EC456 Power System Protection Lab #1 Overcurrent Protection Relay
|
|
- Aubrey Hubbard
- 6 years ago
- Views:
Transcription
1 EC456 Power System Protection Lab #1 Overcurrent Protection Relay Learning Objectives: Understand the building blocks of a numerical protection relay Understand the HMI of the relay. Establish communication between the numerical relay and computer o Setting the relay o Monitoring the relay status Set the relay parameters for the given system Inject balanced rated load to the relay and monitor its measurement online Test IDMT characteristics of the relay and plot the theoretical and actual IDMT characteristics Equipments used 1. SEL351 Overcurrent relay 2. SEL AMS relay low voltage test kit Pre-lab assignment For the section of the power distribution system shown in Figure 1 below, find the current pick-up, time dial for relay Ra. The setting of relay Rb is given below. Use the IEC normal inverse curve given by Equation 1.1 for co-ordination t = TD Equation I f 1 I p I f Where: M= Multiple of pick-up setting I p TD Time dial setting Setting of relay Rb: Pick up setting = 5A; Time dial = 0.3 Figure 1. Pre-lab assignment.
2 Procedure Understanding the relay setting 1. Open AcSELerator software, for communicating with the SEL351 relay (icon on the desktop). 2. Open the setting file Lab #1 (In Settings => Open, select Lab#1) 3. Go through the Group 1\Set 1\ General Settings menu and check the relay general settings: Figure2. General settings The relay has been set previously to the following data: CTR Phase (I A, I, B IC ) CT Ratio, CTR: equivalent to the ratio of (10,000A : 5A) PTR Phase (V A, V B, B VC) PT ratio, PRT : (11,000/110) - equivalent to the ratio of (11,000V : 110V) Change the phase and neutral CT ratio for the relay Rb defined in the Pre-lab. 4. Go through the Group 1\ Set 1\ Phase Time Overcurrent and check if Time Delayed Phase Overcurrent element is enabled (51T). The selection on the top dialog box must be set to 1 ECE 456b Lab #1 /
3 Figure3. Phase Time Overcurrent settings The pick-up setting is set to: 5.00 A The IDMT curve is selected as C1 (IEC normal inverse) 0.14 t = TD sec 0.02 I f 1 I s The time dial setting is set to 1.0 Change the pick-up setting and time dial setting for the relay Rb defined in the Pre-lab. 5. Check the programming of the output contacts in the Group1\Logic 1\Output Contacts section of the setting file. The OUT 101 Output Contact supposed to be set to TRIP. Figure 4. Output contact settings ECE 456b Lab #1 /
4 6. Save setting file and send it to the relay SEL-351. First from File menu select Save and store it in Lab#1_Rb. There are two File menus in Figure 4 - choose the one below. Then select Send from the same File menu and transfer settings file to the device. This procedure takes few minutes. Injecting a balanced load to the relay 1. We will use SEL-AMS relay low voltage test kit to test the relay 2. Start SEL-5401 software (icon on the desktop). 3. Open the front panel control interface of SEL-AMS from Run=>Front Panel Mode Figure 5. Front Panel settings 4. On the Front Panel set the three phase current values (IA, IB, IC) to 1.00A and set the phase angles of A, B and C phases to 0, -120 and 120 degrees respectively. Set the three phase voltages VA, VB and VC to 63.5 and phase angles of A, B and C phases to 0, -120 and 120 degrees respectively. 5. Press the start button on the software window. 6. Reset the SEL-351 relay by pressing the TARGET RESET button on the front panel of the relay. 7. On the front panel of the SEL-351 relay press METER button and read the data from the LCD display. 8. With the software running, switch to the AccSelerator window and select Meter & Control from HMI menu to monitor the relay status on-line. ECE 456b Lab #1 /
5 Figure 6. Meter and Control window. 9. Read the data from HMI window. 10. Observe the three phase currents and voltages measured by the relay and compare with the values injected (Remember that the relay will display the values in primary). 11. Switch to the SEL-5401 software and stop the signal injection from the Front Panel module. Close the Front Panel module alone. Testing the IDMT characteristics 1. You have the loaded IDMT test file, which was created to test the operating time of the relay and plot the IDMT characteristics. Through this test, the relay is being tested for 5 faults. (M=2, 4, 6, 8 and 10) 2. From the SEL5401 software open the pre-created IDMT test file (File => Open, select IDMT.RTA file from the C:\ECE 456\Lab#1 directory). 3. Go through the 12-stage test sequence of the loaded IDMT file and understand what is being done. ECE 456b Lab #1 /
6 Figure 7. Testing sequence settings 4. Download the test file and run the test by going to Run \ Download Test and Run it on the top menu bar. 5. Observe what happens. Wait for the testing to complete. 6. Note down the operating time of the relay from the result displayed after the test is completed. The measurements for each of the test stages are displayed on a Result window (Figure 8). Figure 8. Test results ECE 456b Lab #1 /
7 7. Verify the obtained result with the expected theoretical value. 8. Plot the expected and obtained curves on the graph sheet. 9. Repeat the entire experiment for the relay Ra defined in the Pre-lab. ECE 456b Lab #1 /
BE3-GPR GENERATOR PROTECTIVE RELAY
BE3-GPR GENERATOR PROTECTIVE RELAY Behind-the-Panel Mounting Semi-flush Mounting Basler Electric s BE3-GPR generator protective relay offers multiple protective features in a single package. Its microprocessor-based
More information1 Summary screens are split into two with one screen showing Overcurrent settings and the
Type: P9680 Combined Overcurrent and Earth Fault Relay True R.M.S. measurements Low Set and High Set tripping thresholds for both Overcurrent and Earth Fault detection 6 selectable IDMT (Inverse Definite
More informationSynchronization Check Relay ARGUS 7
Synchronization Check Relay ARGUS 7 Page 1 of 8 Table of Contents Secondary injection tests:... 3 Phase Angle Test:... 3 CS PHASE ANGLE:... 3 SS PHASE ANGLE:... 3 SLIP FREQUENCY TEST:... 4 CS SLIP FREQUENCY:...
More informationGenerator protection relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and
More informationIQ Analyzer 6400/6600 Series. Cutler-Hammer Power Management Products High End Metering Capabilities
IQ Analyzer 6400/6600 Series Cutler-Hammer Power Management Products High End Metering Capabilities New IQ Analyzer Available May 2000 6400/6600 Series 2 Power Quality Monitoring Over 150 metered parameters
More informationKyongbo Electronics Co., Ltd.
Digital 3-phase Overcurrent & Ground Overcurrent Relay Manual TYPE : GDR-AB01 2006. 7. 18 Version 1.00 Kyongbo Electronics Co., Ltd. Safety Precautions This document is for the safety of the user, and
More informationFunctional overview. System configuration FAQ
Vdc 206-13-40 100/110/115/12 110/125V D C MDE IN JPN RSM100 (Relay Setting and Monitoring System) The PC interface software RSM100 allows users to access Toshiba GR-series relays from a local or remote
More informationTransient Stability Events & Actions
ETAP TIP No. 009 Transient Stability Events & Actions Applicable ETAP Versions: 5.5.0, 5.5.5, 5.5.6 (For lower versions, some of the descriptions and procedures below may differ in some ways) Event is
More informationECE 2274 Pre-Lab for Experiment Timer Chip
ECE 2274 Pre-Lab for Experiment 6 555 Timer Chip Introduction to the 555 Timer The 555 IC is a popular chip for acting as multivibrators. Go to the web to obtain a data sheet to be turn-in with the pre-lab.
More informationPQ-Box 100 Quick Start Instructions
PQ-Box 100 Quick Start Instructions These instructions are provided for the purpose on providing a quick start to PQ-Box 100 installation and operation. Please refer to the user handbook for full details.
More informationIntertie Protection M 3520
PROTECTION Intertie Protection M 3520 Integrated Protection System Unit shown with optional HMI and Target modules Integrated Protection System for DR/DG Intertie, Providing: Loss of parallel utility operation
More informationAn Analysis of a Permissive Overreaching Transfer Trip Scheme at a 120kV Substation
An Analysis of a Permissive Overreaching Transfer Trip Scheme at a 120kV Substation Russell Louie and Mehdi Etezadi-Amoli Abstract This paper describes a post fault investigation into an undesired operation
More informationPSC300 Operation Manual
PSC300 Operation Manual Version 9.10 General information Prior to any attempt to operate this Columbia PSC 300, operator should read and understand the complete operation of the cubing system. It is very
More informationINSTRUCTION MANUAL BREAKER FAILURE RELAY GRC100
INSTRUCTION MANUAL BREAKER FAILURE RELAY GRC100 Toshiba Energy Systems & Solutions Corporation 2017 All Rights Reserved. ( Ver. 1.5) Safety Precautions Before using this product, please read this chapter
More informationPanasonic Broadcast. AW-HE100 Menu Information
Panasonic Broadcast AW-HE100 Menu Information Basic menu operations Menus are displayed on the monitor when the unit s settings are to be selected. The monitor is connected to the video signal output connector
More informationORDERING Page 6 BASLER RELAY STANDARDS, DIMENSIONS, ACCESSORIES Request bulletin SDA
BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADDITIONAL INFORMATION INSTRUCTION MANUAL ADVANTAGES Helps
More informationSC24 Magnetic Field Cancelling System
SPICER CONSULTING SYSTEM SC24 SC24 Magnetic Field Cancelling System Makes the ambient magnetic field OK for the electron microscope Adapts to field changes within 100 µs Touch screen intelligent user interface
More informationREF620_NAFCCAC3FFxxxAx1xx SINGLE LINE DIAGRAM (TYPICAL) 1MAC DR. Bus 1 (Open Delta) (2)
SHEET 1 OF 10 Bus 1 (Open Delta) REF620_NFCCC3FFxxxx1xx Y or (1) REF620 V2.0 NSI Functional pplication C(C) 50BF-1_TRBU BREKER FIL (3I, CT) REF620 V2.0 NSI Functional pplication C(C) (3U, VT) 2 or 3 SO1
More informationCURRENT INJECTION RELAY TESTER CR-100. ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M / 05A ) (c) CIRCUTOR S.A.
CURRENT INJECTION RELAY TESTER CR-100 ( Code P60212 (770081) ) INSTRUCTIONS MANUAL ( M 981 329 / 05A ) (c) CIRCUTOR S.A. ---- CURRENT- TIME TRIP TESTER CR-100 --------------- Page. 2 CURRENT INJECTION
More informationCAMTO LTD. Arc detecting system DC/AC
CAMTO LTD Arc detecting system DC/AC Arc detecting system DC/AC The system is based on experience with arc protection since 1962. The system units are built into boxes that all fit on a 35 mm DIN-rail.
More informationPRINCIPLES AND APPLICATIONS
GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,
More informationSC24 Magnetic Field Cancelling System
SPICER CONSULTING SYSTEM SC24 SC24 Magnetic Field Cancelling System Makes the ambient magnetic field OK for the electron microscope Adapts to field changes within 100 µs Touch screen intelligent user interface
More informationLAB 1: Plotting a GM Plateau and Introduction to Statistical Distribution. A. Plotting a GM Plateau. This lab will have two sections, A and B.
LAB 1: Plotting a GM Plateau and Introduction to Statistical Distribution This lab will have two sections, A and B. Students are supposed to write separate lab reports on section A and B, and submit the
More informationLMH0340/LMH0341 SerDes EVK User Guide
LMH0340/LMH0341 SerDes EVK User Guide July 1, 2008 Version 1.05 1 1... Overview 3 2... Evaluation Kit (SD3GXLEVK) Contents 3 3... Hardware Setup 4 3.1 ALP100 BOARD (MAIN BOARD) DESCRIPTION 5 3.2 SD340EVK
More informationPOWER MONITORS ENERIUM RANGE. Minimize your energy consumption and optimize your installation
POWER MONITORS ENERIUM RANGE Minimize your energy consumption and optimize your installation From 0.2s critical electricity metering to the collection of metering data on all utilities Electrical feeder
More informationSoftware Manual Control Panel for Professional Single Booster Units Models: MM3 BW3
Software Manual Control Panel for Professional Single Booster Units Models: MM3 BW3 EN Software Manual.. 1-14 1 1. DESCRIPTION 3 2. DISPLAY LAYOUT 4 3. MODES 5 3.1 Power On 5 3.2 Standby 5 3.3 Power off
More informationCommunication-Assisted Transfer Trip Schemes
Session 17; Page 1/4 Communication-Assisted Transfer Trip Schemes The MathCAD sheet below implements some basic relay calculations. The file takes data read from a Comtrade file and postprocesses it. The
More informationmulti-function meters
multi-function meters eclipse 2 eclipse 7 installation and operating manual 1 GENERAL DESCRIPTION 2 INSTALLATION 3 WIRING INFORMATION 4 2 ECLIPSE 2 METERS 2.1 PROGRAMMING THE METER 5 2.2 INFORMATION 6
More informationGrid Interactive Advanced Features Self-Supply Mode
Grid Interactive Advanced Features Self-Supply Mode CHILICON POWER MICROINVERTERS AND CP-100 CORTEX GATEWAY SYSTEM OVERVIEW Chilicon Power Advanced Inverter functions Power Factor Control: -0.8 to +0.8
More informationPHY221 Lab 1 Discovering Motion: Introduction to Logger Pro and the Motion Detector; Motion with Constant Velocity
PHY221 Lab 1 Discovering Motion: Introduction to Logger Pro and the Motion Detector; Motion with Constant Velocity Print Your Name Print Your Partners' Names Instructions August 31, 2016 Before lab, read
More informationECE438 - Laboratory 4: Sampling and Reconstruction of Continuous-Time Signals
Purdue University: ECE438 - Digital Signal Processing with Applications 1 ECE438 - Laboratory 4: Sampling and Reconstruction of Continuous-Time Signals October 6, 2010 1 Introduction It is often desired
More informationORDERING Page 6 STANDARDS, DIMENSIONS and ACCESSORIES Request bulletin SDA
BE1-59NC CAPACITOR NEUTRAL OVERVOLTAGE RELAY The BE1-59NC Capacitor Neutral Overvoltage Relay provides sensitive protection for capacitor banks. ADVANTAGES Helps avoid cascading capacitor failures. Sensing
More informationUser Guide Stand-Alone Metering for OptiPlant
User Guide Stand-Alone Metering for OptiPlant BAS-SVU030A-GB Table of Contents Introduction...4 General Features...5 User Interface...6 Top display area... 6 Bottom display area... 6 Main display area...
More informationCDHD Servo Drive. Technical Training Manual. Manual Revision: 2.0 Firmware Version: 1.3.x Software Version: 1.3.x.x
CDHD Servo Drive Technical Training Manual Manual Revision: 2.0 Firmware Version: 1.3.x Software Version: 1.3.x.x CDHD Introduction Revision History Document Revision Date Remarks 1.0 June 2012 Initial
More informationToronto Hydro - Electric System
Toronto Hydro - Electric System FIT Commissioning Requirements and Reports Comments and inquiries can be e-mailed to: FIT@torontohydro.com Customers without e-mail access can submit through regular mail
More informationSC26 Magnetic Field Cancelling System
SPICER CONSULTING SYSTEM SC26 SC26 Magnetic Field Cancelling System Makes the ambient magnetic field OK for electron beam tools in 300 mm wafer fabs Real time, wideband cancelling from DC to > 9 khz fields
More informationTelephony Training Systems
Telephony Training Systems LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 07/2018 Table of Contents General Description 2 Topic Coverage 6 Features & Benefits 6 List of Available Training Systems
More informationME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition
ME EN 363 ELEMENTARY INSTRUMENTATION Lab: Basic Lab Instruments and Data Acquisition INTRODUCTION Many sensors produce continuous voltage signals. In this lab, you will learn about some common methods
More informationControllers, series CON Indicators, series IND. Controllers and indicators
JJ Controllers, series CN JJ Indicators, series IND Controllers and indicators DS_Controllers_and_indicators 06/2016 161 Effective implementation of visualisation and control tasks Electronic indicating
More informationE X P E R I M E N T 1
E X P E R I M E N T 1 Getting to Know Data Studio Produced by the Physics Staff at Collin College Copyright Collin College Physics Department. All Rights Reserved. University Physics, Exp 1: Getting to
More informationCHA EVAPORATOR Short Reference User guidelines
CHA EVAPORATOR Short Reference User guidelines by Carlos Manzanedo. Last revised: 10/05/2000 p.1 Procedure: The CHA evaporator is divided into 16 different panels. These panels are labeled on the machine
More informationThe DataView PowerPad III Control Panel
Setting Up a Recording Session in the DataView PowerPad III Control Panel By Mike Van Dunk The DataView PowerPad III Control Panel is designed for working with AEMC PowerPad III Power Quality Analyzers,
More informationOWL micro+ WIRELESS ELECTRICITY MONITOR
COS T NOW TARIFF 3A SENDER 30 25 20 15 10 5 0 SETTING UP YOUR OWL Index of pages 2. Setting up date and time 3. Tariff setting 4. To set up a single tariff 5. To set up a two tiered time tariff 6. To set
More informationDMX and 4000 air circuit breakers from 800 to 4000 A
DMX 3 20 and 00 air circuit breakers from 800 to 00 NEW 286 56 + 288 02 (p. 4) 286 4 + 288 02 (p. 4) 28 56 + 288 02 (p. 4) Dimensions (p. to 53) Electrical characteristics (p. 54 to 5) ir circuit breakers
More informationAMIQ-K2 Program for Transferring Various-Format I/Q Data to AMIQ. Products: AMIQ, SMIQ
Products: AMIQ, SMIQ AMIQ-K2 Program for Transferring Various-Format I/Q Data to AMIQ The software AMIQ-K2 enables you to read, convert, and transfer various-format I/Q data files to AMIQ format. AMIQ-K2
More informationActivity P27: Speed of Sound in Air (Sound Sensor)
Activity P27: Speed of Sound in Air (Sound Sensor) Concept DataStudio ScienceWorkshop (Mac) ScienceWorkshop (Win) Speed of sound P27 Speed of Sound 1.DS (See end of activity) (See end of activity) Equipment
More informationMSP 200PRO Quick Start
MSP 200PRO Quick Start Touch Screen control Output a range of signal types Set and select from a range of common output formats Audio output test included Genlock Y&HS outputs Input live signals for preview
More informationOperating Manual RISH OPTIMA VAF
Operating Manual RISH OPTIMA VAF 2-60-006-00-00511_Rev. A - 5/2014 Section DIGITAL MULTIFUNCTION INSTRUMENT Programmable Multi-function Digital Panel Meter Installation & Operating Instructions Contents
More informationMCR3 POWER EQUIPMENT. Microprocessor Controlled Constant Current Regulator. Compliance with Standards. Uses. Features
Microprocessor Controlled Constant Current Regulator Compliance with Standards FAA: ICAO: IEC: 61822 CENELEC: AC 150/5345-10 (current edition), L-828, L-829. Aerodrome Design Manual Part 5, para. 3.2 (current
More informationDAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER. For the DAAB EP104 automatic control system with software version 4.
DAAB DB409 INSTRUCTION MANUAL FOR THE VFD-EL FREQUENCY CONVERTER For the DAAB EP104 automatic control system with software version 4.07 Revision: 12 FAAC Nordic AB BOX 125, SE-284 22 PERSTORP SWEDEN, +46
More informationExperiment: Real Forces acting on a Falling Body
Phy 201: Fundamentals of Physics I Lab 1 Experiment: Real Forces acting on a Falling Body Objectives: o Observe and record the motion of a falling body o Use video analysis to analyze the motion of a falling
More informationD-901 PC SOFTWARE Version 3
INSTRUCTION MANUAL D-901 PC SOFTWARE Version 3 Please follow the instructions in this manual to obtain the optimum results from this unit. We also recommend that you keep this manual handy for future reference.
More informationAgilent MOI for HDMI 1.4b Cable Assembly Test Revision Jul 2012
Revision 1.11 19-Jul 2012 Agilent Method of Implementation (MOI) for HDMI 1.4b Cable Assembly Test Using Agilent E5071C ENA Network Analyzer Option TDR 1 Table of Contents 1. Modification Record... 4 2.
More informationVSP 516S Quick Start
VIEWSIZE THE WORLD VSP 516S Quick Start Max 2048 1152@60Hz/2560 816 60Hz input/output resolution User customize output resolution 3G/HD/SD-SDI input Multiple cascade mapping for super resolution Seamless
More informationAurora Grid-Tie Installation Instructions (Model Number: PVI-3.0-OUTD-US-W) Revision 4.1
Aurora Grid-Tie Installation Instructions (Model Number: PVI-3.0-OUTD-US-W) Revision 4.1 Contents 1) Grid-Tie Installation Block Diagram... 3 2) Installation Steps.... 4 2.1) Initial Setup.... 4 2.1.1)
More informationMICROPROCESSOR-BASED METERING EQUIPMENT SECTION SECTION 16901
MICROPROCESSOR-BASED METERING EQUIPMENT PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B. C. The listing of specific manufacturers above does not imply acceptance of their products that do not meet
More informationTL-2900 AMMONIA & NITRATE ANALYZER DUAL CHANNEL
TL-2900 AMMONIA & NITRATE ANALYZER DUAL CHANNEL DATA ACQUISITION SYSTEM V.15.4 INSTRUCTION MANUAL Timberline Instruments, LLC 1880 S. Flatiron Ct., Unit I Boulder, Colorado 80301 Ph: (303) 440-8779 Fx:
More informationVSP 198CVS Quick Start
VIEWSIZE THE WORLD VSP 198CVS Quick Start Max 2048 1152@60Hz/2560 1152 50Hz input/output resolution User customize output resolution 3G/HD/SD-SDI input Multiple cascade mapping for super resolution DVI
More informationNERC Reliability Standard PRC-024 Generator Frequency and Voltage Protective Relay Settings
NERC Reliability Standard PRC-024 024-1 Generator Frequency and Voltage Protective Relay Settings Rick Terrill Luminant Power Generation Compliance NERC Standards Drafting Team Member Reliability Standard
More informationRYKO Italia s.r.l. V. Casale Morano Po (Al) t f
Italia RYKO Italia s.r.l. V. Casale 43-15025 Morano Po (Al) t.0142 494411 f. 85872 June 30, 2003 ITALIA SERVICE BULLETIN - # 4-013 VFD parameter settings for conveyor equipment with Mitsubishi PLC MACHINES
More informationForm C: Type Test Verification Report
Form C: Type Test Verification Report Type Approval and Manufacturer declaration of compliance with the requirements of G98. This form should be used when making a Type Test submission to the Energy Networks
More informationForm C: Type Test Verification Report
Form C: Type Test Verification Report Type Approval and Manufacturer declaration of compliance with the requirements of G98. This form should be used when making a Type Test submission to the Energy Networks
More informationA summary of all menu lines available in self-diagnostic mode is shown below.
1057-03 rev A 10/08/02 Page 9/33 4. CLUSTER DIAGNOSTICS 4.1. Test at Turn On When ignition voltage is first applied to the cluster, all the tell-tales, except turn signals, turn on for 2 seconds, then,
More informationFor applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted.
For applications from 0.25 to 5 HP, the MD60 is a simple AC Microdrive that can be panel mounted as well as wall or machine mounted. N223 Reliance Electric s MD60 AC Drive is ready to operate out-of-the-box!
More informationTelephony Training Systems
Telephony Training Systems LabVolt Series Datasheet Festo Didactic en 240 V - 50 Hz 04/2018 Table of Contents General Description 2 Topic Coverage 6 Features & Benefits 6 List of Available Training Systems
More informationMarshall. M-CT5 Camera-Top Monitor Owner s Manual M-CT5. Camera-Top Monitor. Owner s Manual
M-CT5 Camera-Top Monitor Owner s Manual Dear users: Thank you for purchasing Marshall s M-CT5-CE6 HD DSLR LCD Monitor. This 5 Pro HD LCD Monitor is designed to be used as an external video display, allowing
More informationDimensions. Model Number. Electrical connection. Features. Pinout Product information. Indicators/operating means. LGS25 Serie.
Q Dimensions Transmitter Detection field + 9. Detection field 7.8 n Beam. Beam Receiver III 0. 0 Fix H H H Fn Model Number Light grid with fixed cable with -pin, M x connector, and fixed cable with 8-pin,
More informationCyAn User Manual. Flow & Mass Cytometry Center Biomedical Core facility. Technion Faculty of Medicine
CyAn User Manual Flow & Mass Cytometry Center Biomedical Core facility For assistant please call: Technion Faculty of Medicine Amir Grau 054-210-0778 Yaakov Sakoury 050-749-8586 Ofer Shenker 052-456-8846
More informationWe ve got the best technology to fit your power monitoring needs. Scenario works on all!
Version 1.21 Beta Release Reliable Power Meters 400 Blossom Hill Road Los Gatos, CA 95032 408-358-5100 Fax 408-358-4420 www.reliablemeters.com Scenario-Compatible RPM s Scenario software lets you build
More informationITS-I. Test station for evaluation of image quality of image intensifier tubes. Fig. 1. Photo of the ITS-I test station: a)photo, b)block diagram
OS-1 stage Monitor S-I support VM-I microscope M-I microscope Control center Target projector OS-2 stage DC-I camera Tube holder P-I platform IM meter Target slider a) b) BASIC INFORMATION: LVS voltage
More informationGS122-2L. About the speakers:
Dan Leighton DL Consulting Andrea Bell GS122-2L A growing number of utilities are adapting Autodesk Utility Design (AUD) as their primary design tool for electrical utilities. You will learn the basics
More informationMonitorKey Operation Manual: content/uploads/ MonitorKey Operation Manual.pdf
Additional Resources: MonitorKey Operation Manual: www.editraffic.com/wp content/uploads/888 1212 001 MonitorKey Operation Manual.pdf CMUip 2212 Operation Manual: www.editraffic.com/wp content/uploads/888
More informationINSTRUCTION MANUAL AUTORECLOSING RELAY GRR100 - B
INSTRUCTION MANUAL AUTORECLOSING RELAY GRR1 - B Toshiba Energy Systems Solutions Corporation 217 All Rights Reserved. ( Ver. 1.1) Safety Precautions Before using this product, please read this chapter
More informationPHASE HL SEL 1 HL SEL 2 EXT MONITOR ELAN ELAN ELAN ELAN MLM-201 HLM-201 HLM-201 TBM-201 MLM-201 GAIN GAIN GAIN LEFT GAIN RIGHT SELECT SELECT SELECT
Audio Promotional Information "Kestrel-12" and "Kestrel-16" Modular Dual Channel Stereo "On-Air" Mixer "Kestrel-12" "KESTREL-12" HL SEL 1 HL SEL 2 EXT MITOR VU O'LOAD PHASE VU VU AUDIO AIR DELAY DUMP TLM-201
More informationB2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006
B2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006 The B 2 Spice A/D software allows for the simulation of digital, analog, and hybrid circuits. CPE 169, however, is only concerned with the
More informationOperating Instructions
Operating Instructions HAEFELY TEST AG KIT Measurement Software Version 1.0 KIT / En Date Version Responsable Changes / Reasons February 2015 1.0 Initial version WARNING Introduction i Before operating
More informationSafety Light Curtain Orion1 Extended
Safety Light Curtain is an easy to use light curtain with compact dimensions. It has two resolutions for detection of fingers and hands, and comes with advanced features like cascading, muting and blanking.
More informationRT-DRIVE DLM808 DIGITAL PROCESSOR AUDIO MATRIX PROCESSOR
RT-DRIVE DLM808 DIGITAL PROCESSOR AUDIO MATRIX PROCESSOR 2 1. Introduction 2. Features 3. Usefull Data 4. Function Buttons and LED Indicators 5. Rear Panel 6. DSP Control 1. Configuration of IP Address
More informationINSTRUCTION MANUAL POWER QUALITY ANALYZER
INSTRUCTION MANUAL 3196 POWER QUALITY ANALYZER Contents i Contents Introduction...1 Symbols...1 Outlook of Operating Procedures...2 Chapter 1 Overview 3 1.1 Product Overview...3 1.2 Features...4 Chapter
More informationUser Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT
Universal Control Unit UC-1-E User Manual General Information Universal Control Unit UC-1 Of Central Lubrication CC DC 24 V 5A / M 15 SL /MK 31 M Z 30 General Information Contents Universal Control Unit
More informationCalibrating and Profiling Your Monitor
Calibrating and Profiling Your Monitor For this module, you will need: Eye-One measurement device Counterweight (used for LCD screens only) New, modern displays are better First, you need to use a good
More informationHS-509 VIBRATION TRIP MODULE
HS-509 VIBRATION TRIP MODULE 1. Overview The HS-509 is a configurable trip amplifier capable of accepting a 4-20mA signal from a HS-420 sensor and providing two trip action relay outputs along with an
More informationEDL8 Race Dash Manual Engine Management Systems
Engine Management Systems EDL8 Race Dash Manual Engine Management Systems Page 1 EDL8 Race Dash Page 2 EMS Computers Pty Ltd Unit 9 / 171 Power St Glendenning NSW, 2761 Australia Phone.: +612 9675 1414
More informationUNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load Cell
99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com UNIVERSAL DIGITAL METER DC Volts and Amps AC RMS Volts and Amps Thermocouples and RTDs Process Signals Strain Gauge and Load
More informationProcurement of IC TESTER & TRAINER KITS, OSCILLOSCOPES, FG S, DECADE BOXES AND ANALOG METERS
र य गक स थ न प द र न ह नगर, क र ल 609 605 NATIONAL INSTITUTE OF TECHNOLOGY PUDUCHERRY Nehru Nagar, Karaikal 609 605 NIQ No.: NITPY / 015-16/ECE/ DE & CE LAB / Q00 Date: 05-0-016 NOTICE INVITING QUOTATION
More informationCOMPANY. MX 9000 Process Monitor. Installation, Operating & Maintenance Manual AW-Lake Company. All rights reserved. Doc ID:MXMAN082416
COMPANY MX 9000 Process Monitor Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:MXMAN082416 1 Table of Contents Unpacking...3 Quick Guide...3 Connect to Sensor...3
More informationSession 1 Introduction to Data Acquisition and Real-Time Control
EE-371 CONTROL SYSTEMS LABORATORY Session 1 Introduction to Data Acquisition and Real-Time Control Purpose The objectives of this session are To gain familiarity with the MultiQ3 board and WinCon software.
More informationAutomatic Transfer Switch Control PLC Operator s Manual
MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch Control PLC Operator s Manual Dedicated Single Phase Transfer Switch ATS-22AG Automatic Transfer Switch INTRODUCTION 1.1 Preliminary
More informationUSER MANUAL. Compact dimensions 6 DIN modules, with 4 LED s display with 7 segments, for an excellent reading of the measurements
DUCATI SISTEMI S. P. A. DUCA47 USER MANUAL Introduction The instrument DUCA47 is a digital multimeter that allows the measurement of the principal electrical parameters in threephase 230/400Vac networks
More informationP XGA TFT Monitor. User s Manual
P6151 15 XGA TFT Monitor User s Manual Disclaimers This manual has been carefully checked and believed to contain accurate information. Axiomtek Co., Ltd. assumes no responsibility for any infringements
More informationInstallation and User Guide 458/CTR8 8-Channel Ballast Controller Module
Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach
More informationVIDEO ALARM VERIFICATION UNIT VIVER
VIDEO ALARM VERIFICATION UNIT VIVER viver_en 09/08 The VIVER module provides remote video alarm verification, based on image sequences transmitted from cameras installed in the protected facility. The
More informationDual Power and Control. Backup System. Armor. SUT43X Series. Ideal Solution For Control Room
Dual Power and Control Backup System Armor SUT43X Series Ideal Solution For Control Room 1.2 1.5 1.6 1.9 2.0 2.5 3.1 mm Pixel Pitches Seamless Optimized Cooling Good Flstness Slow Temp. Rise Long Lifetime
More informationYellow Frog. Manual Version 1.1
Yellow Frog Manual Version 1.1 1 YellowFrog Contents PC Requirements...... 2 YellowFrog Power Meter Measurement.... 3 YellowFrog PC Software..... 3 Main Screen....... 4 Input Overload....... 5 Battery
More informationSEL-251 SEL SEL DISTRIBUTION RELAY
SEL-251 SEL-251-2 SEL-251-3 DISTRIBUTION RELAY PHASE OVERCURRENT RELAY WITH VOLTAGE CONTROL NEGATIVE-SEQUENCE OVERCURRENT RELAY GROUND OVERCURRENT RELAY MULTIPLE SHOT RECLOSING RELAY SELECTABLE SETTING
More informationDUCATI SISTEMI S. P. A. DUCA47-96 USER MANUAL
DUCATI SISTEMI S. P. A. DUCA47-96 USER MANUAL Introduction The instrument DUCA47-96 is a digital multimeter for panel mounting that allows the measurement of the principal electrical parameters in three-phase
More informationECE 372 Microcontroller Design
E.g. Port A, Port B Used to interface with many devices Switches LEDs LCD Keypads Relays Stepper Motors Interface with digital IO requires us to connect the devices correctly and write code to interface
More informationVAD Mobile Wireless. OBD-II User's Manual Version 1.0
VAD Mobile Wireless OBD-II User's Manual Version 1.0 Table of Contents What Is VAD Mobile Wireless?... 1 What is the OBD-II Module?... 1 Where to Get a VAD Mobile Wireless System... 1 Installing the OBD-II
More informationTutorial 3 Normalize step-cycles, average waveform amplitude and the Layout program
Tutorial 3 Normalize step-cycles, average waveform amplitude and the Layout program Step cycles are defined usually by choosing a recorded ENG waveform that shows long lasting, continuos, consistently
More informationSlimLine. Compliant to DO-160D Document # Rev H. www. rosenaviation.com. www. rosenaviation.com
10.4 Model DISPLAY SlimLine Number 1042 www. rosenaviation.com OEM SALES 8 Shackleford Plaza, Suite 201 Little Rock, AR 72211 1-888-523-7523 Fax (501) 225-1015 Document # 9200-0102-835 Rev H CORPORATE
More information