ECS INSTALLATION OF SERVICE WAYS AND CABLES (SCHNEIDER ELECTRIC)
|
|
- Annabel Anderson
- 5 years ago
- Views:
Transcription
1 THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE ENGINEERING CONSTRUCTION STANDARD ECS INSTALLATION OF SERVICE WAYS AND CABLES (SCHNEIDER ELECTRIC) Network(s): EPN, LPN, SPN Summary: This standard details the termination kits and Service Ways to be used for the installation of Service cables into UK Power Network's LV Distribution Cabinets supplied by Schneider Electric. Owner: Paul Williams Approved By: Steve Mockford Approved Date: 31/03/2014 Review Date: 31/03/2017 This document forms part of the Company s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of UK Power Networks Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Document History (The document history notes below are intended as a guide only and may not cover all of the changes. If you wish to make use of this document it should be read in full.) Version Date Details Author /03/2014 Document reviewed no changes required Paul Williams /07/2012 Document reviewed for publishing on G81 website Lee Strachan /08/2011 Document reclassified from EI to ECS Don Fossett /03/2011 Document rebranded Peter Rix /08/2010 Reviewed and review date extended Jesse Garcia /06/2010 Review of original Jesse Garcia /06/2007 Original D J Collis
2 Contents 1 Introduction Scope Glossary and Abbreviations Distribution Way Removal Removing LV Distribution Ways Installing a 600A Service Way Installing an 800A Service Way Top Entry 800A Service Way (LV Distribution Boards) Cable Installation Options Dependent Documents UK Power Networks 2014 All rights reserved 2 of 12
3 1 Introduction This engineering standard details cable installation methods to be used when installing a 600A or 800A service way into the new range of Schneider Electric (Merlin Gerin) LV distribution equipment. This engineering standard also provides details of the different cabling options and cable installation methods. The previous practice of purchasing bespoke cabinets to provide 800A services will be phased out as stocks are run down and the Schneider Electric LV distribution equipment, with the kits outlined in this engineering standard, will replace them. Individual cabling instructions are contained in this document and the associated drawings are available as appendices on Alfresco. 2 Scope This standard applies to the common range of UK Power Network s LV distribution equipment and includes: 13975S LV cabinet 4 x 500A ways 800A busbars C LV cabinet 5 x 500A ways 1600A busbars M LV cabinet 7 x 500A ways 1600A busbars B LV pillar 6 way 1600A L LV pillar 8 way 1600A T 1600A indoor LV board D 1600A indoor extension board. 3 Glossary and Abbreviations Term UK Power Networks Definition UK Power Networks (Operations) Ltd consists of three electricity distribution networks: Eastern Power Networks plc (EPN). London Power Network plc (LPN). South Eastern Power Networks plc (SPN). UK Power Networks 2014 All rights reserved 3 of 12
4 4 Distribution Way Removal 4.1 Removing LV Distribution Ways UK Power Networks now buys LV distribution cabinets and pillars preloaded with 630A distribution ways. To allow the installation of a 600A service way, one distribution way must be removed. When installing an 800A service way, two distribution ways must be removed. Follow the instructions below to remove either one or two distribution ways to allow installation of the service ways. For LV cabinets the 800A service ways have been designed to go on the left hand end of the cabinets away from the transformer disconnector. On LV boards the position of the service way may be chosen to suit site requirements. 1. Undo and remove the phase screen retaining screw. This allows the phase screen to be removed. 2. The screening may now be removed. Lift each phase screen slightly and remove to expose the stalks and mounting bolts. 3. Remove the black plastic plug to expose the 17mm nuts that secure the distribution way to the busbars and remove the nut. There is one nut per phase. UK Power Networks 2014 All rights reserved 4 of 12
5 4. Remove the fixing bolts at the bottom and top of the distribution way. 5. The distribution way may now be removed. These components may be retained for spares or returned to the plant store for re-use. For an 800A service repeat the process and remove a second way adjacent to the first way removed. UK Power Networks 2014 All rights reserved 5 of 12
6 5 Installing a 600A Service Way The 600A service way takes up the same space as one distribution way. Follow the removal process in Section 3.1 to remove the distribution way. 600A service ways have been designed to accommodate only un-armoured single core cables up to 400mm 2 and UK Power Networks uses a UT/9I connector to terminate these cables. 1. Install the 600A service way into one way on the LV cabinet, board or pillar. 2. Install the spacer washer provided behind the service way as shown. Install the top mounting bolt and clear plastic screen. 3. Install the bottom mounting bolt. Note: The screen provided should be mounted on the bottom fixing bolt for top entry cables. 4. Install the busbar connecting nut on each phase and tighten all three phases and the unit mounting bolts. 5. Install the four-way cable cleat to replace original. 6. Install the neutral connection. This is either a double bolt unit (shown) or has a single bolt connection to the LV cabinet and pillar neutral bars. Check that all electrical and support nuts and bolts have been tightened before cabling. UK Power Networks 2014 All rights reserved 6 of 12
7 6 Installing an 800A Service Way The 800A service way takes up the same space as two distribution ways. Follow the removal process in Section 3.1 to remove the distribution ways. 800A service way kits have been designed to work with un-armoured and armoured single core cables. These cabling options will remain available and include: 185mm 2 bunched waveform. 300mm 2 stranded copper (double insulated un-armoured). 740mm 2 sectorial aluminium (armoured). 630mm 2 stranded copper (armoured). 300mm 2 parallel waveform cables. A range of cabling solutions are available to cope with these different existing and new cabling options. These are provided in the attached drawings listed in Section 7, which detail cable installation, SAP codes and phasing of the cable connections. Where UK Power Networks provides and owns the service cables, our preferred cabling solution is to use bunched 185mm 2 waveform cables and a UT/9I connector to terminate these cables. The instructions in this section apply to all 800A service way kits as the installation process is common to all cable solutions. 1. Install the 800A service way into two ways on the LV cabinet, board or pillar. Install the busbar screen in the left hand position. 2. Install the spacer washer provided. Install top mounting bolt and clear plastic screen. 3. Install the bottom mounting bolt. Note: The screen provided should be mounted on the bottom fixing bolt for top entry cables. UK Power Networks 2014 All rights reserved 7 of 12
8 4. Install the busbar connecting nut on each phase and tighten all three phases and the unit mounting bolts. 5. The 800A service way is now secure in position. 5. Install the cable cleat, to replace the two original cleats. Note: EPN/SPN 630/740mm cabling solution shown. 6. Install the neutral connection. Both busbar bolts must be installed and tightened. Check that all electrical and support nuts and bolts have been tightened before cabling. You are now ready to start cabling. UK Power Networks 2014 All rights reserved 8 of 12
9 7 Top Entry 800A Service Way (LV Distribution Boards) When installing an 800A service way onto a LV distribution board it may be reversed to cope with top entry cables where the cables enter the substation at high level. Top entry cable access requirements are more common on the LPN network, therefore the LPN cabling solution was used to demonstrate the process. To allow the 800A service way to accept top entry cables the copper work must be reversed. This may be done more easily before the service way is mounted on the LV distribution board. The pictures below illustrate the process to be followed. 800A service ways, supplied by Schneider Electric, are ready for bottom entry cables. 1. The clear plastic screening and the white phase covers must be removed in one piece. The screen is secured by the bolt at the top of the distribution Way and a bolt on the busbar screen. 2. This will expose the busbar stalks and cable connection plates. 3. You may now reverse the busbar screen so that the steel bracket is at the bottom. UK Power Networks 2014 All rights reserved 9 of 12
10 4. Remove the cable connection plates and reverse their position. The copper-work from L3 moves to L1 Note: A packing washer must be placed between the connector plate and the mounting stalk. The copper work from L2 is reversed The copper work from L1 moves to L3 UK Power Networks 2014 All rights reserved 10 of 12
11 5. Move the neutral connection to the top neutral bar. 6. Install the cable cleat at the top of the LV board as shown. 7. The clear plastic screening must now be removed from the white phase barriers and moved up so that the bottom of the screening is level with the bottom of the L3 phase shield. 8. The cut-out on the clear plastic screen must be removed. This will allow the screen to be refitted. 9. To maintain the IP rating of the board, insert the small angled clear plastic piece shown and mount with bracket supplied behind the circuit designation label. UK Power Networks 2014 All rights reserved 11 of 12
12 8 Cable Installation Options New service cables owned by UK Power Networks will use 185mm² bunched cables. The new 800A service ways have been designed to handle this cabling solution. Current cabling options are still supported. 600A service way currently used in LPN will remain unchanged apart from changes to allow installation into the Schneider Electric LV distribution equipment. Kits are also available to deal with the current cabling and termination solutions being used on LPN, SPN and EPN. The drawings associated with this engineering standard provide cabling information, Stores codes and phasing information. Wherever possible, common components have been used. The current SPN and EPN solutions will be phased out. The LPN solution will use the same service way with an alternative cable cleat. The current practice on the LPN network, which requires the customer to supply the service cables, will remain in force. There are six cabling options available. These are shown in the attached drawings: ECS A Service 300/400mm Stranded Copper Cables (UK Power Networks). ECS A Service 185mm 2 Bunched Cables (UK Power Networks). ECS A Service 2 x 300mm 2 cables (LPN). ECS A Service 740mm 2 Armoured Cables (SPN). ECS A Service 630mm 2 Armoured cables (EPN). ECS A Service Parallel 300mm 2 Waveform Cables (EPN). 9 Dependent Documents The documents below are dependent on the content of this document and may be affected by any changes. ECS ECS ECS ECS ECS ECS A Service 300/400mm Stranded Copper Cables (UK Power Networks) 800A Service 185mm 2 Bunched Cables (UK Power Networks) 800A Service 2 x 300mm 2 cables (LPN) 800A Service 740mm 2 Armoured Cables (SPN) 800A Service 630mm 2 Armoured cables (EPN) 800A Service Parallel 300mm 2 Waveform Cables (EPN) UK Power Networks 2014 All rights reserved 12 of 12
ECS COMBINED CUT-OUT AND CT CHAMBER INSTALLATION
Document Number: ECS 13-0080 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 13-0080 COMBINED CUT-OUT AND CT CHAMBER INSTALLATION EPN, LPN, SPN This standard details the procedure for installing
More informationAccessories. EasyPact and Vigi CVS100/160/ short LV long LV Steel connectors 1 x (1.5 to 95 mm²) ; y 160 A Set of 3 LV429242
Catalogue numbers Accessories CVS100/160/250 DB112225 2 short LV429235 2 long LV429236 DB112226 Steel connectors 1 x (1.5 to 95 mm²) ; y 160 A Set of 3 LV429242 LV429243 DB112225 DB112726 Aluminium connectors
More informationAssembly instructions
Assembly instructions Model: MXR0024/KIT TV Aerial - 18 Element Kit Contact: Helpline: +44 (0)1553 811000 Email: support@maxview.co.uk Web: www.maxview.co.uk Maxview reserve the right to change specifications
More informationART2000i Digital Dimming System. Installation guide. Stock number *8200-
ART2000i Digital Dimming System Installation guide Stock number 8200-0159 *8200- 0159* Useful Avolites phone numbers:- Avolites England Sales and service* (+44) (0) 20 8965 8522 Service out of hours* (+44)
More informationIdentification of LV Cables
Identification of LV Cables Owner Name Title Peter Vujanic Head of Health Safety and Environment Signature Date 09 July 2018 Authoriser Name Title Dudley Sparks Operational Safety Manager Signature Date
More informationCatalogue numbers. PowerPact Multistandard. H-Frame, J-Frame unit-mount circuit breaker F-2. H-Frame, J-Frame circuit breaker accessories F-3
PowerPact Multistandard Catalogue numbers Functions and characteristics A-1 Installation recommendations B-1 Dimensions C-1 Wiring diagrams D-1 Additionals characteristics E-1 H-Frame, J-Frame unit-mount
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS BEFORE INSTALLING OR ADJUSTING THIS PRODUCT, PLEASE READ THESE INSTRUCTIONS CAREFULLY. PLEASE KEEP THIS GUIDE FOR FUTURE REFERENCE FIBER OPTIC SWING-OUT PATCH PANEL INSTRUCTION
More information2100, 2200, 4100, 6200, MPB Series Side Mount Drive Package for Light Load 60 Hz Gearmotors
00, 00, 400, 600, MPB Series Side Mount Drive Package for Light Load 60 Hz Gearmotors Installation, Maintenance & Parts Manual DORNER MFG. CORP. INSIDE THE USA OUTSIDE THE USA P.O. Box 0 975 Cottonwood
More informationEffective earthing of screened cables
NOVEMBER 2006 Effective earthing of screened cables All metallic containment items, other extraneous metalwork and the screens of telecommunications cables in an information technology environment must
More informationHCS - HES Cabling Systems
HCS - HES Cabling Systems Installation Manual for HCS High-Capacity Fiber-Optic Rack-Mount Cabinets Be sure to read and completely understand this procedure before applying product. Be sure to select the
More informationPOLICY & APPLICATION GUIDE FOR 11kV POLYMERIC CABLES
1. SCOPE This document provides information and guidance on the application of polymeric cables on the SPEN 11kV network. Throughout this document, references to 11kV shall by inference also relate to
More informationSingle sensor setup with NIVEL210
Single sensor setup with NIVEL210 Essential Items: 576 198 NIVEL210 RS232 748 335 Cable, Lemo 0 power supply cable Lemo 1 802 902 Cable, Lemo 0 722 409 Power supply plus power cords 802 902 576 198 748
More information2100/2200/4100/6200 & MPB Series Bottom Mount Drive Pack. for Standard Load Parallel Shaft 60 Hz Gearmotors
00/00/400/600 & MPB Series Bottom Mount Drive Pack. for Standard Load Parallel Shaft 60 Hz Gearmotors Installation, Maintenance & Parts Manual DORNER MFG. CORP. INSIDE THE USA OUTSIDE THE USA P.O. Box
More information3M Distribution Box (DDB)
3M Distribution Box (DDB) Merged Copper and Fiber Pole/Post Mount Enclosure Installation Instructions November 2015 78-0015-2736-1-A 2 November 2015 78-0015-2736-1-A Contents 1.0 General 2.0 Enclosure
More informationSCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS UP TO 300 cm. of width
SCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS UP TO 300 cm. of width Before installing the screen winch system, please read the following instructions carefully: The screen winch system must be used
More informationPendant Light Fitting IEC Series 6470/2
> Available light sources high-pressure sodium lamps (HSE) metal halide lamps (HIE) halogen lamps (QT) > Versatile mounting methods > Enclosure made of saltwater-resistant aluminium www.stahl.de 11435E
More informationMedium Box for Cable Termination
FIST-MB2-T I N S T A L L A T I O N I N S T R U C T I O N Medium Box for Cable Termination Contents 1 Introduction 1.1 Product description. 2 General 2.1 Tools 2.2 Kit contents 3 Installation and pre assembling
More informationSQM40/41 Actuators for air and gas dampers
SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The
More informationFIST-MB2-S. FIST Medium Box for Cable Splicing Only. 4 Cable installation. 1 Introduction. Contents. 2 General. 5. Fiber routing to individual trays
FIST-MB2-S I N S T A L L A T I O N I N S T R U C T I O N FIST Medium Box for Cable Splicing Only Contents 1 Introduction 1.1 Product description 2 General 2.1 Tools 2.2 Kit contents 3 Installation and
More informationDIGITUS WALL MOUNT ENCLOSURE
Product Picture: Product Description: The DIGITUS Compact Series is a range of 19" wall mount enclosures developed for installation of both cabling and equipment. The enclosures are special designed to
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMC1-A160 Circuit-breaker, 3p, 160A Part no. NZMC1-A160 Catalog No. 283296 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationOptical Distribution Box 300 Installation Guide. Version : R0.0
Optical Distribution Box 300 Installation Guide Document No. : OD16-546-L-01 Version : R0.0 Date: 21-Mar-2018 IMPORTANT INSTRUCTIONS When using fiber optic equipment, basic precautions should always be
More informationINSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN
INSTRUCTION AND MAINTENANCE VIDEO MOTORE PROJECTION SCREEN 1.1 TECHNICAL DATA PRODUCT DESCRIPTION Screens made with the following projection fabrics: SOFT WHITE, MATT WHITE SOFT, SOFT WHITE TRANSOUND,
More informationFIST-GCOG2-Dx6. Follow all local safety regulations related to optical fiber plant elements.
FIST-GCOG2 I N S T A L L A T I O N I N S T R U C T I O N TC-986-IP Rev A, Mar 2017 www.commscope.com FIST-GCOG2-Dx6 Content 1 Introduction 2 General 2.1 Abbreviations 2.2 Kit contents 2.3 Tools 2.4 Accessories
More informationUNDERGROUND CONSTRUCTION MANUAL MATERIAL DATA
UNDERGROUND CONSTRUCTION MANUAL Back to MAIN INDEX Go to SECTION INDEX CONSTRUCTION DESCRIPTION DWG CONSTRUCTION DESCRIPTION DWG LV cable details 5108 HV cable details 5109 Insect protected LV cable details
More informationOperation and Maintenance Guide Electric Needle Scalers
Operation and Maintenance Guide Electric Needle Scalers Models Covered Model Number ENS100V ENS200V Electric Needle Scaler, 110V-1ph Electric Needle Scaler, 220V-1ph Description IMPA Number 59 12 01 59
More informationCONSTRUCTION SPECIFICATION FOR TRAFFIC SIGNAL EQUIPMENT
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 620 APRIL 2017 CONSTRUCTION SPECIFICATION FOR TRAFFIC SIGNAL EQUIPMENT TABLE OF CONTENTS 620.01 SCOPE 620.02 REFERENCES 620.03 DEFINITIONS 620.04
More informationSCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS UP TO 300 cm. of width
SCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS UP TO 300 cm. of width Before installing the screen winch system, please read the following instructions carefully: The screen winch system must be used
More informationGF-KSW-48 Series of Fiber Optic Distribution Box. Instruction Manual
Instruction manual GF/KSW/48 Page Nr 1 GF-KSW-48 Series of Fiber Optic Distribution Box Instruction Manual 1. General Introduction GF-KSW-48 series of fiber optic distribution box is applicable to fiber
More informationFiber Optic Splice Closure GPJ Instruction Manual. [Escribir texto]
Fiber Optic Splice Closure GPJ09-8205 Instruction Manual [Escribir texto] 0 Table of Contents 1. General Introduction 2 2. Specification 2 3. Structure 2 4. Installation instructions. 4 5. Operation procedure.
More informationNC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM
NC-1000 INSTALLATION MANUAL NC-1000 FIBRE OPTIC CROSS-CONNECTION SYSTEM Content 1. General 5 2. The products of NC-1000 system 6 3. Mounting of the frame 8 4. Earthing of the frame 8 NC-1000 FIBRE OPTIC
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. CSA 100. conductor. I r A 50-63
Circuit-breaker,4p,63A Partno. NZMH1-4-A63 Articleno. 284426 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function System and cable protection Standard/Approval IEC
More informationFor Sales & Information, Call Toll Free: (888)
PCR Outline Dimensions 2.75" (69.8 mm) 0.44" (11 mm) 0.25" (6.3 mm) (-) (+) 15.8" (401 mm) 9.3" (236 mm) Nameplate 1.25" (31.8 mm) 3.0" (76 mm) 7.40" (188 mm) 12.63" (321 mm) R 0.219" (R 5.56 mm) Serial
More information2178-L/S Series Fiber Optic Splice Case with Gasket
2178-L/S Series Fiber Optic Splice Case with Gasket Instructions for: 2178-S Splice Case 2178-LS Splice Case 2178-LL Splice Case 2181-LS Cable Addition Kit May 1997 34-7041-9949-5-A 1 Table of Contents
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100
DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective
More informationControl cabinet interface and cable entry systems
Modlink MPV Control cabinet interface The Modlink MPV control cabinet interface provides the connection from the control cabinet to the fieldbus environment (outside) in a simple way. Durable connection
More informationEXPlora. Introduction
Introduction EXPlora The EXPlora range is most suited to manufacturers of ancillary electrical equipment such as motors, pumps, lighting equipment, process and control gear for use in factories and plant
More informationTV Lift System Model CL-65 Installation Instructions
TV Lift System Model CL-65 Installation Instructions Contact: Support@Nexus21.com Toll Free: (866) 500-5438 Phone: (480) 951-6885 Fax: (480) 951-6879 Revised: 01/17/17 Below is a parts list describing
More informationSECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.
SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of
More informationIndustrial Monitor Update Kit
Industrial Monitor Update Kit (Bulletin Number 6157) Installation Instructions 2 Table of Contents Table of Contents Industrial Monitor Update Kit... 3 Overview... 3 Part 1 - Initial Preparation... 5 Part
More informationEXEL. Ex de. - Double locking system operated by hexagonal-head tool - Double channel electronic ballast - Zones 1, 2, 21, 22. G13 bi-pin lamp holder
EXEL - Double locking system operated by hexagonal-head tool - Double channel electronic ballast - Zones 1, 2, 21, 22 Reinforced polyester resin body G13 bi-pin lamp holder Internal emergency batteries
More information3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx Preparing drop cable with micro-tubes
FIST-GCOG2-Dx24 I N S T A L L A T I O N I N S T R U C T I O N FTTH closure for micro-tubes and micro-cables Content 1 Introduction 2 Kit content 3 Closure preparation 3.1 Work-stand 3.2. Opening FIST-GCOG2-Dx24
More informationInstallation instructions Ex frames
General information Installation and maintenance: For European member countries of GENELEC shall standard EN 60079-14 and EN 60079-17 be considered. For countries members of IECEx shall standard IEC 60079-14
More informationRKSlimlift / EM. Two-stage lifting column
RKSlimlift / EM Two-stage lifting column Two-stage lifting column - RKSlimlift / EM Rod-shaped design and extremely quiet operation RKSlimlift RKSlimlift EM 4 fixing threads 9Simple 9 connection Drive
More informationCONTACT-DUO-PROFILE. Contact-Duo-Profile overview
13 6.3 13 6.3 4.7 20.7 24.6 +1/-0 24.6 +1/-0 2.5 24.6 +1/-0 20.7 4.3 +0.3-0.4 3.6 ±0.3 32.5 32.5 32.5 5 2 CONTACT-DUO-PROFILE Contact-Duo-Profile overview 13 6.3 13 6.3 4.7 2.5 16±0.8 4.7 2.5 4.7 2.5 2.6
More informationUSER MANUAL. GOLDMUND LOGOS 1N-2N SPEAKER SYSTEM Active Speaker
USER MANUAL GOLDMUND LOGOS 1N-2N SPEAKER SYSTEM Active Speaker Thank you for purchasing the Goldmund LOGOS 1N-2N SPEAKER SYSTEM The Goldmund Logos line fully incorporates the technological expertise developed
More informationSignalling Cable Equivalent Sizes (formerly RT/E/C/11213)
NR/GN/SIG/11213 Ref Date (formerly RT/E/C/11213) This temporary front sheet facilitates change to the new Network Rail Standards referencing nomenclature. The Ref above will be formally allocated to this
More information2000i. Projector Replacement Guide. for Projector Replacement Kits. NEC MT1060R ( ) and NEC MT860R ( ) Interactive Whiteboard
2000i Interactive Whiteboard Projector Replacement Guide for Projector Replacement Kits NEC MT1060R (03-00043) and NEC MT860R (03-00041) 99-00496-00 Rev A0 FCC Warning This equipment has been tested and
More information24 Channel Demultiplexer
USER GUIDE 24 Channel Demultiplexer Doc. No. : 88 601 27 (408481 A?0/3) k!rand Lighting Issue: 2 Date : Oct 1990 i; Contents INTRODUCTION................................ 1 Delivery Inspection..............................
More informationSignalling Cable Equivalent Sizes
Signalling Cable Equivalent Sizes Signatures removed from electronic version Submitted by... Jim Harper Nominated Responsible Manager Synopsis This Standard Authorises the use of cables to GS/ES 0872 as
More informationOPTEVA 828 LOBBY ATM FRONT LOAD PLAN VIEW FRONT ELEVATION SIDE ELEVATION
L0 CALL -800--600 OPTEVA 88 LOBBY ATM FRONT LOAD WITH 0mm ( 6") CEN III AND CEN IV SAFE CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS AND INFORMATION. PLEASE SEE PLANNING AND
More informationSatellite Dish Installation Manual (Ver. 2) 1
Satellite Dish Installation Manual Provided by DiscoverNet, Inc. Satellite Dish Installation Manual (Ver. 2) 1 Table of Contents Section 1: Introduction Page 3 Section 2: Recommended Tools and Materials
More informationMONO AMPLIFIER KIT ESSENTIAL INFORMATION. Version 2.2 CREATE YOUR OWN SPEAKER DOCK WITH THIS
ESSENTIAL INFORMATION BUILD INSTRUCTIONS CHECKING YOUR PCB & FAULT-FINDING MECHANICAL DETAILS HOW THE KIT WORKS CREATE YOUR OWN SPEAKER DOCK WITH THIS MONO AMPLIFIER KIT Version 2.2 Build Instructions
More informationLifestyle. Dual Channel Programmer. for heating AND hot water. Installation and User Instructions DUAL CHANNEL ISSA
Lifestyle Dual Channel Programmer for heating AND hot water Installation and User Instructions DUAL CHANNEL 06490197001 ISSA INSTALLATION INSTRUCTIONS PLEASE NOTE: INSTALLATION MUST ONLY BE CARRIED OUT
More informationInformation on new products!
ApS Industriparken 10 4760 Vordingborg Denmark T + 45 55 98 55 99 F + 45 55 98 55 04 cabelcon@cabelcon.dk CVR-nr. 17 37 66 32 www.corning.com To our customers and users December 2009 Information on new
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationI r A Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100
Circuit-breaker,3p,400A Partno. LZMC3-A400-I Articleno. 111955 Similar to illustration Deliveryprogramme Product range Circuit-breaker Protective function System and cable protection Standard/Approval
More informationDS1 Cross-Aisle Panel
DS1 Cross-Aisle Panel Model 005-0005-0100 Installation Guide 1.1 Overview 1.1.1 Inspection Compare the contents of the DS1 Cross-Aisle Panel shipping container with the packing list. Call Telect if anything
More informationSCdefault. 900 Installation instructions. Accessories Part No. Group Date Instruction Part No. Replaces :36-29 Sep
SCdefault 900 Installation instructions SITdefault Upgrade to Premium 300 sound system MONTERINGSANVISNING INSTALLATION INSTRUCTIONS MONTAGEANLEITUNG INSTRUCTIONS DE MONTAGE Accessories Part No. Group
More informationImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL
SPECIFICATIONS MODEL NUMBER: XRT910-0-0-GB-XX XRT911-0-0-GB-XX XTT911-0-0-NN-XX IMPROX TRT ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL Working Environment XRT910-0-0-GB-XX... (Aluminium Extruded
More informationCables: Positive Identification and Spiking. Approval: EO Production Revision: A
Clean Green & Safe SP24-75 Cables: Positive Identification and Spiking Process Authority: Area Manager Lower Tumut Approval: EO Production Version Date: 14/03/2011 Revision: A 1. Purpose This procedure
More informationLM 1. Owner s manual
LM 1 Owner s manual Figure 1 LM 1 Owner s manual English...1 Français...2 Deutsch...3 Español...4 Português...5 Figure 2 Italiano...6 Nederlands...7 >1.5m Ελληνικά...8 Русский...9...10...11 Polski...12
More informationFiber Optic Splice Closure GPJ Instruction Manual
Fiber Optic Splice Closure GPJ09-9401 Instruction Manual 1. Brief Introduction GPJ09-9401 type of Fiber Optic Splice Closure is a member in dome series, the main function is to provice direct pass, branch
More informationInductive sensor. 2-wire, analog output BI8-M18-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M18 x 1 Chrome-plated brass 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection Wiring diagram Type code Ident no.
More informationOPERATION NOTES FOR PSIDEX AUDIO PGP-1A PRE-AMPLIFIER DESCRIPTION INSTALLATION
OPERATION NOTES FOR PSIDEX AUDIO PGP-1A PRE-AMPLIFIER DESCRIPTION The Psidex Audio Laboratory PGP- 1A is a vacuum tube based microphone preamp and program line amplifier designed to provide solid, robust
More information3 SLiC Aerial Closure with Rubber End Seal
3 Aerial Closure with Rubber End Seal Instructions 1.0 General 1.1 This instruction bulletin describes the assembly of the 3M Aerial Closure with external bonding hanger brackets. These closures are suitable
More informationRCA3 SOLENOID PILOT VALVES PENTAIR CLEAN AIR SYSTEMS
RCA3 SOLENOID S PENTAIR CLEAN AIR SYSTEMS GOYEN RCA3D REMOTE PILOT Remote solenoid pilot valve to control the actuation of dust collector diaphragm valves. RCA3D with flying lead connection INSTALLATION
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationSERIES BNC 50, COAXIAL MINIATURE CONNECTORS
SERIES BNC 50, COAXIAL MINIATURE CONNECTORS DESCRIPTION CONTENTS PAGE HUBER+SUHNER BNC is still one of the most popular connector series, featuring a two stud bayonet coupling mechanism, which is particularly
More informationLCS 2 RJ 45 Cat. 6A HD panels and units
87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1
More information2178 Fiber Optic Splice Case and 2181 Cable Addition Kit
2178 Fiber Optic Splice Case and 2181 Cable Addition Kit Instructions January 1994 Issue 1, 34-7029-6387-6 1 2 Contents: 1.0 General... 4 2.0 Specifications... 4 3.0 Kit Contents... 5 SECTION 1: 2178 Splice
More informationTroubleshooting Guide 9630 Series
Troubleshooting Guide 9630 Series Satellite Solutions for Mobile Markets 11200 Hampshire Avenue South, Bloomington, MN 55438-2453 Phone: (800) 982-9920 Fax: (952) 922-8424 www.kingcontrols.com 1305-SEMI
More informationSPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment
1993 Specifications CSJ 0500-01-117 SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic Video
More informationTurret Replacement Instruction Manual
Automatic Multi-Satellite TV Antenna Turret Replacement Instruction Manual for models RPSKLGL, RPSKSML, SK-LG00, SK-SM00, & RP-SWM For help, email help@winegard.com or call -800-788-7 568 Raising the Antenna
More informationSCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS FROM 300 cm. UP TO 450 cm. of width
SCREEN WINCH SYSTEM INSTALLATION MANUAL FOR SCREENS FROM 300 cm. UP TO 450 cm. of width Before installing the screen winch system, please read the following instructions carefully: The screen winch system
More informationUltra-Grip 2 Crimp Connector Hand Tool Kit for Coaxial Cable Connectors, Powerpole Connectors, Insulated and Non-Insulated Crimp Terminals
Ultra-Grip 2 Crimp Connector Hand Tool Kit for Coaxial Cable Connectors, Powerpole Connectors, Insulated and Non-Insulated Crimp Terminals DXE-UT-KIT-CRMP2 DXE-UT-KIT-CRMP-INS-Revision 0a DX Engineering
More informationCable entry and cable holding systems Solutions for cable applications
Cable entry and cable holding systems Solutions for cable applications Overview Murrplastik Systemtechnik GmbH has offered cable entry strips, cable entry panels, strain relief systems, cable holding systems
More informationRegister your product and get support at www.philips.com/welcome SDV8625T/27 User manual Contents 1 Important 4 Safety 4 For indoor use 4 For outdoor use 4 Notice for USA 4 Notice for Canada 5 Recycling
More information1 de 18 4/1/ :53
1 de 18 4/1/2012 09:53 Calendar Members Search Help Logged in as: DJ Cleberson ( Log Out ) My Controls View New Posts My Assistant My Friends 0 New Messages Invision Power Board > Help Desk > Innofader
More informationQuad 7-segment display board
Quad 7-segment display board www.matrixtsl.com EB008 Contents About this document 3 Board layout 3 General information 4 Circuit description 4 Protective cover 5 Circuit diagram 6 2 Copyright About this
More informationInstallation instructions, accessories. Subwoofer. Volvo Car Corporation Gothenburg, Sweden. Page 1 / 29
Installation instructions, accessories Instruction No 30752136 Version 1.1 Part. No. 30752135 Subwoofer Volvo Car Corporation Subwoofer- 30752136 - V1.1 Page 1 / 29 Equipment A0000162 A0000161 A0801178
More informationSTB Distribution Box Screw or IDC Type Indoor DP Outdoor DP Wall & Pole DP Pillar DP
Distribution Boxes STB Distribution Box Screw or IDC Type Indoor DP Outdoor DP Wall & Pole DP Pillar DP BOOK 1.indd 27 9/22/10 7:22:14 PM STB Distribution Box for Telecommunication 2 Pair Distribution
More informationA449-6S 70 CENTIMETER FM YAGI ANTENNA MHz
ASSEMBLY AND INSTALLATION A449-6S 70 CENTIMETER FM YAGI ANTENNA 440-450 MHz COMMUNICATIONS ANTENNAS 951425 (7/93) WARNING THIS ANTENNA IS AN ELECTRICAL CONDUCTOR. CONTACT WITH POWER LINES CAN RESULT IN
More informationFOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N
FOSC-600 C and D I N S T A L L A T I O N I N S T R U C T I O N In-line and butt version Cold applied re-usable fiber optic closure Contents 1 Introduction 1.1 Product description 1.2 Capacity 2 General
More informationRevision 1.0 Parts List Mega
Revision.0 www.grindex.com Parts List 824.390 Mega Table of Contents Table of Contents Introduction... 2. Specially approved products... 2 2 Product Description...3 2. Products included... 3 2.2 The data
More informationM SERIES DISPENSER M SERIES DISPENSER
M SERIES DISPENSER PART NUMBER 5006621 M SERIES DISPENSER M SERIES DISPENSER... M - 1 M15 TOP EXPLODED VIEW... M - 2 M15 TOP PARTS LIST... M - 3 M15 BASE EXPLODED VIEW... M - 4 M15 BASE PARTS LIST... M
More informationGENUINE PARTS. SIRIUS Under Glass Antenna Kit
GENUINE PARTS SATELLITE RADIO INSTALLATION INSTRUCTIONS 1. DESCRIPTION: Satellite Radio System 2. APPLICATION: Pathfinder (2006-2007) 3. PART NUMBERS: XM Tuner Kit 999U9-AS005 SIRIUS Tuner Kit 999U9-AS006
More information19" TiRAX cabinet system. from page 3. 19" NETcell cabinet system from page 31. Open 19" racks from page 43
19" TiRAX cabinet system from page 3 19" NETcell cabinet system from page 31 Open 19" racks from page 43 all-mounting/stand-alone distribution systems from page 53 all-mounting enclosure systems from page
More informationA CENTIMETER FM YAGI ANTENNA MHz
ASSEMBLY AND INSTALLATION A449-70 CENTIMETER FM YAGI ANTENNA 440-450 MHz COMMUNICATIONS ANTENNAS 951424 (10/91) WARNING THIS ANTENNA IS AN ELECTRICAL CONDUCTOR. CONTACT WITH POWER LINES CAN RESULT IN DEATH
More informationINSTALLATION AND OPERATING MANUAL FOR ALL MATSUKO SWITCHBOX MODELS SWB 5 SWB 5P SWB 5P+PG WARNING:
MSB12906121MAN UK English INSTALLATION AND OPERATING MANUAL FOR ALL MATSUKO SWITCHBOX MODELS SWB 5 SWB 5P SWB 5P+PG WARNING: Ensure that the Matsuko Switchbox is switched off at the mains before you attempt
More informationPanzer 3.0 Assembly Instructions & Checklist
Panzer 3.0 Assembly Instructions & Checklist Parts Included & Preparation Legend A. 5x Silver M4 Aluminum Screws B. 4x 10-24 Screws C. 8x 4-40 Pan head Screws D. 2x 4-40 Flat head Screws E. 2x 4-40 Nuts
More informationGENUINE PARTS SATELLITE RADIO INSTALLATION INSTRUCTIONS. 1. DESCRIPTION: Satellite Radio System 2. APPLICATION: Frontier (2006~)
GENUINE PARTS SATELLITE RADIO INSTALLATION INSTRUCTIONS 1. DESCRIPTION: Satellite Radio System 2. APPLICATION: Frontier (2006~) Xterra (2006~) 3. PART NUMBERS: XM Tuner Kit 999U9-AS003 SIRIUS Tuner Kit
More informationAutomatic Connector MHV Connectors MHV Introduction MHV series connectors Contents Polarized mating interfaces Anti-Rock mating interfaces
Automatic s 2004 Automatic. All rights reserved. pdf 1.0 3-18-04 Contents Specifications........................... 2 Straight Cable Plugs...................... 3 Right Angle Cable Plugs...................
More information3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket
3M SLiC 530/533/733-2 Port 0.61 Cable Entry Bracket 3M SLiC 530/533/733-2 Port-MSM 0.61 Cable Entry Bracket For use with 3M SLiC Free-Breathing Fiber Optic Closures and Terminals Instructions November
More informationCatalog. Industrial Plugs & Sockets The complete range
Catalog Industrial Plugs & Sockets The complete range Contents Type Page Introduction... 4 IEC 60309-2 (clock)... 5 Product overview Critical & Safe... 6 Tough & Safe... 7 Easy & Safe... 8 Plugs Splashproof...
More informationS Regulators. Supplement 1. Contents. Control Replacement Assembly Installation Instructions Supplement
Regulators Control Replacement Assembly Installation Instructions Supplement Service Information S225-40-1 Supplement 1 Figure 1. CL-6A Control Replacement Assembly. Contents Safety Information... 2 Product
More informationENCAPSULATED TRANSFORMERS FOR HARSH LOCATIONS
SECTION ENCAPSULATED TRANSFORMERS FOR HARSH LOCATIONS 600 Volt Class, Encapsulated Single Phase and Three Phase Description and Applications... 8 Copper NEMA R Features... 8 Copper Single Phase Selection
More informationINSTALLATION INSTRUCTIONS FOR
INSTALLATION INSTRUCTIONS FOR MODEL 2240LED www.sportablescoreboards.com 1 Table of Contents 8 X 7 INDOOR SCOREBOARD... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:... 3 INSTRUCTIONS FOR
More informationDLMP-45/45R Installation Instructions
DLMP-45/45R Installation Instructions Tools Needed Posidrive No.3 Screwdriver Large Flat Head Screwdriver 2x 10mm Spanner 1x 13mm Spanner Ø8mm Drill Ø6mm Drill Kit Contents [ ] 1x Tube 2.5M long 17420
More informationInstallation instructions Roxtec RM ES B
Installation instructions Roxtec RM ES B Environmental side Termination/ interior side Pipe Cable screen/armor Layers Termination/ interior side Cable sheath Layers Environmental side Vertical screen Plastic
More information