UCDSB Winchester PS Addition Wireless AP Cabling Specs

Size: px
Start display at page:

Download "UCDSB Winchester PS Addition Wireless AP Cabling Specs"

Transcription

1 UCDSB Winchester PS Addition Wireless AP Cabling Specs 1.1 Systems Description A. Horizontal copper cabling system consists of Category 6 cables with four unshielded twisted pairs of solid annealed copper wrapped in plenum rated insulation with an overall plenum rated jacket with a wire thickness of 23 AWG. Each four pair cable is terminated onto 8 position 8 conductor Category 6 connectors using 110 style IDCs. Connectors are placed into NEMA rated faceplates at the work area and placed into rack mounted patching panels in the equipment / networking rooms. B. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called "permanent link," a term that is used in the testing protocols. 1) TIA-568-C.0 requires that one telecommunications outlet/connectors be installed to each predetermined location. 2) Horizontal cabling will contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector. 3) Bridged taps and splices will not be installed in the horizontal cabling. C. The maximum allowable horizontal cable length is 295 feet (90 m). This maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) to the workstation equipment. The maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) in the horizontal cross-connect. 1.2 Manufacturer Qualifications A. Manufacturer shall be a telecommunications product manufacturer with at least 20 years experience. B. Manufacturer shall be ISO 9001 certified manufacturer and shall employ Six Sigma methodology in its manufacturing process. 1.3 Warranty A. Contractor shall provide a 1 year parts and labor warranty against defective workmanship and/or system component failure. B. Contractor shall execute a Lifetime Applications Assurance Warranty for parts and labor to support stated applications from the connectivity Manufacturer. C. This warranty covers the copper and fiber optic permanent links of the network as defined by TIA- 568-C.0 which includes the cable and connecting hardware. This warranty will be extended to include the entire channel provided that the applicable Manufacture patch cords and Manufacture equipment cords are utilized, and all products are installed within areas protected from outside elements. D. Supplier will honor claims on this warranty for Life (which is defined as the usable life of the building and is referred to as the Warranty Period ). If system performance or material fails to meet the appropriate industry specification, the owner must notify Supplier, in writing, within ten 10 days of defect discovery date 1

2 E. The electrical performance provided by the combination of the different components of the permanent link will be certified by Supplier to meet the applicable performance specifications in effect at the time of manufacture as long as each condition listed below is met: 1) The network cabling infrastructure must be designed in accordance with TIA 568 Series Standards, and installed by the tendered participants after becoming certified to run the cables. Supplier is not liable for design errors or improper construction. 2) Each permanent link or channel in the network must be field tested in accordance with the TIA 568 series industry standard in force at the time of purchase AND the installed permanent links and channels must have passed all applicable TIA and Manufacturer performance requirements. Minimum testing for copper systems includes Wire Map, Length, Attenuation, Near End Crosstalk, Far End Crosstalk, Return Loss, PS NEXT, ELFEXT, and PS ELFEXT. 3) Copies of all certification test reports must be kept on file by the registrant to be resubmitted when requested by Supplier. Data must be saved in raw data and summary formats. 2

3 Part 2 Products 2.1 General A. The Electrical Code referred to in these specifications is the National Electrical Code as currently adopted by the Provence of Ontario. All work will be provided in strict compliance with the Electrical Code and all regulations that may apply. B. Where standards exist, for a particular category, products used on this project will be listed by an approved Nationally Recognized Testing Laboratory (NRTL), and be approved or listed for the intended service and application. C. These specifications do not undertake to repeat the requirements of codes, regulations or NRTL listing or labeling instructions. The Specifications or Drawings may require items or work beyond the requirements of applicable codes or regulations. The stricter, higher quality, greater quantity or higher cost will be provided. It is incumbent on the Installer, material and equipment suppliers to meet these specifications, applicable codes, regulations, and NRTL listing agency restrictions. 2.2 Manufacturer A. The copper cabling system and optical fiber cabling system design uses Leviton or Panduit connectors and Leviton or Berk-Tek cables, equivalent equipment from other manufacturers will be allowed upon approval. Approval to be obtained prior to submitting tender. Hubbell, AMP/TYCO are also acceptable materials as long as they meet the stipulated performance specifications and all requirements listed in the tender, including color. If quoting Hubbell AMP/TYCO products the bidder must submit part numbers with their bid, so they can be verified prior to award of contract. B. The word "Manufacturer" will include the Manufacturer, the Manufacturer s Representative, the Distributor, the Fabricator, and the Supplier of the particular classification of equipment, system, product, and material. C. All work, equipment, and systems will be manufactured, provided, repaired, installed, and tested in accordance with the latest edition and all current amendments of the applicable publications and standards of the organizations listed below as of the date of the Contract Documents. When the Specification requirements exceed the requirements of these publications and standards the Specifications will govern: 1) Provincial Building Code 2) Building Department Inspectional Services 3) American Society for Testing and Materials (ASTM) 4) Canadian Underwriter's Laboratories, Inc. (cul) 5) Canadian Standards Association (CSA) 6) Insulated Cable Engineers Association (ICEA) 7) National Electrical Manufacturers Association (NEMA) 8) Institute of Electrical and Electronics Engineers, Inc. (IEEE) 9) American National Standards Institute, Inc. (ANSI) 10) National Fire Protection Association (NFPA) 11) Local Electric Code 12) Building Officials and Code Administrators International, Inc. (BOCA) 13) Department of Labor USA. Safety and Health Regulations for Construction (OSHA) 14) Energy Codes 15) National Electrical Contractors Association (NECA) 16) National Bureau of Standards (NBS) 17) Federal Communications Commission (FCC) 3

4 18) Any and all Federal, Provincial and Local Standards, Codes and Authorities having Jurisdiction. 19) In addition, all phases of the Structured Cabling System installation will adhere to applicable Local Area Network (LAN) Specifications of the Institute of Electrical and Electronics Engineers (IEEE), Electronics Industry Association/Telecommunications Industry Association (TIA/EIA), and Building Industry Consulting Service International (BICSI). The entire system and all components will be NRTL certified to appropriate TIA/EIA performance rating Category, Latest TIA/EIA Standards 455-A, 492AAAA, 568-A (latest revision) and (SP-4195-B and SP B-1), 569-A, 570, 606, 607 and 758, TIA/EIA TSB 67, TSB 72, TSB 75, TSB 95 and other standards as applicable. D. The above requirements will not in any way limit responsibility or requirements to comply with all other codes, standards and laws. E. Material, equipment, enclosures, and systems will be designed for use as required to suit the conditions, exterior or interior operation, dust tight, water tight, explosion-proof, or other special types. 2.3 UTP Pin/pair Termination Assignment A. The UTP cabling systems will have TIA/EIA T568A pin/pair termination assignment. All conductors provided will be properly and consistently terminated at both ends throughout the entire systems. Maintain proper untwist of pairs and removal of jacket per TIA and BICSI. 2.4 System Performance A. Horizontal four pair Category 6 copper cabling system shall be capable of supporting 1000 Base-T applications for a total distance of 100 meters with equipment cords. System shall provide future proof channel performance and guaranteed margins as noted in this document and is guaranteed to exceed ANSI/TIA/EIA-568-B.2 Category 6 specifications for Insertion Loss, NEXT, PSNEXT, ACR, PSACR, ELFEXT, PSELFEXT and Return Losses to 250 MHz. The system is also guaranteed 12 db PSACR headroom at 250 MHz. 2.5 Performance Guarantees A. The system as specified shall have margins as noted below: 2.6 Source Quality Control A. All materials shall be purchased from Distributors authorized by system Manufacturers to sell new and unused components. 2.7 Surface Mount back box A. Manufacturer Leviton Mfg. Co., 201 North Service Rd., Melville, NY Provide Wall plates as specified below: 4

5 1) Leviton QuickPort Single Gang Standard back box a. Black Part # EA (Panduit #NK1FBL) 2) Leviton QuickPort Single Gang Face Plate a WS (Panduit #NK1FIWY) 2.8 Jacks A. Manufacturer Leviton Mfg. Provide wall plates as specified below: 1) Leviton extreme 6+ CAT 6 Connector with / Retention Force Technology a. Part # RR6 (Red) (Panduit #NK688MRD) 2.9 UTP Cable Acceptable Materials A. Manufacturer Leviton Mfg. Co., 201 North Service Rd., Melville, NY Provide UTP Cable as specified below: 1) Leviton Category 6+ all part numbers to be verified by contractor prior to ordering a. Leviton EUT6P Must be red in color b. Leviton EUT6R Must be red in color B. Manufacturer Berk-Tek, A Nexans Co., 132 White Oak Road, New Holland, PA, USA Tel: Provide UTP Cable as specified below: 2) Berl-Tek LANmark-1000 Category 6 enhanced all part numbers to be verified by contractor prior to ordering c. CMP/FT6 Part # (Jacket color Red, packaging pull box) d. CMR/FT4 Part # (Jacket color Red, packaging pull box) C. Manufacturer Panduit 85 Enterprise Boulevard, Suite 400 Markham Ontario L6G 0B5 Canada Tel: Provide UTP Cable as specified below: 1) Panduit High Performance Category 6 all part numbers to be verified by contractor prior to ordering e. CMP/FT6 Part # PUP6004RD-UY (Jacket color Red, reel box) f. CMR/FT4 Part # PUR6004RD-UY (Jacket color Red, reel box) 2.10 Patch Panels A. Leviton QuickPort Modular Patch panel shall be field configurable 24 port density in 1.75"H rack space and 48 port density in 3.5" (2) rack spaces. Rear wire management bracket shall be included. Typical front labeling of traditional patch panels. Panel shall accept full range of manufacturer's connectors. The manufacturer shall provide a one-year limited product warranty and 15 year product performance guarantee. The manufacturer shall provide a lifetime warranty against defects in material and workmanship, and an application guarantee when installed as part of a certified system. 1) Part # (24 port 1 Rack Unit) H24 (Panduit NKFP24Y) 5

6 B. Leviton Category style patch panels with Retention Force Technology - The patch panel shall meet or exceed the requirements for Category 6 described in TIA/EIA-568-B.C as well as the Class E requirements described in ISO/IEC B. The panels shall feature T568A and T568B wiring configurations, white IDC 110-punchdown modules, mounting standoffs for cable management bars, color-coded front window labeling, and a termination standoff for patch panel earthing/grounding. The panels shall have universal T568A and T568B wiring card for terminations. The panels shall be made of 16 gauge steel, and shall have a black painted finish with white silk-screening. The plastic elements shall be fire-retardant with a UL flammability rating of 94V-0. The panel shall be offered in 12-, 24, 48-, 96-port configurations as well as an 89D 12-port configuration. The patch panel shall be configured with six port modules. The 110 termination on the rear of the panel shall follow normal installation color sequence (blue, orange, green, brown) from left to right Patch Cables 1) Part # U** (Panduit NK6PP**P, 24 or 48 port only, 12 port is NK6PPG12WY) a. ** = 89 (12 port 89D wall mount with bracket), 12, 24, 48 or 96 (19 rack mount port count) (Panduit WB89D for 12 port) A.Leviton Slim Line Category 6+ Patch Cables - Patch cords shall meet or exceed requirements for CAT6 performance described in TIA/EIA-568-C.2. Patch cords shall be stranded conductor with an 8 position modular plug on each end. The cords shall be available in 3', 5', 7', 10', 15', and 20' lengths Relay Racks 1) Part Number 6D460-xxR (xx = length in feet: 03,05,07,10,15,20) (Panduit NK6PC*YRD) 1) Middle Atlantic DWR10-22PD or Equivalent Rack if required. Contractor to determine if closets require expansion based on site visits Horizontal Manager A. Leviton Versa Duct - Cable Management System shall mount horizontally to a standard 19" equipment rack. The system shall be designed with slotted duct configuration for copper and fiber cabling systems. It shall be culus listed and compliant with TIA/EIA-568-C standards. The material shall be PVC rated for 94V-0. It shall have a duct cover, and bend-radius compliant router to transition between horizontal and vertical slotted ducts 1) 1 Rack unit 491RU-HFO (Panduit WMPSE) 2) 2 Rack unit 492RU-HFO (Panduit WMP1E) 2.14 Vertical Cable Manager A. Leviton VersaDuct Cable Manager - The management system shall be culus listed, PCI rated for 94V-O, ABS rated for UL94HB, and compliant with ANSI/TIA/ EIA 568-C standards. Mounting hardware shall be included to insure the proper installation to infrastructure. It shall mount onto a standard TIA/EIA recognized equipment rack. The management system shall offer an assortment of accessories, including a bend radius slack loop organizer and cable retainers 1) 8980L-VFR (Panduit WMPV45E) 2.2 Fiber Optic cabling requirements Acceptable Materials A. Part numbers for reference only. Actual quantities to be determined by contractor. 6

7 B. Contractor must also provide all required HP X120 1G SFP LC SX Transceivers MFG# JD118B. Quantities to be confirmed by contractor. C. Manufacturer Leviton Mfg. Co., 201 North Service Rd., Melville, NY (800) Provide cords as specified below: 1) Provide the following: a. FT-EB012SSXXXF36C36CY-NNBS 12 Fiber OM3, MTP Termination at both ends, polarity method C. (XXX = Length) b. FM-E012CAC0C MTP Module, 12 Fiber LC, Polarity Method C c. 5R1UL-F03 OPT-X 500i 1 RU Fiber enclosure d. 5f100-BLK Blank Adapter Panel D. Manufacturer Berk-Tek, A Nexans Co., 132 White Oak Road, New Holland, PA, USA Tel: Provide cords as specified below: 2) Provide the following: e. BMDP12E77CCPXXX 12 Fiber OM3, MTP Female Termination at both ends, polarity method C (XXX = Length) E. Manufacturer Panduit 85 Enterprise Boulevard, Suite 400 Markham Ontario L6G 0B5 Canada Tel: Provide cords as specified below: 3) Provide the following: f. FSPX1255FXXXA 12 Fiber OM3, MTP Termination at both ends, polarity method C. (XXX = Length) g. FCX-12-10Y MTP Module, 12 Fiber LC, Polarity Method C h. FCE1U OPT-X 500i 1 RU Fiber enclosure i. FAPB Blank Adapter Panel Part 3 Execution 3.1 Installation Requirements A. Install one Category 6+ UTP cable to each area location identified on drawings. Cable installation methods shall comply with the system manufacturers specifications, EIA/TIA 568 series requirements and/or BICSI Installation Methods. Must be certified Cat6 end to end. Design intent is that no cabling run is over 90M. B. Install Fiber run from each closet that has wireless AP s connected to it back to the main closet noted on the dwg. Homerun. Successful contractor to measure all fiber runs prior to ordering for exact sized cable as ends are pre-terminated. All Fibre to be certified to support 10GB data transmission. C. When coming through ceiling spaces in wiring closets wiring sleeves must be installed. Suggest an 18 long piece of 2 conduit. D. No exposed cables are to be ran across ceilings or walls. Cables to be fished above ceilings where possible. If routing the cable above the ceiling or inside a wall is not possible then conduit must be used and exact routing to be approved by project manager prior to routing. Conduit to be painted to match existing surface using school board pre approved painters. All electrical work to be done from supplied prequalified electrical list. Low voltage conduit may be ran by own forces. If not by own forces then use the supplied prequalified list. All work performed by subs must be off the prequalified lists. 7

8 E. Where cables are ran above drop ceilings or ceiling with access above them J hooks must be utilized. Caddy CAT CM Product Line or equivalent spaced no more than 10 apart. J hooks to be utilized on all runs in ceiling access spaces. Nothing is to be secured to Siporex/Tectum ceilings/decks (Alternate means required for supporting cables in these situations to be discussed with project manager for approval) F. Provide point to point cabling as per the attached dwgs. Access points are already purchased by the school board and can be delivered to site when required. The AP s are to be installed as per the attached dwg and the contractor is to populate the board provided spreadsheet with the AP information stickers and locations. The spreadsheet will also indicate which ports of the switch are to be wired to which locations. G. Contractor to install board supplied access points on T-bar ceiling (come with mounting bracket) as indicated in the attached dwg and provide Cat 6 patch cables from termination points to access points. 3-5 in length. Where the ceiling space is not T-Bar ceiling the contractor is responsible to order the proper wall mounting bracket manufactured by Aruba. No home-made brackets approved. Access points mounted to ceiling must be facing down so they are parallel with the floor. H. AP s to be mounted in gymnasiums are to be mounted on the wall using pre-manufactured Aruba wall mount brackets supplied by the contractor. Guards to protect the AP s must also be provided by the contractor. A White wire cage type guard is preferred with a plastic coating over the metal framework. I. Access point specs can be viewed by following The board is providing the 105 model of access points. J. Contractor to leave 5-10 of coiled cable in the ceiling space for each AP so it may be moved in the future if required. K. Label each cable using a unique number at both ends of the cable within 10 inches of the point of termination. Labels shall be a computer printed wrap around adhesive label (Rino part#18489 or equal) Access Points must also be labeled as per spreadsheet. L. All cables shall be install using factory recommended pulling methods and following all related EIA/TIA 568 series and EIA/TIA 569 series guild lines for conduit/cable tray fill, minimum bend radius, a electrical distance separation. In cases where the EIA/TIA standards conflict with local electrical codes the higher requirements will apply. M. All outlets are to be terminated using a 110 punch tool or Rapid Jack Tool (LEV2) to ensure that each conductor is properly seated and trimmed to the correct length. Cable slack shall not exceed 1 foot at the termination location. Slack cable will be neatly coiled and stored so that it does not kink or have opportunity to be damaged from external sources. N. All outlets shall be labeled on the Wall plate, use printed labels (Rhino LV_WP_IDW or equal). Labeling system convention to be confirmed with the owner prior to installation. O. All equipment room panels and equipment shall be laid out for owners approval prior to being installed. Install cable slack as per TIA/EIA 568 series standard and Factory recommendations. A minimum of 10 feet of Slack must be left on each cable in the Equipment room. Slack shall be stored in a cable tray system and bundled using Velcro straps (Leviton XXX), Cables shall not be coiled. Switches shall be provided by the school board and installed in existing racks where possible by contractor. P. Contractor to determine if closets require expansion during site visit and allow for such using acceptable materials from specifications. Power for new switches is also the responsibility of the cabling contractor. Q. In Wiring closets all cables must be grouped together using Velcro straps to organize cabling at racks. No zip ties allowed. R. A full set of as built drawings shall be provided upon completion of the project. Drawings will show final location of the Equipment racks, elevation draws of equipment rack detail patch panel 8

9 organization, location of each outlet and the associated ID number, any consolidation panels or pull boxes. Cable tray pathway must also be shown. S. A CD/DVD shall be provided upon completion of the project. The CD/DVD will contain pictures of each access point as installed, showing location of the point in the room. Pictures are to be time stamped. The pictures shall be named School Name APx, where x is the number of the AP. T. Contractor to provide report on testing results to prove certified Cat6. Details of testing report are list under the testing section below. U. Contractor responsible for their own ladders and lifts if required. V. All firewalls are to be re-instated using Hilti Fire Stop Caulking FS ONE # W. Cabling work to be scheduled with general contractor prior to commencing. X. If asbestos is present in working areas then board approved asbestos contractors must be used where required Testing Procedures A. Cabling systems shall meet or exceed the electrical and transmission characteristics of the systems specified. B. Cable segments and links shall be tested from both ends of the cable for each of the construction phases. (Verify that cable labeling matches at both ends). C. The system shall not be considered certified until the tester has acknowledged that the performance of the physical layer of the system has been fully tested and is operational at the completion of the installation phase. D. After the installation is complete, in addition to any other required testing as described herein, and at such times as the Owner/Consultant directs, the Contractor shall be present while the Owner conducts an operating test for approval. The installation shall be demonstrated to be in accordance with the requirements of this specification. Any defects revealed shall be corrected promptly at the Contractor's expense and the tests performed again. E. After review of the completed test results, the Owner reserves the right to retest the installed cables, utilizing the Contractor's tester and the Contractor's labor. F. Equipment Manufacturer s Factory Test 1) Each cable and equipment Manufacturer shall factory test their respective products being installed on this project and provide test reports at time of delivery. Provide separate respective test reports indicating that they meet or exceed the latest applicable TIA/EIA Standards and technical bulletins. 2) All other products relative to this specification shall be tested to its respective industry strictest standards. 3) Each Manufacturer shall factory test their respective cable or equipment provided to this project at several lower frequency levels, including the minimum and maximum frequency level indicated herein. The test reports shall indicate test results for at least five equal incremental frequency levels including the maximum required. G. Field Testing Equipment: Submit during shop drawing review on the testing equipment to be utilized on this project. The installer shall test all cables installed under this Section. 9

10 1) Unshielded Twisted Pair Testing Equipment: H. Testing Procedures: a. The cable tester shall have a wide variety of preprogrammed cable types as an integral part of its testing system and have the ability to test cables less than 6 feet (6ft.) from the test point. b. Testing shall be accomplished using level III or higher field tester that is loaded with the most current version of test software by the manufacturer of the test equipment. c. Provide factory calibration report of field test equipment. 1) Testing shall conform to TIA-568-C.0 standard. 2) Testing will be to the Permanent Link Test Parameters. 3) Test each pair and shield of each cable for opens, shorts, grounds, and pair reversal. Correct grounded and reversed pairs. Examine open and shorted pairs to determine if problem is caused by improper termination. If termination is proper, tag bad pairs at both ends and note on termination sheets. 4) Test each UTP cable and passive components. Provide certification that entire installation of UTP cabling, equipment and jacks are NRTL certified meeting or exceeding a minimum of category performance specified on all four pairs of conductors. 5) Tests shall be based on each pair of conductors and not the aggregate multiple pair results. 6) Test all installed cable segments end-to-end, from the telecommunications room horizontal patch panel/cross connect block panel to each work area outlet and from each telecommunications room backbone patch panel/cross-connect block panel to respective main cross connect, and from the work area outlet to the main cross-connect (through patch cables or cross- connect wiring) with a Signal Injector, Graphical Link Testing Meter and Time Domain Reflectometer (TDR) for compliance to latest TIA performance requirements, as well as NEXT, ELFEXT, structural return loss, alternating power sum, opens, shorts, continuity, cable length, and characteristic impedance. 7) Provide report indicating failures and what actions were taken to ensure a passing horizontal cable and its terminations. Any cable failing the certification test (Fail, Fail* or, Pass*) must have remedial work done to provide a full pass test result; Remediation may include retermination or replacement of the cable, which fails. No cables passing within tolerance only (Conditional Pass*) will be accepted. I. Test results: 1) The test results information for each link shall be recorded in the memory of the field tester upon completion of the test. The tester shall be capable of storing test data in either internal or external memory. The external media used shall be left to the discretion of the user. 2) Test results saved by the tester shall be transferred into a Windows based database utility that allows for maintenance, inspection and archiving of these test records. A guarantee must be made that the measurement results are transferred to the PC unaltered as well as any printed reports generated from the software application. 3) Optional formats of data reporting are: comma separated variable (.csv), Portable Document File (.pdf) or compatible, plain text (.txt), or hypertext markup language (.html/.htm). 4) Test Results shall include the following: a. Applicable room number of jack location (room number per Contract Documents) b. Applicable Telecommunications Room number c. Circuit I.D. number with corresponding jack identifier d. Wire Map shall include the following: 1. Continuity to the remote end 2. Shorts between any two or more conductors 3. Crossed pairs 4. Reversed pairs 5. Split pairs 10

11 6. Any other miswiring e. Length f. Insertion Loss g. Near-end Crosstalk (NEXT) Loss h. PS-NEXT (Power Sum Near End Cross Talk) i. ELFEXT (Equal Level Far End Cross Talk) j. PS-ELFEXT (Power Sum Equal Level Far End Cross Talk) k. Propagation Delay l. Delay Skew m. Return loss 5) A full printed report must be presented to the owner as well as a digital copy in one of the above formats for their records Part 1 General Communications Connecting Cords, Devices and Adapters 1.4 Coordination Part 2 Products A. Contractor shall furnish and install the following: 1) Patch and Equipment cords, for both copper and fiber. B. Electrical Contractor shall furnish and install the following: 1) Floor boxes, box covers, straps. 2) Boxes above ceilings and box covers. C. Unless noted, the following items will be the responsibility of the Owner: 1) All electronics and active data networking equipment, etc. 2) Telephones, fax machines and modems, etc. 3) PC s, printers, video display terminals, flat panel displays, etc. D. Contact the Owner s network and computer equipment personnel for specific instructions before starting Work. 2.3 Copper Patch & Equipment Cords Acceptable Materials A. Patch cables and equipment cords shall be factory pre-connectorized, TIA/EIA Category 6 (UL Category 6), 4 pair UTP, 8-position modular jack, stranded conductors. Patch cables and equipment cords shall be able to withstand at least a minimum of 200 jack mating cycles without any transmission degradation. B. Manufacturer Leviton Mfg. Co., 201 North Service Rd., Melville, NY (800) Provide cords as specified below: 1) Leviton Standard UTP Patch Cord with Matching Boot a. [Part # xx* - (Qty #)] C. Manufacturer Panduit 85 Enterprise Boulevard, Suite 400 Markham Ontario L6G 0B5 Canada Tel: Provide cords as specified below: 11

12 2) Panduit Standard UTP Patch Cord with Matching Boot b. [Part # UTPSP-xx* Specify Length and Color] Double check with supplier for exact part # s xx = length (03), (05), (10), (15), or (20) Replace * with: Red=R 2.4 Fiber Optic Patch Cords Acceptable Materials F. Manufacturer Leviton Mfg. Co., 201 North Service Rd., Melville, NY (800) Provide cords as specified below: 1) Leviton Custom Fiber Optic Patch Cords A. 5LDLC-M01 (LC-LC OM3 Patch Cord, 1 Meter) G. Manufacturer Panduit 85 Enterprise Boulevard, Suite 400 Markham Ontario L6G 0B5 Canada Tel: Provide cords as specified below: 2) Panduit Custom Fiber Optic Patch Cords A. FXE10-10M1Y (LC-LC duplex OM3 Patch Cord, 1 Meter) Part 3 Execution FT- 3.3 Additional Information 3.4 Installation A. Install all patch cords in accordance with the Owners I.T. Department or the person in charge of the telecommunications infrastructure.. B. Bend radius of cables shall be maintained as recommended by the manufacturer and per BICSI standards. End of Section 12

13

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017

Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM Date: 05/26/2017 Pre-bid Supplement #01 Communications Specifications and Additional Scope Project Bid: CM-2017-2 Date: 05/26/2017 Additional specification information for data communication to cameras and between Library

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR October 19, 2018 Construction Documents PART 1 - GENERAL 1.1 SUMMARY SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors. 3. Cabling system identification products. 1.2

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. Telecommunications outlet/connectors including patch panels. 3. Cabling identification

More information

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards.

Category 6A UTP cables shall be tested and proved to conform to TIA-568-C.2 standards. 27 08 00 Certification and Commissioning of Communication Systems (Revision date: 7/3/12) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are

More information

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus

REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus REQUEST FOR QUOTE: TELECOMMUNICATIONS CABLING Library/Classroom Building, Beltline Campus PART 1: GENERAL REQUIREMENTS A. Contractor Work 1. Provide and install (except as noted in this document), cable,

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 08 20 COPPER TESTING PART 1 - GENERAL 1.1 SUMMARY A. Test measurements shall be taken for all balanced-twisted pair cabling, including horizontal and backbone copper cables and wall-to-rack

More information

DESIGN!!GUIDELINES!!!!!

DESIGN!!GUIDELINES!!!!! DESIGNGUIDELINES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 1. Testing General 1.1. For acceptance, 100% of the media

More information

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.

California Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1. PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue.

Description: Pair Color Code Chart: Pair Color Chart 1 Brown White Brown 2 Orange White Orange 3 Green White Green 4 Blue White Blue. Description: OZLINX CAT5e cable has a guaranteed performance; exceeds the Category 5e performance requirements and provides positive PSACR up to 155MHz for bandwidth requirement in the future. Product

More information

STRUCTURED CABLE SYSTEM (SCS)

STRUCTURED CABLE SYSTEM (SCS) PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

A. All communications equipment rooms shall be installed in a neat and workmanlike manner.

A. All communications equipment rooms shall be installed in a neat and workmanlike manner. SECTION 27 11 00 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION

SECTION TESTING, IDENTIFICATION AND ADMINISTRATION PART 1 - GENERAL 1.1 SUMMARY SCOPE SECTION 25170 TESTING, IDENTIFICATION AND ADMINISTRATION 1. This section includes the minimum requirements for the testing, certification administration and identification

More information

PREMIUM 5e F/UTP PRODUCTS

PREMIUM 5e F/UTP PRODUCTS Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been

More information

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE

UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and

More information

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab*

Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* Tender Report for Supply and installation of LAN in *Biomedical Imaging and Bioinformatics Lab* General Scope of Work: Supply and installation of Computer Laboratory setup in MIU Location of Installation:

More information

Volition TM RJ45 K5e Jacks

Volition TM RJ45 K5e Jacks Volition TM RJ45 K5e Jacks Part of our 3M Volition Network Solutions, the new K5e range is our ultimate Category 5e hardware component (ISO/IEC 11801, EN 50173 and ANSI/TIA/EIA-568). The K5e jack is a

More information

SECTION COMMUNICATIONS HORIZONTAL CABLING

SECTION COMMUNICATIONS HORIZONTAL CABLING SECTION 27 15 00 COMMUNICATIONS HORIZONTAL CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS AND SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School

BILOXI PUBLIC SCHOOL DISTRICT. Biloxi Junior High School BILOXI PUBLIC SCHOOL DISTRICT Biloxi Junior High School Request for Proposals E-Rate 2014-2015 - Internal Connections Submit Proposals To: Purchasing Department Attn: Traci Barnett 160 St. Peter Street

More information

SECTION TESTING OF COPPER CABLES

SECTION TESTING OF COPPER CABLES SECTION 27 08 13 TESTING OF COPPER CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS BH, CB, CH, ED, MH, LH, Camera Project 1.1.0 GENERAL The purpose of this specification is to establish a requirement for the installation of a voice, video and data cable network. The cable (copper), wire, hardware, equipment racks, jumpers,

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Premium Line Category 6A Cabling Solutions

More information

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices

OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices OASIS CSI (Certified Security Integrators) Direct Attach Warranty for ESS Devices Berk-Tek recommends installing a well-designed structured cabling channel per the TIA standards. This includes up to 100

More information

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017 SECTION 27 15 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Telecommunication Infrastructure Project September 20, 2002

Telecommunication Infrastructure Project September 20, 2002 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Category rated UTP systems shall be provided and tested in accordance with the performance level established in Specification

More information

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting

ADDENDUM NO. 2 This addendum consists of 8 pages. Kenai Peninsula Borough Purchasing & Contracting KENAI PENINSULA BOROUGH Purchasing and Contracting 144 North Binkley Street Soldotna, Alaska 99669-7520 Toll-free within the Borough: 1-800-478-4441, Ext. 2260 PHONE: (907) 714-2260 FAX: (907) 714-2373

More information

CATEGORY 5e CABLING SOLUTIONS

CATEGORY 5e CABLING SOLUTIONS With the high speed data transmission requirement in LAN, 1998 IEEE ratified standard 802.3z defined protocol 1000BASE-T over Category 5e and higher level Ethernet cabling system. After that, with the

More information

SPECIAL SPECIFICATION 8540 Telecommunication Cable

SPECIAL SPECIFICATION 8540 Telecommunication Cable 2004 Specifications CSJ 0914-00-307 & CSJ 0914-25-003 SPECIAL SPECIFICATION 8540 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing,

More information

CATEGORY 6 CABLING SOLUTIONS

CATEGORY 6 CABLING SOLUTIONS With over 20 years experience and know-how on communicating products design & developing, Premium Line has built maturity systems both in high tech develop and research center & complete structural quality

More information

Section Communications Optical Fiber Backbone Cabling

Section Communications Optical Fiber Backbone Cabling Part 1 1.1 Related Documents 1.1.1 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections apply to this Section. 1.2 Related

More information

SPECIAL SPECIFICATION 6559 Telecommunication Cable

SPECIAL SPECIFICATION 6559 Telecommunication Cable 2004 Specifications CSJ 0015-09-147, etc. SPECIAL SPECIFICATION 6559 Telecommunication Cable 1. Description. This specification governs the materials, installation, termination, splicing, testing, training,

More information

CATEGORY 6A CABLING SOLUTIONS

CATEGORY 6A CABLING SOLUTIONS 10 Gigabit Ethernet is nowadays viable solution for destinations with very high data traffic concentration like data center, server farms, MAN s and backbones. Need of 10 Gigabit Service Application as

More information

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE)

Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) PART 1: GENERAL 1.01 Telecommunications Engineer Minimum qualifications for the Telecommunications Engineer are: A. Texas Licensed Profession Engineer (PE) B. Registered Communications Distribution Designer

More information

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 ITB THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 ITB 15-0012 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11

About Nexans 3. About Berk-Tek 4. LANmark-1000 Cat 6 UTP 5. LANmark-1000 Category 6 Plenum 6. LANmark-1000 Category 6 Riser 11 Table of contents About Nexans 3 About Berk-Tek 4 LANmark-1000 Cat 6 UTP 5 LANmark-1000 Category 6 Plenum 6 LANmark-1000 Category 6 Riser 11 LANmark-1000 Category 6 Patch 16 21 7/10/07 - http://www.berktek.com

More information

Follow The Leader In Shielded Technology

Follow The Leader In Shielded Technology 1970s Vampire Tap 1990s Shielded Modular Jack 190s 4 Position Data Connector Follow The Leader In Shielded Technology The new AMP-TWIST Jack is our latest shielded product evolution. It can be terminated

More information

Request for Proposal (RFP)

Request for Proposal (RFP) Request for Proposal (RFP) Data Network for OCMS 017 Inquiries and requests regarding this RFP should be directed to: Michael Hale Technology Director Oconee County Schools PO Box 16 5-A School Street

More information

What really changes with Category 6

What really changes with Category 6 1 What really changes with Category 6 Category 6, the standard recently completed by TIA/EIA, represents an important accomplishment for the telecommunications industry. Find out which are the actual differences

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT

CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT- LAS POSITAS COMMUNITY COLLEGE DISTRICT Purchasing and Warehouse Services Department October 1, 2007 Addendum No. 1 INVITATION FOR BID No. 08-09 Temporary Faculty Offices, Chabot College All Prospective

More information

SECTION FIBER OPTIC STATION CABLES

SECTION FIBER OPTIC STATION CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752

More information

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables

NEMA Standards Publication WC Performance Standard for Twisted Pair Premise Voice and Data Communications Cables NEMA Standards Publication WC 63.1-2005 Performance Standard for Twisted Pair Premise Voice and Data Communications Cables Published by: National Electrical Manufacturers Association 1300 North 17th Street,

More information

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14

About Nexans 3. About Berk-Tek 4. Hyper Plus 5e Cat 5e UTP 5. HyperPlus 5e Plenum 6. Hyper Plus 5e Riser 10. HyperPlus 5e Patch 14 Table of contents About Nexans 3 About Berk-Tek 4 Hyper Plus 5e Cat 5e UTP 5 HyperPlus 5e Plenum 6 Hyper Plus 5e Riser 10 HyperPlus 5e Patch 14 HyperPlus 5e OSP 18 22 7/10/07 - http://www.berktek.com Page

More information

Multi-Media Installation Guide

Multi-Media Installation Guide Multi-Media Installation Guide Coaxial Page 2 Data Plug Page 7 Data Jack Page 10 Telephone Page 13 Splicing Page 15 Cable Types Cable Types Two basic types of cable are used in multimedia installations.

More information

CABLING STANDARDS FOR

CABLING STANDARDS FOR RFB for Wiring in the Outagamie County Courtrooms Attachment B September 1, 2016 CABLING STANDARDS FOR GENERAL The purpose of this document is to provide guidelines for all structured cable installations

More information

SECTION 7 -- CROSS-CONNECT SYSTEMS

SECTION 7 -- CROSS-CONNECT SYSTEMS DETAIL ENGINEERING REQUIREMENTS AT&T March, 2016 Section 7, ATT-TP-76400 Revised NA SECTION 7 -- CROSS-CONNECT SYSTEMS CONTENTS PAGE 1. GENERAL... 7-2 1.1. Introduction... 7-2 1.2. Cable Holes... 7-2 1.3.

More information

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m

Frequency ASRL(db) Attenuation Max. NEXT Power Sum (MHz) Minimum db/100m db/1000ft Minimum db/100m Minimum db/100m Cat.5e 4 Pair UTP Cable Application: Voice ISDN 10Base T(IEEE 802.3) Fast Ethernet(IEEE802.3u) 100Vg-AnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TP-PMD(ANSI X3T9.5) 100Base-T Ethernet(IEEE 802.5) 155/622

More information

Connect with the industry s best CAT6 and CAT5e channel solutions!

Connect with the industry s best CAT6 and CAT5e channel solutions! Connect with the industry s best CAT6 and CAT5e channel solutions! Our CAT6 and CAT5e channel solutions far exceed the TIA/EIA specifications performance standards! To ensure consistent and continuing

More information

HighBand 25. TrueNet Category 6 Solutions

HighBand 25. TrueNet Category 6 Solutions HighBand 25 TrueNet Category 6 Solutions The highest performing cross-connect system in the world. A unique high-density solution with superior cable management. ADC KRONE s HighBand 25 cross connect solution

More information

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.

SECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes. SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of

More information

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions

Robert Burén. Product Manager. Nexans Cabling Solutions. 10G Solutions Robert Burén Product Manager 10G Solutions Nexans Cabling Solutions 1 10 Gigabit Ethernet.Performance 30 GByte can be transmitted within 24 seconds Example: MRI-scan size is 30GB as average A memory device

More information

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008

Information & Communications Technology Network Infrastructure Group. Network Infrastructure Standards June 2008 Information & Communications Technology Group Standards June 2008 Appendix F UTP cabling Version 1.1 Appendix F UTP cabling 1. Introduction This Section details the required standards for Unshielded Twisted

More information

LCS 2 RJ 45 Cat. 6A HD panels and units

LCS 2 RJ 45 Cat. 6A HD panels and units 87045 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: +33 (0)5 55 06 88 88 Page 0 335 85/86 1. General characteristics....1 2. Presentation...1 3. Positioning...1 4. Technical characteristics...1

More information

TX COPPER CABLING SYSTEM

TX COPPER CABLING SYSTEM TX COPPER CABLING SYSTEM PERFORMANCE BEYOND PRODUCTS PANDUIT is the global leader in network connectivity, delivering end-to-end system solutions in support of your most demanding network requirements.

More information

RCIT Cable Certification Testing Revised 10/2017

RCIT Cable Certification Testing Revised 10/2017 RCIT Testing Revised 10/2017 General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall

More information

STRUCTURED CABLING SYSTEMS (SCS)

STRUCTURED CABLING SYSTEMS (SCS) STRUCTURED CABLING SYSTEMS (SCS) ModSecur - Structured Cabling Systems (SCS) A Structured Cabling System (SCS) is the backbone of any building, campus or site communication infrastructure. The sharp growth

More information

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper

3M Supported Applications Map 100,000 (2005) Single-mode. Fiber. Multimode. Fiber. Copper 3M Volition Network Solutions introduces Category 5e (Cat. 5e) copper cabling system to complement its leading fiber optic structured cabling system. Customers can now enjoy a single source of supply and

More information

Public Works Division Lighting District Fiber Optic Specifications April 2009

Public Works Division Lighting District Fiber Optic Specifications April 2009 Public Works Division Lighting District Fiber Optic Specifications April 2009 7000 Florida Street Punta Gorda, Florida 33950 Tele: 941.575.3600 Fax : 941.637.9265 www.charlottecountyfl.com/publicworks

More information

DINTEK LAN Cabling Systems

DINTEK LAN Cabling Systems 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.3u) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

Primex Wireless, Inc. July, Wells Street Lake Geneva, WI

Primex Wireless, Inc. July, Wells Street Lake Geneva, WI Division 0 0 0 0 Primex Wireless, Inc. July, 00 Wells Street Lake Geneva, WI 00--0 www.primexwireless.com Product Guide Specification Specifier Note: This product specification is written according to

More information

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK

Connected Solutions. April $ Post, 19 Rack ELERK1FR BK Connected Solutions April 2018 $30.97 Punch & Go Tool ONQAC3400 $139.97 per 305M Category 6 Riser, UTP, 23 AWG, Blue 305 Meter/1000 FT Pull Box CAB24/4PS6FT4BLUHYP $137.97 2 Post, 19 Rack ELERK1FR1194400BK

More information

Belden IBDN System 10GX Enabling Technologies

Belden IBDN System 10GX Enabling Technologies Belden IBDN System 10GX Enabling Technologies by Paul Kish Director, Systems and Standards Revision 1 November 2008 Belden Belden IBDN System 10GX Enabling Technologies 1/17 Introduction The IEEE 802.3an

More information

LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s

LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s LITWARRANTY Rev. 5 W a r r a n t y P r o g r a m S t r u c t u r e d C a b l i n g S y s t e m s STRUCTUREd CAbLINg SYSTEm WARRANTY PRogRAm As transmission speeds continue to increase, HellermannTyton

More information

Technical Specifications Florida Gulf Coast University

Technical Specifications Florida Gulf Coast University Technical Specifications Florida Gulf Coast University 9/19/2018 Page 1 of 21 Approved Vendors (alphabetical order) Aztek (CIP) Certified Installer Plus Mr. Scott Coyne 4730 Enterprise Avenue Suite #308

More information

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS

Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS VOFP Cabling RFP 1 Request for Purchase DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For The Village of Franklin Park 2014 VOFP Cabling RFP 2 TABLE OF CONTENTS I. PROJECT DESCRIPTION

More information

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING

DATA/TELECOMMUNICATIONS REQUEST FOR PRICING Category 6A 10Gig DATA/TELECOMMUNICATIONS REQUEST FOR PRICING TABLE OF CONTENTS 1. GENERAL 3 1.1. Work Included... 3 1.2. Scope of Work... 3 1.3. Regulatory References... 4 1.4. Quality Assurance... 4

More information

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel 1993 Specifications CSJ 0924-06-223 SPECIAL SPECIFICATION 1160 8:1 Video (De) Mux with Data Channel 1. Description. This Item shall govern for furnishing and installing an 8 channel digital multiplexed

More information

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5

Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 Telecommunications Cabling System Technical Specification for the K-12 Educational Environment Enhanced Category 5 1.0 INTRODUCTION Customer to define background and introduction to the project based on

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for:

Liberty Mutual Structured Cabling Specification Bid and Build Structured Cabling Technical Specification for: Bid and Build Structured Cabling Technical Specification for: Horizontal & Backbone Requirements Page 1 of 30 PUBLICATION RECORD Document Version Publication Date Primary Author Description Revision 1.0

More information

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System

10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System 10Gb/s Copper Physical Infrastructure Next Generation Category 6A Cabling System Next-Generation Category 6A UTP Cabling System Drivers for 10 GbE Aggregation of Gigabit Links Server Consolidation and

More information

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project

Family Health Centers, Inc. Request for Proposal. for. Family Health Centers East Broadway Data and Communications Cabling Project Family Health Centers, Inc. Request for Proposal for Family Health Centers East Broadway Data and Communications Cabling Project Date Issued: 06/07/2014 Date Due: 06/16/2014 Page 1 of 22 Table of Contents

More information

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING

Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING Revision 05/01/2017 Division 27 COMMUNICATION/DATA, PATHWAYS, AND WIRING PART 1 GENERAL 1.1 SECTION INCLUDES A. Voice, Data, and Fiber Cable Product materials B. Voice, Data, and Fiber Cable Execution

More information

10G 6A F/UTP SYSTEM PRODUCTS 10G 6A F/UTP

10G 6A F/UTP SYSTEM PRODUCTS 10G 6A F/UTP 0G A Combining 0 Gb/s performance with the security, noise immunity and pathway space maximisation of a screened cabling system, Siemon s end-to-end solution represents the cutting edge of augmented category

More information

Copper Solution Contents Cabinets Fiber Optic Solution

Copper Solution Contents Cabinets Fiber Optic Solution Contents Copper Solution Category 6A + Cabling Solutions Cat.6A + 1000MHz S/FTP Installation Cable A1 Cat.6A + S/FTP Patch Cord A2 Cat.6A + 90 Fully Shielded Die-casting Keystone Jack A3 Modular German

More information

CAT6Plus System. Brand-Rex Limited

CAT6Plus System. Brand-Rex Limited Brand Rex introduces it's New CAT6Plus Cabling Solution, designed to deliver an optimum performance cabling system. All products in the CAT6Plus system have 3rd party approval* and therefore either meet

More information

Belden IBDN System 10GX The next level of cabling performance

Belden IBDN System 10GX The next level of cabling performance Belden IBDN System 10GX The next level of cabling performance by Paul Kish Director Belden IBDN Systems and Standards Introduction There is a new standard under development in the IEEE 2.3an task force

More information

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points

Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Request for Quote E- Rate Eligible Services Scope of Work - Wireless LAN and Cabling for Access Points Due Date: Allowable Contract Date from Posted 470 The Palo Verde Elementary School District is requesting

More information

Compact Module. Category 6 FTP Cabling System

Compact Module. Category 6 FTP Cabling System Compact Module Shielded design for improved EMI performance Suitable for Gigabit Ethernet applications and beyond Ultra-slimline design Colour coded for quick and accurate termination Interchangeable with

More information

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project

MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project 1.1.0 GENERAL MIDDLESEX COUNTY COLLEGE WIRE AND CABLE NETWORK REQUIREMENTS Projector, Camera and Veteran s Project The purpose of this specification is to establish a requirement for the installation of

More information

Cat.6 4 Pair UTP Cable

Cat.6 4 Pair UTP Cable 4 Pair UTP Cable Application: Voice Fast Ethernet(IEEE802.3u) VgAnyLAN(IEEE 802.12) Token Ring(IEEE 802.5) TPPMD(ANSI X3T9.5) BaseT Ethernet(IEEE 802.5) 155/622 Mbps 1.2/ 2.4 Gbps ATM 0BaseT Ethernet 550

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 23 Communications Cable Management and Ladder Rack A. Provide all labor, materials, and equipment for

More information

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT

TEST REPORT NO.: CRT-081 RENDERED TO: Hubbell Premise Wiring 14 Lord s Hill Road Stonington, CT 3933 US ROUTE 11, CORTLAND, NEW YORK 1345, U.S.A. Phone Number: 1-8-345-3851 Fax Number: 67-758-3648 PROJECT NO.: 322866-311 DATE: February 19, 29 TEST REPORT NO.: 322866CRT-81 RENDERED TO: Hubbell Premise

More information

University Center AV Integration Construction Documents February 8, 2012

University Center AV Integration Construction Documents February 8, 2012 SECTION 27 41 30 AUDIOVISUAL ARCHITECTURAL SPACES PART 1 GENERAL 1.01 SUMMARY A. This Section defines the Audiovisual System requirements for Audiovisual Systems within Architectural Spaces. 1.02 RELATED

More information

10G 6A UTP SYSTEM PRODUCTS 10G 6A UTP

10G 6A UTP SYSTEM PRODUCTS 10G 6A UTP 0G A is Siemon s advanced, end-to-end augmented category UTP structured cabling system, designed to meet or exceed all 0GBASE-T performance requirements, including alien crosstalk. Siemon s full channel

More information

Special Specification 6293 Adaptive Traffic Signal Control System

Special Specification 6293 Adaptive Traffic Signal Control System Special Specification Adaptive Traffic Signal Control System 1. DESCRIPTION 2. MATERIALS Furnish, install, relocate, or remove adaptive traffic signal control (ATSC) system software and equipment at locations

More information

LCS2 Cat. 6 RJ 45 Patch panels and units

LCS2 Cat. 6 RJ 45 Patch panels and units 87045 LIMOGES Cedex Telephone: 33 0 5 55 06 87 87 - Fax: 33 0 5 55 06 88 88 LCS2 Cat. 6 RJ 45 CONTENTS Page 1. General characteristics....1 2. Presentation...2 3. Installation...2 4. Technical characteristics...2

More information

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas

WJHW, Inc. 6 April 2016 Texas Tech University Issue for CD Set Sports Performance Complex Lubbock, Texas SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide materials, labor, and methods for telecommunications grounding and bonding system in accordance with

More information

Project No. # Page 1

Project No. # Page 1 PART 1 - GENERAL This section of the has references, products, procedures, processes, and work descriptions/summaries that are common to many Washington State University Pullman (WSUP) campus telecommunications

More information

Copper Cabling Troubleshooting Handbook

Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The automated DTX Series diagnostics 5 Causes of Cabling

More information

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS.

Clarity. Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Clarity Advanced solutions for 10 Gig, Category 6 and 5e copper connectivity PRODUCT SOLUTION GUIDE EXPERTISE. TECHNOLOGY. SOLUTIONS. Center Tuned Components Higher Signal-to- Noise Ratio Optimal Mated

More information

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving

More information

City of Winter Springs, FL

City of Winter Springs, FL City of Winter Springs, FL Request for Quote RFQ/006/17/LS Commission Chambers Audio Visual System Upgrades The City of Winter Springs will be upgrading its Commission Chambers (Chambers) audio visual

More information

HELLERMANNTYTON DESCRIPTION DIMENSIONS PKG. PART NO. (HXWXD) QTY. RE18 Residential Enclosure Base: 18 H x 14.1 W x 4 D 1 Cover: 19.5 H x 15.

HELLERMANNTYTON DESCRIPTION DIMENSIONS PKG. PART NO. (HXWXD) QTY. RE18 Residential Enclosure Base: 18 H x 14.1 W x 4 D 1 Cover: 19.5 H x 15. HOME NETWORK SCIENCES FROM HELLERMANNTYTON The Home Network Sciences system allows for: Telephone Distribution Video and TV Distribution Whole-House Audio Computer Networking using DSL and Cable Modems

More information

Aerial Cable Installation Best Practices

Aerial Cable Installation Best Practices Aerial Cable Installation Best Practices Panduit Corp. 2007 BEST PRACTICES Table of Contents 1.0 General... 3 2.0 Introduction... 3 3.0 Precautions... 4 4.0 Pre-survey... 5 5.0 Materials and Equipment...

More information

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING

SECTION CONTROL, COMMUNICATION AND SIGNAL WIRING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 27 10 00 CONTROL, COMMUNICATION AND SIGNAL WIRING SPEC WRITER NOTES: 1. Edit this specification section between // //, to fit project, or delete if not applicable.

More information

GenSPEED Category 5e Cables 3

GenSPEED Category 5e Cables 3 Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category

More information

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines.

B. All work shall be in accordance with Building Industry Consulting Services International (BICSI) guidelines. PART 1 - GENERAL 1.1 SUMMARY A. This section includes: 1. Support Structures 2. Cable trays and ladder rack 3. Racks (including wire managers) 4. Cables (copper and optical fiber) 5. Jacks and faceplates

More information