Dynamic Cable Rating Model Guidelines
|
|
- Clementine Freeman
- 5 years ago
- Views:
Transcription
1 lines Introduction This document describes how to set up, configure and run the Dynamic Cable Rating model in Ipsa. The Dynamic Cable Rating model (DCR) has been developed for the WPD FALCON project by Aston University. It models the thermal time constants of a cable and the surrounding soil to determine the cyclic cable rating. The DCR model is provided in the form of an Ipsa Plugin model. It can be added to any cable in the network by following the instructions in the section below. A test network is provided as well as a Python script to assist in the set up of the model. The model calculates the continuous and cyclic ratings of the cable based on the time varying current that flows through it. The Profile analysis in Ipsa is used to represent the time varying network demands. The analysis therefore calculates the current through the cable based on the profile data in the network. The cable current ratings are calculated as single values which are dependent on the shape and magnitude of the profile. The model does not calculate tie varying ratings. The model also calculates the number of times the current ratings are exceeded during a Profile analysis. This guide contains the following sections; 1. Data Requirements 2. Add DCR Model to Ipsa 3. Add Extended Data to Network Model 4. Add DCR Model to Cable 5. DCR Simulations September 2013 Page 1
2 Plugin Model Data Dynamic Cable Rating Model Guide 1. Data Requirements The data required for the DCR model includes the dimensional cable data and thermal parameters of the cable and surrounding soil. All the data is entered into the Plugin Properties dialog. The following tables provide a summary of the input data requirements together with the default values. All data should be entered into Ipsa without units. The DCR model calculates the continuous and cyclic ratings of the cable based on the time varying current that flows through it. The rating results are presented in the extended data associated with the cable. Note that all busbars in the model should have a nominal voltage assigned to them, thereby allowing Ipsa to calculate the cable currents. Table 1 - DCR Data Parameters for the Plugin Parameter Maximum Conductor Temperature (deg C) Default Values 90.0 C Description Maximum allowable conductor temperature in degrees C Burial Depth (mm) 600mm Cable burial depth in mm. Must be greater than 0.0 Cable Diameter (mm) 39.1mm Cable diameter in mm. Must be greater than 0.0 Trefoil = 1, Flat = 2 1 Enter 1 for a trefoil cable, 2 for flat installation with spacing Flat Spacing Factor 0 Spacing between ducts in multiples of the duct diameter. Enter wholes only. For example enter a value of 2 to represent 40mm diameter cables with a spacing of 80mm. Used for flat installation only Screen Diameter (mm) 32.78mm External diameter of the cable screen in mm. Must be greater than 0.0 Insulation Diameter (mm) 29.6mm External diameter of the cable insulation in mm. Must be greater than 0.0 Conductor Diameter (mm) 20.5mm External diameter of the cable conductor in mm. Must be greater than 0.0 Screen Area (mm^2) 35.0mm 2 Cross sectional area of the cable screen in mm 2. Must be greater than 0.0 DC Resistance at 20degC (ohms) Ω DC resistance of the conductor at 20 C in ohms Insulation Thermal Resistivity (m degc/w) Outer Cover Thermal Resistivity (m degc/w) 3.5 m C/W Thermal resistance of the cable insulation material in metre-degrees centigrade per watt 3.5 m C/W Thermal resistance of the cable outer layers in metredegrees centigrade per watt October 2013 Page 2
3 Extended Data Outputs Plugin Model Data Dynamic Cable Rating Model Guide Parameter Conductor Temperature Coefficient (degc -1 ) Screen Temperature Coefficient (degc -1 ) Conductor Resistivity at 20degC (m degc/w) Default Values C C x 10-8 C/W Description Temperature coefficient of the cable conductor material resistance in degc -1 Temperature coefficient of the cable screen material resistance in degc -1 Conductor thermal resistivity measured at 20 C in metre-degrees centigrade per watt Ambient Soil Temperature (degc) 10 C Ambient soil temperature for the cable Soil Thermal Diffusivity (m 2 /sec) 5 x 10-7 m 2 /sec The soil diffusivity, or conductivity, in metres 2 per second Soil Thermal Resistivity (m degc/w) 0.9 m C/W Thermal resistance of the soil and materials surrounding the cable in metre-degrees centigrade per watt Table 2 - DCR Output Data Parameter Cyclic_Rating_Amps Sustained_Rating_Amps Cyclic_Overloads Sustained_Overloads Description The cyclic cable rating calculated by the DCR model is presented in this field. Value is in amps. The sustained or continuous cable rating calculated by the DCR model is presented in this field. Value is in amps. The number of cyclic overloads identified during the last profile analysis. This value is reset for each profile analysis. The number of sustained overloads identified during the last profile analysis. This value is reset for each profile analysis. October 2013 Page 3
4 2. Add DCR Model to Ipsa 2.1. The DCR model is provided in the form of a DLL file and is normally supplied as part of the Ipsa install Confirm that there is a file called IFalconDynCableRating.dll in the Ipsa plugins directory C:\Program Files\IpsaPower\Ipsa 2.3\plugins, as shown below; October 2013 Page 4
5 2.3. The DCR model will be checked when Ipsa is launched and the user can check it has been correctly loaded by starting Ipsa and viewing the Progress window. The following message will be displayed if the model is present; 2.4. If the above message is not displayed then please contact for further assistance. October 2013 Page 5
6 3. Add Extended Data to Network Model Some of the cable data is set using Ipsa Extended Data fields. For convenience a Python script has been provided which configures the required Extended Data fields automatically. Perform the following steps to add the required data fields to each Ipsa network; 3.1. Open the Ipsa network containing the transformers to which the DCR model is to be applied 3.2. Go to the Analysis menu and select the Run Script item 3.3. Navigate to the ConfigureDCR.py script. Normally this will be in the Ipsa script directory should below. If the script has been ed or downloaded from the website then navigate to the folder where it was saved into. C:\Program Files\IpsaPower\Ipsa 2.3\scripts 3.4. Select the script and click Open. The script will prompt you as required and issue warnings if not successful. Please contact support@ipsa-power.com if errors are encountered. October 2013 Page 6
7 4. Add DCR Model to Cables 4.1. Open the network model in Ipsa and locate the line which is to have the DTR model added to it Display the Line properties dialog shown below by either; Double clicking the branch on the diagram Double click the item in the stack bar 4.3. Select the Main tab 4.4. Select the FALCON Cable DAR from the selection box. The dialog will now display the selected plug-in name and an Edit button as shown below; October 2013 Page 7
8 4.5. Click the Edit button and the DCR Properties dialog will be displayed as shown below. This dialog contains the thermal properties for the cable; 4.6. The parameters can be edited as required for each cable. The Restore Defaults button can be used to return to the default parameters as shown above Click OK to save the data and return to the Line dialog 4.8. The rating results are presented in the extended data fields for the line October 2013 Page 8
9 4.9. Click the Extended Data tab in the Line dialog to view the rating result fields, as shown below; Click OK to save the data for the Line The DCR model is now ready for use October 2013 Page 9
10 5. DCR Simulations The DCR model is intended for use with Ipsa load profiles to allow a time series representation of the network load changes. The model will run automatically during any Profile studies, it will not run during normal load flow studies. No further set up is required in order to run the model. For this version of the model all output data is saved in the extended data fields associated with the line. A test network has been provided which can be used to ensure that the model operates correctly. This network contains a line with a DCR model and a load profile. Follow the steps below to run the model and reproduce the test case results; 5.1. Open Ipsa and open the Profile Test network supplied with the DCR model 5.2. This contains a line with a DCR model, the model properties are shown below; October 2013 Page 10
11 5.3. The model also contains a single 11kV load with a profile as shown above. This profile contains 48 values representing one day of half hourly demand data Click on the Analysis menu and select the Run Profile option. This runs all the load flow calculations for the profile associated with the load. The results are presented in the Progress window as shown below, indicating the number of profile periods that the ratings were exceeded; [Oct :26:22] Starting profile analysis [Oct :26:22] Plugin item FALCON Cable DAR controlling Busbar1.Busbar2.Line connected to plugin (FALCON Cable DAR) instance [1] [Oct :26:22] Plugin: loaded model (FALCON Cable DAR): FALCON Cable DAR controlling Busbar1.Busbar2.Line [Oct :26:22] Plugin FALCON Cable DAR [1]: Cable extended data DCR parameters ok [Oct :26:22] Plugin FALCON Cable DAR [1]: Cable sustained rating of amps exceeded for hours [Oct :26:22] Plugin FALCON Cable DAR [1]: Cable cyclic rating of amps exceeded for hours [Oct :26:22] 24 profile categories run The calculated cable rating results are shown in the extended data for the branch. Double click on the branch and select the Extended Data tab, as shown below; October 2013 Page 11
12 5.6. The diagram results also show the maximum and minimum current flows; October 2013 Page 12
Defining and Labeling Circuits and Electrical Phasing in PLS-CADD
610 N. Whitney Way, Suite 160 Madison, WI 53705 Phone: 608.238.2171 Fax: 608.238.9241 Email:info@powline.com URL: http://www.powline.com Defining and Labeling Circuits and Electrical Phasing in PLS-CADD
More informationYellow Frog. Manual Version 1.1
Yellow Frog Manual Version 1.1 1 YellowFrog Contents PC Requirements...... 2 YellowFrog Power Meter Measurement.... 3 YellowFrog PC Software..... 3 Main Screen....... 4 Input Overload....... 5 Battery
More informationETAP PowerStation 4.0
ETAP PowerStation 4.0 User Guide Copyright 2001 Operation Technology, Inc. All Rights Reserved This manual has copyrights by Operation Technology, Inc. All rights reserved. Under the copyright laws, this
More informationLED Driver Linear / area fixed output
Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For
More informationIn-situ Port Cal for Dual Carriages Tuner
In-situ Port Cal for Dual Carriages Tuner In-Situ port cal method is the calibration technique mainly for cascaded tuners or multi-carriage tuner. Unlike in-situ system cal which requires 2 VNA calibrations
More informationSWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L
SWA Cable BS6724 Steel Wire Armoured LSZH Eland Product Group A9L Application SWA Cable power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for
More informationTransmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
More informationLED Driver Compact fixed output
Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000
More informationTransient Stability Events & Actions
ETAP TIP No. 009 Transient Stability Events & Actions Applicable ETAP Versions: 5.5.0, 5.5.5, 5.5.6 (For lower versions, some of the descriptions and procedures below may differ in some ways) Event is
More informationPHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series
Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection
More informationLED Driver Compact fixed output
Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000
More informationSWA Cable - BS5467 Steel Wire Armoured PVC Eland Product Group A9S
SWA Cable - BS5467 Steel Wire Armoured PVC Eland Product Group A9S Application SWA Cable - power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and
More informationInstallation and User Guide 458/CTR8 8-Channel Ballast Controller Module
Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach
More informationHV/PHA Adjustment (PB) Part
HV/PHA Adjustment (PB) Part Contents Contents 1. How to set Part conditions...1 1.1 Setting conditions... 1 2. HV/PHA adjustment sequence...7 3. How to use this Part...9 HV/PHA Adjustment (PB) Part i
More informationLuminaire installation box Surface-mounted box Ceiling installation box
-Smart PTM Ambient light sensor and motion detector for constant lighting control uminaire installation box Surface-mounted box Ceiling installation box Overview: -SMART PTM i is an ambient light sensor,
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
DATASHEET - NZMH2-A100 Circuit-breaker, 3p, 100A Part no. NZMH2-A100 Catalog No. 259099 Similar to illustration Delivery program Product range Circuit-breaker Protective function System and cable protection
More informationLED control gear Compact dimming. Uconverter LCAI 2x38 W 0500 K013 one4all ECO series. Ordering data
Product description Dimmable built-in for LED Constant current (with 2 adjustable output channels) Designed for outdoor and street luminaire Output power 2 x 38 W Suitable for mains voltage peaks (burst/surge)
More informationGetting started with
Getting started with Electricity consumption monitoring single phase for homes and some smaller light commercial premises OVERVIEW: The OWL Intuition-e electricity monitoring system comprises of three
More informationLog viewer and analyser for switchboard and downhole sensor
Log viewer and analyser for switchboard and downhole sensor Novomet-Perm cc, 2010 2013 User guide User manual 2 http://www.novomet.ru/eng Novomet-Perm cc 395 Cosmonauts st, Perm, 614065, Russia Novomet
More informationLED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series
Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires
More informationLED Driver Compact dimming
Driver CA 15W 180-350mA flexc PH-C SR ADV ADVACED series Product description Dimmable constant current ED Driver (SEV) Independent ED Driver with cable clamps Selectable output current between 180, 250
More informationTriLIN Program Utility TPU_ TriLIN Programming Manual
Program Utility TPU_2.8.2 TriLIN Programming Manual 1. Programming the electronics a. Tool necessary Power supply 12-32 V DC Computer with appropriate USB port and a Windows Operating System (We recommend
More informationInstructions for DataMark PDF Temperature Logger
Instructions for DataMark PDF Temperature Logger DataMark provides a convenient way to obtain high accuracy temperature data in transit. The unit is a self contained temperature logger that plugs directly
More informationAurora Grid-Tie Installation Instructions (Model Number: PVI-3.0-OUTD-US-W) Revision 4.1
Aurora Grid-Tie Installation Instructions (Model Number: PVI-3.0-OUTD-US-W) Revision 4.1 Contents 1) Grid-Tie Installation Block Diagram... 3 2) Installation Steps.... 4 2.1) Initial Setup.... 4 2.1.1)
More informationCLIPSTER. 3D LUT File Generation with the Kodak Display Manager. Supplement
Supplement: CLIPSTER 3D LUT File Generation with the Kodak Display Manager (Version 1.0) CLIPSTER 3D LUT File Generation with the Kodak Display Manager Supplement Supplement for the CLIPSTER Documentation:
More informationAnalyzing and Saving a Signal
Analyzing and Saving a Signal Approximate Time You can complete this exercise in approximately 45 minutes. Background LabVIEW includes a set of Express VIs that help you analyze signals. This chapter teaches
More informationKRF EMC Filters Installation, Operation and Maintenance Manual
KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC
More informationRevision 1.2d
Specifications subject to change without notice 0 of 16 Universal Encoder Checker Universal Encoder Checker...1 Description...2 Components...2 Encoder Checker and Adapter Connections...2 Warning: High
More informationChannel Controller for Light Show with Remote Control. HomLiCon RCL164R
16 + 4 Channel Controller for Light Show with Remote Control Application: Managing dynamic illuminated advertising signs, spectacular light walls, podiums, etc. Managing groups of lamps 120V/60Hz or 230V/50Hz
More informationHYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Constant current LED driver DALI Dimmable Product description Dimmable Independent constant current Adjustable output current between 350 and 1,050mA via DIP switch Max. output power 35 W Up to 88 % efficiency
More informationSingle output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.
RoHS Lead-Solder-Exemption Compliant New 3.3 V and 5 V Output Models Universal Input 85-264 VAC Industry-Standard Footprint: 7.0" x 4.3" x 1.97" (177.8 x 109.2 x 50.0 mm) Input Transient & ESD Compliance
More informationIRIG-B PTP Clock Converter Output Module Hardware Installation Manual
IRIG-B PTP Clock Converter Output Module Hardware Installation Manual Kyland Technology Co., LTD. Publication Date: May 2012 Version: V1.2 Customer Service Hotline: (+8610) 88796676 FAX: (+8610) 88796678
More informationLDG TW-2 Talking Wattmeter For VHF and UHF
LDG TW-2 Talking Wattmeter For VHF and UHF LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com
More informationContents: 1 LANsmart Pro Main Unit 4 Remote Unit: ID1, ID2, ID3, ID4
LANsmart Pro user manual Introduction LANsmart Pro is a hand-held, multifunction Cable Map Tester and Cable Length Meter. It has an integrated Analog and Digital Tone Generator, Port Finder, and Quick
More informationHYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.
Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.
More informationLED control gear Compact fixed output
Driver LC 40W 900mA fixc SR SNC ESSENCE series Product description Independent fixed output LED Driver Constant current LED Driver Output current 900 ma Max. output power 39 W Nominal life-time up to 50,000
More informationUTH-70T INSTALLATION AND MANUAL
UTH-70T INSTALLATION AND MANUAL DISPLAY SCREENS AND FUNCTIONS DISPLAY SCREENS AND FUNCTIONS LCD DISPLAY SCREEN BAR DISPLAY: THIS DISPLAYS THE PRESENT STATE OF OUTPUT TO THE SIDE OF HEATER AS ON / OFF WHILE
More informationAccessories. Servo Motors. Servo Motors B-45. Accessories
Servo Motors Servo Motors Accessories Accessories Introduction NX Accessories Page Cables B-46 Flexible Couplings B-50 Control Module B-51 Data Setting Software B-51 Accessory Sets B-52 Regeneration Units
More informationHDRFI Series Tensolite High-Performance Cable & Interconnect Systems. High Density RF Interconnect
HDRFI Series Tensolite High-Performance Cable & Interconnect Systems High Density RF Interconnect HDRFI is a patented Tensolite connection system that transfers high frequency signals through a unique
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
DATASHEET - NZMN3-VE630 Circuit-breaker, 3p, 630A Part no. NZMN3-VE630 Catalog No. 259133 EL-Nummer (Norway) 0004358791 Similar to illustration Delivery program Product range Circuit-breaker Protective
More informationTOSHIBA Industrial Magnetron E3328
TOSHIBA E3328 is a fixed frequency continuous wave magnetron intended for use in the industrial microwave heating applications. The average output power is 3kW in the frequency range from 2450 to 2470
More informationENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 48-3 2011 Test Procedure for Measuring Shielding Effectiveness of Braided Coaxial Drop Cable Using the GTEM Cell
More informationLocation. Electrical. Loads. 2-wire mains-rated, 0.5 mm² to 1.5 mm² Max. length: 300 m (with 1.5 mm² cable). Example: Belden 8471.
Product Description Installation and User Guide Transistor Dimmer (454) The DIN rail mounted 454 is a fourchannel transistor dimmer that can operate in one of two modes: leading edge or trailing edge.
More informationT3316 IP QAM Modulator User Manual
T3316 IP QAM Modulator User Manual SW Version: 1.02 HW version: 0.70.0.0 Web NMS version: 1.02 Intended Audience About This Manual This user manual has been written to help people who have to use, to integrate
More informationGetting started with
PART NO. CMA11 3 MADE IN CHINA 1. Measuring CAT II 2. Max. voltage 250V ~ 3. Max. current 71 Amp Getting started with Electricity consumption & Solar PV generation monitoring single phase, for homes fitted
More informationData Acquisition Using LabVIEW
Experiment-0 Data Acquisition Using LabVIEW Introduction The objectives of this experiment are to become acquainted with using computer-conrolled instrumentation for data acquisition. LabVIEW, a program
More informationSceneStyle2 User Guide
SceneStyle2 User Guide Mode Lighting (UK) Limited. The Maltings, 63 High Street, Ware, Hertfordshire, SG12 9AD, UNITED KINGDOM. Telephone: +44 (0) 1920 462121 Facsimile: +44 (0) 1920 466881 e-mail: website:
More informationUser Manual. May 2005 AIN LIGHT
May 2005 AIN LIGHT This user manual is designed to help the operators and owners of Soft-LED products use, troubleshoot, and utilize all of the product s potential. Customers seeking additional help not
More informationAgilent MOI for HDMI 1.4b Cable Assembly Test Revision Jul 2012
Revision 1.11 19-Jul 2012 Agilent Method of Implementation (MOI) for HDMI 1.4b Cable Assembly Test Using Agilent E5071C ENA Network Analyzer Option TDR 1 Table of Contents 1. Modification Record... 4 2.
More informationMESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITHOUT METALLIC SCREEN
Engineering Specification Electrical Networks MESP 030000-02 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical
More informationTGL2209 SM 8 12 GHz 50 Watt VPIN Limiter
Product Overview The Qorvo is a high power, X-band GaAs VPIN limiter capable of protecting sensitive receive channel components against high power incident signals. The does not require DC bias, and achieves
More informationLED Driver Compact dimming
Driver LCA 17W 250 700mA one4all SC PRE PREMIUM series Product description Dimmable built-in constant current LED Driver Can be either used build-in or independent with clip-on strain-relief (see accessory)
More informationPQ-Box 100 Quick Start Instructions
PQ-Box 100 Quick Start Instructions These instructions are provided for the purpose on providing a quick start to PQ-Box 100 installation and operation. Please refer to the user handbook for full details.
More informationREGO Start&Go USER MANUAL
REGO Start&Go USER MANUAL Version 0 Rev. B of 03/03/16 Page 1 of 15 Introduction The purpose of the manual is to describe all of the steps required to commission and correctly operate the REGO Start&Go
More informationREMOTE I/O R30 SERIES. PC CONFIGURATOR SOFTWARE Model: R30CFG Ver Users Manual
REMOTE I/O R30 SERIES PC CONFIGURATOR SOFTWARE Model: R30CFG Ver. 1.13 Users Manual 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Tel: +81-6-6659-8201 Fax: +81-6-6659-8510 http://www.m-system.co.jp/
More informationTGL2210-SM_EVB GHz 100 Watt VPIN Limiter. Product Overview. Key Features. Applications. Functional Block Diagram. Ordering Information
.5 6 GHz Watt VPIN Limiter Product Overview The Qorvo is a high-power receive protection circuit (limiter) operating from.5-6ghz. Capable of withstanding up to W incident power levels, the allows < dbm
More informationVIDEO GRABBER. DisplayPort. User Manual
VIDEO GRABBER DisplayPort User Manual Version Date Description Author 1.0 2016.03.02 New document MM 1.1 2016.11.02 Revised to match 1.5 device firmware version MM 1.2 2019.11.28 Drawings changes MM 2
More informationLED Driver Linear / area dimming. Driver LCAI 38/75W TW lp Tunable White
Driver LCAI 38/75W TW lp Tunable White Product description 2-channel LED Driver with LI DT8 Output power: 38 W or 75 W Power input on standby < 0.3 W Nominal life-time up to 50,000 h 5-year guarantee Properties
More informationThis document describes the different ways to allow the automation system to close a gpi contact from the transmission list.
GPI BOARD (RELAY ACTUATOR & ISOLATED D/I CARD) Date: August 03, 2000 This document describes the different ways to allow the automation system to close a gpi contact from the transmission list. CABLE REQUIREMENTS
More informationLED Driver Compact dimming
Driver LCA 17W 250 700mA one4all C PRE PREMIUM series Product description Dimmable built-in constant current LED Driver Adjustable output current between 250 and 700 ma via ready2mains Programmer, I-select
More informationDescription Set value in neutral conductor is synchronous with set value Ir of main pole. R.m.s. value measurement and thermal memory CSA 100
DATASHEET - NZMN3-4-AE400 Circuit-breaker, 4p, 400A Part no. NZMN3-4-AE400 Catalog No. 265891 Similar to illustration EL-Nummer (Norway) 0004358857 Delivery program Product range Circuit-breaker Protective
More informationI r A I i = I n x. Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Deliveryprogramme Circuitbr.,3pmotorprotection Partno. Articleno. 265784 NZMN4-ME875 Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation type Fixed Release
More informationXRD-DSC Sample Alignment (BB) Part
XRD-DSC Sample Alignment (BB) Part Contents Contents 1. How to set Part conditions...1 1.1 Setting conditions... 1 1.2 Customizing scan conditions and slit conditions... 5 2. Sample alignment sequence...9
More informationUser Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.
EF User Guide UD51 Second encoder small option module for Unidrive Part Number: 0460-0084-05 Issue Number: 5 www.controltechniques.com Safety Information The option card and its associated drive are intended
More informationBooBox Flex. OPERATING MANUAL V1.1 (Feb 24, 2010) 6 Oakside Court Barrie, Ontario L4N 5V5 Tel: Fax:
BooBox Flex OPERATING MANUAL V1.1 (Feb 24, 2010) 6 Oakside Court Barrie, Ontario L4N 5V5 Tel: 905-803-9274 Fax: 647-439-1470 www.frightideas.com Connections The BooBox Flex is available with Terminal Blocks
More informationKNX Dimmer RGBW - User Manual
KNX Dimmer RGBW - User Manual Item No.: LC-013-004 1. Product Description With the KNX Dimmer RGBW it is possible to control of RGBW, WW-CW LED or 4 independent channels with integrated KNX BCU. Simple
More informationGVD-120 Galvano Controller
Becker & Hickl GmbH June 2007 Technology Leader in Photon Counting Tel. +49 / 30 / 787 56 32 FAX +49 / 30 / 787 57 34 http://www.becker-hickl.de email: info@becker-hickl.de GVD-120 Galvano Controller Waveform
More informationSINGLE ZONE CLIMATE ZONING SYSTEM. Technical Manual. Polyaire Pty Ltd
SINGLE ZONE CLIMATE ZONING SYSTEM Technical Manual Polyaire Pty Ltd 11-13 White Road GEPPS CROSS South Australia, 5094 Tel: (08) 8349 8466 Fax: (08) 8349 8446 www.polyaire.com.au CONTENTS Features 1 Application
More informationGamma instabus. Technical product information
Gamma instabus Technical product information Universal dimmer N 554D31, 4 x 300 VA / 1x 1000 VA, AC 230 V Universal dimmer N 554D31 Control of dimmable lamps, including LED without minimum load Output
More informationI r A Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100
Circuit-breaker,3p,160A Partno. NZMN2-M160 CatalogNo. 265724 Similar to illustration Deliveryprogram Product range Circuit-breaker Protective function Motor protection Standard/Approval IEC Installation
More informationHD/SD-SDI TO VGA CONVERTER. DAC-60 Quick Start Guide.
HD/SD-SDI TO VGA CONVERTER DAC-60 Quick Start Guide www.datavideo.com Warranty Standard Warranty Datavideo equipment is guaranteed against any manufacturing defects for one year from the date of purchase.
More informationDM1624, DM1612, DM812
Installation Guide Hardware and Software DM Series Digital Processors models DM1624, DM1612, DM812 LECTROSONICS, INC. 1 Installation Specific Information Only This guide covers only installation related
More informationB2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006
B2 Spice A/D Tutorial Author: B. Mealy revised: July 27, 2006 The B 2 Spice A/D software allows for the simulation of digital, analog, and hybrid circuits. CPE 169, however, is only concerned with the
More information21 Channel Light Show PWM LED Controller with Remote Control
21 Channel Light Show PWM LED Controller with Remote Control Application: Managing dynamic illuminated advertising signs, spectacular light walls, podiums, etc. Managing groups LED and LED strips - from
More informationSEM- EDS Instruction Manual
SEM- EDS Instruction Manual Double-click on the Spirit icon ( ) on the desktop to start the software program. I. X-ray Functions Access the basic X-ray acquisition, display and analysis functions through
More informationModular pulse operated latching relay 16 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Modular pulse operated latc / 05 / 07 / 08 / 10 / 11 / 12 / 14 / 16 / 20 and 927 00 / 49 CONTENTS PAGES 1. Description,
More informationEVC300i. Generator Automatic Voltage Regulator Operation Manual
EVC300i Generator Automatic Voltage Regulator Operation Manual 1. INTRODUCTION The EVC300i Voltage Regulator is thyristor base to control the DC exciter field power of conventional 50 or 60 Hz brushless
More informationJul03 Rev C EC
Product Specification Coaxial BNC Solder Receptacle Connector 108-12079 10Jul03 Rev C EC 0990-0940-03 1. SCOPE 1.1. Content This specification covers the performance, tests and quality requirements for
More information220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX
220KV EHV NETWORK AT RELIANCE JAMNAGAR REFINERY COMPLEX JAMNAGAR 220KV CABLE NETWORK: 2 2. DESIGN 2A. NETWORK: 220 KV NETWORK DESIGN IS DESIGNED WITH 100% REDUNDANCY FROM 220 KV BUS TO LOAD. THIS IS ACHIEVED
More informationEVC600i. Generator Automatic Voltage Regulator Operation Manual
EVC600i Generator Automatic Voltage Regulator Operation Manual 1. INTRODUCTION The EVC600i Voltage Regulator is thyristor base to control the DC exciter field power of conventional 50 or 60 Hz brushless
More informationCalibrating and Profiling Your Monitor
Calibrating and Profiling Your Monitor For this module, you will need: Eye-One measurement device Counterweight (used for LCD screens only) New, modern displays are better First, you need to use a good
More informationDimming actuators GDA-4K KNX GDA-8K KNX
Dimming actuators GDA-4K KNX GDA-8K KNX GDA-4K KNX 108394 GDA-8K KNX 108395 Updated: May-17 (Subject to changes) Page 1 of 67 Contents 1 FUNCTIONAL CHARACTERISTICS... 4 1.1 OPERATION... 5 2 TECHNICAL DATA...
More informationProcedures to Characterize Maury s Automatic Tuner Using ATS Software Version 5.1 or above
Procedures to Characterize Maury s Automatic Tuner Using ATS Software Version 5.1 or above Things to check before tuner characterization Make sure tuner is power up and USB cable is connected to the computer
More informationLED Driver Linear / area dimming
Driver LCA 75W 350 1050mA one4all lp PRE PREMIUM series Product description Dimmable built-in constant current LED Driver Adjustable output current between 350 and 1,050 ma via ready2mains Programmer,
More informationProtective function Systems, cable, selectivity and generator protection. i 2 t constant function: switchable. I r A
Deliveryprogramme Circuitbreak.3pselect.protection Partno. Articleno. 265777 NZMH4-VE1600 Product range Circuit-breaker Protective function Systems, cable, selectivity and generator protection Standard/Approval
More informationSession 1 Introduction to Data Acquisition and Real-Time Control
EE-371 CONTROL SYSTEMS LABORATORY Session 1 Introduction to Data Acquisition and Real-Time Control Purpose The objectives of this session are To gain familiarity with the MultiQ3 board and WinCon software.
More informationMulti channel programmable Filter-Amplifier
Operating instructions VS 21 Multi channel programmable Filter-Amplifier Operation LED Handset OK 41A For digital and analogue channels 6 terrestrial inputs: B I-II / B III / VHF-UHF and 3 UHF inputs over
More informationUSB Mini Spectrum Analyzer User s Guide TSA5G35
USB Mini Spectrum Analyzer User s Guide TSA5G35 Triarchy Technologies, Corp. Page 1 of 21 USB Mini Spectrum Analyzer User s Guide Copyright Notice Copyright 2011 Triarchy Technologies, Corp. All rights
More informationDigital Temperature & Analog Sensor. Analog Input Port. Digital Port. Front
AVTECH Digital Temperature & Analog Sensor AVTECH s Digital Temperature & Analog Sensor monitors ambient indoor temperature and a connected 0 to 5 VDC analog sensor. This compact, light-weight sensor has
More informationLED Driver Compact fixed output
Driver LC 10W 250mA fixc R ADV ADV series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 250 ma For luminaires of protection class II For ambient temperatures
More informationSetup Guide. CalMAN Client for SCRATCH. Rev. 1.1
Setup Guide CalMAN Client for SCRATCH Rev. 1.1 Introduction CalMAN Required Software Version: CalMAN Display Calibration Software interfaces directly with ASSIMILATE SCRATCH software through the CalMAN
More informationCable installation guidelines
The Quality Connection Cable installation guidelines Business Unit Industrial Projects 2 Cable installation guidelines www.leoni-industrial-projects.com GENERAL Installation methods Many different methods
More informationDSIM-GI Installation Guide Revision P
Installation Guide Revision P 1. Quick Start Instructions for Single Pilot AGC Operatation 1. With the ADU jumper in Auto position, turn ADU pot to MIN amplifier output level. Then place the ADU jumper
More informationPackage Contents. LED Protocols Supported. Safety Information. Physical Dimensions
Pixel Triton Table of Contents Package Contents... 1 Safety Information... 1 LED Protocols Supported... 1 Physical Dimensions... 1 Software Features... 2 LED Status... 2 Power... 2 Activity LED... 2 Link
More informationL-series Instructions for 3D configurator.
L-series Instructions for 3D configurator www.hypertronics.com These instructions are intended to guide the customer through the process of creating and generating valid L-series connector assemblies.
More informationRK-2 ENVIRONMENTAL DATA CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD. Main characteristics
RK-2 CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER WITH FLANGED HEAD (ANALOG OR START/STOP OUTPUT) Main characteristics Absolute transducer Strokes from 50 to 4000mm (RK-2- -N/E/S) Digital output
More informationDimming actuators of the FIX series DM 4-2 T, DM 8-2 T
Dimming actuators of the FIX series DM 4-2 T, DM 8-2 T DM 4-2 T 4940280 DM 8-2 T 4940285 Updated: Jun-16 (Subject to change) Page 1 of 70 Contents 1 FUNCTIONAL CHARACTERISTICS... 4 1.1 OPERATION... 5 2
More informationSystem pro M DT1-IK DT1-IK/24V DT1-IK/DCF DT2-IK 2CSM204275R0611 2CSM441017D5601 2CSM204285R0611 2CSM204295R0611 2CSM204325R0611
DT1-IK 2CSM204275R0611 DT1-IK/24V 2CSM204285R0611 DT1-IK/DCF 2CSM204295R0611 DT2-IK 2CSM204325R0611 System pro M 2CSM441017D5601 GB WEEKLY DIGITAL TIME SWITCH + PROGRAMMING KEY I INTERRUTTORE ORARIO DIGITALE
More informationLED Driver Compact dimming
Driver LCA 45W 500 1400mA one4all C PRE PREMIUM series Product description Dimmable built-in constant current LED Driver Adjustable output current between 500 and 1,400 ma via ready2mains Programmer, I-select
More informationRack-Mount Receiver Analyzer 101
Rack-Mount Receiver Analyzer 101 A Decade s Worth of Innovation No part of this document may be circulated, quoted, or reproduced for distribution without prior written approval from Quasonix, Inc. Copyright
More information