SIREC P, PA, L, LA. Manual

Size: px
Start display at page:

Download "SIREC P, PA, L, LA. Manual"

Transcription

1 SIREC P, PA, L, LA Multipoint recorder P 7ND 3021-xB... Multipoint recorder PA 7ND 3021-xA... Line recorder L 7ND 3121 Line recorder LA 7ND 3125 Manual Line recorder Multipoint recorder

2 The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights created by the granting of patents or registration of a design are reserved.technical data subject to change without notice SIMATIC, SIREC, SIPROM are Siemens registered trademarks. All other product or system names are (registered) trademarks of their respective owners and must be treated accordingly.

3 SIEMENS Chapter Introduction 0 Application 1 SIREC Multipoint recorder P 7ND 3021-xB... Multipoint recorder PA 7ND 3021-xA... Line recorder L 7ND 3121 Line recorder LA 7ND 3125 Design and Mode of Operation 2 Preparation for Operation 3 Operation 4 Measuring and Recording Mode 5 Servicing and Maintenance 6 Technical Data 7 Scope of Delivery, Options, Accessories 8 Parts List 9 Subject Index Order No.: C79000-G7376-C188 Printed in France AG MG 168 en SIREC P, PA, L, LA Manual I-1

4 I-2 SIREC P, PA, L, LA Manual

5 Contents Contents 0 Introduction General Information Qualified Person Warning Information Approved Use Application Design and Mode of Operation Summary Recorder Components Housing Measured-value Acquisition Central Processing Unit Power Supply Chassis Mode of Operation Scope of Delivery Accessories, Consumable Materials Options Digital Input/Output DC 24 V Output PC Cable SIPROM R - LA/PA Preparation for Operation Recorder Identification Jumper Settings 50/60 Hz, Summer Time/Winter Time Installation Guidelines Mechanical Preparation of Recorder for Operation Connection of Power Supply Connection of Analog Channels Digital Input/Output DC 24 V Output Starting Up the Recorder Operation Display and Control Elements SIREC P, PA, L, LA Manual i

6 Contents 4.2 Display Elements Levers Functions of Service Lever and Lever Functions of Levers 1, 3 and 4 in Recording Mode (L/LA version) Functions of Levers 1, 3 and 4 in Recording Mode (P/PA version) Functions of Levers 1, 3 and 4 in the PAUSE Status Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu PC Interface Settings using PROG Menu Chart Feed Measured-value Table (only recorders with alphanumeric text) Parameterizing the Analog Channels Parameterizing the Digital Channel (only LA version) Alarm Print (only recorders with alphanumeric text) Settings using TEST Menu Measuring Mode Chart Text (only recorders with alphanumeric text) Clock (only recorders with alphanumeric text) Control Input DI Language (only recorders with alphanumeric text) PROG Locking Parameterization Examples Setting the Chart Feed Setting the Output of the Measured-value Table Parameterizing the Analog Channel Parameterizing the Digital Channel Parameterizing the Alarms Parameterizing the Measuring Mode Parameterizing the Chart (only recorders with alphanumeric text) Parameterizing Texts (only recorders with alphanumeric text) Parameterizing the Time (only recorders with alphanumeric text) Parameterizing the Control Input DI ii SIREC P, PA, L, LA Manual

7 Contents Parameterizing the Language (only recorders with alphanumeric text) Parameterizing the PROG Locking Measuring and Recording Mode Chart Formatting (only recorders with alphanumeric text) Main Time Line (only recorders with alphanumeric text) Main Time Line (recorders without alphanumeric text) Device Text (only recorders with alphanumeric text) Switch-on Text (only recorders with alphanumeric text) Event Text (only recorders with alphanumeric text) Start Line (only recorders with alphanumeric text) Time Marks (only recorders with alphanumeric text) Limit Line (only LA version) Alarm Markers (only P/PA version) Measured-value Table (only recorders with alphanumeric text) Grid (only recorders with alphanumeric text) Priorities of Text Outputs Configuration Data (only recorders with alphanumeric text) Error Messages and Status Messages (only recorders with alphanumeric text) Example Recording with Explanations Servicing and Maintenance Removing the Chart Carriage Inserting the Chart Carriage Setting the Main Time Line Removing a Fanfold Pack Inserting a Fanfold Pack Removing a Chart Roll Inserting a Chart Roll Moving Chassis into Maintenance Position Returning Chassis from Maintenance Position Removing Chassis from Housing Inserting Chassis into Housing Removing the Guide Tongue Inserting the Guide Tongue Labelling and Inserting the Measuring-point Label Replacing the Pens for the Analog Channels SIREC P, PA, L, LA Manual iii

8 Contents 6.16 Replacing the Pen for Alphanumeric Text (only LA version) Replacing the Recording Head (only P/PA version) Replacing the Scale (line recorders) Replacing the Scale (multipoint recorders) Replacing the Battery (only recorders with alphanumeric text) Replacing the fuse Adjustment, Test Prints, Carriage/Text Positions Adjustment Carrying Out the Adjustment Test Print Maintenance Service Removal of Transport Protection (only PA version) Insertion of Transport Protection (only PA version) Technical Data Operation, Displays Recording Line Recorders Multipoint Recorders Digital Input/Output (Option) DC 24 V Output (Option) Power Supply Ambient Conditions Mounting Position Degree of Protection Electric Safety Electromagnetic Compatibility Dimensions, Mounting Weight Explanation of Error Data Scope of Delivery, Options, Accessories Scope of Delivery Line Recorders Multipoint Recorders Available Accessories and Consumable Material Line Recorders Multipoint Recorders iv SIREC P, PA, L, LA Manual

9 Contents 8.3 Available Options Parts List SIREC P, PA, L, LA Manual v

10 Contents vi SIREC P, PA, L, LA Manual

11 Introduction 0 Introduction 0.1 General Information This Manual contains the information required for approved use of the products described in it. It is directed at technically qualified personnel who are specially trained or have appropriate knowledge in the field of instrumentation and control, referred to below as automation technology. Knowledge of the safety information and warnings present in this Manual and their technically correct application are requirements for safe installation and commissioning as well as safe operation and repair of the described products. Only qualified personnel in the sense of Section 0.2 have the required specialist knowledge in order to correctly interpret the general safety information and warnings present in this document for a specific case, and to apply them appropriately. For organizational reasons, this Manual must be ordered separately. For clarity reasons, the manual does not cover all details on all types of the described products, and cannot describe every possible case in connection with installation, operation or maintenance. Should you require further information, or should particular problems occur which are not handled in sufficient depth in this Manual, help can be requested through your local Siemens office or representative. Your attention is additionally drawn to the fact that the contents of this Instruction Manual are not part of a previous or existing agreement, commitment or statutory right and do not change these. All commitments on the part of Siemens are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions. These warranty conditions in the contract are neither extended nor limited by the contents of this Manual. SIREC P, PA, L, LA Manual 0-1

12 Introduction 0.2 Qualified Person Unqualified interventions in the devices or the non-observance of the warnings present in this Manual or on the devices may lead to severe personal injury or damage to property. Therefore only suitably qualified personnel may work on these devices: T Configuring personnel familiar with the safety concepts of automation technology T Operating personnel instructed in the handling of equipment for automation technology and acquainted with the contents of this Manual which are important for operation T Commissioning and servicing personnel who are trained to repair such automation technology equipment or who are authorized to energize, ground and tag circuits and devices in accordance with established safety practices. 0-2 SIREC P, PA, L, LA Manual

13 Introduction 0.3 Warning Information Warning information with the following meanings is used in this Instruction Manual and in the warning information on the products: Danger means that death, severe personal injury or substantial damage to property will occur if the appropriate safety precautions are not observed. Warning means that death, severe personal injury or substantial damage to property can occur if the appropriate safety precautions are not observed. Caution means that slight personal injury or damage to property can occur if the appropriate safety precautions are not observed. Note is important information on the product, its handling or the respective part of the documentation to which particular attention should be paid. SIREC P, PA, L, LA Manual 0-3

14 Introduction 0.4 Approved Use T The devices must only be used for applications described in the Catalog and the Instruction Manual, and only in conjunction with other devices and components recommended by or approved of by Siemens. T The products have been developed, manufactured, tested and documented in accordance with the appropriate safety standards. If the handling guidelines and safety information are observed during configuring, assembly, approved use and maintenance, the products do not therefore present a danger in the normal case with respect to property or the health of persons. Warning T Following removal of the housing or the guard, certain parts of these devices are accessible which may carry dangerous voltages. T Only suitably qualified personnel should work on these devices. T These should be thoroughly familiar with all sources of danger and maintenance measures according to the information in this Manual. T Correct and safe operation of the products is dependent on proper transport, storage, installation and assembly as well as careful operation and maintenance. 0-4 SIREC P, PA, L, LA Manual

15 Introduction Documentation In addition to this Instruction Manual which can be used by all target groups the following relevant technical documentation is also available for the devices: T Leaflet "Parameterization a concise overview". Explains in visual form the basic operation and parameterization as well as the PROG and TEST menus. Target group: configuring and maintenance personnel. T Leaflet "Operation a concise overview". Contains charts showing the displays and controls, comprehensible parameterization examples, defined basic statuses of the devices, visual displays of important maintenance operations. Target group: plant operators, maintenance personnel. T A5 pamphlet "Installation instructions". Contains information required for assembly and installation of the devices. Target group: configuring and assembly personnel. T Catalog: "Recorders, flush-mounted instruments in standardized cases". Contains the most important technical data, charts, brief description, ordering information. Target group: plant management, configuring personnel. SIREC P, PA, L, LA Manual 0-5

16 Introduction 0-6 SIREC P, PA, L, LA Manual

17 Application 1 Application Purpose Standard The devices T line recorder, referred to below as "L version", T line recorder with alphanumeric text output, referred to below as "LA version", T multipoint recorder, referred to below as "P version", T multipoint recorder with alphanumeric text output, referred to below as "PA version", can be used to measure, record and monitor analog and digital values. The recorders with standard measuring ranges can be used to cyclically measure the following variables : T DC voltage (DC U), T direct current (DC I), and the recorders with universal measuring ranges also the additional variables T thermocouple connection (TC), T thermoelectric resistance, resistance and potentiometer connection (RTD, R), to process these and to document them on chart paper. As a result of the short cycle time, the recorders are also suitable for recording fast, dynamic process parameters. Even when delivered according to customer-specific requirements, the recorders can still be subsequently and easily adapted to requirements within the input, measuring and recording ranges. The L and LA versions can be equipped with up to three colored pens for the analog recording of measured values connected via channels #1 to #3. The LA version has an additional pen for a text channel for the output of alphanumeric characters and the recording of up to two digital channels d#1 and d#2. The P and PA versions are equipped with a recording head for values recorded via channels #1 to #6. In addition to this, two digital channels d#1 and d#2 can be recorded. The PA version can additionally output alphanumeric characters. The recorder functions can be set manually using levers or via a PC interface with connected laptop or PC. SIREC P, PA, L, LA Manual 1-1

18 Application Designs The recorders vary with respect to their recording systems, measuring ranges and power supplies: T L version: no alphanumeric text T LA version: with alphanumeric text T P version: no alphanumeric text T PA version: with alphanumeric text Standard measuring ranges T Universal measuring ranges Power supply AC 230 V Power supply AC 115 V Power supply AC 24 V T Power supply DC 24 V Options The recorders can be equipped with the following options: T Digital input/output T DC 24 V output T PC cable. The "Digital input/output" provides four inputs (DI1 to DI4) for control functions and six outputs (DO1 to DO6) for alarms, status signals or control signals. The inputs and outputs are electrically isolated from the recorder circuits. Two different outputs can be selected: T Digital input/output, electronic version with semiconductors or T Digital input/output, relay version with changeover contacts. The option "DC 24 V output" provides a power output for external devices or options to a limited extent such as e.g. a transmitter or digital input/output. The option "PC cable" permits connection to a laptop or PC. Delivery The recorders are delivered as standard designs, or manufactured, parameterized and prepared for operation in the factory according to the customer's order. Conversion Conversions to the recorders such as e.g. changing the power supply or subsequently installing options must only be carried out by the manufacturer or by personnel trained by the manufacturer. Environmental protection Only environmentally-friendly materials have been used for the packaging system of the recorders. This Instruction Manual has been printed on paper bleached without chlorine. 1-2 SIREC P, PA, L, LA Manual

19 Design and Mode of Operation 2 Design and Mode of Operation The following chapter describes the mechanical and electrical design as well as the recorder components. 2.1 Summary The recorders are designed as panel mounted instruments with a format 144 mm x 144 mm. Installation without interspacing is possible in panels and mosaic systems with sufficient ventilation. The modern recorders have digital data processing. Measured values are recorded serially in channels and with solid state technology. As a result of the exclusive use of step motors, the drive system for recording operates completely without contacts. This technology permits a wide range of applications and high functional reliability. Fig and Fig show views of the recorder. The mode of operation of the recorders is explained down to the block chart level using Fig SIREC P, PA, L, LA Manual 2-1

20 Design and Mode of Operation SERVICE PROG Door 2 Chart carriage 3 Levers 4 PC interface 5 LEDs 6 Visual operating aids Fig Front view of the recorders (line recorder shown as example; identical with multipoint recorder except for recording system) 2-2 SIREC P, PA, L, LA Manual

21 Design and Mode of Operation 1 Ground connection for cable screen 2 Terminals for DC 24 V output 3 Connection of digital input/output 4 Fuse F1 5 Connection of power supply 6 Fuse F2 7 Window for adjustment of measuring ranges 8 Input terminals Fig Rear view of recorders (LA version shown as example, design for AC 115/230 V) SIREC P, PA, L, LA Manual 2-3

22 Design and Mode of Operation 2.2 Recorder Components Housing The housing is made of sheet-steel. The chassis and the chart carriage are present at the front, the measuring module, the central processing unit, parts of the power supply and the options are located at the rear. The housing is mounted in the panel, mosaic system or desk upright panel using the supplied, standardized mounting elements Measured-value Acquisition Measured-value acquisition consists of a multiplexer with semiconductor relays and an analog-to-digital converter. The input ranges are set specifically for each channel using jumpers. The channels are electrically isolated from one another by staggered control of the semiconductor relays. Control is handled by the central processing unit. All channels to be measured during a cycle are connected to the input amplifier in succession via the individual semiconductor relays. The amplified signal is applied to an analogto-digital converter which operates according to the dual-slope procedure. In order to permit equally accurate measurements in sensitive ranges, reference measurements are carried out cyclically in the recorder version with universal measuring ranges. A cyclic check is also carried out for opencircuits. The terminal block also contains a sensor for measuring the terminal temperature when carrying out temperature measurements using thermocouples Central Processing Unit The central processing unit is the heart of the electronics. It contains a microprocessor as well as the program memory (EPROM), main memory (RAM) and non-volatile memory (EEPROM) for configuration data. Central component of the processing section is a microprocessor system with firmware. This is used, inter alia, for: T Sequence control T Calculation of measured values T Positioning of pen assemblies T Evaluation of input commands T Use of PC interface. The central processing unit permits control of the module "Digital input/output" and the PC interface. 2-4 SIREC P, PA, L, LA Manual

23 Design and Mode of Operation A crystal-controlled calendar/clock with external synchronization facility provides the date and time as a reference for sets of measured values and the chart. The central processing unit is located at the rear of the housing and is accessible from the front following removal of the chassis. It contains the plugs for connection of the other modules Power Supply AC 230 V or AC 115 V The recorders have different designs on the input side as a result of the four different power supplies which can be ordered. The mains power supply is connected to the recorder via an appliance plug with subsequent fuses, filter and transformer. The stepped down AC voltage is rectified, filtered and applied to DC/DC converters which generate the required internal DC voltages. Note The recorder must only be connected to the envisaged power supply. Observe the corresponding note on the rear of the recorder. DC 24 V The DC 24 V supply connected via the terminals is applied via a fuse to a power inverter whose output is connected to a transformer. The secondary side of the transformer is connected as in the recorder version with a mains power supply. AC 24 V The AC 24 V supply connected via the terminals is applied via a fuse to the primary side of the transformer. The secondary side is connected as in the recorder version with a mains power supply Chassis The chassis contains the chassis support, control PCB, recording system, user interface, PC interface and chart carriage. The chassis is connected to the central processing unit via a multi-conductor ribbon cable with plug. The cable length is such that the chassis can be completely removed from the housing without loosening the connection. Chassis support This is the support for the motors of the recording system, the control PCB, user interface and PC interface. The chart carriage latches into the chassis support and can be removed at any time using lever 2, e.g. to replace the chart. SIREC P, PA, L, LA Manual 2-5

24 Design and Mode of Operation Control "PCB" The control PCB contains the power electronics for the step motors of the drives as well as the light barrier for detection of the carriage zero points. It also contains a microswitch for recognizing the end of the chart paper, and several microswitches which are activated using the levers. Clock backup Only versions with alphanumeric text: the clock backup consists of a backup battery and capacitor. If a battery is not present, or if the chassis is separated from the central processing unit, the capacitor buffers the internal clock for approx. 5 minutes. The status of the clock buffer is checked when the power supply is switched on. The support for the backup battery is present on the control PCB and accessible following removal of the chassis. Recording system Chart carriage The recording system consists of up to seven step motors depending on the recorder version. These are used for: T Chart drive T Positioning of the pens (L/LA version) or the recording head (P/PA version) in the x-direction T Lifting of pens (L/LA version) or recording head (P/PA version) and T LA version: positioning of pen for text channel in x- and y-directions The chart carriage permits fanfold packs or rolls to be used as the chart paper. A take-up spool is required when using rolls (included in delivery). In addition, the chart carriage must be adapted when changing from fanfold paper to rolls. The required operations are described in Section 6 "Servicing and Maintenance". User interface The user interface consists of four levers and two LEDs underneath the chart carriage. A further lever is present on the side of the chassis and is only visible when the chassis is in maintenance position. Mechanical operations are directly activated by two of the four levers underneath the chart carriage. The other two levers can be used for two different actions each by moving the respective lever to the left or right. The TEST menu can activated and switched off again using the switch which is accessible on the side of the chassis. Green and red LEDs indicate different recorder statuses depending on how they are activated (on, off, flashing). PC interface The recorders are equipped with a PC interface. A laptop or PC can be connected via a special adapter cable. Convenient parameterization of the recorder is possible via the PC interface using a Windows desktop (SIPROM R). In addition, measured values, alarm statuses, date/time and chart feed A or B can also be scanned. 2-6 SIREC P, PA, L, LA Manual

25 Design and Mode of Operation Fig Block diagram of the recorders SIREC P, PA, L, LA Manual 2-7

26 Design and Mode of Operation 2.3 Mode of Operation As a result of the many different possible uses, the recorders are delivered preset to the basic setting of 4 to 20 ma. Customer-specific presetting is also possible as required. The recorder can then be used immediately following installation and commissioning. It is additionally possible to easily change the parameter settings of the recorder via the user or PC interface, thus permitting optimum and subsequent adaptation to the monitored process. The values measured cyclically by the recorder are amplified, digitized and processed further by a microprocessor system. In addition to processing of the measured values, the microprocessor system is responsible for sequence control, self-test, event processing, communication via the PC interface, control of the step motors of the recording system, feedbacks from the recording system and the user interface. The microprocessor system converts the measured value into positioning commands for the recording system. The recording system draw a continuous line on the chart paper. You can adjust the measuring and recording ranges such that the signal is recorded with an optimum resolution and display. It is also possible to define limits which are constantly recorded in the LA version as vertical lines. The recorders with alphanumeric text can output an alarm text if the limit is violated. The number of limits and the alarm function can be parameterized within wide ranges. If the recorder is equipped with the digital input/output option, the alarms can be output for further processing. Recorders with alphanumeric text can output a measured-value table, event text and recorder text cyclically or event-controlled. The texts must be entered previously via the user or PC interface when setting up the recorder. The outputs are made depending on the recorder parameters. 2-8 SIREC P, PA, L, LA Manual

27 Design and Mode of Operation 2.4 Scope of Delivery The scope of delivery is listed in Section Accessories, Consumable Materials The accessories and consumable materials are listed in Section Options The following options are available: T Digital input/output with 4 inputs and 6 outputs T DC 24 V output T PC cable Digital Input/Output The input signals (DI1 to DI4) of the four digital inputs are applied to the basic electronics via opto isolators and processed further on the central processing unit. The output signals (DO1 to DO6) of the digital outputs are externally available at the interface electrically isolated either via opto isolators or via relays depending on the version. T Electronic version: the output signals are generated by short-circuitresistant semiconductor switches. The switches are controlled via opto isolators. The semiconductor switches must be powered via an external voltage source since they are electrically isolated from the basic device. T Relay version: the electrical isolation is provided by relays whose changeover contacts are externally available DC 24 V Output The DC 24 V output option can be used for the following purposes: T Power supply to external transmitters T Power supply to digital input/output The DC 24 V output module is powered by the secondary winding of the transformer. The floating output is available as a bipolar terminal on the rear of the recorder. Refer to Section 8.3 for the ordering data. SIREC P, PA, L, LA Manual 2-9

28 Design and Mode of Operation PC Cable A special cable is required for connection of the recorders to a PC. The plug housing contains a module for adaptation to the recorder interface. Refer to Section 8.3 for the ordering data SIPROM R - LA/PA SIPROM R - LA/PA is a Windows desktop for recorder parameterization which permits simple and convenient operation of the devices (see Section 8.3 for ordering data) SIREC P, PA, L, LA Manual

29 Preparation for Operation 3 Preparation for Operation This chapter describes all preparations necessary for operation of the recorders. 3.1 Recorder Identification The recorders and modules can be identified with respect to their application and release version by means of various labels: T Rating plate with object version for recorder T Part No. with release version for modules Rating plate The rating plate (Fig ) provides information on: Recorder type Serial number Object version T Channel assignments (only rating plate on rear). There are three rating plates on the recorder: On the rear (e.g. Fig ), On the left inside the housing (visible after removing the chassis), T On the right side of the chassis If the input ranges are changed, a blank label can be inscribed using a waterresistant felt pen and adhered to the part of the rating plate which is no longer valid. SIREC P, PA, L, LA Manual 3-1

30 Preparation for Operation Object version The "object version" of the recorder can be read from the rating plate (Fig ). The digit marked with a cross identifies the hardware release of the recorder. SIEMENS SIREC LA Linienschreiber 7ND 3125-xxxx F-Nr. Serial-No XX-XXX No de fabr. X CHANNEL 1 xxxx 2 xxxx 3 xxxx Fig Example of rating plate for LA version Module release version The release version documents the hardware release of modules. The release version is indicated on the following relevant modules: T Central processing unit with power supply (bottom right, visible following removal of chassis) T Chassis (bottom right, visible following removal of chassis) 3-2 SIREC P, PA, L, LA Manual

31 Preparation for Operation Firmware version The release version of the firmware can be read on a label adhered to the EPROM. The release version can be read on the EPROM label following removal of the chassis. Fig Positions of EPROM and jumper for 50 / 60 Hz on module "Central processing unit" 3.2 Jumper Settings 50/60 Hz, Summer Time/Winter Time The jumpers can be set during operation. Selection of 50/60 Hz The measured values are recorded according to an integrating measuring procedure. In order to suppress interferences (hum), the measuring period (integration time) must be matched to the mains frequency. The basic setting is 50 Hz. The setting can be changed using a jumper on the module "Central processing unit" (Fig ). If the recorder is powered via a DC supply, the frequency of the surrounding AC supply must be set. The chassis must be removed from the housing in order to check or change the jumper setting (Section 6.10). Summer time/ winter time switchoff Simple switching over between summer time and winter time is possible, in addition to control via input DI4, using a jumper setting on module "Control" (visible on the rear of the removed chassis (Fig and Fig )). The factory setting is "MEZ". MEZ = central European time MESZ = central European summer time SIREC P, PA, L, LA Manual 3-3

32 Preparation for Operation 1 Ground connection for cable screen 2 DC 24 V output (option) 3 Digital input/output (option) 4 Transformer with rating plate 5 Fuse F1 6 Power supply connection (AC 230 V or AC 115 V) 6a 6b Power supply connection for DC 24 V design Power supply connection for AC 24 V design 7 Fuse F2 (only with AC 115/230 V power supply) 8 Window with channel inscription for setting of input ranges 9 Connection of channels #1 to #6 Fig Rear view of the recorders (AC 24 V design) 3-4 SIREC P, PA, L, LA Manual

33 Preparation for Operation 3.3 Installation Guidelines Insert the recorder into the prepared panel cut-out (see Fig for dimensions), insert two clamps into the corresponding positions on the housing, and tighten the screws. Special clamps must be used when fitting in a 72-mm mosaic system. The permissible ambient temperature according to the technical data must be observed at the mounting position. This must be particularly observed when installing without interspacing. Note When installing, observe the safety guidelines in Section a b R Minimum opening angle 115 for operation Panel cut-out to DIN Distance between centers of 2 adjacent instruments or one above the other 144 mm Installation in a b Sheet-steel panel Sheet-steel desk upright panel Panel or desk upright panel with basic grid dimensions 72 x 72 2 to to e-145 Fig Dimensions for installation of the recorders SIREC P, PA, L, LA Manual 3-5

34 Preparation for Operation The following information is generally applicable to installation: T No special requirements are placed on power supply, measuring and control cables which do not carry a dangerous contact potential. T Voltages which are not dangerous to contact are up to DC 50 V or AC 25 V if they are generated by safety transformers, batteries etc. and are not connected to other circuits (low-voltage networks with safe isolation). T The isolation of power cables with a dangerous contact potential must be selected according to the max. voltage. T The cross-section of the protective earth conductor must be selected at least as large as the largest cross-section of the power cable. 3.4 Mechanical Preparation of Recorder for Operation Note Only use recorders with the scales and recording system fitted. The following points refer to the mechanical preparation of the recorders, and must be carried out in the defined sequence prior to starting up: 1. Remove chart carriage (Section 6.1) 2. Insert recording system (Section 6.15 to 6.17) 3. Insert roll or fanfold pack (Section 6.7, Section 6.5) 4. Insert chart carriage (Section 6.2) 3-6 SIREC P, PA, L, LA Manual

35 Preparation for Operation 3.5 Connection of Power Supply Depending on the recorder design, the connection is for T AC 230 V or T AC 115 V or T AC 24 V or T DC 24 V. Before connecting the recorder, check that the power supply agrees with the technical data specified on the recorder (Fig ). Warning T Check that the operating voltage of the recorder agrees with the supply voltage to be connected. T The recorder may only be converted from AC 115 V to AC 230 V or vice versa by the manufacturer or personnel trained by the manufacturer! T It must be possible to separate the recorder from the power supply using the appliance plug or an easily accessible disconnecting device for at least 1.6 A. T The appropriate regulations (e.g. DIN VDE) for the installation of power systems must be observed. T The cross-section of the PE conductor must be at least as large as that of the largest cross-section of the power supply, signal or control cables. AC 230 V 50/60 Hz 25 VA F1 = F2 = T 160 L 250V Fig Power supply information on recorder (e.g.: LA version, AC 230 V design) SIREC P, PA, L, LA Manual 3-7

36 Preparation for Operation Connection to AC 230 V or AC 115 V The connection to an AC 230 V mains supply is made using the supplied appliance plug. The correct connection for AC 230 V and AC 115 V is identical and shown in Fig Warning Before connecting the appliance plug, make sure that the power supply connection is dead! L PE N Fig Connection of mains supply Connection to AC 24 V or DC 24 V The connection inscriptions depend on the recorder design. The connection must be made to the provided screw terminals according to the defined inscriptions. The cable must be secured using a grip to reduce the strain (Fig ). L N L+ L- AC 24 V connection DC 24 V connection Loop for cable detensioning Fig Cable clip Connection of AC 24 V or DC 24 V 503e SIREC P, PA, L, LA Manual

37 Preparation for Operation 3.6 Connection of Analog Channels The following types of measurement are possible for each channel: T DC U or T DC I or T TC (only recorder design with universal measuring ranges) or T RTD, R (only recorder design with universal measuring ranges) The type of measurement is set using jumpers. In order to set the jumpers, you must first remove the window for setting the input ranges (Fig ). The transparent plastic part can be easily removed by inserting a small screwdriver at the side. Ground connection for cable screen Fig Connection of analog channels (example: SIREC L/LA version with universal measuring range) Jumper positions Input ranges Measuring ranges Direct connection TC/RTD/R/Pot./U (only recorder with universal range) Fig Jumper settings ±1 V DC U 0/1 V 0.2/1 V ±1 V ±10 V DC U 0/10 V 2/10 V ±10 V ±20 ma DC I 0/20 ma 4/20 ma ±20 ma SIREC P, PA, L, LA Manual 3-9

38 Preparation for Operation Fig Basic connections for standard ranges of recorders (shown here: e.g. 3-channel line recorder) 3-10 SIREC P, PA, L, LA Manual

39 Preparation for Operation Fig Basic connections for universal ranges of recorders (shown here: e.g. multipoint recorder) SIREC P, PA, L, LA Manual 3-11

40 Preparation for Operation Labels A label with information (Fig or Fig ) on the possible connections of the analog channels is adhered on the transformer (Fig ) above the window for setting the input ranges DC U/I Fig Possible connections for analog channels in design with standard measuring ranges DC U/I The connection is made according to Fig and the jumper settings according to Fig The parameters are set according to Section DC U/I TC RTD, R Fig Label with information on the possible connections for the analog channels in design with universal measuring ranges TC Thermocouples can be connected as follows: T Directly with an internal cold junction T Indirectly with an external cold junction at constant temperature T Indirectly with an external cold junction at any temperature The basic connections are shown in the following Figs. The jumpers of the input channels are set according to Fig and the parameters according to Section SIREC P, PA, L, LA Manual

41 Preparation for Operation Direct thermocouple connection (Internal cold junction) The connections of the thermocouples or the associated equalizing conductors must be connected directly to the recorder terminals. The temperature of the terminal block (reference temperature) is measured by the recorder and compensated. The connection is made as in Fig Fig TC Thermocouple connection Indirect thermocouple connection, constant cold junction temperature (External cold junction at constant temperature) The connections of the thermocouple are connected via a cold junction, e.g. thermostat. The temperature of the cold junction must be parameterized. The cables between the external cold junction and the recorder terminals can be made using any conductors with the same material (usually Cu). The connection is made according to Fig TC Fig Thermocouple connection to external cold junction at constant temperature SIREC P, PA, L, LA Manual 3-13

42 Preparation for Operation Indirect thermocouple connection, variable cold junction temperature (External cold junction at variable temperature) The connections of the thermocouple are connected via a cold junction at any temperature. The temperature of the cold junction must be measured using another channel and is calculated internally. Thermocouples as well as resistance thermometers are possible for recording the cold junction temperature. The connection is made according to Fig ϑ TC Fig TC RTD Thermocouple connection to external cold junction at any temperature RTD, R Thermoelectric resistors as well as standard resistors can be connected as follows: T Two-wire measurement T Three-wire measurement Two-wire measurement of thermoelectric resistance and standard resistance This type of connection is preferably selected for a short distance between the sensor and the recorder. It is necessary to either select the cables with such a low resistance that an error in measurement does not occur (Fig ), or they must be adjusted to 10 Ω (Fig ) ϑ Fig RTD, R Two-wire system without additional line compensation R A R L1 Fig R L2 ϑ R L1 + R L2 + R A = 10 RTD, R Two-wire connection with line compensation (R A ) to 10 Ω SIREC P, PA, L, LA Manual

43 Preparation for Operation Three-wire measurement of thermoelectric resistance and standard resistance This type of connection presupposes that the resistances of the cables between the sensor and terminals 12 and 13 on the recorder are of equal magnitude. The connection is made according to Fig ϑ Fig RTD, R Three-wire system Three-wire measurement of potentiometers The resistances of the three cables between the sensor and the recorder must also be of equal magnitude with this measurement. The setting is made according to the Section Two methods are basically possible. 1. The cables have such a low resistance that no errors in measurement occur Fig % 0% R Connection for potentiometer measurement The total of the full-range resistance of the potentiometer and the cable resistance is adjusted to 10 Ω using additional external line compensation R A3 R A2 R L3 Fig : R L1 R L2 R L2 + R A2 = 10 R L3 + R A3 = 10 R Connection for potentiometer measurement with additional line compensation (RA 2, RA 3 ) to 10 Ω 100% 0% SIREC P, PA, L, LA Manual 3-15

44 Preparation for Operation 3.7 Digital Input/Output A 25-pin subminiature plug (Fig and Fig ) is present on the rear of the recorder for the option "Digital input/output". See Section for technical details. A 25-pin subminiature plug for connection of the digital input/output is included in the delivery. The pin assignments are shown in Table and Table Parameterization of the digital input/output is described in Section Table Pin assignments "Digital input/output" (DI1 to DI4) Plug pin Input Parameterizable functions Remarks 24 Input DI1 Measuring mode normal on/off Measuring mode fast on/off Measured-value table 1) Event text 1) Digital channel 1) Low off, High on Low off, High on Edge following High output Edge following High output Recording of time characteristic 12 Input DI2 Chart feed A on Chart feed B on Measured-value table 1) Event text 1) Digital channel 1) 25 Input DI3 Measured-value table 1) Event text 1) Digital channel 1) Event marking 2) 13 Input DI4 Control input for - Chart feed 10 mm to 100 mm - Time mark - Clock synchronization 3:00 - Summer time (MESZ) - TEST locking Measured-value table 1) Event text 1) Digital channel 1) 11 Reference potential 0 V (DI) 1) Only recorders with alphanumeric text 2) Only without alphanumeric text 3) Max. two channels Edge following High on Edge following High on, only if condition for A is not fulfilled Edge following High output Edge following High output Recording of time characteristic 2) Edge following High output Edge following High output Recording of time characteristic 3) Edge following High acc. to feed Edge following High zero adj. Edge following High synchronization Low MEZ, High MESZ Low on, High off Edge following High output Edge following High output Recording of time characteristic 2) 3-16 SIREC P, PA, L, LA Manual

45 Preparation for Operation Table Plug pin Pin assignments "Digital input/output" (DO1 to DO6) Assignments for Assignments for electronic version relay version Output DO1: NO contact Common point NC contact Output DO1 - - Output DO2 - - Output DO3 - - Output DO4 - - Output DO5 - - Output DO Ext. power supply 24 V (DO) - 1 Ext. power supply 0 V (DO) - Output DO2: NO contact Common point NC contact Output DO3: NO contact Common point NC contact Output DO4: NO contact Common point NC contact Output DO5: NO contact Common point NC contact Output DO6: NO contact Common point NC contact Synchronization of several recorders In the case of the electronic version, the semiconductor switches separated from the basic electronics by opto-isolators must be powered from an external 24-V source. If the recorder is equipped with a DC 24 V output (option), this voltage source can be used as an alternative, taking into account the technical data (Fig ). The recorder can synchronize the internal calendar/clock of several devices as slaves using a digital input/output. To achieve synchronization, any output of the digital input/output can be used on the master, and the input DI4 on the slave. Parameterization is described in Section SIREC P, PA, L, LA Manual 3-17

46 Preparation for Operation Elektronic version Relay version Fig Connection of digital input/output 3-18 SIREC P, PA, L, LA Manual

47 Preparation for Operation Fig Example of connection for digital input/output Explanations on Fig : The example shows two recorders with the digital input/output option. The digital input/output of the top recorder is powered by its own DC 24 V option output. The internal calendar/clock is synchronized for the two recorders. The required synchronization signal is provided via input DI4 by e.g. a master clock. The clocks of both recorders are set to 3:00 a.m. when the positive edge of the 24-V pulse arrives. The date remains unchanged. In addition to this, the digital output DO1 (alarm) of the top recorder triggers a lamp. SIREC P, PA, L, LA Manual 3-19

48 Preparation for Operation 3.8 DC 24 V Output Following installation of the option "DC 24 V output" by the manufacturer or by personnel trained by the manufacturer, a bipolar terminal (Fig ) is available at the rear of the recorder with a floating output for the supply of external components. The following connections are permissible since the current output is limited to max. 75 ma: T Up to three two-wire transmitters with a current consumption of 25 ma each T Digital input/output Note If several two-wire transmitters are powered, these must be connected together on one side and are thus not electrically isolated from one another. For noise reasons (differences in potential), this arrangement is only meaningful for transmitters which are close together. When additionally using the digital input/output, observe whether switching transients occur, and their effect. Fig Example of connection for two-wire transmitter to the DC 24 V output option (L version, DC 24 V design) 3-20 SIREC P, PA, L, LA Manual

49 Preparation for Operation 3.9 Starting Up the Recorder All recorder settings have already being made in the factory if the recorder has been delivered according to customer specifications. The standard settings have been made for recorders delivered without customer specifications. The standard settings are listed in Section 4 "Operation" in the respective subsections. If you are not acquainted with the recorder, it is recommendable to start with simple measurements after working through Sections 1 to 4. Measurements with the standard settings are most appropriate initially. SIREC P, PA, L, LA Manual 3-21

50 Preparation for Operation 3-22 SIREC P, PA, L, LA Manual

51 Operation 4 Operation The following chapter describes how to operate the recorders. Note Replacing the chart and the battery for backing up the clock are described in Section 6. You are guided by menus when operating the recorders. The menus provide information in the form of a table on the respective functions or values for an input (leaflet "Parameterization a concise overview"). The input menus consist of several elements which are comprised in turn of menu code numbers and designations. In the first input step (selection of row) you decide which function or parameter is to be called. The red LED lights up. In the second step (selection of column) you can define or modify the corresponding setting of the recorder. The red LED flashes. The input of a menu code number is terminated by ENTER. You can scroll through the menu using the INC/DEC functions. 4.1 Display and Control Elements Operation is carried out using four horizontal levers located below the chart carriage (Fig ). A further lever is present on the side of the chassis. Two colored LEDs which are also located below the chart carriage serve to support you when setting up the recorders and for the output of status messages. In recorders with alphanumeric text, status messages are additionally printed on the chart paper by means of the text channel (LA version) or the recording head (PA version) (Section 5). The PC interface, which is designed as a flat plug, is located between the service lever and lever 1. It is possible to connect a laptop to this plug in order to carry out PC-controlled parameterization. SIREC P, PA, L, LA Manual 4-1

52 Operation 1 Scale, channel 3 7 Lever 2 13 Scale for P/PA 2 Pen, channel 1 8 LED, red 14 Recording head 3 Pen, channel 2 9 Lever 1 15 Parameterization 4 Pen, channel 3 10 PC interface scale 5 Lever 3 11 Service lever 6 LED, green 12 Parameterization scale Fig Display and control elements at front 4-2 SIREC P, PA, L, LA Manual

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS SINAMICS G130 / G150 Line harmonics filter Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 / G150 Operating Instructions Mechanical installation 3 Electrical

More information

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics Operating Instructions 07/2007 Edition SINAMICS G130/G150 Line harmonics filter sinamics s Safety information 1 General 2 SINAMICS SINAMICS G130/G150 Operating Instructions Mechanical installation 3 Electrical

More information

Trusted 40 Channel 120 Vac Digital Input FTA

Trusted 40 Channel 120 Vac Digital Input FTA PD-T8824 Trusted Trusted 40 Channel 120 Vac Digital Input FTA Product Overview The Trusted 40 Channel 120 Vac Digital Input Field Termination Assembly (FTA) T8824 is designed to act as the main interface

More information

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130 Operating Manual (Edition 04/2004) sinamics Line Reactors SINAMICS G130 Contents 1. Safety Information 2 2. General 5 3. Mechanical Installation 6 4. Electrical Installation 8 5. Technical Specifications

More information

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS

SINAMICS G130. dv/dt filter plus Voltage Peak Limiter. Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s dv/dt filter plus Voltage Peak Limiter Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Electrical

More information

MICROMASTER Encoder Module

MICROMASTER Encoder Module MICROMASTER Encoder Module Operating Instructions Issue 01/02 User Documentation Foreword Issue 01/02 1 Foreword Qualified Personnel For the purpose of this Instruction Manual and product labels, a Qualified

More information

Trusted 40 Channel 120 Vac Digital Input FTA

Trusted 40 Channel 120 Vac Digital Input FTA ICSTT-RM290F-EN-P (PD-T8824) Trusted Product Overview The Trusted 40 Channel 120 Vac Digital Input Field Termination Assembly (FTA) T8824 is designed to act as the main interface between a field device

More information

Electronic MICROSTAT-T Temperature controller with digital indication for use with resistance thermometers and thermocouples Series 8650

Electronic MICROSTAT-T Temperature controller with digital indication for use with resistance thermometers and thermocouples Series 8650 M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.de

More information

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500

Industriefunkuhren. Technical Manual. IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C / AFNOR NF S87-500 Industriefunkuhren Technical Manual IRIG-B Generator-Module for analogue / digital Signals of Type: IRIG-B / IEEE C37.118 / AFNOR NF S87-500 Module 7628 ENGLISH Version: 02.01-06.03.2013 2 / 20 7628 IRIG-B

More information

Trusted 40 Channel Analogue Input FTA

Trusted 40 Channel Analogue Input FTA PD-T8830 Trusted Trusted 40 Channel Analogue Input FTA Product Overview The Trusted 40 Channel Analogue Input Field Termination Assembly (FTA) T8830 is designed to act as the main interface between a field

More information

Flat-Bed Module Recorders

Flat-Bed Module Recorders Flat-Bed Module Recorders Model No. 08376-50 08376-55 08376-60 0115-0192 4/28/00 Table of Contents Introduction...3 Power Requirements...3 Chart Paper Installation...3 Pen Installation...5 Grounding...5

More information

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated)

R1MS-GH3 BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL THERMOCOUPLE & DC INPUT MODULE MODEL. (8 points; isolated) INSTRUCTION MANUAL THERMOCOUPLE & INPUT MODULE (8 points; isolated) MODEL BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.

More information

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE

FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE FX-4AD-TC SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D55901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-4AD-TC special

More information

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4

UDC100 Universal Digital Controller. Specification. Overview. Features. Features, continued /99 Page 1 of 4 UDC100 Universal Digital Controller 51-52-03-29 11/99 Page 1 of 4 Specification Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area

Guide for installers. METTLER TOLEDO MultiRange System solution analog Ex1. Hazardous area. Safe area Guide for installers METTLER TOLEDO MultiRange System solution analog Ex1 Hazardous area Safe area System solution analog Ex1 Contents Contents Page 1 Safety precautions... 2 2 System overview... 3 2.1

More information

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency,

Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency, Electronic Panel Meters DIGEM Preference Program Process control, automation & laboratory uses Class 0.01 to 1 Current, Voltage, Frequency, Temperature, RPM, Pressure, etc. LED/ LCD displays 1999 to 99999

More information

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE

INTRODUCTION TERMINAL LAYOUTS FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE FX2N-4AD-TC SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65501A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4AD-TC

More information

I R T Electronics Pty Ltd A.B.N. 35 000 832 575 26 Hotham Parade, ARTARMON N.S.W. 2064 AUSTRALIA National: Phone: (02) 9439 3744 Fax: (02) 9439 7439 International: +61 2 9439 3744 +61 2 9439 7439 Email:

More information

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL

ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL UM-TS02 -E026 PROGRAMMABLE CONTROLLER PROSEC T2-series ANALOG I/O MODULES AD268 / DA264 / TC218 USER S MANUAL TOSHIBA CORPORATION Important Information Misuse of this equipment can result in property damage

More information

High Resolution Multicolor Contrast Scanner. Dimensioned drawing

High Resolution Multicolor Contrast Scanner. Dimensioned drawing Specifications and description KRTM 20 High Resolution Multicolor Contrast Scanner Dimensioned drawing en 01-2011/06 50116669 12mm 20mm 50mm 12-30 V DC 50 / 25 khz We reserve the right to make changes

More information

(1) (2) (3) Bedienungs- und Montageanleitung. Safety instructions. Structure of the device

(1) (2) (3) Bedienungs- und Montageanleitung. Safety instructions. Structure of the device 3 x cinch/s-video socket Order no. 33 1532 xx USB/3.5 mm audio socket Order no. 33 1539 xx VGA socket Order no. 33 1540 xx VGA socket with screw-in lift terminals Order no. 33 1541 xx High definition socket

More information

Owner s Manual. multiswitch Firmware-Version 1.06 OS- Version 1.02

Owner s Manual. multiswitch Firmware-Version 1.06 OS- Version 1.02 Owner s Manual multiswitch 1.41 Firmware-Version 1.06 OS- Version 1.02 The information contained in this manual is subject to change without prior notice. All rights reserved. Current as of: Juli 19 th

More information

SIMATIC. ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Preface. Properties 1. Parameters 2. Error and system messages 3

SIMATIC. ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Preface. Properties 1. Parameters 2. Error and system messages 3 Preface SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O IM151-1 BASIC interface module (6ES7151-1CA00-0AB0) Properties 1 Parameters 2 Error and system messages 3 Response times 4 Manual

More information

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5.

User Guide UD51. Second encoder small option module for Unidrive. Part Number: Issue Number: 5. EF User Guide UD51 Second encoder small option module for Unidrive Part Number: 0460-0084-05 Issue Number: 5 www.controltechniques.com Safety Information The option card and its associated drive are intended

More information

Litile34 OPERATION MANUAL

Litile34 OPERATION MANUAL Litile34 OPERATION MANUAL Seamless Tiled Panel Wall Solution for Large Area Digital Signage Display (1st Edition 3/25/2009) All information is subject to change without notice. Approved by Checked by Prepared

More information

REGO Start&Go USER MANUAL

REGO Start&Go USER MANUAL REGO Start&Go USER MANUAL Version 0 Rev. B of 03/03/16 Page 1 of 15 Introduction The purpose of the manual is to describe all of the steps required to commission and correctly operate the REGO Start&Go

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Rooftop Energy Recovery Module for TKD / TKH / WKD / WKH YKD / YKH / DKD / DKH # 125-155-175-200 250 265-290-340 # 275-300-350-400-500-600 April 2011 RT-SVX42B-E4 General

More information

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV

MG-XV operating instruction. Measuring of norm signals, 4-8-digit. Panel instrument type MG-BV Construction instrument type MG-AV MG-XV operating instruction Measuring of norm signals, 4-8-digit Panel instrument type MG-BV Construction instrument type MG-AV Contents 1. Brief description... 3 2. Safety instructions... 3 2.1. Proper

More information

Installation Manual IPT Installation of skillet systems with 125 A track current. MV a-E.

Installation Manual IPT Installation of skillet systems with 125 A track current. MV a-E. www.wampfler.com Page 1 of 27 Index Page 1 Basics...4 2 Basic understanding of an IPT -system...5 3 General rules regarding metal parts in close proximity...6 3.1 Envelope free of ferromagnetic material...6

More information

NewScope-7A Operating Manual

NewScope-7A Operating Manual 2016 SIMMCONN Labs, LLC All rights reserved NewScope-7A Operating Manual Preliminary May 13, 2017 NewScope-7A Operating Manual 1 Introduction... 3 1.1 Kit compatibility... 3 2 Initial Inspection... 3 3

More information

4 Wiring Brochure Wiring and installation of specific control

4 Wiring Brochure Wiring and installation of specific control - Wiring Brochure tekmarnet 4 User Switch 480 W 480 09/09 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in

More information

Model 1421 Distribution Amplifier

Model 1421 Distribution Amplifier Model 1421 Distribution Amplifier Installation and Operating Instructions The 1421 Distribution Amplifier provides four independent, wide bandwidth outputs from one video input. The unit is color compatible

More information

Model Number Structure

Model Number Structure Cycle Control Units CSM DS_E_7_1 Refer to Safety Precautions for All Power Controllers. Used in Combination with the to Enable High-precision Temperature Control Use cycle control to achieve power control

More information

Product information. Front-door station series with video for surface-mount

Product information. Front-door station series with video for surface-mount Product information Front-door station series with video for surface-mount series VPES series VPDS 2 05/2006 Table of contents Scope of delivery...3 Safety notices...3 General notes on the cabling in TCS

More information

EGM Einthoven Goldberger Module Type 701

EGM Einthoven Goldberger Module Type 701 Operating Instructions for the PLUGSYS Module EGM Einthoven Goldberger Module Type 701 ECG amplifier for bipolar extremity leads after Einthoven and unipolar extremity leads after Goldberger (Version:

More information

Model: S-4904T/R. Wireless HD Transmission System. User Manual. Please read this User Manual throughout before using.

Model: S-4904T/R. Wireless HD Transmission System. User Manual. Please read this User Manual throughout before using. Model: S-4904T/R Wireless HD Transmission System User Manual Please read this User Manual throughout before using. Preface Congratulations on your purchase of this product. Please read this user manual

More information

Technical data. General specifications. Indicators/operating means

Technical data. General specifications. Indicators/operating means Model Number Single head system Features Sensor head bidirectional and rotatable Function indicators visible from all directions Quick mounting bracket Selectable sound lobe width Programmable Diagrams

More information

SQM40/41 Actuators for air and gas dampers

SQM40/41 Actuators for air and gas dampers SQM40/41 Actuators for air and gas dampers Description SQM40/41 actuators are used for the positioning of flow control valves, butterfly valves, dampers or any application requiring rotary motion. The

More information

ACTIVE IF SPLITTER/COMBINER UHP-IFS

ACTIVE IF SPLITTER/COMBINER UHP-IFS ACTIVE IF SPLITTER/COMBINER UHP-IFS GENERAL DESCRIPTION AND INSTALLATION GUIDE DOCUMENT RELEASE 2 [UHP.IFS.2.EN] JUNE 2016 CONTENT Acronyms and Abbreviations... 4 Introduction... 5 Required level of qualification...

More information

Hybrid Chart Recorder 250 mm (10")

Hybrid Chart Recorder 250 mm (10) Hybrid Chart Recorder 250 mm (10") RD5100 Series U High Speed Scanning at 36 Points/Sec and High-Speed Recording U High Accuracy of 0.05% U Various Industrial Values Can be Measured at the Same Time with

More information

Trusted TMR I/O SmartSlot Slot Cables

Trusted TMR I/O SmartSlot Slot Cables PD-TC500 Trusted Trusted TMR I/O SmartSlot Slot Cables Product Overview This document provides detailed information for the types of Trusted input/output (I/O) Cables available within the SmartSlot group.

More information

OPERATING MANUAL. DMX / DSI / DALI Dekoder 3004B-H Mk2

OPERATING MANUAL. DMX / DSI / DALI Dekoder 3004B-H Mk2 OPERATING MANUAL DMX / DSI / DALI Dekoder 3004B-H Mk2 (C) SOUNDLIGHT 1996-2004 * ALL RIGHTS RESERVED * NO PART OF THIS MANUAL MAY BE REPRODUCED, DUPLICATED OR USED COMMERCIALLY WITHOUT THE PRIOR WRITTEN

More information

Function Manual SIMATIC HMI TP900. Operator Panel.

Function Manual SIMATIC HMI TP900. Operator Panel. Function Manual SIMATIC HMI TP900 Operator Panel Edition 10/2016 www.siemens.com Introduction 1 Safety notes 2 Medium-voltage converters SIMATIC Description 3 Screens 4 Installing software 5 Function

More information

ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL

ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL SPECIFICATIONS MODEL NUMBER: XRT910-0-0-GB-XX XRT911-0-0-GB-XX XTT911-0-0-NN-XX IMPROX TRT ImproX (TRT) Twin Remote Terminal INSTALLATION MANUAL Working Environment XRT910-0-0-GB-XX... (Aluminium Extruded

More information

Gamma instabus. Technical product information

Gamma instabus. Technical product information Gamma instabus Technical product information Universal dimmer N 554D31, 4 x 300 VA / 1x 1000 VA, AC 230 V Universal dimmer N 554D31 Control of dimmable lamps, including LED without minimum load Output

More information

TABLE OF CONTENTS. Instructions:

TABLE OF CONTENTS. Instructions: TABLE OF CONTENTS Instructions: 1 Overview 1 2 Main technical parameters 1 3 Display and keyboard 2 3.1 Display Window 2 3.2 Indicator 4 4. Operation 4 4.1 Power 4 4.2 Zero 4 Modified 4 4.3 Modified 4

More information

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function.

Triple RTD. On-board Digital Signal Processor. Linearization RTDs 20 Hz averaged outputs 16-bit precision comparator function. Triple RTD SMART INPUT MODULE State-of-the-art Electromagnetic Noise Suppression Circuitry. Ensures signal integrity even in harsh EMC environments. On-board Digital Signal Processor. Linearization RTDs

More information

Sensor module. Safety instructions. Function Correct use. Product characteristics. Structure of the device. Operation. Ref.No.

Sensor module. Safety instructions. Function Correct use. Product characteristics. Structure of the device. Operation. Ref.No. Sensor module Ref.No.: SM 1608 V03 Safety instructions Caution! Electrical devices may only be installed and fitted by electrically skilled persons. Non-compliance with the installation information could

More information

LWC Series LWC-80. Design. LWC Series Laser Wire Counters. Product name: Accessories: LWC-80

LWC Series LWC-80. Design. LWC Series Laser Wire Counters. Product name: Accessories: LWC-80 LWC Series LWC-80 Laser Wire Counting - Insensitive to outside light (due to interference filter, modulated light) - Visible laser spot (red light 670 nm) - Parameterisable through integrated switch and

More information

SPX-5600 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface SPX-5600MAN. Page 1 of 20

SPX-5600 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface SPX-5600MAN. Page 1 of 20 SPX-5600 Series Operations Manual Suprex Reader Extender - RF Wireless Interface SPX-5600MAN Page 1 of 20 SPX-5600 Series: Cypress Suprex SPX-5600 Series This manual covers the operation and setup of the

More information

Capacitance Limit Detection nivotester FTC 420/421/422

Capacitance Limit Detection nivotester FTC 420/421/422 Technical Information TI 127F/00/en Capacitance Limit Detection nivotester FTC 420/421/422 Limit switches in Minipac design for liquids and bulk solids Application Nivotester FTC 420...422 capacitive limit

More information

Industrial Monitor Update Kit

Industrial Monitor Update Kit Industrial Monitor Update Kit (Bulletin Number 6157) Installation Instructions 2 Table of Contents Table of Contents Industrial Monitor Update Kit... 3 Overview... 3 Part 1 - Initial Preparation... 5 Part

More information

O P E R A T I O N M A N U A L. RF-Reader. Stand-alone-Reader Leser 2plus with RS-232 interface

O P E R A T I O N M A N U A L. RF-Reader. Stand-alone-Reader Leser 2plus with RS-232 interface O P E R A T I O N M A N U A L Version 01/05 RF-Reader Stand-alone-Reader Leser 2plus with RS-232 interface Important! Read by all means! To maintain the perfect shipping conditions and to ensure safe operation

More information

DLP200M 2 Relay Module for Heating and Cooling Plants

DLP200M 2 Relay Module for Heating and Cooling Plants Product Sheet TH6.24 Thermostat Type DLP200M DLP200M 2 Relay Module for Heating and Cooling Plants The DLP 200 M is a relay module for activation of loads (namely thermal actuators or circulators) in wireless

More information

Operating Instructions Dimmer for V Incandescent Lamps

Operating Instructions Dimmer for V Incandescent Lamps Operating Instructions Incandescent Lamps 1. Safety instructions Attention: Electrical equipment must be installed and fitted only by qualified electricians and in observance of the current accident prevention

More information

Signal Conditioners. Highlights. Battery powered. Line powered. Multi-purpose. Modular-style. Multi-channel. Charge & impedance converters

Signal Conditioners. Highlights. Battery powered. Line powered. Multi-purpose. Modular-style. Multi-channel. Charge & impedance converters Signal Conditioners Highlights Battery powered Line powered Multi-purpose Modular-style Multi-channel Charge & impedance converters Industrial charge amplifiers & sensor simulators PCB Piezotronics, Inc.

More information

4-PROJECTOR BAR WITH 3 X 9W LEDS AND 1 X 1W FLASH LED USER GUIDE

4-PROJECTOR BAR WITH 3 X 9W LEDS AND 1 X 1W FLASH LED USER GUIDE 4-PROJECTOR BAR WITH 3 X 9W LEDS AND 1 X 1W FLASH LED USER GUIDE 10482 - Version 1 / 04-2016 English LIVESET - LIVESET - 4-Projector bar with 3 x 9W LEDs and 1 x 1W Flash LED 1 - Safety information Important

More information

P XGA TFT Monitor. User s Manual

P XGA TFT Monitor. User s Manual P6151 15 XGA TFT Monitor User s Manual Disclaimers This manual has been carefully checked and believed to contain accurate information. Axiomtek Co., Ltd. assumes no responsibility for any infringements

More information

ALO 030 MKII. 30 Watt DMX LED scanner. User manual

ALO 030 MKII. 30 Watt DMX LED scanner. User manual ALO 030 MKII 30 Watt DMX LED scanner User manual Safety instructions WARNING! Always keep this device away from moisture and rain! Hazardous electrical shocks may occur! WARNING! Only connect this device

More information

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15 > 8 channels for 2-wire HART transmitters > Inputs for Ex nl, Ex na and Nonincendive > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit >

More information

IRT Eurocard. Type RWA RF Distribution Amplifier for 70 MHz IF signals

IRT Eurocard. Type RWA RF Distribution Amplifier for 70 MHz IF signals I R T Electronics Pty Ltd A.B.N. 5 000 8 575 6 Hotham Parade, ARTARMON N.S.W. 064 AUSTRALIA National: Phone: (0) 949 744 Fax: (0) 949 749 International: +6 949 744 +6 949 749 Email: sales@irtelectronics.com

More information

Kramer Electronics, Ltd. USER MANUAL. Model: VM Video Component Distributor

Kramer Electronics, Ltd. USER MANUAL. Model: VM Video Component Distributor Kramer Electronics, Ltd. USER MANUAL Model: VM-1045 Video Component Distributor Contents Contents 1 Introduction 1 2 Getting Started 1 2.1 Quick Start 1 3 Overview 3 4 Your VM-1045 Video Component Distributor

More information

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D52801C This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-2DA special

More information

CARLO GAVAZZI Automation Components

CARLO GAVAZZI Automation Components CARLO GAVAZZI Automation Components UDM 35/40 Digital Panel Meter Programming Guide Index Description 2 Programming Fundamentals 3 Access to Programming Mode/Password Protection 4 Programming 5-18 Inputs

More information

Documentation. Magnetic Encoder System (MES) Version: Date:

Documentation. Magnetic Encoder System (MES) Version: Date: Documentation Magnetic Encoder System (MES) Version: Date: 1.1 2016-02-26 Table of content Table of content 1 Foreword... 4 1.1 Notes on the documentation... 4 1.2 Intended use... 5 1.3 Documentation

More information

Electrical connection

Electrical connection (I)GSU 14C Ultrasonic Label Fork Dimensioned drawing en 06-2011/12 50109234-01 4mm 12-30 V DC 4 m/s We reserve the right to make changes DS_IGSU_14C_en.fm Ultrasonic forked sensor for universal application

More information

SIMOREG DC Master. Application SIMOREG 1Q-device, braking to defined speed using reversing. 6RA70 Series

SIMOREG DC Master. Application SIMOREG 1Q-device, braking to defined speed using reversing. 6RA70 Series SIMOREG DC Master 6RA7 Series Application SIMOREG Q-device, braking to defined speed using reversing Microprocessor-ased Converters from 6kW to 9kW for Variable-Speed DC Drives Edition Edition 2 NOTE This

More information

Operating instructions Retro-reflective sensor. OJ50xx laser / / 2010

Operating instructions Retro-reflective sensor. OJ50xx laser / / 2010 Operating instructions Retro-reflective sensor OJ50xx laser 70481 / 00 05 / 010 Contents 1 Preliminary note3 1.1 Symbols used 3 Safety instructions 3 4 Installation 4 4.1 Installation of the supplied mounting

More information

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH

Industriefunkuhren. Technical Manual. OEM Sync-Module FE1000 (IRIG-B) ENGLISH Industriefunkuhren Technical Manual OEM Sync-Module FE1000 (IRIG-B) ENGLISH Version: 07.02-24.03.2014 2 / 19 FE1000 IRIG-B Synchronisation - V07.02 IMPORTANT NOTES Version Number (Firmware / Manual) THE

More information

Spare Parts, Accessories, Consumable Material for Older Design Recorders

Spare Parts, Accessories, Consumable Material for Older Design Recorders Spare Parts, Accessories, Consumable Material for Older Design Recorders 4/2 Summary 4/2 Accessories for multipoint and line recorders SIREC 2010 4/2 Accessories for hybrid recorders VARIOGRAPH 4/2 Accessories

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process, Strain & Potentiometer Follower Signals Features Selectable ±0.2, ±2, ±20, ±200, ±300 & ±600 Vdc voltage ranges Selectable ±2, ±20, ±200

More information

USER S MANUAL. FX2N-8AD Analog input block

USER S MANUAL. FX2N-8AD Analog input block USER S MANUAL FX2N-8AD Analog input block FX2N-8AD Analog input block Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation

More information

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter

AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter Broadcast Devices, Inc. AES-402 Automatic Digital Audio Switcher/DA/Digital to Analog Converter Technical Reference Manual Broadcast Devices, Inc. Tel. (914) 737-5032 Fax. (914) 736-6916 World Wide Web:

More information

KACO-display. Wireless Solar Monitoring System. Operating Instructions KACO-display. full of energy...

KACO-display. Wireless Solar Monitoring System. Operating Instructions KACO-display. full of energy... Wireless Solar Monitoring System. Operating Instructions KACO-display full of energy... KACO-display provides high-technology monitoring of your valuable photovoltaic installation. It shows the desired

More information

Six-Channel TDM Multiplexers for 3G, HD, SDI, and ASI. Installation and Operations. Manual

Six-Channel TDM Multiplexers for 3G, HD, SDI, and ASI. Installation and Operations. Manual Manual DigiLink DLC156 Function modules Six-Channel TDM Multiplexers for 3G, HD, SDI, and ASI Installation and Operations Manual WWW.ARTEL.COM ii DLC156 Function Modules Installation and Operations Manual

More information

SCALE & WEIGHT DISPLAYS

SCALE & WEIGHT DISPLAYS The MICRO SERIES SCALE & WEIGHT DISPLAYS LARGE DIGIT MODELS Mighty-5S DPM MODELS Micro-S & Mighty-1S Mighty-1S Micro-S ELECTRO-NUMERICS, INC. Introduction The Electro-Numerics family of Digital Panel Meters

More information

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT

User Manual CC DC 24 V 5A. Universal Control Unit UC-1-E. General Information SET. Universal Control Unit UC-1 Of Central Lubrication PAUSE CONTACT Universal Control Unit UC-1-E User Manual General Information Universal Control Unit UC-1 Of Central Lubrication CC DC 24 V 5A / M 15 SL /MK 31 M Z 30 General Information Contents Universal Control Unit

More information

Panel cutout required: 1.772" x 3.622" (45mm x 92mm) 1.76" (45mm) 2.45" (62mm) 3.20" (81mm) 3.60" (91mm) 0.59" (15mm) Special Features

Panel cutout required: 1.772 x 3.622 (45mm x 92mm) 1.76 (45mm) 2.45 (62mm) 3.20 (81mm) 3.60 (91mm) 0.59 (15mm) Special Features NEMA4X, IP65 Front Bezel Meter with Relays Option RELAY2 RELAY1 24V OUT POWER 4 3 2 1 6 5 2 1 2 1 NO NC COM NO NC COM RTD TC P P RTD 3 4 1 2 5 TC 6 SWITCH Rear View Gasket APM765 Panel Meter Description

More information

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/ > 8 channels for 2-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit > Module

More information

Process transmitter RMA422

Process transmitter RMA422 Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set

More information

CardModule. Reference Manual. Series C DA Channel SDI to CVBS Converter. Version 1.0

CardModule. Reference Manual. Series C DA Channel SDI to CVBS Converter. Version 1.0 Reference Manual C DA 5005 5 Channel SDI to CVBS Converter Version 1.0 Series 5000 CardModule LYNX Technik AG Brunnenweg 3 D-64331 Weiterstadt Germany www.lynx-technik.com Information in this document

More information

INSTALLATION INSTRUCTIONS FOR

INSTALLATION INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR MODEL 2240LED www.sportablescoreboards.com 1 Table of Contents 8 X 7 INDOOR SCOREBOARD... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:... 3 INSTRUCTIONS FOR

More information

CONTACT-DUO-PROFILE. Contact-Duo-Profile overview

CONTACT-DUO-PROFILE. Contact-Duo-Profile overview 13 6.3 13 6.3 4.7 20.7 24.6 +1/-0 24.6 +1/-0 2.5 24.6 +1/-0 20.7 4.3 +0.3-0.4 3.6 ±0.3 32.5 32.5 32.5 5 2 CONTACT-DUO-PROFILE Contact-Duo-Profile overview 13 6.3 13 6.3 4.7 2.5 16±0.8 4.7 2.5 4.7 2.5 2.6

More information

Simply clever! The digital DIN-rail time switches by Grässlin

Simply clever! The digital DIN-rail time switches by Grässlin Simply clever! The digital DIN-rail time switches by Grässlin talento pro Trends and developments on the market. Maximum energy efficiency at low efforts In a saturated fast-moving market, the trend towards

More information

Assembly. Front view. LEDs. Parametrization interface. Power Bus

Assembly. Front view. LEDs. Parametrization interface. Power Bus otation Speed Monitor Features Assembly 1-channel signal conditioner 2 V DC supply Input for 2- or -wire sensors Input frequency 10 mhz... 50 khz elay contact output Start-up override and restart inhibit

More information

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel 1993 Specifications CSJ 0924-06-223 SPECIAL SPECIFICATION 1160 8:1 Video (De) Mux with Data Channel 1. Description. This Item shall govern for furnishing and installing an 8 channel digital multiplexed

More information

Quick Operation Guide of LTN7700/7600 Series NVR

Quick Operation Guide of LTN7700/7600 Series NVR Quick Operation Guide of LTN7700/7600 Series NVR UD.6L0202B0042A02 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable

More information

INSTALLATION INSTRUCTIONS FOR. MODEL 2230LED

INSTALLATION INSTRUCTIONS FOR. MODEL 2230LED INSTALLATION INSTRUCTIONS FOR MODEL 2230LED www.sportablescoreboards.com 1 Table of Contents MODEL 2230LED... 3 8 X 4 INDOOR SCOREBOARD... 3 THE SCOREBOARD SYSTEM SHOULD INCLUDE THE FOLLOWING PARTS:...

More information

Radio receiver EXL. 4-channel / up to 1000 memory locations. Mounting and operating instructions for qualified electricians

Radio receiver EXL. 4-channel / up to 1000 memory locations. Mounting and operating instructions for qualified electricians Radio receiver EXL 4-channel / up to 1000 memory locations Mounting and operating instructions for qualified electricians Please keep these instructions so that you have them available if you have any

More information

COHERENCE ONE PREAMPLIFIER

COHERENCE ONE PREAMPLIFIER COHERENCE ONE PREAMPLIFIER OWNER S MANUAL TABLE OF CONTENTS Introduction Features Unpacking Instructions Installation Phono Cartridge Loading Basic Troubleshooting Technical Specifications Introduction

More information

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module

Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach

More information

User Manual. Model 1372A and 1374A HDMI Switchers. 1T-SX-632 Model 1372A 2X1 Switcher. v1.3 2x1 SWITCHER. v1.3 INPUT ENHANCE POWER

User Manual. Model 1372A and 1374A HDMI Switchers. 1T-SX-632 Model 1372A 2X1 Switcher. v1.3 2x1 SWITCHER. v1.3 INPUT ENHANCE POWER User Manual 1T-SX-632 Model 1372A 2X1 Switcher v1.3 v1.3 2x1 SWITCHER 1 2 INPUT ENHANCE POWER 1 2 INPUT ENHANCE POWER Model 1372A and 1374A HDMI Switchers Table Of Contents 1.0 Introduction.......................

More information

Electrical connection

Electrical connection Splice sensor Dimensioned drawing en 04-2014/06 50116166-01 4mm 12-30 V DC We reserve the right to make changes DS_IGSU14CSD_en_50116166_01.fm Reliable detection of splice on paper web or plastic web With

More information

SIWAREX FTA Weighing Module for High Accuracy Requirements Calibrating SIWAREX FTA with SIWATOOL FTA

SIWAREX FTA Weighing Module for High Accuracy Requirements Calibrating SIWAREX FTA with SIWATOOL FTA SIWAREX FTA Weighing Module for High Accuracy Requirements Calibrating SIWAREX FTA with SIWATOOL FTA Quick Guide For modules with order number 7MH4900-2AA01 Contents 1 2 3 4 5 6 Hardware-Requirements..

More information

PSM-003. Micro Polarization Controller/Scrambler. User Guide

PSM-003. Micro Polarization Controller/Scrambler. User Guide PSM-003 Micro Polarization Controller/Scrambler User Guide Version: 1.0 Date: August 23, 2012 General Photonics, Incorporated is located in Chino California. For more information visit the company's website

More information

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide

Peak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide GB05-7 Peak Atlas IT RJ45 Network Cable Analyser Model UTP05 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2001/2013 In the interests of development, information

More information

Safety Light Curtain C 4000

Safety Light Curtain C 4000 O P E R A T I N G I N S T R U C T I O N S Safety Light Curtain C 4000 Operating Instructions Chapter 2 On safety 2 On safety This chapter deals with your own safety and the safety of the equipment operators.!

More information

Dragonfly Quad. User Manual V1.4. Order code: EQLED101

Dragonfly Quad. User Manual V1.4. Order code: EQLED101 Dragonfly Quad User Manual V1.4 Order code: EQLED101 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please

More information

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz

MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz Mobile Communications MASTR II BASE STATION 12/24V POWER SUPPLY 19A149979P1-120 VOLT/60 Hz 19A149979P2-230 VOLT/50 Hz CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO

More information

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1

USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1 by USER MANUAL FOR THE ANALOGIC GAUGE FIRMWARE VERSION 1.1 www.aeroforcetech.com Made in the USA! WARNING Vehicle operator should focus primary attention to the road while using the Interceptor. The information

More information