IEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by

Size: px
Start display at page:

Download "IEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by"

Transcription

1 IEEE-SA SCC-18 Report by Representatives to NFPA NEC CMP-6 January 6-8, 2010 on Actions Taken on Proposals by CMP-6 for NEC 2011 ROC Prepared by Bruce McClung, McSquared Electrical Consulting LLC and Don Voltz, British Petroleum

2 CMP-6 Summary 101 Proposals Submitted/Received by CMP-6 Accepted 50 (A) Rejected 33 (R) Accepted in Principle 9 (AIP) Accepted Part 4 (AP) Accepted in Principle and Part 4 (APP) Hold 1 (H)

3 CMP-6 Summary (Cont d) Four Categories of Comments dominated the review/actions activity of CMP-6 Rewrite of Article 310, 400 and Annex B; and Harmonization of NEC with CEC Article 310 and Annex B Non-shielded MV power cable Ampacity of Conductors on Rooftops Single Phase Dwelling Services and Feeders

4 CMP-6 Summary (Cont d) Rewrite of Article 310, 400 and Annex B; and Harmonization of NEC with CEC Article 310 and Annex B, (being presented for information only): ROP actions were undertaken mainly to locate Tables with same section/articles as text and to harmonize ampacities between NEC and CEC. Comment 6-21, (AIP with unanimous vote), illustrates that all Ampacity Tables will show dual identity for the next two Code cycles: such as Table (B)(6) formerly Table

5 CMP-6 Summary (Cont d) Non-shielded MV power cable, (being presented for information only): Comment Code Source Panel Panel Vote *Designates IEEE Action FOR-Against-Abstain A 11* R 7* AIP 11* AIPP 11*----0 Illustrates that efforts to restore use of non-shielded MV power cable for use in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation will be in the NEC 2011.

6 CMP-6 ER s Voted AGAINST the Panel Vote Seeks Concurrence From SCC-18 Membership Ampacity of Conductors on Rooftops, (IEEE-SA SCC 18 ER s need concurrence and support for voting against the CMP-6): Comment Code Source Panel Panel Vote *Designates IEEE Action FOR-AGAINST-ABSTAIN (B)(2)(c)&FPN R * Table (B)(2)(c) (B)(2)(c)&FPN R * Table (B)(2)(c) (B)(2)(c)&FPN R * Table (B)(2)(c) All three comments pertain to ROP Proposal 6-70 which IEEE-SA SCC 18 directed CMP-6 ER s to act to accept proposals that call for deleting (B)(2)(c). Voting against the Panel on all three proposals above will be acting to accept all four proposals which would delete (B)(2)(c) from the NEC CMP-6 ER s suggest the statement to be found on the next slide to submit with vote against the Panel vote to reject the proposals shown above.. (Cont d)

7 Statement Suggested by CMP-6 ER s to Accompany Negative Votes on Comment Ballot for Each of Comments 6-41, 6-43, 6-44 and 6-47 (Cont d) Code Panel 6 has now addressed the issue of solar radiation effects on the ampacity of wire in conduits (i.e. circular raceways) and Type MC Cable for rooftop applications since the 2005 cycle. The answer was to insert Table (B)(2)(c) Ambient Temperature Adjustment for Conduits Exposed to Sunlight On or Above Rooftops The data submitted to the Panel over this period has been developed from one site specific application where it was recognized that the intense sunlight had immediate effect on the temperature rise in the conduit and Type MC Cable. It should be noted that this testing was done on non-energized conductors in conduit and in Type MC Cable and that the data submitted did not address any long term aging effects. Yes, it gets hot inside the conduit or cable but to this point there has been no data presented showing any detrimental effects. Also, at no point during this period has the data submitted to the Panel been independently (i.e. third-party) verified. To this point the Panel has excluded Type MC Cable from Table (B)(2)(c) as it recognized that there was insufficient data submitted for inclusion. The panel should continue to do so.

8 Statement Suggested by CMP-6 ER s to Accompany Negative Votes on Comment Ballot for Each of Comments 6-41, 6-43, 6-44 and 6-47 Cont d) For years now, the electrical industry has safely used the allowable ampacity in Table including all adjustment factors, especially temperature, to size conductors in conduits and Type MC Cable for rooftop applications. Over this period, there has been no reported evidence of conductor or cable degradation due to the increased temperature rise inside the conduit or Type MC Cable. If there was a problem, you would think failure data would have been included in the many reports submitted to the panel. Therefore, the present method of sizing conductors in conduit or Type MC Cable for rooftop applications using the time honored allowable ampacity values in Table with appropriate adjustments is adequate.

9 Statement Suggested by CMP-6 ER s to Accompany Negative Votes on Comment Ballot for Each of Comments 6-41, 6-43, 6-44 and 6-47 (Cont d) Rather than relying on experimental data to size conductors in conduit and Type MC Cable for rooftop applications or using the time honored allowable ampacity values found in Table , the ampacity values can be calculated using the electrical/thermal circuit found in the IEEE (R2006) IEEE Standard Power Cable Ampacity Tables which includes the air space inside the conduit. The ampacity values contained in this standard are based on the Neher-McGrath calculation method. For conductors in horizontal conduit or cable in free air as would be found on rooftops, the ampacity calculation includes the effect of sun (solar radiation) and wind. From Table 29 of that standard, the following are some representative ampacity values for three, 600V copper conductors in horizontal conduit in free air based on a conductor temperature of 90 C and an ambient temperature of 40 C.

10 Statement Suggested by CMP-6 ER s to Accompany Negative Votes on Comment Ballot for Each of Comments 6-41, 6-43, 6-44 and 6-47 From IEEE (R2006 From Table #12 - No Sun, No Wind (0 ft/s) - 28 A #12 - No Sun, 2 ft/s - 29 A #12 - Full Sun, No Wind (0 ft/s) - 21 A #12 - Full Sun, 2 ft/s - 24 A #10 - No Sun, No Wind (0 ft/s) - 37 A #10 - No Sun, 2 ft/s - 38 A #10 - Full Sun, No Wind (0 ft/s) - 27 A #10 - Full Sun, 2 ft/s - 31 A Using the temperature adjustment factor of 0.88 for a 40 C ambient temperature for comparison, the 90 C allowable ampacity values from Table are 26.4 A for a #12 and 35.2 A for a #10. As one can see, the IEEE values are a little less in the full sun cases than the adjusted allowable ampacity from Table but are more than the adjusted values using Table (B)(2)(c). In any case, the Panel should reconsider their position on this issue and render their judgment based on scientific methods versus experimental methods from a single test site.

11 CMP-6 Summary (Cont d) Single Phase Dwelling Services and Feeders, (being presented for information only): Comment Code Source Panel Panel Vote *Designates IEEE Action FOR-AGAINST-ABSTAIN 6-55 by Cline (B)(6) AIP 9* by Pauley Proposed (B)(7) AIPP 8* Both comments pertain to CMP-6 Proposal 6-83a to the ROP in an attempt to clarify the original intent of Table (B)(6). This table was introduced many years ago by the utility companies to take advantage of load diversity in individual dwelling units of one family, two family and multifamily dwelling units. Originally it was described that the feeder conductors to a dwelling unit shall not be required to have an allowable ampacity greater than their service entrance conductors. Like table the ampacities listed for conductor types and sizes in Table (B)(6) are those values established by historic time-honored usage. Changes are occurring each Code cycle. The continual changes are creating misunderstandings. CMP-6 spent an inordinately amount of time on this issue- indicative of the overall problems with it as written. Improvements were made by combining the best of both comments.. (Cont d)

12 CMP-6 Summary (Cont d) Single Phase Dwelling Services and Feeders, (being presented for information only): NFPA NEC does not include any means for adjusting ampacity where main power panel is a significant distance from the service entrance disconnect or covered with household thermal insulation. Expect improvements to be proposed for this issue during 2014 Code cycle. Meanwhile IEEE Members involved in determining ampacity and sizing conductors for individual dwelling units of one family, two family and multi-family dwelling units should follow the IEEE Standard 835 NFPA NEC Definitions does not include any definition for Diversity Factor. Diversity Factor is described/defined in IEEE Standard 100 as the ratio of the sum of the individual non-coincident maximum demands of various subdivisions of the system to the maximum demand of the complete system. The diversity factor is always 1 or greater. Load Diversity refers to the percent of time available that a machine, piece of equipment, or facility has its maximum or nominal load or demand; i.e. a 70% diversity means that the device in question operates at its maximum or nominal load level 70% of the time that it is connected and turned on. Where there is no load diversity the device operates at maximum or nominal load 100% of the time.

Next Generation PoE Standards and Codes Update. Frank Straka Panduit Corporation

Next Generation PoE Standards and Codes Update. Frank Straka Panduit Corporation Next Generation PoE Standards and Codes Update Frank Straka Panduit Corporation Introduction Power over Ethernet is a HOT topic! New power levels dramatically increasing PoE device types New standards

More information

Selecting Cables for Power over Ethernet

Selecting Cables for Power over Ethernet Hitachi Cable America Inc. Selecting Cables for Power over Ethernet Factors to Consider when Selecting the Appropriate Cable 8/12/217 Ratio of Power Dissipated vs 1 Power over Ethernet Standards and applications

More information

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS

Power and Control T YPE BY RAVI GANATR November/December IAEI NEWS Power and Control 26 1999 November/December IAEI NEWS T YPE BY RAVI GANATR This article discusses how the requirements in both the installation code and the product standard are utilized to manufacture

More information

Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles

Continuous Currents. When inspectors see a photovoltaic (PV) power system. through Curious Cables. by John Wiles PV Wiring: Continuous Currents through Curious Cables by John Wiles When inspectors see a photovoltaic (PV) power system for the first time, they will usually be faced with a type of wiring method not

More information

Safety Codes Council Conference Banff C Panel Discussion

Safety Codes Council Conference Banff C Panel Discussion Safety Codes Council Conference Banff 2014 90 C Panel Discussion Tim Driscoll OBIEC Consulting Ltd. George Morlidge Fluor Canada Ltd. Scott Basinger Eaton Canada René Leduc Marex Canada Limited Perspectives

More information

Report on Comments June 2013 NFPA 70

Report on Comments June 2013 NFPA 70 10-1 Log #1392 NEC-P10 Dennis Darling, Stantec Consulting Ltd. 10-5 Delete text to read as follows: Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished

More information

Errata NFPA 70. Proposed 2014 Edition

Errata NFPA 70. Proposed 2014 Edition Reference: 14-1 (Log #392) CC Action Errata NFPA 70 National Electrical Code (Report on Comments) Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes the following

More information

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by:

Cambria County Association for the Blind and Handicapped 175 Industrial Park Road Ebensburg, PA Prepared for: Prepared by: Cable Management in Solar PV Arrays: A Review of Requirements in the National Electrical Code and how CAB Cable Rings and Saddles Meet These Requirements Prepared for: Cambria County Association for the

More information

How to Implement PoE in Your Harsh Industrial Environment

How to Implement PoE in Your Harsh Industrial Environment Produced by: Engineering 360 Media Solutions July 2018 How to Implement PoE in Your Harsh Industrial Environment Sponsored by: Quabbin Wire & Cable Co., Inc. There is little doubt that the internet of

More information

Insulated Cable Engineers Assoc., Inc. Publication No. ICEA P NEMA Standards Publication No. WC

Insulated Cable Engineers Assoc., Inc. Publication No. ICEA P NEMA Standards Publication No. WC Approved as an American National Standard ANSI Approval Date: January 9, 2004 Insulated Cable Engineers Assoc., Inc. Publication No. ICEA P-54-440 NEMA Standards Publication No. WC 51-2003 Ampacities of

More information

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure

FORENSIC CASEBOOK. By Bob Huddleston, Eastman Chemical Co. One of the most common. reasons for marriage failure The Case of the Energized Cable Cutting Incident How miscommunication leads to an electrical helper slicing through live 13.8kV cable and miraculously walking away to tell about it By Bob Huddleston, Eastman

More information

High Temperature Operation of Extruded Distribution Cable Systems. White Paper

High Temperature Operation of Extruded Distribution Cable Systems. White Paper High Temperature Operation of Extruded Distribution Cable Systems White Paper October 2018 NOTICE The information contained herein is, to our knowledge, accurate and reliable at the date of publication.

More information

Fiberglass - Technical Data

Fiberglass - Technical Data - Technical Data Cable Tray Thermal Contraction and Expansion X : Denotes hold-down clamp (anchor) at support. _ : Denotes expansion guide clamp at support. It is important that thermal contraction and

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

1 NATIONAL FIRE PROTECTION ASSOCIATION 2 ANNUAL ASSOCIATION TECHNICAL MEETING. 4 Thursday, June 13, STENOGRAPHIC REPORT OF PROCEEDINGS

1 NATIONAL FIRE PROTECTION ASSOCIATION 2 ANNUAL ASSOCIATION TECHNICAL MEETING. 4 Thursday, June 13, STENOGRAPHIC REPORT OF PROCEEDINGS 1 1 NATIONAL FIRE PROTECTION ASSOCIATION 2 ANNUAL 2013 3 ASSOCIATION TECHNICAL MEETING 4 Thursday, June 13, 2013 5 6 STENOGRAPHIC REPORT OF PROCEEDINGS 7 had in the above-entitled matter held at the 8

More information

ENGINEERING COMMITTEE

ENGINEERING COMMITTEE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 32 2016 Ampacity of Coaxial Telecommunications Cables NOTICE The Society of Cable Telecommunications Engineers

More information

System 500. Non-fire-rated, mineral insulated copper sheathed wiring cable

System 500. Non-fire-rated, mineral insulated copper sheathed wiring cable Non-fire-rated, mineral insulated copper sheathed wiring cable For retrofitting feeders in buildings and for ease of installation in tight spaces and difficult runs Cable construction Solid copper conductors

More information

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For

More information

CABLE TRAY MANUAL Based on the 2014 National Electrical Code

CABLE TRAY MANUAL Based on the 2014 National Electrical Code 2014 CABLE TRAY MANUAL Based on the 2014 National Electrical Code Mark shown is the property of its respective owner. MAN-1 Table of Contents Page No. Introduction... MAN-3 Why Cable Tray? MAN-4 MAN-4

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

WIRE AND CABLE FIRE TESTS

WIRE AND CABLE FIRE TESTS TEST CSA C22.2 No 2556-13 Section 9.4 (FV-2/VW-1) (Small Scale Vertical) # OF VALUES REPORTED FOOTAGE REQUIRED 3 3 pieces: 24 each 5 7 days PERFORMANCE TIME CSA-FT1 (Small Scale Vertical) 3 5 pieces: 24

More information

Toronto Hydro - Electric System

Toronto Hydro - Electric System Toronto Hydro - Electric System FIT Commissioning Requirements and Reports Comments and inquiries can be e-mailed to: FIT@torontohydro.com Customers without e-mail access can submit through regular mail

More information

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS

INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 FIRE PREVENTION FOR CABLES, CABLE TRAYS AND CONDUITS CERN INSTRUCTION DE SÉCURITÉ SAFETY INSTRUCTION Mandatory as defined in SAPOCO/42 Edms 335813 TIS IS 48 Edited by: TIS/GS Publication Date: June 2001 Original: English FIRE PREVENTION FOR CABLES, CABLE

More information

Material about the patent policy is available at

Material about the patent policy is available at All participants in this meeting have certain obligations under the IEEE-SA Patent Policy. Participants [Note: Quoted text excerpted from IEEE-SA Standards Board Bylaws subclause 6.2]: Shall inform the

More information

AGENDA. NEC Code-Making Panel 16. Report on Comment Meeting. December 3-December 8, Redondo Beach, CA

AGENDA. NEC Code-Making Panel 16. Report on Comment Meeting. December 3-December 8, Redondo Beach, CA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 16 Report on Comment Meeting December 3-December

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000

More information

INTRODUCTION This procedure should only be performed if the instrument fails to meet the Performance Check tests for Output Zero or Offset Accuracy

INTRODUCTION This procedure should only be performed if the instrument fails to meet the Performance Check tests for Output Zero or Offset Accuracy INTRODUCTION This procedure should only be performed if the instrument fails to meet the Performance Check tests for Output Zero or Offset Accuracy (steps A and B). Gain, which affects DC Accuracy, cannot

More information

Power Injector 1520 Series

Power Injector 1520 Series Power Injector 1520 Series Technical Specifications Input voltage 100 to 240 VAC Output voltage 56.0 VDC Voltage range tolerance 54 VDC to 57 VDC Maximum current 1.43 A No load current 15 ma 56VDC@0.71A

More information

ETAP PowerStation 4.0

ETAP PowerStation 4.0 ETAP PowerStation 4.0 User Guide Copyright 2001 Operation Technology, Inc. All Rights Reserved This manual has copyrights by Operation Technology, Inc. All rights reserved. Under the copyright laws, this

More information

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection

More information

3M Sensored Termination (15 kv) QX-T15I-vi1-E

3M Sensored Termination (15 kv) QX-T15I-vi1-E 3M Sensored Termination () QX-T15I-vi1-E Data Sheet May 2016 Kit Contents: Each kit contains sufficient quantities of the following materials to make three single-phase terminations. 31" (REF) One piece

More information

S Regulators. Supplement 1. Contents. Control Replacement Assembly Installation Instructions Supplement

S Regulators. Supplement 1. Contents. Control Replacement Assembly Installation Instructions Supplement Regulators Control Replacement Assembly Installation Instructions Supplement Service Information S225-40-1 Supplement 1 Figure 1. CL-6A Control Replacement Assembly. Contents Safety Information... 2 Product

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Kinetix Application Note

Kinetix Application Note Applying 2094 LIM Modules to Multiple Loads Kinetix Application Note PURPOSE This document addresses application cases where it is desired to utilize a single 2094 LIM module to supply three phase power

More information

LCS 2 RJ 45 Cat. 6A HD panels and units

LCS 2 RJ 45 Cat. 6A HD panels and units 87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1

More information

PRELIMINARY Sunny Boy 240-US

PRELIMINARY Sunny Boy 240-US PRELIMINARY Sunny Boy 240-US SB 240-US-10 Optimized reliability Simple installation Unrivaled monitoring SMA-backed security Multigate technology allows for reduced component count Private band powerline

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 SUMMARY A. Section includes cables and related cable splices, terminations, and accessories for mediumvoltage (2001 to 35,000 V) electrical distribution

More information

LED control gear Compact fixed output

LED control gear Compact fixed output Driver LC 40W 900mA fixc SR SNC ESSENCE series Product description Independent fixed output LED Driver Constant current LED Driver Output current 900 ma Max. output power 39 W Nominal life-time up to 50,000

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-02 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical

More information

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes. SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of

More information

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS

SECTION INTERCOMMUNICATIONS AND PROGRAM SYSTEMS SECTION 27 51 23 SPEC WRITER NOTES: 1. Use this section only for NCA projects. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Contact Department of Veterans

More information

Aging test: integrated vs. non-integrated splices shield continuity systems.

Aging test: integrated vs. non-integrated splices shield continuity systems. Aging test: integrated vs. non-integrated splices shield continuity systems. George Fofeldea Power Engineer, 3M Canada November 2018 Abstract To maximize long-term splice performance, the implications

More information

GESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE

GESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE GESTAMP CHATTANOOGA, LLC CHATTANOOGA, TENNESSEE April, 2013 Infrared Inspection Report Gestamp Chattanooga, LLC Company Contact Emil Richards Project: 06020413 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

DANGER. DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING

DANGER. DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Installation Guide Smart-UPS C 1000/1500 VA 120/230 Vac 2000/3000 VA 230 Vac Tower Important Safety Messages SAVE THESE INSTUCTIONS - This manuals contains important instructions that should be followed

More information

EXLUX ECOLUX 6480 Series

EXLUX ECOLUX 6480 Series EXLUX ECOLUX 6480 Series L I G H T I N G 6000 6008 6400 6408 6600 6608 6480 Explosion Protected Fluorescent Luminaires for Hazardous and Corrosive Applications Features: Electronic Ballasts For Fluorescent

More information

Installation Manual SaVi Note Underwater LED Light

Installation Manual SaVi Note Underwater LED Light Installation Manual SaVi Note Underwater LED Light Model Numbers SAVI-NOTE7, SAVI-NOTE0 Table of Contents Safety Precautions...2 SaVi Note Install Instructions...3- M Instructions...- Warnings READ AND

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16)

Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16) Satellite multiswitch Instructions for Use P.154-UP (9/4) P.155-UP (9/8) P.150-UP-12 (9/12) P.150-UP-16 (9/16) EMP-CENTAURI is a registered trademark Dear Customer, Thank you for buying the EMP-Centauri

More information

KRF EMC Filters Installation, Operation and Maintenance Manual

KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee. ANSI/SCTE (Formerly IPS SP 001)

ENGINEERING COMMITTEE Interface Practices Subcommittee. ANSI/SCTE (Formerly IPS SP 001) ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 74 2003 (Formerly IPS SP 001) Specification for Braided 75 Ω Flexible RF Coaxial Drop Cable NOTICE The Society

More information

GS122-2L. About the speakers:

GS122-2L. About the speakers: Dan Leighton DL Consulting Andrea Bell GS122-2L A growing number of utilities are adapting Autodesk Utility Design (AUD) as their primary design tool for electrical utilities. You will learn the basics

More information

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires

More information

apple Service Source Apple Studio Display 17" LCD (ADC) Updated 6 Decenber Apple Computer, Inc. All rights reserved.

apple Service Source Apple Studio Display 17 LCD (ADC) Updated 6 Decenber Apple Computer, Inc. All rights reserved. apple Service Source Apple Studio Display 17" LCD (ADC) Updated 6 Decenber 2004 2003 Apple Computer, Inc. All rights reserved. apple Service Source Take Apart Apple Studio Display 17" LCD (ADC) 2003 Apple

More information

Flygt Submersible Motor Cables

Flygt Submersible Motor Cables Flygt Submersible Motor Cables This brochure contains an overview of the Flygt motor cable assortment. The cables are especially designed for submersible use and made of carefully selected materials. The

More information

LED Driver Compact dimming

LED Driver Compact dimming Driver CA 15W 180-350mA flexc PH-C SR ADV ADVACED series Product description Dimmable constant current ED Driver (SEV) Independent ED Driver with cable clamps Selectable output current between 180, 250

More information

Advanced PoE - The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling

Advanced PoE - The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling Advanced PoE - The Impact of Higher Power PoE++ on Twisted-Pair Structured Cabling Next Generation PoE Connect significantly more devices due to higher power Affects cabling due to the additional heat

More information

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical

More information

Development of REBCO Twisted Stacked-Tape Cables for Magnet Application

Development of REBCO Twisted Stacked-Tape Cables for Magnet Application Development of REBCO Twisted Stacked-Tape Cables for Magnet Application L. Chiesa, N. Allen Tufts University, ME, Medford, MA 02155 presented by M. Takayasu, MIT, PSFC W. Nachtrab, M.K. Rudziak, T. Wong

More information

REGO Start&Go USER MANUAL

REGO Start&Go USER MANUAL REGO Start&Go USER MANUAL Version 0 Rev. B of 03/03/16 Page 1 of 15 Introduction The purpose of the manual is to describe all of the steps required to commission and correctly operate the REGO Start&Go

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT A & B OUTERWEAR LTD. Plot # 29-30, CEPZ, Chittagong, Bangladesh. Factory List: 1. Inspected by: Al-Amin Report Generated by: Al-Amin Inspected on March 7 th 2015 SUMMARY

More information

HDBT Installation Guide

HDBT Installation Guide KRAMER ELECTRONICS LTD. HDBT Installation Guide MODELS: Kramer HDBT Cable Recommendations for Usage and Termination Guidelines For the latest information on our products and a list of Kramer distributors,

More information

LCS2 Cat. 6 RJ 45 Patch panels and units

LCS2 Cat. 6 RJ 45 Patch panels and units 87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2

More information

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz Mobile Communications MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO

More information

Re-defining the utility-scale inverter

Re-defining the utility-scale inverter Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demand while supporting a smart grid that serves a smart society. Solution at a

More information

IEEE 383 Standard for Qualifying Electric Cables and Splices for. NPEC January 2015 Robert Konnik. Nuclear Facilities Preview II

IEEE 383 Standard for Qualifying Electric Cables and Splices for. NPEC January 2015 Robert Konnik. Nuclear Facilities Preview II IEEE 383 Standard for Qualifying Electric Cables and Splices for NPEC January 2015 Robert Konnik Nuclear Facilities Preview II IEEE 383 Background This standard provides guidance for developing a program

More information

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd.

ELECTRICAL SAFETY INSPECTION REPORT. MTM Garments Ltd. ELECTRICAL SAFETY INSPECTION REPORT MTM Garments Ltd. 15934/16004, Chanpara, Medical Road, Uttarkhan, Dhaka, Bangladesh. Factory List MTM Garments Ltd. Inspected by: Hemlal Dahal Report Generated by: Hemlal

More information

HDMI 1.3 Demystified

HDMI 1.3 Demystified October 5, 2006 HDMI 1.3 Demystified Xiaozheng Lu, Senior Vice President, Product Development, AudioQuest The release of the new HDMI 1.3 specification on 6/22/2006 created both excitement and confusion

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

The Chan-L-Wire Pro Series Lighting Distribution

The Chan-L-Wire Pro Series Lighting Distribution Lighting Distribution System Offers Maximum Flexibility The Chan-L-Wire Pro Series Lighting Distribution System offers maximum flexibility while saving up to 40% in labor installation costs. The system

More information

NewScope-7A Operating Manual

NewScope-7A Operating Manual 2016 SIMMCONN Labs, LLC All rights reserved NewScope-7A Operating Manual Preliminary May 13, 2017 NewScope-7A Operating Manual 1 Introduction... 3 1.1 Kit compatibility... 3 2 Initial Inspection... 3 3

More information

Implementation of LED Roadway Lighting

Implementation of LED Roadway Lighting Implementation of LED Roadway Lighting Ken Taillon, Principal Investigator Short Elliot Hendrickson, Inc. (SEH ) May 2016 Research Project Final Report 2016-17 To request this document in an alternative

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 10W 250mA fixc R ADV ADV series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 250 ma For luminaires of protection class II For ambient temperatures

More information

Electrical Depth Work

Electrical Depth Work Electrical Depth Work Introduction With changes in a lighting system in a building come changes in the electrical system. The first part of the electrical work involves the analysis of the affected panelboards

More information

DESIGN STANDARD FOR AUDIOVISUAL SYSTEMS

DESIGN STANDARD FOR AUDIOVISUAL SYSTEMS DESIGN STANDARD FOR AUDIOVISUAL SYSTEMS General: Solano Community College (SCC) is intent on moving to 21 st century unified communications and data systems, consistent with industry standards and best

More information

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.

CURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A. CURRENT INJECTION RELAY TESTER CR-100 ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M 981 329 / 05A ) (c) CIRCUTOR S.A. ---- CURRENT- TIME TRIP TESTER CR-100 --------------- Page. 2 CURRENT INJECTION

More information

16 th Annual PQSynergy International Conference and Exhibition 2016

16 th Annual PQSynergy International Conference and Exhibition 2016 16 th Annual PQSynergy International Conference and Exhibition 2016 Er. Muhammad Najmi Bin Bohari MSc(Power Eng), B.Eng (EEE) P.Eng, MIES, M-CIGRE najmi@powerquality.sg Professional Engineer (Singapore).

More information

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16)

Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-CP-12 (13/12) P.160-CP-16 (13/16) Satellite multiswitch Instructions for Use P.160-AP-8 (13/8) P.160-CP-8 (13/8) P.160-AP-12 (13/12) P.160-CP-12 (13/12) P.160-AP-16 (13/16) P.160-CP-16 (13/16) EMP-CENTAURI is a registered trademark Dear

More information

DS1 Cross-Aisle Panel

DS1 Cross-Aisle Panel DS1 Cross-Aisle Panel Model 005-0005-0100 Installation Guide 1.1 Overview 1.1.1 Inspection Compare the contents of the DS1 Cross-Aisle Panel shipping container with the packing list. Call Telect if anything

More information

Starling Tab-Tension 2 Series

Starling Tab-Tension 2 Series Electric Wall/Ceiling Projection Screen Starling Tab-Tension 2 Series For: Spectra White FG and CineGrey 5D User s Guide Important Safety & Warning Precautions Make sure to read this user s guide and follow

More information

Detailed Specifications & Technical Data

Detailed Specifications & Technical Data For more Information please call 1-800-Belden1 General Description: CAT6A (625MHz), 4-Pair, U/UTP-Unshielded, Plenum-CMP, Premise Horizontal Cable, 23 AWG Solid Bare Copper Conductors, FEP Insulation,

More information

AMERICAN NATIONAL STANDARD

AMERICAN NATIONAL STANDARD Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 108 2018 Test Method for Dielectric Withstand of Coaxial Cable NOTICE The Society of Cable Telecommunications Engineers (SCTE) / International

More information

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE

OCC Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Installation Conduit Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE Conduit Installation A conduit cable installation involves placement of one or more optical cables inside a preinstalled

More information

AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE

AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE AEROTRAK PORTABLE AIRBORNE PARTICLE COUNTER MODEL 9110 QUICK START GUIDE Thank you for purchasing a TSI AeroTrak Model 9110 Portable Airborne Particle Counter (particle counter). This guide will help you

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication WC 63.1-2005 Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street,

More information

1 Power Protection and Conditioning

1 Power Protection and Conditioning Power Protection and Conditioning MCR Hardwired Series Power Line Conditioning with Voltage Regulation The MCR Hardwired Series provides excellent noise filtering and surge protection to safeguard connected

More information

Product Manual MNX10015 / REV C MODEL SB142, SB242. Dual Output Series Switch Boxes

Product Manual MNX10015 / REV C MODEL SB142, SB242. Dual Output Series Switch Boxes Product Manual MNX10015 / REV C MODEL SB142, SB242 Dual Output Series Switch Boxes Contents Section I Overview Introduction.... 2 Description... 2 Section II Installation Mounting... 3 Electrical Connections...

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

INSTALLATION AND OPERATION M

INSTALLATION AND OPERATION M INSTALLATION AND OPERATION M RUBYSTAR INSTALLATION AND OPERATION MANUAL Safety Instructions : Only authorised installers should install and or replace Rubystar inverters. Ensure that all electrical installations

More information

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N

Weekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control

More information

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE The Society of Cable Telecommunications

More information

Mohawk Master Catalog

Mohawk Master Catalog Mohawk Master Catalog Cabling Excellence for Open Architecture Mohawk s Green Initiative Even in the early stages of product development, ecological aspects from energy and resource consumption to the

More information

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS

USER MANUAL. 27 Full HD Widescreen LED Monitor L27ADS USER MANUAL 27 Full HD Widescreen LED Monitor L27ADS TABLE OF CONTENTS 1 Getting Started 2 Control Panel/ Back Panel 3 On Screen Display 4 Technical Specs 5 Care & Maintenance 6 Troubleshooting 7 Safety

More information

Mechanical aspects, FEA validation and geometry optimization

Mechanical aspects, FEA validation and geometry optimization RF Fingers for the new ESRF-EBS EBS storage ring The ESRF-EBS storage ring features new vacuum chamber profiles with reduced aperture. RF fingers are a key component to ensure good vacuum conditions and

More information

DIN Power Module - Phase Adaptive

DIN Power Module - Phase Adaptive DIN Power Module ow Capacity Phase Adaptive DIN Power Module - Phase Adaptive 369849a 1 08.06.15 The Phase Adaptive Power Module family is a group of modular products for the control of lighting loads.

More information

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 103 2018 Test Method for DC Contact Resistance, Drop cable to F connectors and F 81 Barrels NOTICE The Society of Cable Telecommunications

More information

Warner Photoscanner MCS-500 Series LED Photoelectric Control

Warner Photoscanner MCS-500 Series LED Photoelectric Control Warner Photoscanner MCS-500 Series LED Photoelectric Control P-241-100 819-0504 Installation & Operating Instructions Contents Description.............................. 2 Specifications.........................

More information

Lifestyle. Dual Channel Programmer. for heating AND hot water. Installation and User Instructions DUAL CHANNEL ISSA

Lifestyle. Dual Channel Programmer. for heating AND hot water. Installation and User Instructions DUAL CHANNEL ISSA Lifestyle Dual Channel Programmer for heating AND hot water Installation and User Instructions DUAL CHANNEL 06490197001 ISSA INSTALLATION INSTRUCTIONS PLEASE NOTE: INSTALLATION MUST ONLY BE CARRIED OUT

More information