1 Workshop 6: Maintenance and monitoring Medium and High Voltage Circuit Breakers Characteristic Time Quantities of the Circuit Breaker with Applications Alexander Herrera OMICRON electronics GmbH 3 December 2013
2 High and Medium Voltage Circuit Breakers Page 2
3 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 3
4 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 4
5 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 5
6 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 6
7 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 7
8 Definition of Circuit Breaker According to IEC and ANSI C Is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as short circuit. Page 8
9 Short circuit oscillogram CB trips and opens short-circuit in about 2 cycles Initiation of shortcircuit current Normal load current flowing Page 9
10 Short circuit oscillogram CB trips and opens short-circuit in about 2 cycles Initiation of shortcircuit current Normal load current flowing Page 10
11 Standards ANSI C Standard ratings defined C Schedule of preferred ratings C Type tests Routine tests C37.081, C37.082, IEEE 693 Page 11
12 Standards IEC IEC , 2001 Type, routine & field tests Timing definitions Guide for selection and specification IEC 60694, 2001 Normal service conditions Schedule of preferred ratings Altitude correction IEC 60427, IEC 60815, IEC 60529, IEC 61166, IEC Page 12
13 Characteristics Compulsory rated characteristics Rated voltage Rated insulation level Rated normal current Rated short-time withstand current Rated peak withstand current Rated short-circuit duration Rated supply voltage for opening and closing devices and auxiliary circuits Rated frequency Rated short-circuit breaking current Rated transient recovery voltage Rated short-circuit making current Rated time quantities Rated operating sequences Page 13
14 Characteristics Time Quantities Rated time quantities Opening time Closing time Simultaneity or synchronization Close-open time Open-close time Rated operating sequence O t CO t CO Page 14
15 Timing definitions According to IEC [O] Opening time [C] Closing time [CO] Close-open time [O-C] Open-close time Reclosing time the interval of time between the specified instant of initiation of the opening operation and the instant of energizing the opening release, the circuit-breaker being in the closed position, and the instant when the arcing contacts have separated in all poles. the interval of time between the initiation of the closing operation and the instant when the contacts touch in all poles. the interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation. Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle. Interval of time between the begining of the opening time and the instant when the contacts touch in all poles during a reclosing cycle. Page 15
16 Timing Explanations [O] Opening time the interval of time between the specified instant of initiation of the opening operation and the instant of energising the opening release, the circuit-breaker being in the closed position, and the instant when the arcing contacts have separated in in all all poles poles Closed position Contact movement Open position Current Flow Opening time Break time Arcing time Final arc extinction in all poles Time Separation arcing contacts in all poles Energising of opening release Separation arcing contacts in first pole Page 16
17 Timing Explanations [O] Opening time the interval of time between the specified instant of initiation of the opening operation and the instant of energising the opening release, the circuit-breaker being in the closed position, and the instant when the arcing contacts have separated in all poles Closed position Contact movement Open position Current OPENING Flow time Opening time Break time Arcing time BREAKING time Final arc extinction in all poles Time Separation arcing contacts in all poles Energising of opening release Separation arcing contacts in first pole Page 17
18 Timing Explanations [O] Opening time CB opening time Opening time PhA Opening time PhB Instant when the arcing contacts have separated in all the poles Opening time PhC Instant of energising the opening release Page 18
19 Timing Explanations [C] Closing time the interval of time between the initiation of of the closing operation and the instant when the contacts touch in all poles Closed position Contact movement Open position Current Flow Make time Time Pre-arcing time Closing time Contacts touch in all poles Energising of closing release Start of current flow in first pole Page 19
20 Timing Explanations [C] Closing time CB closing time Closing time Phase B Instant when the contacts touch in all the poles Closing time Phase A Closing time Phase C Instant of energising the closing release Page 20
21 Simultaneity or Synchronization > 1 Interrupting unit (per phase) > 2 or more interrupting units connected in series Page 21
22 Simultaneity or Synchronization > 1 Interrupting unit per phase > 2 or more interrupting units connected in series 2 or more interrupting units connected in series (per phase) Page 22
23 Simultaneity or Synchronization One interrupting unit per phase According to IEC and ANSI C , when no special requirement with respect to simultaneous operation of poles is stated, the maximum difference during opening shall not exceed 1/6 of a cycle of rate frequency and during the closing shall not exceed 1/4 of a cycle of rate frequency as well. Page 23
24 Simultaneity or Synchronization One interrupting unit per phase According to IEC and ANSI C , when no special requirement with respect to simultaneous operation of poles is stated, the maximum difference during opening shall not not exceed 1/6 1/6 of of a cycle a cycle of rate frequency and during the the closing shall not exceed 1/4 of a cycle of rate frequency as well. During OPENING maximum difference 1/6 of a cycle 3,33 50 Hz 2,78 60 Hz During CLOSING maximum difference 1/4 of a cycle 5,0 50 Hz 4,17 60 Hz Page 24
25 Simultaneity or Synchronization One interrupting unit per phase During CLOSING maximum difference 1/4 of a cycle 5,0 50 Hz 4,17 60 Hz Page 25
26 Simultaneity or Synchronization One interrupting unit per phase During OPENING maximum difference 1/6 of a cycle 3,33 50 Hz 2,78 60 Hz Page 26
27 Simultaneity or Synchronization Two or more interrupting units connected in series (per phase) If one pole consists of more than one interrupter unit connected in series, the maximum difference between the instants of contact separation within these series connected interrupter units shall not exceed 1/8 of a cycle of rated frequency, and between the instants of contacts touching within these series connected interrupter units shall not exceed a 1/6 of a cycle of rated frequency. Page 27
28 Simultaneity or Synchronization Two or more interrupting units connected in series (per phase) If one pole consists of more than one interrupter unit connected in series, the maximum difference between the instants of contact separation within these series connected interrupter units shall not exceed 1/8 of a cycle of rated frequency, and between the instants of contacts touching within these series connected interrupter units shall not exceed a 1/6 of a cycle of rated frequency. During OPENING maximum difference 1/8 of a cycle 2,50 50 Hz 2,08 60 Hz During CLOSING maximum difference 1/6 of a cycle 3,33 50 Hz 2,78 60 Hz Page 28
29 Simultaneity or Synchronization Two or more interrupting units connected in series (per phase) During OPENING maximum difference 1/8 of a cycle During CLOSING maximum difference 1/6 of a cycle Synchronization time between interrupter units Page 29
30 Timing Explanations [CO] Close-Open time the interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation. Closed position Contact movement Open position Open position Current Flow Close-open time Time Contact touch in the first closing pole Contact touch in all poles Separation arcing contacts in all poles Energising of closing circuit Page 30
31 Timing Explanations [CO] Close-Open time the interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation. Closed position Contact movement Open position Open position Current Flow Time Make-break time Final arc extinction in all poles Start of current flow in first pole Page 31
32 Timing Explanations [CO] Close-Open time the interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation. Closed position Contact movement Open position Open position Current Flow Close-open time Time Make-break time Contact touch in the first closing pole Contact touch in all poles Start of current flow in first pole Final arc extinction in all poles Separation arcing contacts in all poles Energising of closing circuit Page 32
33 Timing Explanations [CO] Close-Open time the interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation Page 33
34 Timing Explanations [O-C] Open-Close time Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle. Closed position Contact movement Closed position Open position Current Flow Open-close time Current Flow Time Separation arcing contacts in all poles Energising of opening release Energising of closing circuit Contact touch in first pole Page 34
35 Timing Explanations Reclosing time Interval of time between the begining of the opening time and the instant when the contacts touch in all poles during a reclosing cycle. Closed position Contact movement Closed position Open position Current Flow Dead time Current Flow Time Re-make time Reclosing time Energising of opening release Final arc extinction in all poles Energising of closing circuit Contact touch in all poles Contact touch in first pole Start of current in first pole Page 35
36 Timing Explanations [O-C] Open-Close time Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle. Closed position Contact movement Closed position Open position Current Flow Dead time Open-close time Re-make time Reclosing time Current Flow Time Energising of opening release Final arc extinction in all poles Separation arcing contacts in all poles Energising of closing circuit Contact touch in all poles Contact touch in first pole Start of current in first pole Page 36
37 Timing Explanations [O-C] Open-Close time Reclosing time Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle Interval of time between the begining of the opening time and the instant when the contacts touch in all poles during a reclosing cycle Page 37
38 Duty cycles It is also required that a Circuit Breaker is capable of performing more complex sequences, for example: Three rated operating sequences exist: O t CO t CO t = 3 min for circuit breakers not intended for rapid auto-reclosing t = 0,3 sec for circuit breakers intended for auto-reclosing (dead time) t = 3 min Note: Instedad of t = 3 min, other values: t 15 s and t = 1 min are also used for circuit breakers intended for auto-reclosing. Page 38
39 Duty cycles t t I SC I r O C O C O Time Page 39
40 Duty cycles t t I SC I r O C O C O Time Page 40
41 Questions?? Page 41
42 Thank you!!! Page 42
Toronto Hydro - Electric System
Toronto Hydro - Electric System FIT Commissioning Requirements and Reports Comments and inquiries can be e-mailed to: FIT@torontohydro.com Customers without e-mail access can submit through regular mail
More informationSoft starter, 66 A, V AC, Us= 24 V DC, with control unit, Frame size N. Function Soft starter for three-phase loads, with control unit
DATASHEET - S811+N66N3S Delivery program Soft starter, 66 A, 200-600 V AC, Us= 24 V DC, with control unit, Frame size N Part no. S811+N66N3S Catalog No. 168978 Eaton Catalog No. S811PLUSN66N3S EL-Nummer
More information3AH3 Vacuum Circuit-Breakers
Catalog HG 11.03 Edition 2018 3AH3 Vacuum Circuit-Breakers Medium-Voltage Equipment siemens.com/3ah3 2 3AH3 Vacuum Circuit-Breakers Siemens HG 11.03 2018 R-HG11-373.tif Contents 3AH3 Vacuum Circuit-Breakers
More informationImproved Synchronization System for Thermal Power Station
Improved Synchronization System for Thermal Power Station Lokeshkumar.C 1, Logeshkumar.E 2, Harikrishnan.M 3, Margaret 4, Dr.K.Sathiyasekar 5 UG Students, Department of EEE, S.A.Engineering College, Chennai,
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100
DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationGenerator protection relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationTeSys contactors. Model d. Type of contactor LC1- LC1- LC1- LC1- LC1-D115 & D09 D18 D25 D38 D40 D50 D95 LC1-D150 DT20 & DT25 DT32 & DT40
Characteristics Type of contactor LC- LC- LC- LC- LC-D & D09 D8 D2 D38 D40 D0 D9 LC-D0 DT20 & DT2 DT32 & DT40 Environment Rated insulation voltage (Ui) Conforming to IEC 947-4-, overvoltage category III,
More informationMILLITARY SPECIFICATION SHEET
INCH-POUND MILLITARY SPECIFICATION SHEET 10 November 2000 SUPERSEDING MIL-R-6106/14B 10 March 1989 RELAY, ELECTRIC, PERMANENT DRIVE, 50 AMP, SPDT (DB) DOUBLE MAKE DOUBLE BREAK AUXILIARY CONTACTS (5 AMP),
More informationLC1D150G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 150 A V AC coil
Product data sheet Characteristics LC1D150G7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationHD4/R. MV SF6 circuit-breakers for secondary distribution
HD4/R MV SF6 circuit-breakers for secondary distribution DESCRIPTION CIRCUIT-BREAKER SELECTION AND ORDERING SPECIFIC PRODUCT CHARACTERISTICS OVERALL DIMENSIONS ELECTRIC CIRCUIT DIAGRAM 3 9 25 45 49 1
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63
Circuit-breaker,4p,63A Partno. NZMH1-4-A63 Articleno. 284426 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC
More informationDMX and 4000 air circuit breakers from 800 to 4000 A
DMX 3 20 and 00 air circuit breakers from 800 to 00 NEW 286 56 + 288 02 (p. 4) 286 4 + 288 02 (p. 4) 28 56 + 288 02 (p. 4) Dimensions (p. to 53) Electrical characteristics (p. 54 to 5) ir circuit breakers
More informationI r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Deliveryprogramme Circuitbr.,3pmotorprotection Partno. Articleno. 265784 NZMN4-ME875 Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation type Fixed Release
More information50 Hz 60 Hz VOLTAGE Connections
CONTINUOUS DUTY MECHANICAL CHARACTERISTICS 372 207 31,8 12,7 15,1 14,0 3,0 336 187 28,7 11,5 13,6 12,6 2,7 312 174 26,7 10,7 12,6 11,7 2,5 413 230 35,3 14,1 16,7 15,5 3,3 Winding code M0 Number of leads
More informationLC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A V AC coil
Product data sheet Characteristics LC1D25G7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V AC coil
Product data sheet Characteristics LC1D09B7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationDIGITAL INSTRUMENTS S.R.L. SPM-ETH (Synchro Phasor Meter over ETH)
DIGITAL INSTRUMENTS S.R.L. SPM-ETH (Synchro Phasor Meter over ETH) SPM-ETH (Synchro Phasor Meter over ETH) Digital Instruments 1 ver the years, an awareness of the criticality of the Power Grid and Orelated
More informationLC1D32P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A V AC 50/60 Hz coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationTRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES
TABLE OF CONTENTS 1.0 PURPOSE 2.0 SCOPE 3.0 CODES, STANDARDS AND REFERENCES 4.0 ORDER OF PRECEDENCE 5.0 SYSTEM PARAMETERS 5.1 Frequency 5.2 System Voltage 5.3 Short Circuit Rating 5.4 Insulation Levels
More informationDefinitions. Common Corridor:
Definitions Common Corridor: Contiguous right-of-way or two parallel right-of-ways with structure centerline separation less than the longest span length of the two transmission circuits at the point of
More informationLC1D12P7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Circuit-breaker,3p,160A Partno. NZMN2-M160 CatalogNo. 265724 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
Deliveryprogramme Circuitbreak.3pselect.protection Partno. Articleno. 265777 NZMH4-VE1600 Product range Circuit-breaker Protective function Systems, cable, selectivity and generator protection Standard/Approval
More informationPORTABLE TYPE ARC WELDING MACHINE
PORTABLE TYPE ARC WELDING MACHINE Heena Machine Products (Rajkot, Gujarat) HMP portable welding machine with modern looks and novel design is suited for small repair and maintenance job, where portability
More informationI r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100
Circuit-breaker,3p,400A Partno. LZMC3-A400-I Articleno. 111955 Similar to illustration Deliveryprogramme Product range Circuit-breaker Protective function System and cable protection Standard/Approval
More informationTRISHALA ELECTROLYTICS PVT LTD BANGALORE
P TRISHALA ELECTROLYTICS PVT LTD BANGALORE- 560044 AC MOTOR START ALUMINIUM ELECTROLYTIC CAPACITORS (Aluminum Body / Bakelite (Phenolic) Body) Scope Aluminum electrolytic Motor Start Capacitors are used
More informationSingle output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.
RoHS Lead-Solder-Exemption Compliant New 3.3 V and 5 V Output Models Universal Input 85-264 VAC Industry-Standard Footprint: 7.0" x 4.3" x 1.97" (177.8 x 109.2 x 50.0 mm) Input Transient & ESD Compliance
More informationANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester
ANSI DESIGN TEST REPORT Report No. EU1250-HR-00 Type PVI Intermediate Class Surge Arrester This report records the results of the design tests made on Type PVI Intermediate Class surge arresters in accordance
More informationLC1D12B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V AC coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationLC1D65AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC 50/60 Hz coil
Characteristics TeSys D contactor - 3P(3 NO) - AC-3 -
More informationGV3P80 TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink
Characteristics TeSys GV3P thermal-magn motor circuit breaker 70-80A EverLink Main Range Product name Device short name Product or component type Device application Trip unit technology Complementary Poles
More informationImplementation of a High-Speed Distribution Network Reconfiguration Scheme by Greg Hataway, Ted Warren, and Chris Stephens.
The following technical papers supporting this presentation are available at www.selinc.com: Trip and Restore Distribution Circuits at Transmission Speeds by Jeff Roberts and Karl Zimmerman International
More informationSIPROTEC 5 Application Note
www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-018: Answers for infrastructure and cities. SIPROTEC 5 - Application: SIP5-APN-018 Breaker-and-a-half Automatic reclosing and leader follower
More informationSeries CDP2 Definite Purpose Contactors
Series CDP2 Definite Purpose Contactors High performance economical contactors for commercial applications up to 90 Sprecher + Schuh s Definite Purpose contactors are ideal for commercial applications
More informationAPQ Series Type C Power Factor Correction Banks
APQ Series Type C Power Factor Correction Banks N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Regardless of the load size or type, APQ will work
More informationLC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC
Product datasheet Characteristics LC2D09E7 REVERSING CONTACTOR 575VAC 9A IEC Price* : 86.25 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category
More informationType: DILM25 10(24V50HZ) Article No.:
Type: DILM25 10(24V50HZ) Article No.: 277119 Ordering information Rated operational current AC 3 400 V I e A 25 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
More informationLC1D150B7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 150 A - 24 V AC 50/60 Hz coil
Product data sheet Characteristics LC1D150B7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationGrid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31
Data sheet Grid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31 The CM-UFD.M31 is a multifunctional grid feeding monitoring relay. It provides different monitoring functions in accordance
More informationAS09..S 3-pole Contactors - Spring Terminals
4 kw 5 hp AS09..S 3-pole Contactors - Spring AC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Rail-mounted, no tools required, - Additional
More informationLC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Product datasheet Characteristics LC1D09FE7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationType: DILM12 10(24VDC) Article No.:
Type: DILM12 10(24VDC) Article No.: 276845 Ordering information Rated operational current AC 3 400 V I e A 12 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
More informationPRINCIPLES AND APPLICATIONS
GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,
More information3M Sensored Termination (15 kv) QX-T15I-vi1-E
3M Sensored Termination () QX-T15I-vi1-E Data Sheet May 2016 Kit Contents: Each kit contains sufficient quantities of the following materials to make three single-phase terminations. 31" (REF) One piece
More informationLC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A V AC 50/60 Hz coil
Product datasheet Characteristics LC1D80F7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationSeries CT7N Bimetallic Overload Relays
Series CT7N imetallic Overload Relays Choose CT7N overloads in DC applications and when monitoring Variable Frequency Drives Sprecher + Schuh has always paid particular attention to the subject of motor
More informationContactors. Agency approvals. UL 508 Guide No. NLDX2, File # E CE/Semko Certified EN :1991 IEC DP 30 C 3P - 1 /B
Contactors Applications Type DP provide high performance with flexibility and reliability, designed to match numerous applications including: Motors Power supplies Food service equipment Compressors Business
More informationLC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil
Product data sheet Characteristics LC1D50AF7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationA V 50Hz / V 60Hz
A16-22-00 400-415V 50Hz / 415-440V 60Hz Products Low Voltage Products and Systems Control Products Contactors Block Contactors General Information Extended Product Type: A16-22-00 400-415V 50Hz / 415-440V
More informationAgency approvals UL 508 Guide No. NLDX2, File # E CE/Semko Certified EN :1991 IEC DP 30 C 3P - 1 /B
11 Applications Type DP provide high performance with flexibility and reliability, designed to match numerous applications including: Motors Power supplies Food service equipment Compressors Business machines
More informationBreaker-and-a-half Automatic reclosing and leader follower.
Breaker-and-a-half Automatic reclosing and leader follower www.siemens.com/siprotec SIPROTEC 5 Application Breaker-and-a-half Automatic reclosing and leader follower APN-018, Edition 1 Content 1... 3 1.1
More informationLC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Product data sheet Characteristics LC1D09F7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationCLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase)
CLASS 300 EQUIPMENT BE3-25A AUTO-SYNCHRONIZER (Single Phase) In applications requiring parallel operation of multiple generators or a single generator to an energized station bus, the BE3-25A automatically
More informationHYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.
More informationMANAGING POWER SYSTEM FAULTS. Xianyong Feng, PhD Center for Electromechanics The University of Texas at Austin November 14, 2017
MANAGING POWER SYSTEM FAULTS Xianyong Feng, PhD Center for Electromechanics The University of Texas at Austin November 14, 2017 2 Outline 1. Overview 2. Methodology 3. Case Studies 4. Conclusion 3 Power
More informationType: NZMN1 A100 Article No.: Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles
Type: NZMN1 A100 Article No.: 259085 Sales text Circuit breaker3p systems/cable prot. Ordering information Number of poles Description Rated current = rated uninterrupted current Setting range 3 pole I
More informationProtection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Circuit-breaker3psystems/cableprot. Partno. NZMB2-A250 Articleno. 259090 Deliveryprogramme Range Circuit-breaker Protective function System and cable protection Standard/Approval IEC Installation type
More informationHigh performance circuit breakers
Series High performance Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific trip characteristics
More informationLED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data
Product description Dimmable built-in for LED Constant current (with 2 adjustable output channels) Designed for outdoor and street luminaire Output power 2 x 38 W Suitable for mains voltage peaks (burst/surge)
More informationLC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A V AC 50/60 Hz coil
Product data sheet Characteristics LC1D50AFE7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationAutomatic Transfer Switch Control PLC Operator s Manual
MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch Control PLC Operator s Manual Dedicated Single Phase Transfer Switch ATS-22AG Automatic Transfer Switch INTRODUCTION 1.1 Preliminary
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker
Magnetic and Hydraulic-Magnetic Circuit Breaker 850-... Description Single, two, three and four pole magnetic and hydraulic-magnetic circuit breakers with trip-free-mechanism and toggle or rocker actuation.
More informationZero Crossover Dynamic Power Synchronization Technology Overview
Technical Note Zero Crossover Dynamic Power Synchronization Technology Overview Background Engineers have long recognized the power benefits of zero crossover (Figure 1) over phase angle (Figure 2) power
More informationGV2ME083 TeSys GV2 - Circuit breaker - thermal-magnetic A - spring terminals
Product datasheet Characteristics GV2ME083 TeSys GV2 - Circuit breaker - thermal-magnetic - 2.5...4 A - spring terminals Main Range Product name Device short name Product or component type Device application
More informationABB CM-UFD.M31 monitoring datasheet
ABB CM-UFD.M31 monitoring datasheet http://www.manuallib.com/abb/cm-ufd-m31-monitoring-datasheet.html The CM-UFD.M31 is a multifunctional grid feeding monitoring relay. It provides different monitoring
More informationHYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Constant current LED driver DALI Dimmable Product description Dimmable Independent constant current Adjustable output current between 350 and 1,050mA via DIP switch Max. output power 35 W Up to 88 % efficiency
More informationPBC series. RoHS. Ready. IEC-Type Contactors & Accessories 9-80 Amp AC-3, Amp AC-1 AC Coils. P&B PBC Series IEC Type Contactors & Accessories
PBC series IEC-Type Contactors & Accessories 9-80 Amp AC-3, 25-125 Amp AC-1 AC Coils File E38802 (PBC) RoHS Ready Users should thoroughly review the technical data before selecting a product part number.
More informationMagnecraft Power Relays
Description DPST-NO, 30 A; DPDT, 30 A (NO) / 3 A (NC) Description The series power relays offer a small package size and features Class F insulation for a maximum coil temperature of 55 C (3 F). These
More informationMAP110 AC-DC Series Data Sheet
Description Single-Output Model Selection VOLTAGE RANGE OUTPUT CURRENT OUTPUT CURRENT REGULATION REGULATION %p-p (NOTE 1) ACCURACY MAP110-1005 5V 4.95V to 5.50 16A 2 0.2% 1% 1% 5.09V to 5.11V MAP110-1012
More informationGV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A - screw clamp terminals. Main.
Product data sheet Characteristics GV2ME06 TeSys GV2-Circuit breaker-thermal-magnetic - 1...1.6 A - screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationGV2ME. Product data sheet Characteristics. TeSys GV2-Circuit breaker-thermal-magnetic A -screw clamp terminals. Main.
Product data sheet Characteristics GV2ME04 TeSys GV2-Circuit breaker-thermal-magnetic- 0.4...0.63 A -screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationGV2ME. Main. Device short name. Device application
Product datasheet Characteristics GV2ME32 TeSys GV2-Circuit breaker-thermal-magnetic - 24...32 A - screw clamp terminals Main Range Product name Device short name Product or component type Device application
More informationType MG-6 Auxiliary Relay Class 1E
Type MG-6 Auxiliary Relay Class 1E Product Guide Device Number: 94X, Y, Z ZPA Rating 4.2g ABB Application MG-6 relays have been specially designed and tested to establish their suitability for Class 1E
More informationPower Circuit of a UL508A Panel. Typical UL489 Application
Typical UL489 Application Power Circuit of a UL508A Panel Disclaimer: This is an application example. Installation should be done by a qualified electrician under the guidance of UL specifications.. Altech
More informationFixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Medium-Voltage Switchgear Totally Integrated Power NXPLUS Catalog HA 35.51 Edition 2015 siemens.com/medium-voltage-switchgear
More informationACB l COMET AIR CIRCUIT BREAKER
ACB l COMET AIR CIRCUIT BREAKER MASCHINENBAU HALBERSTADT GROUP, building on its 60 years legacy in power generation, introduces COMET Air Circuit Breaker designed to meet the standards and the requirements
More information10/13/2011 Planning Coordination Committee. Standards
Document name Category System Performance Regional Criterion ( ) Regional Reliability Standard (X) Regional Criterion ( ) Policy ( ) Guideline ( ) Report or other Document date 12/01/2011 Adopted/approved
More information02/11/2015
DIN Rail Mount 17.5 mm MUS/MUSF 80 AC/DC Part number 84872141 Control relays monitoring their own power supply - MUS : Over/undervoltage control Selectable latching (memory) function - MUSF : Over/undervoltage
More information20 mm Beam Pitch General Purpose Area Sensor. Distance between parts shelf and sensor can be shortened (Enables miniaturization of equipment)
OTHER SUNX PRODUCTS SERIES 0 mm Beam Pitch General Purpose Area Sensor Diagnosis Self-diagnosis Test input Interference prevention Wide sensing area of 7 m,60 mm with 0 mm beam pitch Refer to p.9l for
More informationGV2ME086 TeSys GV2 - Circuit breaker - thermal-magnetic A - lugs-ring terminals
Product data sheet Characteristics GV2ME086 TeSys GV2 - Circuit breaker - thermal-magnetic - 2.5...4 A - lugs-ring terminals Main Range Product name Device short name Device application Trip unit technology
More informationGV2P05. Main. Device short name. Device application
Product datasheet Characteristics GV2P05 Main Range Product name Device short name Product or component type Device application Trip unit technology TeSys TeSys GV2 GV2P Circuit breaker Motor Thermal-magnetic
More informationCatalogue numbers. PowerPact Multistandard. H-Frame, J-Frame unit-mount circuit breaker F-2. H-Frame, J-Frame circuit breaker accessories F-3
PowerPact Multistandard Catalogue numbers Functions and characteristics A-1 Installation recommendations B-1 Dimensions C-1 Wiring diagrams D-1 Additionals characteristics E-1 H-Frame, J-Frame unit-mount
More informationLC3D115M7 TeSys D - star delta starter - 3 x 3P (3 NO) A V AC coil
Characteristics TeSys D - star delta starter - 3 x 3P (3 NO) - 115 A - 220 V AC coil Main Range Product name Product or component type Device short name Contactor application Utilisation category Device
More informationMovable Contacts Heavy duty silver cadmium oxide composition to resist welding and contact erosion for greater reliability
Compare These Features Built-in Shock bsorber Reduces contact bounce for longer life. Coil Dust Cover Keeps dust and dirt away from magnet and coil area. Coil Class B (1300 C Insulation System) with wide
More informationCT7N CT7 CT7K 4 6 CT TJ 4 6 CT7K TKK 6 10 CT TK 6 9 CT7K TKL
Obsolete Overload Cross Reference Series CT7/CT7K to Cross Reference CT7 CT7K Directly Mounts to Contactor... Adjustment Catalog Adjustment Catalog Adjustment Catalog Code Code Range (A) Number Range (A)
More informationNERC Reliability Standard PRC-024 Generator Frequency and Voltage Protective Relay Settings
NERC Reliability Standard PRC-024 024-1 Generator Frequency and Voltage Protective Relay Settings Rick Terrill Luminant Power Generation Compliance NERC Standards Drafting Team Member Reliability Standard
More informationWeekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N
Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control
More informationLC1D09M7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A V AC coil
Bảng thông số sản phẩm Đặc diểm LC1D09M7 TeSys D contactor - 3P(3 NO) - AC-3 -
More informationINSTRUCTION MANUAL AUTORECLOSING RELAY GRR100 - B
INSTRUCTION MANUAL AUTORECLOSING RELAY GRR1 - B Toshiba Energy Systems Solutions Corporation 217 All Rights Reserved. ( Ver. 1.1) Safety Precautions Before using this product, please read this chapter
More informationLED Driver Compact fixed output
Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000
More informationLED Driver Linear / area fixed output
Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For
More informationGV2ME. Main. Device short name. Device application
Product datasheet Characteristics GV2ME10 Main Range Product name Device short name Product or component type Device application Trip unit technology TeSys TeSys GV2 GV2ME Circuit breaker Motor Thermal-magnetic
More informationPHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series
Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection
More informationOperating instructions Electronic preset counter Type series 717
Operating instructions Electronic preset counter Type series 717 1. Description 5.98.3_gb 6-digit adding/subtracting counter with two presets Very bright 8mm high LED display Counting and preset range
More informationSeries CDP2 Definite Purpose Contactors
Series 2 Definite Purpose High performance economical contactors for commercial applications up to 90 Sprecher + Schuh s Definite Purpose contactors are ideal for commercial applications including air
More informationAC1036. Definite Purpose Contactors
Definite Purpose Contactors Definite purpose contactors Definite purpose Contactors Applications Type DP contactors provide high performance with flexibility and reliability, designed to match numerous
More informationLED Driver Compact fixed output
Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000
More information