuration

Fiber Optics Lab Manual. Instructor s Manual. For Classroom and Hands-On Laboratory Sessions

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

Sidelighter TM Optical distance to fault measurement module

FIBRE CHANNEL CONSORTIUM

IQOTXD Dual-Channel Multimode Fibre Optic Transmitter for SDI

SPECIAL SPECIFICATION 6559 Telecommunication Cable

HI-DEX PRODUCT SET DATASHEET

Small Form-Factor Pluggable (SFP) Module Installation Guide

SPECIAL SPECIFICATION 8540 Telecommunication Cable

OP940. Insertion Loss & Return Loss Meter Instruction Manual. (Also supports the OP725 Integration)

MPS Webinar Technical Series

Delaware County Community College Project # Marple Campus Renovation - Phase % Construction Documents November 23, 2011

Installing Gigabit Interface Converters and Small Form Factor Pluggable Gigabit Interface Converters

NO MORE LOOSE ENDS PRE-TERMINATED FIBER CABLE: FAST. TESTED. READY TO GO (BBOX) BLACKBOX.COM/PRETERMFIBER

COPYRIGHT 2011 AXON DIGITAL DESIGN B.V. ALL RIGHTS RESERVED

OP750. Multichannel Source Instruction Manual

Compact live fiber identifier with integrated optical power meter

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

D131x-apbpmslc TECHNICAL DATA. Fiber Optic Patch Cords Simplex LSZH. Description. Features & Benefits

SPECIFICATION 96F SM LOOSE TUBE, DRY CORE MINI CABLE

Copper Cabling Troubleshooting Handbook

KI7400C/7800C Series Optical Light Source KI7600C Series Optical Power Meter KI7300C/7700C Series Optical Loss Test Set

OFI Optical Fiber Identifier User s Guide

Assembly code page 46. Cable code page 47. Assembly classes page 48. Polarization maintaining assemblies page 52

100G-FR and 100G-LR Technical Specifications

OPERATOR MANUAL OSD553 TRIPLE VIDEO FIBRE OPTIC RECEIVER

Recommended Changes to Optical PMD Proposal

XCOM1002JE (8602JE) Optical Receiver Manual

SPECIAL SPECIFICATION 6191 Fiber Optic Cable

Triax TechInfo. Installing and pulling Fibre Optic cables

How to accelerate your cabling system approvals

FiberLink 3350 Series

ST800K-U Optical Power Meter. User Manual V1.0

OFI-400 Series Optical Fiber Identifiers. OFI-400 Series Models

L-Band Fiber Optic Link

Understanding Multimode Launching Conditions and TIA TSB-178

PM-240-MTP Multifiber Optical Power Meter INSTRUCTION MANUAL

Fibre Optic Cable & Connector Guide

KI 3600 Series Power Meter KI 3800 Series Light Source OPERATION & MAINTENANCE GUIDE

Transcription:

Page 1 of 5 ISO/IEC 14763-3 testing LC to LC (Duplex Multimode) DTX-MFM ISO/IEC 11801 now refers fibre testing to ISO/IEC 14763-3. More importantly, the limits have changed and we'll show you how in this article. This standard permits two methods: 3 Jumper: If the test equipment does not have changeable adapters on the input ports (DTX-MFM) 1 Jumper: If the test equipment does have changeable adapters on the input ports (DTX-MFM2) Since you have the DTX-MFMs shown below, we'll show you the 3 Jumper method described in this article. Items required in addition to a DTX CableAnalyzer: Cleaning is critical. It is the single most reason for ending up with negative loss values. You cannot clean without some means of visually inspecting the end face. This can be anything from a simple Fiber Viewer to a Video Scope such as the FiberInspector Mini shown above. If you have no inspection device, you cannot proceed. Let's define what is acceptable and not acceptable. 1. Perfect. Test Reference Cords are required to be perfect. 2. No scratches, but there are a few deposits on the end face and whilst they are not on the core, they could move to the core during referencing/testing. 3. Dirt is clearly covering the core. The hazy stripes across the ferrule indicates poor cleaning practices. 4. The cladding has been chipped. This could cause damage to anything you insert it into, including the test equipment. The Test Reference Cords (TRCs) are critical to a successful measurement. Your multimode TRCs loss MUST not exceed 0.10 db at each end. And yes, you must inspect and clean these TRCs every time you use them - even new ones out of the bag. Where did Fluke Networks get that 0.10 db requirement? ISO/IEC 14763-3 requires that the TRC must not exceed 0.10 db for multimode and 0.20 db for singlemode at the connectors. In this example, we're going to test a 100 m duplex 50/125 µm multimode fibre link with LC connectors at each end to ISO/IEC 14763-3.

Page 2 of 5 Setting up the DTX CableAnalyzer 1. With the fibre modules inserted into the DTX CableAnalyzer, power up the main and remote units. Sources will need at least five minutes to stabilize, longer in colder or hotter environments. 2. Rotate the dial on the DTX CableAnalyzer to SETUP. 3. Select Fiber Loss and press ENTER. 4. Change the Test Limit to ISO/IEC 14763-3. 5. Change the Fiber Type to the cable you are testing. This setting changes the Refractive Index (n) value. The DTX uses n to calculate the length of the fibre. You can manually enter the n values in Tab 3 of the Setup. If you cannot find your cable in the DTX Cable Library, look to the cable vendor's website for their datasheet. Since the ISO/IEC 14763-3 limit is calculated based on length, it is important to get this value right. 6. The Number of Adapters is going to be 0. This is always the number of adapters per fibre strand added after the reference has been set. 7. Set the Connector Type to LC. This will not affect the outcome of the result. It only affects the help screens and is of course recorded with the test result. 8. Set the Test Method to 3 Jumper. (With this Test Limit, it will affect the outcome of the result) 9. Clean AND inspect the TRCs. 10. Connect the main and remote units together as shown below. Mandrels must be used. Failure to do so can result in good fibre links failing. Red and grey mandrels are shipped with the fibre modules from Fluke Networks. The red is for 50/125 µm and the grey is for 62.5/125 µm TRCs. 11. Rotate the dial to SPECIAL FUNCTIONS. 12. With Set Reference selected, press TEST. 13. You will then be presented with the results of the Reference.

Page 3 of 5 For 50/125 µm it should be better than -24.50 dbm where -23.50 dbm is better than -24.50 dbm. For 62.5/125 µm it should be better than -20.00 dbm where -19.50 dbm is better than -20.00 dbm. These values reflect the cleanliness of the Ports and TRCs. The fact that your reference values are better than the minimum stated above does not mean they are good/clean. 14. Press F2 OK. 15. You can enter the length of your TRCs here. It does not affect the outcome of the test, but will be displayed on the test report. 16. Press F2 OK when done. 17. Remove the Field Calibration Cord and put the dust caps back on the ends. Never disconnect from the Output Ports. Doing so invalidates the reference you just set. 18. Connect the TRCs to the link you're testing.

Page 4 of 5 19. Rotate the dial to AUTOTEST and press TEST. The 0.20 db at the connectors is not an error. ISO/IEC 14763-3 states that the maximum permitted loss between a multimode TRC and a random (installed) fibre connector is 0.30 db. But don't forget, we referenced out 0.10 db in step 10. So the actual allowable loss is 0.30 db - 0.10 db = 0.20 db There has been some dispute over this calculation. An addendum to ISO/IEC 14763-3 gives the formulae in an easier way to understand and clarifies the issue. The 0.4 db below consists of two 0.20 db TRCs to random fibre connectors. Your DTX is correct. Using the default three test cord reference method specified in 9.1.12, the permanent link limits are as follows: for MMF: Limit = 0.4 db + Σ (cable attenuation) + Σ (embedded connection attenuation) for SMF: Limit = 0.6 db + Σ (cable attenuation) + Σ (embedded connection attenuation Let's take a look at another link with a fibre connector in the middle of it. You will note the adapter count has increased to one (since we have one more adapter in the link than when we referenced) and that the middle connection is permitted to be 0.75 db. That's because the mated connectors in the middle do not involve a Test Reference Cord. These are two random mated connectors.

Page 5 of 5 The DTX CableAnalyzer will calculate the correct test limit (optical loss budget) for you. Changing the number of adapters/splices will of course increase the test limit. Be sure the Number of Adapters is set correctly. How often should I Set Reference? The quick answer is; every time you begin to test a series of fibre links. It is critical to continually inspect the TRCs.