INTRODUCTION INTRODUCTION

Size: px
Start display at page:

Download "INTRODUCTION INTRODUCTION"

Transcription

1 INTRODUCTION INTRODUCTION This manual describes the 5740X-400/401 Strider Speed Control, and is intended to be a guide in the installation and operation of the control. This first section, the INTRODUCTION, describes the features of the Strider, its applications, and how it operates. Next comes the INSTALLATION section that goes into detail on wiring and programming. Following the INSTALLATION section is the RUN section, which describes what the operator can get out of the Strider, and how he should put things into the Strider. The final sections are TROUBLESHOOT- ING, SPECIFICATIONS, and DIMENSIONS. Optional System Control Logic The Strider's job is to control the speed of a motor by adjusting the voltage speed input to an AC, DC, or servo-type variable speed drive. This is typically done in a closed-loop system by comparing a feedback input to a calculated reference speed and tweaking the Strider's analog output voltage to the drive. The two modes of operation for the Speed Control are the Master Mode and the Follower mode. In the Master mode, the user enters a speed preset ad the control adjusts the analog output to have the motor reach and maintain this speed. Figure 1 illustrates the Master Mode. Ext. Reference Input Feedback Input Speed Control Variable Speed Motor Follower Speed Control for Process or System Variable Speed Drive System can be made up of DC, AC, or Servo type components. Variable Speed Motor Figure 2. Follower Mode Optional System Control Logic Speed Feedback Control Input Variable Speed Motor Figure 1. Master Mode Master Speed Control for Process or System Variable Speed Drive System can be made up of DC, AC, or Servo type components. Variable Speed Motor The Follower mode uses the same "parts" as the Master mode plus an external reference input. This is a speed input from a master motor. The user enters a speed preset as a percentage of follower speed to master speed. Figure 2 illustrates the Follower mode. Strider Features and Terminology Preset - commonly known also as "setpoint". This is the speed value entered by the operator to which the Strider will control the motor. In the master mode, presets are rate values, such as motor RPM, conveyor feet per minute, pump gallons per minute, etc. In the follower mode, presets are ratios of the speeds of the follower motor to the master motor. Presets may be normal or inverse. Most users will employ normal presets, in which there is a direct relationship between the preset and motor speed - the higher the preset, the faster the motor turns. Some applications, such as baking time, will go with the inverse preset approach. In this case, the Strider does its arithmetic "upside-down" and the higher the preset entered, the slower the motor turns. Scaling - units conversion. The Strider calculates how fast the motor should be turning and how fast it really is turning in units of RPM. In many master mode application, and all follower mode applications, the operator must be able to enter presets in other types of units. Also, the operator may want to view the speed of the process in units other than 1

2 INTRODUCTION continued motor RPM. Scaling arithmetically converts motor RPM into preset and speed units that make sense to the operator. Proper scaling values used during initial programming are essential to the predictable and responsive operation of the control. The scaling process is covered in detail in the installation section of this manual. Feedback - the pulsed, frequency signal produced by a sensor driven directly or indirectly by the motor. The Strider compares the feedback speed to the speed it has calculated that the motor should run. If there is a difference, the Strider adjusts its output until the difference is zero. The feedback signal is necessary for closed-loop operation. Ramped Reference - the calculated value in RPM at which the motor should run. This is calculated based on the operator entered preset and also in the follower mode, the speed of the master motor. Error - the difference between ramped reference speed and feedback speed. The Strider uses proportional - integral (PI) error correction to reduce the error to zero. Speed - the speed displayed to the operator is either a scaled conversion of feedback RPM or, optionally in follower mode, the ratio of follower motor to master motor. If presets are selected to be inverse, the speed will also be calculated inversely. Generally, the speed will be displayed in the same units as the preset, letting the operator know that the process is running at the preset speed. External Reference - the pulsed, frequency signal produced by a sensor driven directly or indirectly by the master motor. The follower motor speed, which is calculated by the Strider, depends upon the speed of the master motor and the preset entered by the operator. The external reference signal is used only when the Strider is in the follower mode. Ratio - follower mode presets are determined by taking the ratio of follower speed to master speed. Also, the speed displayed to the operator is usually chosen as the ratio of feedback speed to master speed. Drive Signal - the Strider calculates a ramped reference speed, in RPM, at which the motor should run. The Strider must then calculate the percentage of its analog output voltage required to get the motor to that speed. This number, in percent, is called drive signal. The drive signal is sent to the digital-to-analog converter (DAC) where it is converted into an output voltage in the range of 0-10 VDC. Models There are two models of the Strider, the basic 5740X-400 and the 5740X-401, which does everything the -400 does and: 1. The -401 has two speed presets; the -400 has one. 2. The -401 has reversing capability; it can switch the polarity of its output to an appropriate drive to cause the motor to reverse The 0-10 VDC output of the -401 is adjustable down to 0-3 VDC. 4. The -400 has four control inputs; the -401 has twelve. The additional inputs give the -401 more I/ O flexibility. A detailed I/O comparison is made below. Control Inputs Model 5740X-400 of the Speed Control has four control inputs. Two of these inputs are fixed (START, RAMPED STOP) and two inputs are programmable with six options for each. These options are JOG OPEN LOOP FAST STOP LOCK ALL LOCK PROGRAM DISABLED Model 5740X-401 has 12 control inputs. Eight inputs have fixed functions. START RAMPED STOP JOG OPEN LOOP FAST STOP PRESET ECT INCREMENT PRESET DECREMENT PRESET The other four inputs are programmable with seven options for each one. REVERSE HOLD SPEED UNLATCH ALARM INHIBIT LOW ALARM LOCK PROGRAM LOCK ALL DISABLED All control inputs are activated when they are tied to DC common. This can be done directly with a wire jumper, contact closure, or an NPN sensor. Outputs Both models of the Speed Control have four NPN opencollector transistor outputs. These outputs can each be assigned one of seven functions. ERROR ALARM NO FEEDBACK LOW SPEED ALARM, FOLLOWS HIGH SPEED ALARM, FOLLOWS ZERO SPEED AT SPEED DISABLED

3 INTRODUCTION continued I/O Note: Model 5740X-401 contains the following three functions in addition to the above seven functions: LOW SPEED ALARM, LATCH HIGH SPEED ALARM, LATCH REVERSE I/O Comparison 5740X-400 Feedback Input Encoder Ext. Ref. Input Encoder Start Ramped Stop Input 3 SPEED 10.0 RPM PGM CLR DC Common VIEW ADJ STEP P EXIT ENT +12 VDC Output 1 Output 2 Output 3 Output 4 Input 4 Drive Signal Drive Common Variable Speed Drive L1 L2 5740X-401 Feedback Input Encoder Ext. Ref. Input Encoder Start Ramped Stop Jog DC Common +12 VDC Open Loop Output 1 Fast Stop Inc Preset SPEED 10.0 RPM Output 2 PGM VIEW STEP Output 3 Dec Preset CLR ADJ P Preset Select EXIT ENT Output 4 Input 9 Drive Signal Drive Common Input 10 Input 11 Variable Speed Drive L1 L2 Input 12 3

4 INTRODUCTION continued Theory of Operation / Arithmetic Diagnostic Setup Master Pulse External Reference Scaling REF Setup Follower Setup Jog Setup Or RS Ramp and Limit Control Reference Processing RRS Speed Regulator Control FDBK DS DAC DS 0-10V Motor, Drive, and Load System Speed Out Reference Setup Modes Feedback Scaling Pulse Encoder or Sensor The Speed Control operates every five milliseconds, measuring input speed(s), reading the control inputs, adjusting outputs, and regulating the DAC output to control motor speed. The Strider can be operated in four modes: 1. Master 2. Follower 3. Jog 4. Diagnostic (force) The diagnostic setup is an open loop test mode that will be explained later in this section. The other three setups produce a reference speed (RS) in RPM. The reference speed is calculated by the Strider. Each setup uses a different formula to calculate reference speed; each calculation depends upon programmed parameters and the preset or preset and master motor speed. The abbreviations used in this section are: RS P MAX PST FDBK MAX FDBK REF MAX REF J Reference Speed (RPM) Preset (user units) Maximum Preset (user units) Feedback (RPM) Maximum Feedback (RPM) External Reference Speed (RPM) Maximum External Reference Speed (RPM) Jog Preset (RPM) Reference Speed Calculations (RS) Master Mode RS = RS = P MAX PST MAX PST P Follower Mode RS = REF MAX REF MAX FDBK MAX FDBK P MAX PST for normal presets for inverse presets MAX FDBK for normal presets REF MAX PST RS = MAX FDBK for inverse presets MAX REF P Jog Mode RS = J Ramped Reference Speed (RSS) Once RS is determined, the Strider applies four limitations to this speed. The ramp and limit control block massage RS into ramped reference speed (RSS) by considering: 1. Minimum limit. 2. Maximum limit. 3. Accel time. 4. Decel time. 4

5 INTRODUCTION continued RS Max Min Limit Control LIMIT CONTROL Input RS Maximum Limit Minimum Limit RAMP CONTROL Accel Time INPUTS Starts Ramped Stop Reverse Jog Hold Speed OUTPUTS At Speed Reversed Decel Time RRS The limit control section uses the maximum and minimum limit RPM parameters to modify the reference signal (RS). If RS is less than the minimum limit RPM, the minimum limit value is sent to the ramp control. If RS is greater than the maximum limit RPM, the maximum limit is sent to the ramp control. The minimum limit is not active in the jogging state. Ramp Control The ramp generator produces the ramped reference speed (RRS) by using the acceleration time and deceleration time parameters to alter the reference speed (RS). The acceleration time, deceleration time, and maximum feedback RPM values are used to calculate linear acceleration limits for RS. The ramp generator operates every five milliseconds to produce a smooth ramp from the old RS value to the new one. Drive Signal (DS) The speed regulator control block closes the control loop by comparing the calculated motor speed (RRS) to the actual motor speed (FDBK). The difference, in RPM, between the two speeds is called error. Using PI (proportional/integral) compensation, the Strider increases or decreases its output signal to reduce the error to zero. The amount of increase or decrease to the RRS is called trim. The corrected speed (RRS plus trim) is called drive signal (DS). DS is displayed as a percent, determined by: 0-10V Out RRS + TRIM MAX FDBK = DS 87.5 The DS is transmitted to an isolated digital-to-analog converter (DAC), which puts out 0-10Vdc to the drive. The voltage out (V) is determined by: DS V = (10V) 100 Diagnostic Mode The diagnostic mode allows the user to enter a DS value directly. This is a force mode that is a useful setup tool. The feedback RPM is displayed during the time that the DS is applied to the DAC, but no RRS is calculated, and no error correction is made. Acceleration and Deceleration Times The ramp generator uses these parameters to generate linear (straight-line) acceleration that is applied whenever RS changes (starting, stopping, reversing, changing presets, change in external reference speed, etc.). These parameters are defined as the time to go from zero speed to the maximum feedback RPM or vice versa. Use the following equations to calculate intermediate acceleration times. new RS - old RS time = MFB - 0 accel time old RS - new RS time = MFB - 0 decel time 5

6 INSTALLATION Rear Terminals X-40X Terminal Layout Volt DC: This terminal is a +12 VDC, ±10%, power output, 125 ma maximum. It can be used as a supply for compatible sensors or accessories. DC Common is the negative side of this supply. 2 through 5 - DC Common: These terminals are connected to the negative side of the unit's internal DC power supply. Count inputs are referenced to DC Common. Control inputs are active when connected to DC Common. 6 through 9 - Outputs 1-4 respectively: These four control outputs are NPN open-collector transistors with transient protection. Maximum current capacity is 200 ma at 1.3 VDC. Each output can be programmed for one of ten functions. See Program Outputs in program mode Not used. 11, 12 - AC Power: Connect AC Hot to terminal 12 and Neutral to terminal Control Input 3: For model 5740X-400, this terminal can be assigned one of six functions. For model 5740X-401 this terminal is assigned the jog function Control Input 4: For model 5740X-400 this terminal can be assigned one of six functions. For Model 5740X-401 this terminal is assigned the open loop function DC Common: This terminal is connected to the negative side of the unit's internal DC power supply. Count inputs are referenced to DC Common. Control inputs are active when connected to DC common Feedback Signal: The pulsed output of the feedback sensor is put in at this terminal. The Feedback signal can be supplied by a solid state sensor (encoder, proximity switch, etc.) or a magnetic pickup Ext Ref Signal: The pulsed output of the master motor sensor is put in at this terminal. Model X Model X 115VAC~ 230VAC~ 20 - RS 485 Common: Connect the shield from the communications cable to this terminal Start Input: Activate this input momentarily to put the unit into the motor-running state Ramped Stop: Deactivate this input to cause the unit to leave the motor-running state and slow down to the motorstopped state. This slow-down rate is programmed in the Adjust Setup menu under Decel. This input is normally on RS 485 +: Connect the positive lead of the communications bus to terminal RS 485 -: Connect the negative lead of the communications bus to this terminal. 6

7 INSTALLATION continued 23 - Drive Signal Common: This terminal is the return for the Drive Signal terminal Drive Signal: This signal is connected to the motor drive and acts as a voltage, current, torque, or speed reference. Note: Terminals 25 through 34 are not used on model 5740X-400. They are present, but have no function. Do not use as wiring points Not used Control Input Control Input Control Input Control Input 9: 32 - Increment Preset: Activate this input momentarily to cause the preset value to increase by the 1st Preset Step value. Activate this input for more than 0.5 seconds to cause the preset value to increase by the Repeat Preset Step value every 0.2 seconds. When in the Jogging state, this input affects the jog presets. Note: The preset cannot be increased past the programmed Maximum Preset Value Fast Stop: Deactivate this input momentarily to cause the motor to quickly come to a stop. This input is normally on to allow the unit to be in the motor-running state DC Common: This terminal is connected to the negative side of the unit's internal DC power supply. Count inputs are referenced to DC Common. Control inputs are active when connected to DC Common. Each of these four control inputs can be assigned one of seven functions Preset Select: Use this input to toggle between Preset 1 and Preset 2. When this input is off, Preset 1 will be selected. Activate this input to select Preset 2. When in the jogging state, the jog presets will be affected Decrement Preset: Activate this input momentarily to cause the preset value to decrease by the programmed 1st Preset Step value. Activate this input for more than 0.5 seconds to cause the preset value to decrease by the Repeat Preset Step value every 0.2 seconds. When in the Jogging state, this input affects the jog presets. 7

8 INSTALLATION continued MODULAR COMMUNICATION JACK The RJ-11 modular telephone jack is an alternate method of hooking up a serial communications line. Pin 2 of the jack is negative and is the same as terminal 22. Pin 3 is positive and is the same as terminal 21. Pins 1 and 4 are connected to DC Common and should be used for any shield connections. Note: This jack is intended for connection to Ambassador and other RS-485 communication networks only. It should not be connected to any telephone system as damage or hazard may result. TERMINAL BLOCKS Connections to the control are made through removable, screw terminal blocks to allow for ease of wiring and removal. The terminals can accommodate stranded, solid, or fused wire from 14 to 22 gauge. To remove the terminal block, disconnect power and gently pry underneath each end with a small screwdriver. Press straight on to re-install. GENERAL WIRING PRACTICES 1. Disconnect all power before wiring terminals. A safety hazard exists if this precaution is not observed. Treat all control and count inputs as hazardous since they may carry line voltage. 2 Use shielded cables for frequency signals, control input, drive signal and communications signals. Connect shield to common (terminal 2, 3 or 4) of Speed Control to terminate properly. 3. Keep all signal lines as short as possible. 4. Do NOT bundle or route signal lines with power or machine control wiring. Use separate conduit for power and signal wires. Route Drive Signal separately. 5. Provide "clean" power to the speed control. In severe cases, power may have to be filtered or a separate power source used. Do not use the same power source that is supplying the loads. 6. Use 18 ga. minimum (0.97mm 2, 600V) and 14 ga. maximum (2.1mm 2, 600V) wire for AC power wiring. 7. See page 9, top drawing, for the correct fuse to be used in the power input wiring. DIP SWITCH FUNCTIONS Switch 1: Feedback input sink / source Off: Feedback input requires a current sourcing input signal. On: Feedback input requires a current sinking input signal. Switch 2: External Reference input sink / source Off: External Reference requires a current sourcing input signal. On: External Reference requires a current sinking input signal. Switch 3: Feedback Input threshold level Off: high threshold level use with DC sensors. On: low threshold level use with mag pickups. Turn switch 1 off. Switch 4: External Reference threshold level Off: high threshold level use with DC sensors. On: low threshold level use with mag pickups. Turn switch 2 off. Dip switches may be set through an opening on the bottom of the unit. It is located towards the rear of the control. PANEL MOUNTING The panel mounting kit includes: (1) mounting gasket, (2) mounting clips and (4) screws. Refer to the dimension diagram on page 47 for a drawing of the correct installation of these parts. The mounting gasket is coated on one side with a contact adhesive and a paper backing. Care should be taken during the gasket installation that the gasket be correctly positioned on the panel at the first attempt. Attempting to re-position the gasket once the adhesive has come in contact with the panel is likely to deform or tear the gasket. This may result in an improper seal. For best results, follow these directions: 1. Stand the Speed Control counter on a desk or table with its display down, screw terminals up. 2. Remove and discard the center square of the gasket at the scribe marks in the gasket and paper backing. Do not remove the backing from the remaining outer rim. 3. Slide the gasket down the unit until it is in position at the rear of the unit's front bezel. The paper backing side should be up. 4. Insert the tip of a knife between the paper and the gasket and, while holding the gasket down to the unit with the knife, peel off the paper backing. 5. Slide the unit through the panel cutout until the gasket firmly adheres to the panel. 6. Install the mounting clips and screws as shown in the diagram on page 39. Do not overtighten the mounting screws. The screws should be tight enough to firmly hold the unit in place, but not so tight as to squeeze the gasket out from behind the front bezel. 7. A switch shall be included in the building installation: It shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment. Switches and circuit breakers in Europe must comply with IEC

9 INSTALLATION continued AC Power Input Check part number on controller label to verify correct voltage rating X: 115 VAC X: 230 VAC Ground Neutral Hot AC Power In 115 V, 60 Hz 115 V, 50 Hz 230 V, 60 Hz 230 V, 50 Hz U.S. 1/8 amp 1/4 amp 1/16 amp 1/8 amp Fuse Size Use slow blow fuses for all voltages. European T125 ma, 250 V T250 ma, 250 V T60 ma, 250 V T125 ma, 250 V Control Input Sinking Sensor Only Do not connect terminal 1 if sensor is powered from another source. All DIP switches off Common +12 VDC Signal Control inputs are at terminals on all models. Model 5740X-401 also has control inputs at terminals Wiring DC Loads to Transistor Outputs + Use external diode suppression in parallel with inductive loads. Typically a 1N The control's internal 12 VDC supply can be used to power DC loads. The total current drawn from terminal 1 cannot exceed 125 ma. The load must not draw more than 200 ma. 9

10 INSTALLATION continued Control Input- Contact Pushbutton, limit switch, relay contact, etc Control inputs are at 23 terminals on all models. Model 5740X-401 also has control inputs at terminals Magnetic Pickup Used with Feedback Input or External Reference Input 65 VAC~ RMS maximum into 16K input impedance. Feedback Input DIP switch settings: SW1 off, SW3 on (low threshold). External Reference Input DIP switch settings: SW2 off, SW4 on (low threshold) Dotted line shows alternate connection to External Reference Input DC Common Durant Model Mag Pickup In addition, connect shield to DC Common, separately. AC Generator Used with Feedback Input or External Reference Input 1 65 VAC~ RMS maximum into 16K input impedance. Feedback Input DIP switch settings: SW1 off, SW3 off (high threshold). External Reference Input DIP switch settings: SW2 off, SW4 off (high threshold) Dotted line shows alternate connection to External Reference Input DC Common Dynamatic Model G-2 AC Generator In addition, connect shield to DC Common, separately. 10

11 INSTALLATION continued Encoder or Current Sourcing Sensor Used with Feedback Input or External Reference Input 30K input impedance to DC Common. Do not connect terminal 1 if sensor is powered from another source. Use this method if the encoder has an internal pull-up resistor and supply voltage greater than 5 VDC. Feedback Input DIP switch settings: SW1 off, SW3 off (high threshold). External Reference Input DIP switch settings: SW2 off, SW4 off (high threshold) VDC DC Common Dotted line shows alternate connection to External Reference Input Output Current sourcing sensor (PNP transistor output) In addition, connect shield to DC Common, separately. Encoder or Current Sinking Sensor Used with Feedback Input or External Reference Input 4.7K input impedance to +5 VDC. Do not connect terminal 1 if sensor is powered from another source. Use this method if the encoder or sensor has an open-collector output or the encoder voltage is +5 VDC. Feedback Input DIP switch settings: SW1 on, SW3 off (high threshold). External Reference Input DIP switch settings: SW2 on, SW4 off (high threshold) VDC DC Common Dotted line shows alternate connection to External Reference Input Current sinking sensor (NPN transistor output) Output In addition, connect shield to DC Common, separately. SERIAL COMMUNICATIONS The serial communications capability of the speed control allows a host computer to monitor all unit parameters. All setup parameters can be read and programmed through serial communications. Most of the control input functions are available through serial communications. In addition, the output states and several internal states can be read through the serial port. The speed control serial communications are based on the RS-485 specification and conform to Opto-22 protocol. A separate document describing the serial communications characteristics is available from Eaton Corporation. If you would like a copy of the communications manual, call the Literature Department at 1/

12 INSTALLATION continued Programming This section of the manual presents the programming choices available to the user. Programming gives the Strider the personality to perform a specific application. The Strider is a versatile control, but most users will not use all its features. Those users who are familiar with the Strider's features and terminology may wish to go directly into the program mode. All users are invited to browse the final entry of this section - System Considerations. It provides insight into the programming aspects of scaling, tuning, operator access, etc. Finally, the programming choices for the Strider's serial communication port are given, but the serial format, command list, and programming indices are not. Detailed information is available in a separate manual that can be obtained by calling Cutler-Hammer (Durant) at New users are advised that the somewhat cryptic program menu choices are defined in the section "Description of Program Options" (pp 19-22), following the program menu. All programming is done through the front panel keyboard. Each key has a specific function in the program mode. PGM CLR VIEW ADJ SPEED 20 F/M STEP EXIT ENT EXIT Menu navigation keys. Keys po in the direction that they move y through the program men Program Mode Key Functions PGM CLR Program/Clear - returns control to run mode. While editing numeric data, CLR zeroes the parameter. EXIT Exit - steps one level left, i.e., edit level to sub menu level. VIEW ADJ W View/Adjust - this key has no function in the program mode. ENT Enter - enters program changes at the edit level. STEP P Step/Decimal Point - this key sets the decimal point location during numeric editing. Select - steps one level to the right, i.e., main menu to sub menu. Up Arrow - steps up through options in the program menu. Increments the selected digit during numeric editing. Down Arrow - steps down through options in the program menu. Decrements the selected digit during numeric editing. 12

13 INSTALLATION continued INTRODUCTION TO MENU PROGRAMMING ENTERING THE PROGRAM MODE The programming menus are organized much like an outline. The main menu items are located in the far left column. Each successive subdivision items is located one column further to the right. Press PGM CLR Then ENT To enter Program mode The keystroke sequences to select the programmable options are shown in the programming charts on pages The seven main menus are shown below. OVERVIEW OF PROGRAM MENUS After pressing the PGM/CLR key, the message CAU- TION! PGM MODE will appear on the screen if no lock inputs are activated. Release the PGM/CLR key and press the ENT key within five seconds, otherwise the display will return to the last Run mode screen. Note: If the response to an RSO serial command is in progress and you try to enter the Program mode, the unit will display WAITING FOR RSO. If the motor is still turning, the screen will display STOP UNIT 1st. PROGRAM SETUP PROGRAM FDBK IN PROGRAM FREQ IN PROGRAM INPUTS Select master or follower mode, inverse or normal presets, program max preset, preset units, max speed, and speed units; program minimum and maximum preset values. Program feedback pulses per revolution; program maximum feedback value; program zero speed and no feedback times; select no-feedback action option; select maximum feedback scaling option. Program the reference input pulses per revolution and the maximum reference value. This menu appears only if the unit is in the Follower mode. Select the function to be performed by each of the control inputs. To enter any programmed data, press the ENT key. The display will return from the editing level to the menu level and display the new value or choice. To abort any changes made before the ENT key has been pressed, press the EXIT key. The display will return from the editing level to the menu level and display the original value or choice. PROGRAM OUTPUTS Select the function to be performed by each of the control outputs. PROGRAM DISPLAY PROGRAM SER PORT Select hide or show for the alarms, setup menu, tuning menu, and monitor values. Program the unit ID number, the baud rate, and the transmit delay time; select the serial control option; and display the response to the RDV command. 13

14 INSTALLATION continued For all menus, the default selection is shown. Main Menu Submenu Edit Level PROGRAM SETUP PRESET NORMAL PRESET NORMAL PRESET INVERSE MASTER SP=SPEED MASTER SP=SPEED FOLLOWER SP=SPEED FOLLOWER SP=RATIO MAX PST 2000 MAX PST 2000 Press STEP/ to place decimal point to the right of the blinking digit. Press to scroll through digits. At each digit, press up or down to change digit to desired value. Press ENT to store new value. Range: to Press To Scroll Down P UNITS P_ P UNITS P_ Press to scroll through each position. Press up or down to change to desired character. Press ENT to enter new units. Ranges: First character: Blank or % Second character: Blank or A - Z Third character: P or / (slash) Fourth character: Blank or A-Z MAX SPD 2000 MAX SPD 2000 Press STEP/ to place decimal point to the right of the blinking digit. Press to scroll through digits. At each digit, press up or down to change digit to desired value. Press ENT to store new value. Range: to 9999 SP UNITS P_ SP UNITS P_ Press to scroll through each position. Press up or down to change to desired character. Press ENT to enter new units. Ranges: Same as P Units above. To next page- PROGRAM FDBK IN MIN LMT 0 RPM MAX LMT 2000 RPM MIN LMT 0000 RPM MAX LMT 2000 RPM Press to scroll through digits. At each digit, press up or down to change digit to desired value. Press ENT to store new limit. Range: Min. Limit: 0 to Max. Limit Max. Limit: Min. limit to

15 INSTALLATION continued For all menus, the default selection is shown. Main Menu Submenu Edit Level PROGRAM FDBK IN FDBK IN 60 PPR FDBK IN 0060 PPR Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. Range: 1 to 9999 Press MAX FDBK 2000 RPM MAX FDBK 2000 RPM Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. To Scroll Down 0 SPEED TIME SPEED TIME0.99 Range: to 9999 Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. Range: 0.01 to 0.99 NO FDBK F STOP F STOP NO ACT NO FDBK TIME0.99 NO FDBK TIME0.99 Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. Range: 0.01 to 0.99 MAX FB = 87.5% DS 87.5% 100% The next two items appear only when the Follower mode is selected. PROGRAM FREQ IN REF IN 60 PPR REF IN 0060 PPR Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. Range: 1 to To next page- PROGRAM INPUTS MAX REF 2000 RPM MAX REF 2000 RPM Press to scroll through digits. Press plus or minus to change each digit to desired value. Press ENT to enter value. Range: 1 to

16 INSTALLATION continued For all menus, the default selection is shown. Main Menu Submenu Edit Level The next two menus appear on 5740X-400 only. PROGRAM INPUTS INPUT 3 DISABLED INPUT 4 DISABLED DISABLED JOG LOCK PGM LOCK ALL /F STOP OPN LOOP The next six menus appear on 5740X-401 only. 1st PST STEP 0 1st PST STEP 000 Press key to scroll through each digit. Press up or down to change each digit to desired value. Press ENT to enter value. Range: 0 to 199 Press RPT PST STEP 0 RPT PST STEP 000 Press key to scroll through each digit. Press up or down to change each digit to desired value. Press ENT to enter value. Range 0 to 199 To Scroll Down INPUT 9 DISABLED INPUT 10 DISABLED INPUT 11 DISABLED DISABLED HOLD SPD REVERSE LOCK PGM LOCK ALL UNL ALM INH LOW To next page- PROGRAM OUTPUTS INPUT 12 DISABLED 16

17 INSTALLATION continued For all menus, the default selection is shown. Main Menu Submenu Edit Level PROGRAM OUTPUTS Press OUT1 DISABLED OUT2 DISABLED OUT3 DISABLED OUT4 DISABLED DISABLED O SPEED AT SPEED REVERSED NO FDBK ER ALARM HI ALM FOLL HI ALM LTCH LOW ALM FOLL LOW ALM LTCH NOTE: REVERSED, HI ALM LTCH, LOW ALM LTCH are not available on model 5740X-400. To Scroll Down The following menu appears when an output is programmed as a HI or LOW alarm. FDBK ALM HI/LOW HI/LOW NOM/DIFF NOM/% To next page- PROGRAM DISPLAY 17

18 INSTALLATION continued For all menus, the default selection is shown. Main Menu Submenu Edit Level PROGRAM DISPLAY ALARMS HIDE HIDE SHOW Press SETUP HIDE HIDE SHOW To Scroll Down TUNING HIDE HIDE SHOW MON VAL HIDE HIDE SHOW PROGRAM SER PORT SER PORT ID 0 SER PORT ID 00 Press key to scroll through digits. Press up or down key to change each digit to desired value. Press ENT. Range: 0 to 99 Press To Scroll Down BAUD Tx DELAY S S S SER CTRL DISABLED DISABLED ENABLED ONLY To next page- PROGRAM OPTIONS RDV DATA 5202hh 5202hh for 5740X hh for 5740X-400. hh is the hexadecimal value of the SER PORT ID. 18

19 INSTALLATION continued DESCRIPTION OF PROGRAM OPTIONS PROGRAM SETUP PRESET NORMAL - presets are directly proportional to feedback RPM. Increasing the preset value increases feedback. PRESET INVERSE - presets are inversely proportional to feedback RPM. Increasing the preset value decreases feedback. MASTER SP = SPEED - the motor is controlled to a speed that is dependent only upon the preset entered by the operator. The speed displayed is a scaled rate of feedback motor speed (normal preset) or a scaled time value (inverse preset). FOLLOWER SP = SPEED - the motor is controlled to a speed that is dependent upon the operator-entered preset and the master motor speed. The speed displayed is a scaled rate of follower motor speed (normal preset) or a scaled time value (inverse preset). FOLLOWER SP= RATIO - the motor is controlled to a speed that is dependent upon the operator-entered preset and the master motor speed. The speed displayed is either a ratio of follower motor speed to master motor speed (normal preset) or master motor speed to follower motor speed (inverse preset). MAX PST - the maximum preset is the preset value that causes the motor to run at maximum feedback RPM. This is an important number for proper scaling. To determine this number, see the section on Scaling, P 23. If you choose a value that is less than an existing preset (for normal preset), the value will not be accepted and the display will read VALU<PST for three seconds. If you choose a value that is greater than an existing preset (for inverse preset), the value will not be accepted and the display will read VALU>PST for three seconds. P UNITS - the engineering units that describe the preset can be entered here and displayed on the Maximum Preset screen and on the two preset editing screens in the Adjust Menu. MAX SPD - the maximum speed is the value that is shown on the speed display when the motor is at maximum feedback RPM. This value scales the speed display. SP UNITS - the engineering units that describe the displayed speed (either speed or ratio) can be entered here. MIN LMT - the programmed Minimum Limit value sets the lower limit of the Reference Speed. This lower limit is disregarded at startup until after the Ramped Reference Speed has reached or exceeded the Minimum Limit. The range is from 0 to the MAX LMT value. MAX LMT - the programmed Maximum Limit value sets the upper limit of the Reference Speed. The range is from the MIN LMT to PROGRAM FEEDBACK INPUT (FDBK IN) FDBK IN - enter the pulse per revolution ratio of the feedback sensor. MAX FDBK - the maximum feedback value represents the RPM of the motor at a particular value of the drive signal, either 87.5% or 100%. Max feedback is an important number for proper scaling and is the first scaling value to be determined. See the section on Scaling, P 23. If you choose a value that is less than an existing jog preset, the value will not be accepted and the display will read VALU<PST for three seconds. 0 SPEED TIME - enter the amount of time between Feedback input pulses that must elapse before the speed is considered to be zero. This time-out value will be used whenever the Ramped Reference Speed is zero. A Zero Speed output will turn on when this time has elapsed. NO FDBK F STOP - this causes the Speed Control to enter the Fast Stop mode when no Feedback pulses have been received for the programmed No Feedback Time and the Drive Signal is greater than 25%. NO FDBK NO ACT - no action occurs when no Feedback pulses have been received for the programmed No Feedback Time. NO FDBK TIME - the no feedback time is the amount of time that must elapse between feedback pulses before the control will recognize the no feedback condition. The no feedback condition can cause the control to fast stop, or trigger an output, or both MAX FB = 87.5% DS - this is the normal choice for most drives. The Maximum Feedback RPM value corresponds to 87.5% of the Drive Signal Reference voltage. This choice allows about 14% overhead so that the Speed Control can momentarily force DC drives to increase the motor voltage when the motor response is too slow. MAX FB = 100% DS - this is a special choice for some AC adjustable frequency (AF) drives. The Maximum Feedback RPM value corresponds to the Drive Signal Reference voltage. On an AF drive the maximum input voltage corresponds to the maximum drive frequency, and the AF drive will not provide any extra boost in frequency for a higher Drive Signal voltage. 19

20 INSTALLATION continued PROGRAM FREQUENCY INPUT (FREQ IN) Note: the PROGRAM FREQ IN menus appear only if the Speed Control is in the follower mode. REF IN - enter the pulse per revolution ratio of the master motor (external reference) sensor. MAX REF - the maximum external reference value corresponds to the RPM of the master motor when the follower motor is at maximum feedback RPM and the preset is set to the maximum preset value. Maximum reference is an important number for proper scaling; see Scaling, P 23. PROGRAM INPUTS FOR 5740X-400 Note: For Model 5740X-400 the four control inputs are assigned the following functions: 1 START 2 RAMPED STOP 3 Programmable Function 4 Programmable Function Programmable Functions: DISABLED JOG LOCK PROGRAM LOCK ALL FAST STOP OPEN LOOP PROGRAM INPUTS FOR 5740X-401 NOTE: For Model 5740X-401 the 12 control inputs are assigned to following functions: 1 START 2 RAMPED STOP 3 JOG 4 OPEN LOOP 5 FAST STOP 6 INCREMENT PRESET 7 DECREMENT PRESET 8 PRESET ECT 9 Programmable Function 10 Programmable Function 11 Programmable Function 12 Programmable Function Programmable Functions: DISABLED HOLD SPEED REVERSE LOCK PROGRAM LOCK ALL UNLATCH ALARMS INHIBIT LOW ALARMS Note: The two following menus appear on Model 5740X-401 only. 1st PST STEP - The currently selected preset will change by this programmed amount each time the INCREMENT PRE- SET or DECREMENT PRESET is momentarily activated. The range is 0 to 199. RPT PST STEP - The currently selected preset will repeatedly change by this programmed value every 0.2 seconds whenever the INCREMENT PRESET or DECREMENT PRE- SET input is activated for more than 0.5 seconds. The range is 0 to 199. DISABLED - the input performs no function when activated. JOG - Activate this input to cause the Speed Control to enter the jogging state. The RAMPED STOP and FAST STOP inputs must be on and the START input must be off in order to enter the jogging state. LOCK PROGRAM (PGM) - connect this input to DC Common to inhibit access to the Program mode from the frontpanel keypad and from the serial port. Keyboard and serial diagnostic modes are also inhibited. All Run mode items can be accessed. LOCK ALL - activate this input to eliminate all operator access to both program mode and run mode options. FAST STOP (/F STOP) - deactivate this input to cause the motor to stop immediately. This input must be on to allow the motor to resume running. This input is usually used with a normally closed switch. OPEN (OPN) LOOP - this option is intended for system calibration and diagnostics. When activated, the Speed Control adjusts the Drive Signal output according to the Reference Speed only, and ignores the Feedback signal. HOLD SPEED (SPD) - activate this input to cause the Speed Control to maintain the current Ramped Reference Speed and ignore any attempts to change this speed. When this input is turned off the control will again change the speed according to the preset value and/or External Reference Speed. Deactivating the fast stop input always overrides hold speed. Deactivating ramped stop, even momentarily, will cause a ramped stop after the hold speed input is removed. A momentary ramped stop can be cancelled by a start input. REVERSE - in its normal state (off), this input allows a positive speed command voltage. When activated, the control will supply a negative voltage. If this input is turned on while the unit is in the motor-running mode, the Speed Control will cause the motor to decelerate to zero at the rate programmed in the Deceleration Time, and then accelerate in the opposite direction at the rate programmed in the Acceleration Time. 20

21 INSTALLATION continued Note: Do not use the REVERSE input if your motor drive does not allow motor reversing by a negative voltage. UNLATCH ALARMS (UNL ALM) - turn this input on to unlatch any Feedback Alarm output and the No Feedback output. When this input is turned off, these outputs will be allowed to turn on again the next time the Feedback speed is sampled. INHIBIT LOW ALARMS (INH LOW) - activate this input to hold the Feedback Low Alarm in the off state. Turn the Inhibit Low input off to allow the low alarm to again be operational. PROGRAM OUTPUTS Note: Reversed, High Alarm Latched, and Low Alarm Latched are not available in model Aside from that, each of the four digital control outputs can be assigned any of the following options. The conditions that control the outputs are evaluated every five milliseconds. DISABLED - the output will remain in the off, or unlatched, condition when programmed for this option. ZERO (0) SPEED - this output is on when the Ramped Reference Speed is zero and no Feedback pulses have been received for the programmed Zero Speed time. AT SPEED - this output is on when the control is in the motorrunning state and the Ramped Reference Speed equals the Reference Speed. REVERSED - this output turns on when two conditions are met: The Reverse Input is on The Drive Signal voltage is less than or equal to zero. NO FEEDBACK (FDBK) - this output is on when the Ramped Reference Speed is greater than zero and no Feedback pulses have been received for the programmed No Feedback time. ERROR (ER) ALARM - this output turns on when the error value is outside of the programmed allowable error limits. HIGH ALARM FOLLOWS (HI ALM FOLL) - this output turns on when the Feedback Speed becomes greater than or equal to the programmed High Alarm value. If the Feedback Speed returns below the High Alarm value, this output will turn off. Thus, the output "follows" the alarm condition. HIGH ALARM LATCHED (HI ALM LTCH) - this output turns on when the Feedback Speed becomes greater than or equal to the programmed High Alarm value. This output remains on (latched) even if the Feedback Speed returns below the High Alarm value. The Unlatch Alarms control input will turn this output off. LOW ALARM FOLLOWS (LOW ALM FOLL) - this output turns on when the Feedback Speed becomes less than or equal to the programmed Low Alarm value. If the Feedback Speed returns above the Low Alarm value, this output will turn off. Thus, the output "follows" the alarm condition. LOW ALARM LATCHED (LOW ALM LTCH) - this output turns on when the Feedback Speed becomes less than or equal to the programmed Low Alarm value. This output remains on (latched) even if the Feedback Speed returns above the Low Alarm value. The Unlatch Alarms control input will turn this output off. Note: The following menus appear only when a control output is programmed as a High or Low alarm. FDBK ALM HI/LOW - this option allows you to enter high and low feedback alarm setpoints directly into the Adjust Alarms menu. FDBK ALM NOM/DIFF - this option allows you to program the high and low Feedback Speed alarms by specifying a nominal speed value and a tolerance range of speeds that will not turn on the alarms. The first Feedback alarm value in the Adjust Alarms menu will become the nominal speed value and the second will become the difference offset above and below the nominal speed. The high alarm setpoint will be the nominal RPM value plus the difference RPM. The low alarm setpoint will be the nominal RPM value minus the difference RPM. If the low alarm setpoint is negative, the low alarm is disabled. FDBK ALM NOM/% - this option allows you to program the high and low Feedback Speed alarms by specifying a nominal speed value and a tolerance range of speeds that will not turn on the alarms. The first Feedback alarm value in the Adjust Alarms menu will become the nominal speed value and the second will become the percentage tolerance above and below the nominal speed. The high alarm setpoint will be the nominal RPM value plus the percentage of nominal RPM. The low alarm setpoint will be the nominal RPM value minus the percentage of nominal RPM. PROGRAM DISPLAY ALARMS HIDE/SHOW - Select HIDE to prevent access to the Alarm Adjust menu. Select SHOW to allow access to this menu. Note that the Adjust Alarms screen will show up only if an output has been programmed to one of the alarm types. SETUP HIDE/SHOW - Select HIDE to prevent access to the Adjust Setup menu. Select SHOW to allow access to this menu. 21

22 INSTALLATION continued TUNING HIDE/SHOW - Select HIDE to prevent access to the Adjust Tuning menu. Select SHOW to allow access to this menu. MON VAL HIDE/SHOW - Select HIDE to prevent access to the Monitor Values menus. Select SHOW to allow access to these menus. PROGRAM SERIAL PORT SERIAL (SER) PORT ID - Enter a two-digit serial port identification number form 00 to 99 decimal. All serial communications to this Speed Control must contain this ID number in hexadecimal. BAUD - Enter the desired serial port transmit and receive baud rate. Choices are 19200, 9600, 4800, 2400, 1200 and 300. TRANSMIT (Tx) DELAY - Enter a transmission delay of either 2 milliseconds or 100 milliseconds. The Speed Control waits for the selected time period before responding to any serial commands. This delay is provided to allow the host computer to switch from transmit to receive mode. SERIAL CONTROL (SER CTRL) DISABLED - The serial input of WSI and RSI commands will have no effect. The control inputs are active. SER CTRL ENABLED - The serial input of WSI or RSI commands is allowed. The control inputs are active. SER CTRL ONLY - The serial input of WSI or RSI commands is allowed. The control inputs are not active, except for the FAST STOP, UNLATCH ALARMS, INHIBIT LOW ALARM, LOCK PROGRAM, and LOCK ALL inputs. RDV DATA - This screen displays the model type of the Speed Control and its hexadecimal SERIAL PORT ID, as shown on page 18. This data is the response to the RDV command. SYSTEM CONSIDERATIONS This section of the manual is intended to provide practical information on several key concepts to the installer. Note that this manual starts with an introduction and description of the control, then goes into installation. The installation section begins with wiring, and the minimum wiring requirements (AC power, sensor input(s), start and stop inputs, 0-10V output to the drive) are generally well understood by installers. Next follows the rather lengthy program menu, and even with the definitions following the menu, an installer may wonder where to begin. The following topics are presented informally, with the intention of providing practical installation guidance. 2. Scaling - a step-by-step approach to determining your "Max" values. Proper scaling is essential responsive performance, yet too many people don't understand how to pick these values. Scaling does make sense and there is a method to the apparent "madness". 3. VALU>PST error message - it may appear while programming the Max Preset value when presets are inverse. 4. Setup and tuning - once the control is installed, accel and decel times can be determined, and the tuning process can begin. 5. Operator access - how much information should the operator get from the Strider, and what should be locked out? DIRECT DRIVE SIGNAL CONTROL - TEST MODE For a quick visual reference of what is going to happen as you explore this feature, turn back to the block diagram shown on page 4. Note that the diagnostic setup is directly connected to the DAC block. Also note that when the motor is running, the sensor signal goes into the Strider's feedback scaling block. You are probably now thinking that if the Strider had a screen where you could directly set the drive signal out and read the feedback RPM in, you could: 1. Send out either 87.5% or 100% drive signal and read your Max Feedback RPM. Since Max Feedback is the most critical scaling value to be determined, and since it is the first scaling value to be determined, this would be a very handy feature to the installer. 2. Determine the linearity of the drive and see how smoothly the motor runs over the intended operating range. As luck would have it, the Strider does have this capability. The screen is located in the test mode. Before going into the test mode, there are three choices to make in the program mode. Two of these choices are the first and last screens of the program menu PROGRAM FDBK IN - see page 15. After you have entered the FDBK IN PPR and MAX FDBK = DS, go to PROGRAM DISPLAY and change SETUP HIDE to SETUP SHOW. Next, exit the program mode and go the Adjust Menu screen ADJUST SETUP. Navigation through the view and adjust menus is shown on page 29. ADJUST SETUP ACCEL 10.0S DECEL 10.0S 1. Direct drive signal control - test mode. Test the linearity of the system and its low speed limits. Experimentally determine your Maximum Feedback value. 1st KEY STEP 0 RPT KEY STEP

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap

Figure 1: Standard 906 Sensor and Pulser Disc. Figure 2: Standard 906 Sensor and Pulser Wrap Description: The TR5000 is a Full Logic Control Process ratemeter that can display up to three separate values of rate and compare them to programmable set points. Rates A & B can be programmed by the

More information

INTRODUCTION / DESCRIPTION. Description

INTRODUCTION / DESCRIPTION. Description INTRODUCTION / DESCRIPTION This manual describes the installation of models 5775X-40X and 5775X- 41X. Because of unique features, these counters may be used in a variety of applications. However, they

More information

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL

THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL INTRODUCTION The Gemini 5200 is another unit in a multi-purpose series of industrial control products that are field-programmable to solve multiple

More information

Part No. ENC-LAB01 Users Manual Introduction EncoderLAB

Part No. ENC-LAB01 Users Manual Introduction EncoderLAB PCA Incremental Encoder Laboratory For Testing and Simulating Incremental Encoder signals Part No. ENC-LAB01 Users Manual The Encoder Laboratory combines into the one housing and updates two separate encoder

More information

M Traverse User Manual Revision F

M Traverse User Manual Revision F M Traverse User Manual 0001-0122 Revision F i Technical Assistance If you have comments or questions concerning the operation of the M Traverse, a member of our Technical Support Staff will be happy to

More information

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416

COMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416 COMPANY MX 9000 Process Monitor Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:MXMAN082416 1 Table of Contents Unpacking...3 Quick Guide...3 Connect to Sensor...3

More information

TABLE OF CONTENTS SPECIFICATIONS...1 MOUNTING...3 WIRING...4 THEORY OF OPERATION...6 MILIVOLT INPUT OPTION JUMPER SELECTIONS...7

TABLE OF CONTENTS SPECIFICATIONS...1 MOUNTING...3 WIRING...4 THEORY OF OPERATION...6 MILIVOLT INPUT OPTION JUMPER SELECTIONS...7 TABLE OF CONTENTS SPECIFICATIONS...1 MOUNTING...3 WIRING...4 THEORY OF OPERATION...6 MILIVOLT INPUT OPTION JUMPER SELECTIONS...7 FRONT PANEL OPERATIONS...8 PROGRAMMING FLOW CHART...8 DEFINITIONS OF MENU

More information

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell

UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load

More information

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630)

Vorne Industries. 87/719 Analog Input Module User's Manual Industrial Drive Itasca, IL (630) Telefax (630) Vorne Industries 87/719 Analog Input Module User's Manual 1445 Industrial Drive Itasca, IL 60143-1849 (630) 875-3600 Telefax (630) 875-3609 . 3 Chapter 1 Introduction... 1.1 Accessing Wiring Connections

More information

Electronic Lineshaft With Alignment F7 Drive Software Technical Manual

Electronic Lineshaft With Alignment F7 Drive Software Technical Manual Electronic Lineshaft With Alignment F7 Drive Software Technical Manual Software Number: VSF11005X, Drive Models: CIMR-F7UXXXXXX-064, CIMR-F7UXXXXXX-065 Document Number: TM.F7SW.064, Date: 02/25/2010, Rev:

More information

THE ASTRO LINE SERIES GEMINI 4000 INSTRUCTION MANUAL

THE ASTRO LINE SERIES GEMINI 4000 INSTRUCTION MANUAL THE ASTRO LINE SERIES GEMINI 4000 INSTRUCTION MANUAL INTRODUCTION The Gemini 4100 and 4200 are both units in a multi-purpose series of industrial control units that are field-programmable to solve multiple

More information

For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted.

For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted. For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted. N223 Reliance Electric s MD60 AC Drive is ready to operate out-of-the-box!

More information

Revision 1.2d

Revision 1.2d Specifications subject to change without notice 0 of 16 Universal Encoder Checker Universal Encoder Checker...1 Description...2 Components...2 Encoder Checker and Adapter Connections...2 Warning: High

More information

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual

ORM0022 EHPC210 Universal Controller Operation Manual Revision 1. EHPC210 Universal Controller. Operation Manual ORM0022 EHPC210 Universal Controller Operation Manual Revision 1 EHPC210 Universal Controller Operation Manual Associated Documentation... 4 Electrical Interface... 4 Power Supply... 4 Solenoid Outputs...

More information

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

Panel cutout required: 1.772 x 3.622 (45mm x 92mm) 1.76 (45mm) 2.45 (62mm) 3.20 (81mm) 3.60 (91mm) 0.59 (15mm) Special Features NEMA4X, IP65 Front Bezel Meter with Relays Option RELAY2 RELAY1 24V OUT POWER 4 3 2 1 6 5 2 1 2 1 NO NC COM NO NC COM RTD TC P P RTD 3 4 1 2 5 TC 6 SWITCH Rear View Gasket APM765 Panel Meter Description

More information

THE ASTRO LINE SERIES GEMINI 1000/2000 INSTRUCTION MANUAL

THE ASTRO LINE SERIES GEMINI 1000/2000 INSTRUCTION MANUAL THE ASTRO LINE SERIES GEMINI 1000/2000 INSTRUCTION MANUAL INTRODUCTION The Gemini 1000 and 2000 are both units in a multi-purpose series of industrial control units that are field-programmable to solve

More information

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features

ED3. Digital Encoder Display Page 1 of 13. Description. Mechanical Drawing. Features Description Page 1 of 13 The ED3 is an LCD readout that serves as a position indicator or tachometer. The ED3 can display: Speed or position of a quadrature output incremental encoder Absolute position

More information

FS340 and FS641. High Performance Low Cost Controller for Flying Shears and Saws

FS340 and FS641. High Performance Low Cost Controller for Flying Shears and Saws control motion interface motrona GmbH Zwischen den Wegen 32 78239 Rielasingen - Germany Tel. +49 (0)7731-9332-0 Fax +49 (0)7731-9332-30 info@motrona.com www.motrona.com FS340 and FS641 High Performance

More information

Operating instructions Electronic preset counter Type series 717

Operating instructions Electronic preset counter Type series 717 Operating instructions Electronic preset counter Type series 717 1. Description 5.98.3_gb 6-digit adding/subtracting counter with two presets Very bright 8mm high LED display Counting and preset range

More information

Rotary Knife Controller

Rotary Knife Controller PCM-22 Rotary Knife Controller Information furnished by EMERSON Motion Control is believed to be accurate and reliable. However, no responsibility is assumed by EMERSON Motion Control for its use. EMERSON

More information

Noise Detector ND-1 Operating Manual

Noise Detector ND-1 Operating Manual Noise Detector ND-1 Operating Manual SPECTRADYNAMICS, INC 1849 Cherry St. Unit 2 Louisville, CO 80027 Phone: (303) 665-1852 Fax: (303) 604-6088 Table of Contents ND-1 Description...... 3 Safety and Preparation

More information

PCM-22 Rotary Knife Controller Operators Manual

PCM-22 Rotary Knife Controller Operators Manual PCM-22 Rotary Knife Controller Operators Manual Information furnished by EMERSON EMC is believed to be accurate and reliable. However, no responsibility is assumed by EMERSON EMC for its use. EMERSON EMC

More information

Model 1476-C SuperQuad HR

Model 1476-C SuperQuad HR Model 1476-C SuperQuad HR Installation and Operating Instructions Table of Contents Page Table of Content... 2 System Description... 3 Features... 3 Installation... 4 Internal Setups... 4 Connections...

More information

Motion Control G7 Drive Software Technical Manual

Motion Control G7 Drive Software Technical Manual Software Number: VSG13306X, Drive Models: CIMR-G7UXXXXX-117 Document Number: TM.G7SW.117, Date: 05/16/08, Rev: 08-05 Motion Control G7 Drive Software Technical Manual Contents: 1.0 Overview... 3 2.0 Changes

More information

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B

Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B Quick Start Function Summary Instructions for ASHCROFT GC52 Differential Pressure Transmitter Version 6.03 Rev. B (See Complete I&M Manual for Further Detail) LOOK FOR THIS AGENCY MARK ON OUR PRODUCTS

More information

GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS

GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS 99880 05/14/03 ! SAFETY INSTRUCTIONS The following instructions must be observed. This instrument was designed and is checked in accordance with regulations

More information

CT340 and CT641. High Performance Low Cost Controller for Rotating Cutters and Printing Rolls. Operating Instructions

CT340 and CT641. High Performance Low Cost Controller for Rotating Cutters and Printing Rolls. Operating Instructions CT340 and CT641 High Performance Low Cost Controller for Rotating Cutters and Printing Rolls Precision controller for Rotating Cutters and Printing Rolls Easy parameter setting and immediately ready to

More information

LE-650s Instruction Manual

LE-650s Instruction Manual LE-650s Instruction Manual LE-650s Controller The LE-650s Controller is a user-friendly panel mounted operator interface for Servo Motor Rotary Cutting machines. Everything required to provide correct

More information

BC104 BATCH CONTROLLER

BC104 BATCH CONTROLLER Instruction Manual Anderson Instrument Co. Inc. 156 Auriesville Road Fultonville, NY 12072 1-800-833-0081 www.anderson-negele.com Instrument Model Number Instrument Serial Number ANDERSON INSTRUMENT COMPANY

More information

Standard RS232 RS ma

Standard RS232 RS ma 1 / 5 CONTROL AND VISUALIZATION OF AC CURRENT IN SINGLE PHASE LINES BY EXTERNAL SHUNT Function Operating mode Current control Frequency control DC component control Shunt Timer Resolution Current precision

More information

Single Axis Position Controller

Single Axis Position Controller SERIES P9511 Single Axis Position Controller Compact Construction Simple Go-to operation Integrated Relay Output Integrated Mains Power Supply ELEKTRO-TRADING sp. Z o.o. 44-109 Gliwice, ul. Mechaników

More information

GAUGEMASTER PRODIGY EXPRESS

GAUGEMASTER PRODIGY EXPRESS GAUGEMASTER PRODIGY EXPRESS DCC01 USER MANUAL Version 1.2 2014 1 T A B L E O F C O N T E N T S 1 Getting Started Introduction Specifications and Features Quick Start Connecting to Your Layout Running a

More information

Operating Instructions

Operating Instructions CNTX Contrast sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target

More information

6-DIGIT FREQUENCY METER, TACHOMETER, RATE METER, TIMER, PULSE TOTALIZER, PROCESS METER & TOTALIZER WITH RS-232 PENTA P6000

6-DIGIT FREQUENCY METER, TACHOMETER, RATE METER, TIMER, PULSE TOTALIZER, PROCESS METER & TOTALIZER WITH RS-232 PENTA P6000 6-DIGIT FREQUENCY METER, TACHOMETER, RATE METER, TIMER, PULSE TOTALIZER, PROCESS METER & TOTALIZER WITH RS-232 PENTA P6000 NEWPORT PRODUCT INFO MANUAL (HTML) - (PDF Version) P6000A/P5000 - INPUT OPTIONS

More information

SCALE & WEIGHT DISPLAYS

SCALE & WEIGHT DISPLAYS The MICRO SERIES SCALE & WEIGHT DISPLAYS LARGE DIGIT MODELS Mighty-5S DPM MODELS Micro-S & Mighty-1S Mighty-1S Micro-S ELECTRO-NUMERICS, INC. Introduction The Electro-Numerics family of Digital Panel Meters

More information

02/11/2015

02/11/2015 24 x 48 Totalizers CTR24 non-backlit model Part number 87622062 Display : 8-digit LCD, height 8 mm Powered by a lithium battery Counter inputs : solid state (4-30 VDC) or voltage (10 260 VAC) Reset on

More information

16 Stage Bi-Directional LED Sequencer

16 Stage Bi-Directional LED Sequencer 16 Stage Bi-Directional LED Sequencer The bi-directional sequencer uses a 4 bit binary up/down counter (CD4516) and two "1 of 8 line decoders" (74HC138 or 74HCT138) to generate the popular "Night Rider"

More information

SIGNET 5500 Flow Monitor ENGLISH

SIGNET 5500 Flow Monitor ENGLISH ENGLISH 3.0901 H (6/01) English CAUTION! Remove power to unit before wiring input and connections. Follow instructions carefully to avoid personal injury. Contents 1. Power Connections 2. Compatible Sensor

More information

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display.

1 Output 1 operation. 3 Pressure unit display. 4 Main display Large 4-character LCD display. 5 Sub-display Small 4-character LCD display. ure Sensor DP-100 Series INSTRUCTI MANUAL High-performance Digital Display For use outside Japan MEUML-DP100 V1.1 Thank you for purchasing products from Panasonic Electric Works SUNX Co., Ltd. Please read

More information

Durant. Durant. INSTALLATION AND OPERATION MANUAL Number AMBASSADOR SERIES COUNT CONTROL

Durant. Durant. INSTALLATION AND OPERATION MANUAL Number AMBASSADOR SERIES COUNT CONTROL Durant INSTALLATION AND OPERATION MANUAL Number 57600-90-05 AMBASSADOR SERIES COUNT CONTROL MODELS: 57600-40 (0-5 VDC) 5760-40 (5 VAC) 5760-45 (Red Display) 5760-40 (0 VAC) 57605-45 (4 VAC) Six Digit,

More information

Special Applications Modules

Special Applications Modules (IC697HSC700) datasheet Features 59 1 IC697HSC700 a45425 Single slot module Five selectable counter types 12 single-ended or differential inputs TTL, Non-TTL and Magnetic Pickup input thresholds Four positive

More information

Veeder-Root brand Series C628 Dual Preset Counter (C628-8XXX) Technical Manual

Veeder-Root brand Series C628 Dual Preset Counter (C628-8XXX) Technical Manual Introduction Your Veeder-Root brand C628 Dual Preset Counter is one model in a family of 1/8 DIN units which offers breakthrough display technology as well as easy-to-program single-line parameters. Designed

More information

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual

Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual Self Excited Automatic Voltage Regulator For Generator Compatible with Marathon SE350* Operation Manual s * Use for reference purpose only and not a genuine Marathon product. 1. INTRODUCTION Sensing Input

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process, Strain & Potentiometer Follower Signals Features Selectable ±0.2, ±2, ±20, ±200, ±300 & ±600 Vdc voltage ranges Selectable ±2, ±20, ±200

More information

Understanding VFD. Variable Frequency Drive. nfi. nfi

Understanding VFD. Variable Frequency Drive. nfi. nfi Understanding VFD Variable Frequency Drive Practical Demonstration of VFD Delta- M Series 1.5 KW I/P: 230V 1/3 Phase O/P: 230 3 Phase VFD Status Screen Motor OFF Command Freq. Parameters Direction Amperes

More information

Element 78 MPE-200. by Summit Audio. Guide To Operations. for software version 1.23

Element 78 MPE-200. by Summit Audio. Guide To Operations. for software version 1.23 Element 78 MPE-200 by Summit Audio Guide To Operations for software version 1.23 TABLE OF CONTENTS IMPORTANT SAFETY AND GROUNDING INSTRUCTIONS COVER 1. UNPACKING AND CONNECTING...3 AUDIO CONNECTIONS...4

More information

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing. Product Data Electrical Data SST (Transmitter) SSR (Receiver) Supply voltage 18 30 V dc Max. Voltage ripple 15 % (within supply range) Current consumption 100 ma (RMS) 75 ma Digital - 100 ma Max. outputs

More information

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument

Installation and Setting up Instructions for the 990 Signal Conditioning Instrument Installation and Setting up Instructions for the 990 Signal Conditioning Instrument Contents Page 1.0 Overview... 3 2.0 Installation.. 4 2.1 Electrical connections... 4 2.2 Cable selection... 4 2.3 Electrical

More information

C200H-AD002/DA002 Analog I/O Units Operation Guide

C200H-AD002/DA002 Analog I/O Units Operation Guide C200H-AD002/DA002 Analog I/O Units Operation Guide Revised September 1995 Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes

More information

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach

More information

PCM-24 Press Feed Controller

PCM-24 Press Feed Controller PCM-24 Press Feed Controller Information furnished by EMERSON EMC is believed to be accurate and reliable. However, no responsibility is assumed by EMERSON EMC for its use. EMERSON EMC reserves the right

More information

DX-10 tm Digital Interface User s Guide

DX-10 tm Digital Interface User s Guide DX-10 tm Digital Interface User s Guide GPIO Communications Revision B Copyright Component Engineering, All Rights Reserved Table of Contents Foreword... 2 Introduction... 3 What s in the Box... 3 What

More information

CARLO GAVAZZI Automation Components

CARLO GAVAZZI Automation Components CARLO GAVAZZI Automation Components UDM 35/40 Digital Panel Meter Programming Guide Index Description 2 Programming Fundamentals 3 Access to Programming Mode/Password Protection 4 Programming 5-18 Inputs

More information

THE APOLLO INTELLIGENT METER SERIES MODEL IMI INSTRUCTION MANUAL

THE APOLLO INTELLIGENT METER SERIES MODEL IMI INSTRUCTION MANUAL THE APOLLO INTELLIGENT METER SERIES MODEL IMI INSTRUCTION MANUAL INTRODUCTION The Intelligent Meter for Rate Inputs (IMI) is another unit in our multi-purpose series of industrial control products that

More information

Sentinel I24 Digital Input and Output Configuration

Sentinel I24 Digital Input and Output Configuration Application Bulletin: #155 Date: October 19, 2007 Sentinel I24 Digital Input and Output Configuration The Sentinel I24 can communicate with external hardware using digital inputs and outputs. There are

More information

Process Transmitter RMA 422

Process Transmitter RMA 422 Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog

More information

APPLICATION NOTE # Monitoring DTMF Digits Transmitted by a Phone

APPLICATION NOTE # Monitoring DTMF Digits Transmitted by a Phone APPLICATION NOTE # Product: 930A Communications Test Set 930i Communications Test Set Monitoring DTMF Digits Transmitted by a Phone Introduction This Application Note describes how to configure and connect

More information

Outback STX. User Guide Supplement. Parts List. STX Terminal Overview

Outback STX. User Guide Supplement. Parts List. STX Terminal Overview Outback STX User Guide Supplement This supplement details the following changes from STX v1.0 to STX v1.1: Parts List below STX Terminal Overview below Connection Diagram on page 2 AC110 Power Up and Power

More information

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper

More information

USER GUIDE. DM Engineering Multi Station Relay Adapter (MSRA and MSRA-RM) Version DM Engineering

USER GUIDE. DM Engineering Multi Station Relay Adapter (MSRA and MSRA-RM) Version DM Engineering USER GUIDE DM Engineering Multi Station Relay Adapter (MSRA and MSRA-RM) Version 1.35 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487 www.dmengineering.com Overview:

More information

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global

Contact-Type Digital Displacement Sensor. HG-S Series. User's Manual WUME-HGS panasonic.net/id/pidsx/global Contact-Type Digital Displacement Sensor HG-S Series User's Manual WUME-HGS-4 2017.1 panasonic.net/id/pidsx/global (MEMO) 2 Panasonic Industrial Devices SUNX Co., Ltd. 2017 Thank you for purchasing an

More information

Chapter 23 Dimmer monitoring

Chapter 23 Dimmer monitoring Chapter 23 Dimmer monitoring ETC consoles may be connected to ETC Sensor dimming systems via the ETCLink communication protocol. In this configuration, the console operates a dimmer monitoring system that

More information

DCP100 Digital Control Programmer Specifications

DCP100 Digital Control Programmer Specifications DCP100 Digital Control Programmer Specifications EN01-6028 October 1996 Overview The DCP100 is a microprocessor based 1 /4 DIN programmer/controller for process variable versus time control of temperature,

More information

We put you first. And keep you ahead. USES FEATURES. Bulletin SS09040 Issue/Rev. 0.2 (10/14)

We put you first. And keep you ahead. USES FEATURES. Bulletin SS09040 Issue/Rev. 0.2 (10/14) SPECIFICATIONS / INSTALLATION / OPERATION MEASUREMENT SOLUTIONS MMRT Bulletin SS09040 Issue/Rev. 0.2 (10/14) We put you first. And keep you ahead. Smith Meter TOTALIZER/RATE METER The MMRT is a combination

More information

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1 by USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1 www.aeroforcetech.com Made in the USA! WARNING Vehicle operator should focus primary attention to the road while using the Interceptor. The information

More information

MICROMASTER Encoder Module

MICROMASTER Encoder Module MICROMASTER Encoder Module Operating Instructions Issue 01/02 User Documentation Foreword Issue 01/02 1 Foreword Qualified Personnel For the purpose of this Instruction Manual and product labels, a Qualified

More information

MF-PFT. Programmable differential pressure transmitter for pressure or flow measurement and control. DIL1 Output/Utsignal

MF-PFT. Programmable differential pressure transmitter for pressure or flow measurement and control. DIL1 Output/Utsignal Operating and installation manual Programmable differential pressure transmitter for pressure or flow measurement and control. MF-PFT Instruction : Mi-202gb_060907 NOTE! Read the entire instruction carefully

More information

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA

ORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADDITIONAL INFORMATION INSTRUCTION MANUAL ADVANTAGES Helps

More information

Digital Ratio Controller

Digital Ratio Controller Digital Ratio Controller RSC-406 Control Panel USER S MANUAL RATIO CONTROLLER SPEED RUN PRG ERR RATIO % CH RSC-406 Prelude Thank you for applying our RSC-406 Ratio Controller (abb.406) to you machinery

More information

EZ Encoder : Optical Incremental (P Series)

EZ Encoder : Optical Incremental (P Series) 1. Introduction Our EZ Encoders effectively eliminate multiple encoder part numbers by bringing intelligence and security to the design. A four-digit LED display with two push-buttons enables the user

More information

Model 5250 Five Channel Digital to Analog Video Converter Data Pack

Model 5250 Five Channel Digital to Analog Video Converter Data Pack Model 5250 Five Channel Digital to Analog Video Converter Data Pack E NSEMBLE D E S I G N S Revision 3.1 SW v2.0.1 This data pack provides detailed installation, configuration and operation information

More information

Electronic converter for level transmitters MT03L Instructions manual

Electronic converter for level transmitters MT03L Instructions manual Electronic converter for level transmitters MT03L Instructions manual R-MI-MT03L Rev.: 1 English version PREFACE Thank you for choosing the MT03L converter from MT03 series of Tecfluid S.A. This instruction

More information

OWNERS MANUAL. Revision /01/ Lightronics Inc. 509 Central Drive Virginia Beach, VA Tel

OWNERS MANUAL. Revision /01/ Lightronics Inc. 509 Central Drive Virginia Beach, VA Tel OWNERS MANUAL Revision 1.8 09/01/2002 OWNERS MANUAL Page 2 of 12 AR-1202 UNIT DESCRIPTION The AR-1202 consists of a processor and 12 dimmer channels of 2.4KW each. Each dimmer channel is protected by a

More information

OTM FREQUENCY AGILE 750MHz F.C.C. COMPATIBLE TELEVISION MODULATOR INSTRUCTION MANUAL

OTM FREQUENCY AGILE 750MHz F.C.C. COMPATIBLE TELEVISION MODULATOR INSTRUCTION MANUAL OTM-4000 FREQUENCY AGILE 750MHz F.C.C. COMPATIBLE TELEVISION MODULATOR INSTRUCTION MANUAL Phone: (209) 586-1022 (800) 545-1022 Fax: (209) 586-1026 E-Mail: salessupport@olsontech.com 025-000331 REV B www.olsontech.com

More information

K3NX Process Meter OPERATION MANUAL

K3NX Process Meter OPERATION MANUAL Cat.No. N90 E1 1 K3NX Process Meter OPERATION MANUAL K3NX Process Meter Operation Manual Produced January 1998 Notice: OMRON products are manufactured for use according to proper procedures by a qualified

More information

General Description. Specifications. 2.1 Electrical

General Description. Specifications. 2.1 Electrical Instruction Manual Models EPN020-000 EPR020-000 EPN040-000 EPR040-000 EPN060-000 EPR060-000 EPN075-000 EPR075-000 EPN100-000 EPR100-000 EPN125-000 EPR125-000 EPN150-000 EPR150-000 EPN200-000 EPR200-000

More information

MultiMac SM. Eddy Current Instrument for Encircling Coil, Sector and Rotary Probe Testing of Tube, Bar, & Wire

MultiMac SM. Eddy Current Instrument for Encircling Coil, Sector and Rotary Probe Testing of Tube, Bar, & Wire MultiMac SM Eddy Current Instrument for Encircling Coil, Sector and Rotary Probe Testing of Tube, Bar, & Wire Features of the MultiMac SM Electronics Simultaneous Coil and/or Rotary Probe operation Differential

More information

INSTALLATION & USER GUIDE

INSTALLATION & USER GUIDE INSTALLATION & USER GUIDE Digidim 458 8-Channel Dimmer STEP 1 Assemble Dimmer Unit STEP 2 Mount Dimmer Chassis STEP 3 Electrical Installation STEP 4 Attach Module and Make Connections STEP 5 Replace Cover

More information

Ku-Band Redundant LNB Systems. 1:1 System RF IN (WR75) TEST IN -40 db OFFLINE IN CONTROLLER. 1:2 System POL 1 IN (WR75) TEST IN -40 db POL 2 IN

Ku-Band Redundant LNB Systems. 1:1 System RF IN (WR75) TEST IN -40 db OFFLINE IN CONTROLLER. 1:2 System POL 1 IN (WR75) TEST IN -40 db POL 2 IN BRK-1000 Series Ku-Band Redundant LNB Systems Introduction Redundant LNB systems minimize system downtime due to LNB failure by providing a spare LNB and an automatic means of switching to the spare upon

More information

Overview: Specifications: Installation Instructions:

Overview: Specifications: Installation Instructions: Overview: The SignalGuys.com Start/Stop Work Timer PT724A is an extremely versatile 24 Hour 365 Day Event Timers designed to support a wide range of applications. Such applications include: Start/Stop

More information

American DJ. Show Designer. Software Revision 2.08

American DJ. Show Designer. Software Revision 2.08 American DJ Show Designer Software Revision 2.08 American DJ 4295 Charter Street Los Angeles, CA 90058 USA E-mail: support@ameriandj.com Web: www.americandj.com OVERVIEW Show Designer is a new lighting

More information

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

More information

+GF+ SIGNET 8860 Dual Channel Conductivity/Resistivity Controller

+GF+ SIGNET 8860 Dual Channel Conductivity/Resistivity Controller OUTPUT OPTION RELAY 3,4 OPEN COLL 3,4 TEMP 1 SGNL 1 TEMP 2 SGNL 2 - OPEN COLL 4 Æ L ENGLISH 3-8860.090 A-7/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions

More information

EA350. Generator Automatic Voltage Regulator Operation Manual

EA350. Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350* * Use for reference purpose only and not a genuine

More information

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25

DATA SHEET. Synchronisers, FAS-113DG ANSI code 25 DATA SHEET Synchronisers, ANSI code 25 Synchronisation of generator to busbar Circuit breaker time compensation LED indication of status LED for activated control LED for synchronising signal 35 mm DIN

More information

FRQM-2 Frequency Counter & RF Multimeter

FRQM-2 Frequency Counter & RF Multimeter FRQM-2 Frequency Counter & RF Multimeter Usage Instructions Firmware v2.09 Copyright 2007-2011 by ASPiSYS Ltd. Distributed by: ASPiSYS Ltd. P.O.Box 14386, Athens 11510 (http://www.aspisys.com) Tel. (+30)

More information

WIRING. Connection connector. NPN output type Standard type. Main circuit. High-function type. Main circuit. PNP output type.

WIRING. Connection connector. NPN output type Standard type. Main circuit. High-function type. Main circuit. PNP output type. INSTRUCTI MANUAL Sensor High-performance Digital Display DP-1 Series Thank you very much for using SUNX products. Please read this Instruction Manual carefully and thoroughly for the correct and optimum

More information

TUSKIN Equipment Corporation

TUSKIN Equipment Corporation TUSKIN Equipment Corporation TC-101 Liquid Color Metering System Operation & Maintenance Manual Warning: Read instructions carefully before attempting to install, operate or service the Tuskin Metering

More information

Electronic converter for flowmeters MT03F Instructions manual

Electronic converter for flowmeters MT03F Instructions manual Electronic converter for flowmeters MT03F Instructions manual R-MI-MT03F Rev.: 0 English version PREFACE Thank you for choosing the MT03F converter from MT03 series of Tecfluid S.A. This instruction manual

More information

Transfer Switch. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Amperes. English Original Instructions (Issue 5)

Transfer Switch. OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) Amperes. English Original Instructions (Issue 5) Operator Manual Transfer Switch 40-1000 Amperes OTECA (Spec A) OTECB (Spec A) OTECC (Spec A) OTECD (Spec A) English Original Instructions 10-2015 962-0131 (Issue 5) Table of Contents 1. SAFETY PRECAUTIONS...

More information

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB

PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB September 2013 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412-CB The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter Broadcast Devices, Inc. AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter Technical Reference Manual Broadcast Devices, Inc. Tel. (914) 737-5032 Fax. (914) 736-6916 World Wide Web:

More information

SC26 Magnetic Field Cancelling System

SC26 Magnetic Field Cancelling System SPICER CONSULTING SYSTEM SC26 SC26 Magnetic Field Cancelling System Makes the ambient magnetic field OK for electron beam tools in 300 mm wafer fabs Real time, wideband cancelling from DC to > 9 khz fields

More information

COUNTER - TOTALIZER TACHOMETER - TOTALIZER FREQUENCY METER CHRONOMETER INSTRUCTION MANUAL DM4500F

COUNTER - TOTALIZER TACHOMETER - TOTALIZER FREQUENCY METER CHRONOMETER INSTRUCTION MANUAL DM4500F COUNTER - TOTALIZER TACHOMETER - TOTALIZER FREQUENCY METER CHRONOMETER INSTRUCTION MANUAL DM4500F Status Instruments, Inc. PH 800-700-3272 456 Park Avenue FX 800-700-5468 Scotch Plains, NJ 07076 www.statinst.com

More information

Operating Instructions for Throttle Valves Using VRC Valve Positioner

Operating Instructions for Throttle Valves Using VRC Valve Positioner ThrottleMaster TM Operating Instructions for Throttle Valves Using VRC Valve Positioner p/n: X709116 $10.00 3/2012 Throttlemaster is a registered trademark of Vacuum Research Corporation Introduction The

More information

BE3-GPR GENERATOR PROTECTIVE RELAY

BE3-GPR GENERATOR PROTECTIVE RELAY BE3-GPR GENERATOR PROTECTIVE RELAY Behind-the-Panel Mounting Semi-flush Mounting Basler Electric s BE3-GPR generator protective relay offers multiple protective features in a single package. Its microprocessor-based

More information

N3ZI Digital Dial Manual For kit with Backlit LCD Rev 4.00 Jan 2013 PCB

N3ZI Digital Dial Manual For kit with Backlit LCD Rev 4.00 Jan 2013 PCB N3ZI Digital Dial Manual For kit with Backlit LCD Rev 4.00 Jan 2013 PCB Kit Components Item Qty Designator Part Color/Marking PCB 1 LCD Display 1 LCD 1602 Volt Regulator 1 U1 78L05, Black TO-92 Prescaler

More information

Operating Manual. Automated Gear. Apollo Design Technology, Inc Fourier Drive Fort Wayne, IN USA

Operating Manual. Automated Gear. Apollo Design Technology, Inc Fourier Drive Fort Wayne, IN USA Operating Manual Automated Gear Apollo Design Technology, Inc. 4130 Fourier Drive Fort Wayne, IN 46818 USA PH: +01(260)497-9191 FX: +01(260)497-9192 www.apollodesign.net 11-25-09 5-6 POWERING UP THE RIGHT

More information

DAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER. For the DAAB EP104 automatic control system with software version 4.

DAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER. For the DAAB EP104 automatic control system with software version 4. DAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER For the DAAB EP104 automatic control system with software version 4.07 Revision: 12 FAAC Nordic AB BOX 125, SE-284 22 PERSTORP SWEDEN, +46

More information

Training Note TR-06RD. Schedules. Schedule types

Training Note TR-06RD. Schedules. Schedule types Schedules General operation of the DT80 data loggers centres on scheduling. Schedules determine when various processes are to occur, and can be triggered by the real time clock, by digital or counter events,

More information