Installation Instructions
|
|
- Daisy Hunter
- 6 years ago
- Views:
Transcription
1 Installation Instructions Smartwired Switching System Installation and Operation Summary This Manual is focused on the needs of the Installing Contractor and the Operator. It assumes that the intent of the installation is to: 1 Provide a relay-based switching system for the lighting 2 Automate the operation of the lighting to comply with building energy codes such as ASHRAE 90.1 In the Smartwired Switching System, the switching platform consists of Relay Panels, Dataline Switches and a Dataline, which connects the parts into a small network. Automatic scheduling functions are provided by either a plug-in, 8-channel Network Clock or a Building Management System (BMS) Interface Module. An optional Photocell Control Module provides daylighting control of exterior lighting. Before starting, read the instructions in this summary. Full instructions detailing the installation and operation of Smartwired Switches, the Network Clock, BMS Interface Module and other optional automation devices follow. If you have any questions, call our Service Team at: Santa Clara, CA The Watt Stopper, Inc.
2 Figure 1 Smartwired Switching System Platform Installation PANEL 01 PANEL PANEL 02 xx PANELS NUMBERED SEQUENTIALLY BEGINNING AT 01 SWITCH BUTTONS (#1 AT TOP) DATALINE 4-CONDUCTOR 18 AWG 1500 FT. MAX. HDLW4P DATALINE SWITCHES FOR EACH PANEL NUMBERED SEQUENTIALLY (PANEL # - SWITCH #) MAXIMUM TOTAL NUMBER OF PANELS AND DATALINE SWITCHES IS Note: To ensure good communications between panels, the installer must comply with the dataline specification. The Watt Stopper will not warrant a system using a dataline that does not meet our specification. To avoid questions, use HDLW4(P) (plenum rated). Do not run the dataline in conduit or wiring trays with power wires. Do not connect the local datalines from two different panels. HDLW4P Dataline Wire Specifications 18 AWG (7 strands x 26 AWG) 2 independent twisted pairs Unshielded copper conductors 2-inch twist lay on pairs, 6-inch on cable Plenum-rated copolymer jacket, 0.230" O.D. FEP 0.010" insulation, 0.060" O.D. 30 pf/foot maximum capacitance -20 C to 150 C operating temperature range 17 lbs. per 500 foot reel UL rated Installing and Commissioning the Smartwired Switching Platform Step 1 Install and Test the Relay Panels, Dataline and Dataline Switches Detailed installation instructions for each of these components is included with the unit, and is also in the following sections of this manual. Two points to remember: 1 Make sure your dataline conforms to The Watt Stopper specifications (see above right). If in doubt, use our dataline wire, HDLW4(P) (plenum rated). 2 The testing process ensures that all of the modules are working properly and that they are communicating with each other over the dataline. Step 2 Number and Document the Relays and Dataline Switches This is a key step. It helps clarify your intent and also provides a simple reference document for the next step. As shown in Figure 1 above, relay panels are numbered sequentially beginning with 01. Relays within a panel are numbered from 01 up to 48. By convention, relay refers to panel 01, relay 22. Once you have confirmed that the relays are connected to the appropriate loads, record the description of the load controlled by each relay on the Smartwired Switching System Relay Schedule form shown in Figure 2 opposite. The dataline switches for each relay panel are also numbered sequentially beginning with (panel 01, switch unit 01). A single switch unit may have one, two, four or eight buttons. Any switch button may be smartwired to any group of relays within a single panel. The relays controlled by each switch button are recorded on the Smartwired Switching System Dataline Switch Documentation form shown in Figure 3 opposite. 2
3 Step 3 Smartwire the Relays and Dataline Switches The actual linking of switches to relays is simple. It can be done using the process shown in Figure 4, or by using the programming function of the Network Clock (see instructions INHCLK-P). When the smartwiring is complete, confirm the operation of every switch button. With the wallplate removed and the switch s master button flipped open continue to flash; LEDs for the other buttons will stop flashing. LEDs for the relays currently controlled by that switch button will also begin to flash. 3 Select the relays to be controlled. In the relay panel, press the associated relay control button to add/delete that relay to/from the group. 4 Press the SMARTWIRE tab again. All LEDs will stop flashing. The selected switch button will now control the selected group of relays. Figure 4 Smartwiring a Dataline Switch to a Relay 1PRESS SMARTWIRE TAB ONCE SMARTWIRE LED FLASHES ONCE ALL SWITCH BUTTON LEDS BEGIN FLASHING 1 Press the SMARTWIRE tab. The LED next to the tab will flash once, then the individual button LEDs will begin to flash on/off. 2 Press the Switch Button you want to smartwire (Master Button on an HDLS1-x). The LED for that button will Test. Press the selected switch button again to toggle the relay group on/off/ on. Now press each relay control button to turn each relay off. The switch button LED will go from red (all relays on) to green (mixed group) to off when the last relay in the group is off. SMARTWIRE TAB SMARTWIRE LED Figure 2 Smartwired Switching System Relay Schedule Form 2 PRESS SWITCH BUTTON TO BE PROGRAMMED SELECTED BUTTON LED CONTINUES TO FLASH OTHER LEDS STOP FLASHING Figure 3 Smartwired Switching System Dataline Switch Documentation Form 3 4 PRESS PRESS CONTROL BUTTON TO ADD OR DELETE FROM THE GROUP SMARTWIRE TAB AGAIN ALL LEDS STOP FLASHING FLASHING LED CONTROL BUTTON 3
4 Network Clock The HCLK8SS Network Clock* provides scheduling for up to eight global channels (A-H). Each relay within a panel may be linked to one of these channels. In addition, each of these channels may be assigned any one of four different automation scenarios: Scenario 1: Scheduled ON/OFF (Interior Lighting) this scenario will turn on whenever the building is scheduled to be occupied and turn off when the building is scheduled to be unoccupied. As an option, the lights will blink to alert occupants five minutes before the scheduled off. Any dataline switch button controlling that relay will also begin to flash. Pressing the switch button will stop the flashing and a timed delay will be applied to the relay, over-riding the scheduled off. Data required by the Network Clock: A Occupancy time by day of week B Override time (in 10-minute increments, up to 4 hours) C Blink warn? Yes/No Scenario 2: Manual ON/Sched OFF (Interior Lighting Alternate) this scenario will not turn on until turned on by an occupant. During unoccupied periods, this scenario acts the same as Scenario 1 and the same data is required by the Network Clock. Scenario 3: Astro (Dark) ON/OFF (Exterior Lighting Security) this scenario will turn on when it is dark outside and turn off when it is light. Dark is defined by the user as a number of minutes before or after sunset. The Network Clock uses an astronomical * Only one Network Clock can be used per system. ** If a Photocell Control Module (HPCU8SS) is on the system, the Network Clock will request Footcandle data instead of Location and Dark data. Typical footcandle settings are: Security and Parking 2 to 20 fc, for Signage 20 to 200 fc. function to determine when sunset and sunrise occur. It does not compensate for rainy or overcast days. Data required by the Network Clock:** A Building location (nearest city/state or province) B Time in minutes before or after sunset that the lights should turn on (They will turn off symmetrically relative to sunrise example: 30 minutes after sunset / 30 minutes before sunrise) Scenario 4: Astro (Dark) ON/Sched OFF (Exterior Lighting Parking Lots/Signs) this scenario will turn on whenever it is dark outside and the building is occupied. It will turn off when the building is scheduled to be unoccupied. Data required by the Network Clock:** A Building location (nearest city/state or province) B Occupancy time by day of week C Time in minutes before or after sunset that the lights should turn on Installing and Commissioning the Network Clock Step 1 Define the Global Channel Scenarios The Smartwired Switching System Network Clock Automation Scenarios form provides a simple method for documenting the different global lighting scenarios and the operating data associated with each. Simply look at the different lighting loads in the building and group them by common function. (Figure 5) Step 2 Assign Relays to the Appropriate Channels With the above form in hand, it s easy to walk through the Smartwired Switching System Relay Schedule form (Figure 6) and select and document which channel a particular relay should follow. (If a relay doesn t follow a channel, it won t be automated.) Step 3 Smartwire Each Relay to its Associated Channel Smartwiring a relay to a channel is similar to smartwiring it to a switch. (Figure 7) Step 4 Install the Network Clock The HCLK8SS simply snaps onto the DIN rail in any panel and plugs into the global dataline as shown at right. Step 5 Enter the Network Clock Operating Data Refer to the Network Clock Installation Instructions INHCLK-S. Step 6 Test the Automatic Operation Set the Network Clock to two minutes before a scheduled action and confirm the operation. 4
5 Figure 5 Define Global Channel Scenarioes Figure 7 Smartwiring Relays to Automation Channels 1 PRESS AND HOLD CHANNEL PUSH BUTTON FOR SEVERAL SECONDS RED LED BEGINS FLASHING 2 SELECT S TO BE CONTROLLED LED BEGINS FLASHING Figure 6 Assign Relays to the Appropriate Channels 3 PRESS CHANNEL PUSH BUTTON AGAIN ALL LEDS STOP FLASHING TEST BY PRESSING THE CHANNEL PUSH BUTTON TO TOGGLE THE GROUP OF S ON/OFF/ON 5
6 BMS Interface Module The HBMS8SS Building Management System Interface Module provides an intelligent interface to other building systems, such as HVAC or Security. It is used instead of the Network Clock (HCLK8SS) to provide smart control scenarios for up to 8 global lighting groups (channels) in the network, and mounts to any panel s DIN rail. Only one BMS Interface Module or one Network Clock may be used in a system. Rather than schedule channels, as the Clock does, the BMS Interface accepts input from an external system to indicate the Occupied or Unoccupied status of a lighting group. For example, in some retail applications, it may be more convenient to turn on lighting when the security system is disabled, just as staff arrives. From a simple contact closure, the BMS Interface automatically applies the proven control scenarios selected for each channel. The same scenarios described for the Clock on page 4 apply to the BMS Interface Module. However, there are a few differences between the two units. Dark scenarios: Because the BMS Interface Module does not provide scheduling information, it has no Astronomical timeclock function. The Dark scenarios for exterior lighting automatically become available when an HPCU8SS Photocell Control Module is connected to the dataline. Egress Delay: Because the BMS Interface Module relies on another system for Occupied/Unoccupied information, it provides an egress delay. The user can set a time up to 4 hours after the channel becomes Unoccupied that allows occupants to exit the area safely before the lights are turned off. Contact Definition: Each channel has an associated Input Contact and Status Output Contact. The user can set parameters for these contacts based on interface requirements. Scenario 1: Scheduled ON/OFF Data required by the BMS Interface Module: A Override time delay (in 10-minute increments, up to 4 hours) B Blink Warn? Yes/No C Egress Time (0, 1, minute in 10-minute increments) D Define Occupied for Input Contact (Occupied = Open or Closed contact) E Define Status Contact (Closed contact = Any ON, All ON, All OFF, Any OFF) Scenario 2: Manual ON/Sched OFF The BMS Interface Module requires the same data as in Scenario 1. Scenario 3: Dark ON/OFF For channels with this scenario, no input contact is required, since it depends completely on the exterior light level, provided by the Photocell Control Module. Data required by the BMS Interface Module: A Define Dark for each channel as any value from 2 to 200 fc. B Define Status Contact (Closed contact = Any ON, All ON, All OFF, Any OFF) Scenario 4: Dark ON/Scheduled OFF Data required by the BMS Interface Module: A Egress Time (0, 1, minute in 10-minute increments) B Define Dark for each channel as any value from 2 to 200 fc. C Define Occupied for Input Contact (Occupied = Open or Closed contact) D Define Status Contact (Closed contact = Any ON, All ON, All OFF, Any OFF) Photocell Control Module The Photocell Control Module is another intelligent dataline module for the Smartwired switching system. It mounts on the DIN rail in any relay panel, and connects to the panel s dataline. A single photocell (HPSA), mounted on the building s roof, provides light level data to the unit. The Photocell Control Module compares the actual outdoor light level with the set point selected by the user for each of up to eight (8) channels in the system. It interacts automatically with either the HCLK8SS Network Clock, or the HBMS8SS BMS Interface Module, one of which must be present in the system. Set points for each channel are programmed through the Clock or BMS Interface Module, which provides scheduling, occupancy information and the smart scenarios that tell the relay panels how to respond to a Dark or Not Dark signal from the Photocell Control Module. An automatic deadband and 5-minute time delay avoid nuisance switching. An OPERATE/TEST switch on the unit makes it easy to simulate light levels for testing the system setup under different light level and occupied/unoccupied conditions. The unit provides quick visible indication of Dark or Not Dark status with bi-color LEDs for each channel. Panel Division INSS-SUM
Installation Instructions
HBMS8SS Lighting Integrator BMS Interface Module Installation and Setup Santa Clara, C 95050 The Building Management System Interface Module (HBMS8SS) provides an intelligent interface to other building
More informationInstallation Instructions
HCLK8SS Network Clock Programmer Installation Instructions The Network Clock (HCLK8SS) adds scheduling capability to the Lighting Integrator Panel. The Network Clock simply mounts to the DIN rail in any
More informationSoftwired Clock. Total Lighting Control. Catalog Number: RCLK8SWS DESCRIPTION FEATURES. Installation Instructions IMRCLK8SWS 1
Total Lighting Control Softwired Clock DESCRIPTION The Softwired Switching (SWS) System is a small network of relay panels and occupant control switches linked by a 4-wire dataline. Together these devices
More informationNo: /16 rev. 1 Installation Instructions Instructions d Installation Instrucciones de Instalación
Wattstopper Lighting Integrator Dataline Switch No: 988 0/6 rev. Installation Instructions Instructions d Installation Instrucciones de Instalación Catalog Numbers Les Numéros de Catalogue Números de Catálogo:
More informationOPERATION AND MAINTENANCE
BAS MS/TP Enabled OPERATION AND MAINTENANCE An Company Contents Powering Up For The First Time... 3 Setting MSTP Communication Parameters... 4 Changing the MSTP Address... 4 Changing the BACNET ID... 5
More informationUser Manual. Relay Panel Interiors. Models: LMCP8, LMCP24, LMCP48. Panel with Digital Lighting Management Support SPECIFICATIONS
Relay Panel Interiors Panel with Digital Lighting Management Support Models: LMCP8, LMCP24, LMCP48 User Manual SPECIFICATIONS Input voltage...115/277v 60 Hz, 120/347V 60 Hz, 240V 60 Hz Class 2 connection
More informationDTS400B - DZS400BP 3/9/07 10:14 AM Page 1
DTS400B - DZS400BP 3/9/07 10:14 AM Page 1 18 DTS400B - DZS400BP 3/9/07 10:14 AM Page 3 TABLE OF CONTENTS Section Page Capabilities and Features.......... 1 Installation Instructions............ 2 Instructions
More informationTORK DGU100/DGUM100 7 DAY DIGITAL TIME SWITCH INSTALLATION AND OPERATING INSTRUCTIONS READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT
TORK DGU100/DGUM100 7 DAY DIGITAL TIME SWITCH INSTALLATION AND OPERATING INSTRUCTIONS READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT INSTALLATION UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN 1. To
More informationSoftswitch128TM. SwitchingSystem. Setup and Maintenance Guide
Softswitch128TM SwitchingSystem TM R Setup and Maintenance Guide Believeitornot,thisissupposed to look likeadictionary! Thisiconwascreated by BrentM.Nye,July 6,1995. Believeitornot,thisissupposed to look
More informationComfort System T-32-P Universal Thermostat. Operation Manual
TM Comfort System T-32-P Universal Thermostat TM O Operation Manual Your new Comfort System T-32-P Universal Thermostat has been built using the highest quality components and design currently available.
More informationNOTICE Do NOT touch circuit board components, contact can create a static discharge, which can damage the microprocessor.
MODEL ET2825 Installation and Setup Instructions Electronic 2-Circuit Astronomic 365/7-Day Time Switch With Supercapacitor Carryover WARNING Risk of Fire or Electric Shock Disconnect power at the circuit
More informationElectronic 1-Circuit Astronomic 7-Day Time Switch With 100-Hour Backup
MODELS ET2815C, ET2815CR, ET2815CP Installation and Setup Instructions WARNING Risk of Fire or Electric Shock Electronic 1-Circuit Astronomic 7-Day Time Switch With 100-Hour Backup Disconnect power at
More informationFlexiScan. Impro FlexiScan 4-Channel Controller INSTALLATION MANUAL
MODEL NUMBER: HCM991-0-0-GB-XX FlexiScan SPECIFICATIONS Impro FlexiScan 4-Channel Controller INSTALLATION MANUAL Working Environment... Security... Input Voltage... The Impro FlexiScan is designed to work
More informationElectronic 2-Circuit Astronomic 7-Day Time Switch With 100-Hour Backup
MODELS ET2825C, ET2825CR, ET2825CP Installation and Setup Instructions WARNING Risk of Fire or Electric Shock Electronic 2-Circuit Astronomic 7-Day Time Switch With 100-Hour Backup Disconnect power at
More informationDIGITAL TIME SWITCH 7 DAY WITH INPUT DGU100A DGUM100A DGLC100A DGLC200A
INSTRUCTION MANUAL LISTED DIGITAL TIME SWITCH 7 DAY WITH INPUT DGU100A DGUM100A DGLC100A DGLC200A FOR TECHNICAL SUPPORT: 888.500.4598 A DIVISION OF NSi INDUSTRIES, LLC USA 800.321.5847 www.nsiindustries.com
More informationWattstopper SPECIFICATIONS. Catalog Numbers Les Numéros de Catalogue Números de Catálogo: LMCP8/LMCP24/LMCP48
Wattstopper Relay Panel Interis Panel with Digital Lighting Management Suppt No: 24811 12/16 rev. 1 User Manual Catalog Numbers Les Numéros de Catalogue Números de Catálogo: LMCP8/LMCP24/LMCP48 Country
More informationLocation. Electrical. Loads. 2-wire mains-rated, 0.5 mm² to 1.5 mm² Max. length: 300 m (with 1.5 mm² cable). Example: Belden 8471.
Product Description Installation and User Guide Transistor Dimmer (454) The DIN rail mounted 454 is a fourchannel transistor dimmer that can operate in one of two modes: leading edge or trailing edge.
More informationINSTRUCTION MANUAL DLC400BP DIGITIAL LIGHTING CONTROLLER FOR TECHNICAL SUPPORT: USA
INSTRUCTI MANUAL DLC400BP DIGITIAL LIGHTING CTROLLER 888.500.4598 USA www.nsiindustries.com 03.14 FOR TECHNICAL SUPPORT: 888.500.4598 MLI-188 (B) TABLE OF CTENTS Section Page Installation Instructions
More informationWaveLinx Mobile. WaveLinx Mobile Quick Start Guide. Programming Steps
WaveLinx Mobile WaveLinx Mobile Quick Start Guide General information WaveLinx Mobile is a unique mobile application to programming and use of the WaveLinx Wireless Connected Lighting system. WaveLinx
More informationCalifornia Polytechnic State University ITS Telecommunications PART 1 GENERAL SECTION AUDIO VISUAL STATION CABLES 1.
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationTORK MODEL DZM200A 2 CHANNEL DIGITAL TIME SWITCH WITH MOMENTARY CONTACT
TORK MODEL DZM200A 2 CHANNEL DIGITAL TIME SWITCH WITH MOMENTARY CONTACT INSTALLATION & OPERATION CAPABILITIES 365 Day Advance Single Holiday and Seasonal Scheduling. ON and OFF set points: Combined total
More informationTORK MODEL DWZ100A 1 CHANNEL DIGITAL TIME SWITCH
TORK MODEL DWZ100A 1 CHANNEL DIGITAL TIME SWITCH INSTALLATION & OPERATION CAPABILITIES 365 Day Advance Single Holiday Scheduling. ON and OFF set points: Total # - 99 per week Minimum setting - 1 minute
More informationSTRUCTURED CABLE SYSTEM (SCS)
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationAutomatic Transfer Switch Control PLC Operator s Manual
MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch Control PLC Operator s Manual Dedicated Single Phase Transfer Switch ATS-22AG Automatic Transfer Switch INTRODUCTION 1.1 Preliminary
More informationTITLE BOX PAGE ONLY. DO NOT MAKE FILM DO NOT PRINT. MATERIAL: White 16lb (60g/m sq), uncoated, prefer recycled stock Ink: Black
REV DESCRIPTION INT: REV. DATE APPROVED 1 ECO# C01429 MJS 9/7/05 CG 2 ECO# 02412 DR TITLE BOX PAGE ONLY. DO T MAKE FILM DO T PRINT MATERIAL: White 16lb (60g/m sq), uncoated, prefer recycled stock Ink:
More informationT775L Series 2000 Electronic Stand-Alone Staging Controller
T775L Series 2000 Electronic Stand-Alone Staging Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of commercial and agricultural
More informationDimensions. Electrical Specifications. Environmental Specifications. General Specifications. Mechanical Specifications.
CPC331T-01 GS8E-XT1-BK GigaSPEED XL GS8E T1 Crossover Stranded Cordage Modular Patch Cord, Black Jacket Dimensions Cord Length, maximum 30 m 100 ft Cord Length, minimum 1 m 1 ft Electrical Specifications
More informationElectronic 1-Circuit 7-Day Time Switch With 100-Hour Backup
MODELS ET2705C, ET2705CR, ET2705CP Installation and Setup Instructions Electronic 1-Circuit 7-Day Time Switch With 100-Hour Backup WARNING Risk of Fire or Electric Shock Disconnect power at the circuit
More informationProgramming Guide and User Manual INS # Model # CKM. ControlKeeper M
Programming Guide and User Manual Model # CKM INS # Contents Contents Description Contents....2 Safety Instructions....3 Introduction....4 Welcome....4 Terminology used in this guide....5 ControlKeeper
More informationElectronic 2-Circuit 24-Hour Time Switch With 100-Hour Backup
MODELS ET2125C, ET2125CR, ET2125CP Installation and Setup Instructions Electronic 2-Circuit 24-Hour Time Switch With 100-Hour Backup WARNING Risk of Fire or Electric Shock Disconnect power at the circuit
More informationLCS-2. Low Voltage Lighting Control Relay Processing Panel. Operator s Manual
Low Voltage Lighting Control Operator s Manual The Lighting Control Company 82 Sandiford Drive, Unit #17, Stouffville, Ontario L4A 3S3 Toll Free 1-888-546-2599 Tel: 905 642-3335 Fax: 905 642-3360 Table
More informationST8-WiFi Timer. Installation Guide and Operations Manual. English MIN M D YYYY
ST8-WiFi Timer Installation Guide and Operations Manual AM M D YYYY English Contents ST8-WiFi Timer Installation Guide and Operations Manual Introduction Welcome to Rain Bird... 1 Timer Features... 1 Controls
More informationDIN Power Module - Phase Adaptive
DIN Power Module ow Capacity Phase Adaptive DIN Power Module - Phase Adaptive 369849a 1 08.06.15 The Phase Adaptive Power Module family is a group of modular products for the control of lighting loads.
More informationController, Scheduler-Timer Model UCS-01. User Guide
Model UCS-01 User Guide QUICK REFERENCE GUIDE Time Date IDLE SCREEN 03:50PM [RUN] 05/09/06 Tue Day of the Week Schedule Mode (change via 'Set Time') [OFF] = No Events Operate [RUN] = Run 'R' Events Operate
More informationController, Scheduler-Timer Model UCS-01 version User Guide
Model UCS-01 version 1.48+ User Guide QUICK REFERENCE GUIDE Time Date IDLE SCREEN 03:50PM [RUN] 05/09/06 Tue Day of the Week Schedule Mode (change via 'Set Time') [OFF] = No Events Operate [RUN] = Run
More informationDALI with KNX Control Unit
DALI with KNX Control Unit Please Read Installation and Operation Guide The GRAFIK Eye QS DALI with KNX control unit allows for direct control of both lights and window treatments from both QS and KNX
More informationVLC-3 USER'S MANUAL. Light Program Controller. M rev. 04 K rev. 00 & ( ( 5, 352*5$0 1 : $ 2 ' 6(77,1*6 )81&7,216
Light Program Controller VLC-3 USER'S MANUAL +50,1 +50,1 1 : $ ' 2 7. 6 8 ' 5, 7 6 6. $ ( 3 352*5$0 0,16(& )81&7,216 6(77,1*6 & 8 5 5 ( 1 7 3 ( 5, 2 ' M 890-00189 rev. 04 K 895-00406 rev. 00 GENERAL...
More informationWDK-2500-STROBE. User Guide
WDK-2500-STROBE User Guide Warning: This device complies with Part 15 of the FCC rules, operation of this device is subject to the following conditions: 1. This device may not cause harmful interference.
More informationwith EcoSystem Please Read
with EcoSystem Please ead Installation and Operation Guide The GAFIK Eye QS with EcoSystem control unit allows for control of both lights and shades, without interfaces, using a single control unit. Features
More informationSBL /SBLG Series Wireless Clock
Installation Manual V8.3 SBL /SBLG Series Wireless Clock Current as of August 2018 The Sapling Company, Inc. SBL and SBLG Series Wireless Clocks Table of Contents Table of Contents 2 Important Safety Instructions
More informationSH2RE16A4. Output relay module. Benefits. Description
Output relay module Benefits Integrated system. Dupline is the brand name for Carlo Gavazzi s 2-wire bus system. Cost reduction. The use of a bus system is a proven way to reduce installation costs - especially
More informationPREMIUM 5e F/UTP PRODUCTS
Siemon s end-to-end cabling system is guaranteed to provide transmission performance margins in excess of industry standards for category 5e parameters, while featuring excellent EMI resistance. has been
More informationMains Supply. 2-wire mains-rated, 0.5 mm² to 1.5 mm² Max. length 300 m (with 1.5 mm² cable). Example: Belden 8471.
4Channel Ballast Controller (474) Product Description Installation and User Guide The Digidim 474 is a fourchannel ballast controller fitted with highinrush relays rated at 16 A per channel, which handle
More informationModel 1476-C SuperQuad HR
Model 1476-C SuperQuad HR Installation and Operating Instructions Table of Contents Page Table of Content... 2 System Description... 3 Features... 3 Installation... 4 Internal Setups... 4 Connections...
More informationSECTION COMMUNICATIONS HORIZONTAL CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD, applicable TC -, and CEHNC Design Guide 0-- (Standard is single UTOs and Double UTOs) B. Roads-Service, Lanes Adequate access is provided to the and AAR D. Testing Results-provided
More informationComfortChoice Touch Thermostat. Designed for ZigBee R Wireless Technology USER GUIDE
ComfortChoice Touch Thermostat Designed for ZigBee R Wireless Technology USER GUIDE TABLE OF CONTENTS PAGE WELCOME... 8,9 THE TOUCH SCREEN... 10,11 Home - Inactive... 10 Home - Active... 11 PHYSICAL BUTTONS...
More informationLifestyle. Dual Channel Programmer. for heating AND hot water. Installation and User Instructions DUAL CHANNEL ISSA
Lifestyle Dual Channel Programmer for heating AND hot water Installation and User Instructions DUAL CHANNEL 06490197001 ISSA INSTALLATION INSTRUCTIONS PLEASE NOTE: INSTALLATION MUST ONLY BE CARRIED OUT
More informationPremium INSTALLATION AND USER GUIDE ENGLISH TAHOMA BOX. - INSTALLATION AND USER GUIDE. Rev A _01-16
Premium INSTALLATION AND USER GUIDE ENGLISH - INSTALLATION AND USER GUIDE TAHOMA BOX Rev A _01-16 www.somfy.com TaHoma, connected homes the Somfy way! Remotely control and manage the devices in your home
More information2 CHANNEL RECEIVER DISPLAY POTENTIOMETER COM2 NC2 NO2
2 CHANNEL RECEIVER RECTSHIVE915-DX Please read this manual carefully before installing the product. 1 DESCRIPTION Receiver Rolling Code, 2 channels with dry contact relay output 20A a 12 Vdc. Programming
More informationInstallation and User Guide 458/CTR8 8-Channel Ballast Controller Module
Installation and User Guide 458/CTR8 8-Channel Ballast Controller Module Helvar Data is subject to change without notice. www.helvar.com i Contents Section Page Introduction 1 Installation 2 1. Attach
More informationSMART CLASSix 48 UTP Patch Panels (with patching switches) -
Features Front-mounted Patching Switches connect ports internally, dramatically reducing the need for patch cords Compatible to Unshielded Twisted Pairs (UTP) cabling systems High performance panel that
More informationInstallation and Operation Manual. YMP Series Signal Programmer
Installation and Operation Manual YMP Series Signal Programmer February 2006 YMP Series Clock/Signal Programmer Installation and Operation Manual YMP Series Clock/Signal Programmers YMP YMP02 YMP04 YMP06
More informationDetailed Specifications & Technical Data
For more Information please call 1-800-Belden1 General Description: CAT6A (625MHz), 4-Pair, U/UTP-Unshielded, Plenum-CMP, Premise Horizontal Cable, 23 AWG Solid Bare Copper Conductors, FEP Insulation,
More informationUNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE
UNIVERSITY of NORTH DAKOTA LOW VOLTAGE COMMUNICATIONS STANDARDS FOR CABLING, PATHWAYS, AND SPACE Prepared in cooperation and approval from BICSI Building Industry Consulting Services International and
More informationPersonal Information Page
Rev. 08.29.07 Personal Information Page Installing Dealer Name Date of Installation Day Month Year Type of System Executive MD500 MD1000.2 MHDTV MD5Slim MSD60 Freedom (not recommended) Serial Number of
More informationGenSPEED 10 MTP Category 6A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk
GenSPEED A Cables GenSPEED 10 MTP A Cable An Unshielded 6A Cable with Superior Protection Against Alien Crosstalk 10 MTP unshielded-twisted pair (UTP) design provides industry-leading protection from external
More informationUser Guide. Anywhere Virtual, Scheduler-Timer. Model UCS-V0
SCHEDULE NOTES Hint: complete the notes before programming the events. Event # Example 01) 02) 03) 04) 05) 06) 07) 08) 09) 10) Channel #; Description (days of the week - SMTWTFS) Chnl 001; Front porch
More informationSR - 516D DESK TOP DMX REMOTE STATION. Version: Date: 05/16/2013
SR - 516D DESK TOP DMX REMOTE STATION Version: 1.10 Date: 05/16/2013 Page 2 of 10 TABLE OF CONTENTS DESCRIPTION 3 POWER REQUIREMENTS 3 INSTALLATION 3 CONNECTIONS 3 POWER CONNECTIONS 3 DMX CONNECTIONS 3
More informationOperating Manual. Basic Control BC16. two-channel for eco moon
Operating Manual Basic Control BC16 two-channel for eco moon Dear Customer, Thank you for choosing a WALTRON daytime lighting controller. Your daytime lighting controller is a high-quality product that
More informationSINCE User Manual 7 DAY PROGRAMMABLE DIGITAL TIMER MODEL PS-100. The best solutions for automation and protection.
SINCE 1973 User Manual 7 DAY PROGRAMMABLE DIGITAL TIMER MODEL PS-100 The best solutions for automation and protection www.nassarelectronics.com Description The PS-100 is a 7 day programmable digital timer
More informationUser s Guide. Dimensions 4000 Series Control System. Topics at a Glance
User s Guide Dimensions 4000 Series Control System Topics at a Glance Installation...See Installation Guide Quick Start Configuration...11 User Interface...8 Initial Setup...19 Scheduling...63 Scene Recording...54
More informationSECTION MEDIUM VOLTAGE CABLE INSTALLATION. 1. Section Underground Ducts and Manholes.
SECTION 33 71 49.23 MEDIUM VOLTAGE CABLE INSTALLATION PART 1 GENERAL 1.1 SCOPE A. Work included in this Section: Medium Voltage Cable (4 kv and 12 kv) Installation and Termination. Removal and return of
More informationSapling Synchronous Communication Clock System Section Master Guide Specification Page 1 October 2013
Master Guide Specification Page 1 SAPLING GUIDE NOTE: This master specification section includes guide notes identified as SAPLING GUIDE NOTE for information purposes and to assist the specification writer
More informationFLAT AND ROUND CABLE PRODUCT DESCRIPTION DESIGN ADVANTAGES. IDC Systems Cable
Cable PRODUCT DESCRIPTION Thomas & Betts flat cable provides the means to reduce mass and weight in flexible wiring assemblies. Available with PVC, TPE or FEP insulation, the cable is extruded to provide
More informationInstruction Manual for Electronic Blowers and Flashboards
Instruction Manual for Electronic Blowers and Flashboards These instructions cover both the table model 17212 table top Electronic Bingo Blower (Fig 1) and the 17213 floor model Electronic Bingo Blower
More informationMODEL HA07 - MASTER CONTROLLER INSTRUCTIONS
Thank you for purchasing Intermatic s Home Settings devices. With these products you can reliably and remotely control lighting and appliances. The outstanding features of the Home Settings program include:
More informationImproX SupaGate 4-Channel Controller INSTALLATION MANUAL
MODEL NUMBER: SGI911-1-1-GB-XX IMPROX SUPAGATE SPECIFICATIONS ImproX SupaGate 4-Channel Controller INSTALLATION MANUAL Working Environment... Passive Frequency... RF Frequency... Security... Input Voltage...
More informationContent BULK CABLES VIDEO CABLES AUDIO CABLES EXTENDERS USB CABLES ETHERNET CABLES VIDEO BALUNS CONNECTORS ADAPTERS PATCH PANELS & WALLPLATES TOOLS
Content BULK CABLES VIDEO CABLES AUDIO CABLES pages 2-8 pages 8-12 pages 12-13 EXTENDERS ETHERNET CABLES USB CABLES page 13 pages 14-15 pages 16-17 CONNECTORS ADAPTERS VIDEO BALUNS pages 17-23 pages 23-25
More informationUnlocking of building entrance door shall be possible by pressing the monitor's door-opener button.
DIGITAL COLOR VIDEO INTERCOM SYSTEM The contractor shall supply, install, test and commission a modern Electronic Digital Color Video Entry Phone System of an approved manufacturer and design to facilitate
More informationMaxLite LED Wall Packs (Cutoff & Standard)
General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions
More informationGenSPEED Category 5e Cables 3
Datacom GenSPEED Category 5e Cables 3 GenSPEED Category 5e cables are available in a wide variety of performance levels and constructions. With many options to pick from, you can select the GenSPEED Category
More informationPassive Video Transceivers
s Installation Manual EB-P104-01Q EB-P116-01Q Model Number Channels EB-P104-01Q 4 EB-P116-01Q 16 Transmits up to 1,300ft (400m) color video or up to 1,950ft (600m) B/W video Built-in surge protection Passive
More informationT775U Series 2000 Electronic Stand-Alone Controller
T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote
More informationComplete Part Number = MIL 72A or E Followed by Suffix Code and Voltage. Example: MIL 72A STuZ-24
GRASSLIN - MIL 72 SERIES (24-Hour, 7-Day) 24-HOUR TIME CONTROL SYNCHRONOUS WITHOUT OVERRIDE WITH 3-WAY OVERRIDE QUARTZ 7-DAY CARRY-OVER**With 3-Way Override Time based control of lighting, ventilating,
More informationMagnecraft General Purpose Relays 750R Series DPDT and 3DPT, 10 A
and 3DPT, 10 A UL Listed when used with proper Magnecraft s The 750R series octal base, plug-in relays offer clear or full-feature covers with multiple mounting options and accessories. 750R 750R Full-Feature
More informationCOLORED CATEGORY 5e BULK CABLE, SOLID-CONDUCTOR PATCH CABLE, & CATEGORY 5e BACKBONE CABLE
COLORED CATEGORY 5e BULK CABLE, SOLID-CONDUCTOR PATCH CABLE, & CATEGORY 5e BACKBONE CABLE Key Features Choose Category 5 cable that meets the proposed enhanced standard. Different colors make it easy to
More informationDIN-1DIMU4. DIN Rail Universal Dimmer, 1 feed, 4 channels
The is a 4-channel universal lighting control module designed to support dimming of both forward and reverse phase type loads. A single model supports both 120 and 220-240 Volt electronic and magnetic
More informationOperations. BCU Operator Display BMTW-SVU02C-EN
Operations BCU Operator Display BMTW-SVU02C-EN Operations BCU Operator Display Tracer Summit BMTW-SVU02C-EN June 2006 BCU Operator Display Operations This guide and the information in it are the property
More informationLINK-RAY TM MODULATORS FOR CONSTANT- VOLTAGE. LinkRay Modulators 12 V / 24 V Constant-voltage Applications MODULATORS
MUSIUM RESTAURANT SOUVENIR SHOP EXIT LinkRay Modulators 12 V / 24 V Constant-voltage Applications LINK-RAY TM MODULATORS FOR CONSTANT- VOLTAGE LINK-RAY TM MODULATORS FOR CONSTANT-VOLTAGE APPLICATIONS 186755
More informationR OPTEVA 868 THROUGH THE WALL ATM. 305mm (12") MAXIMUM WALL THICKNESS IN AREA OF UNIT OUTLINE OF OPTIONAL ILLUMINATED SIGNAGE PANEL
OPTEVA 868 THROUGH THE WALL ATM WITH 40mm ( 6") CEN III AND CEN IV SAFE L0 CALL -800--600 0 (6") REQUIRED FOR WALLS EXCEEDING 0mm (2") CONSULT WITH DIEBOLD INSTALLATION/SERVICE BRANCH FOR ADDITIONAL DETAILS
More informationElectronic Timer Control Day Astronomic Electronic Control
Electronic Timer Control - 365-Day Astronomic Electronic Control Item ET90215CRE / EAN-Code PRODUCT DESCRIPTION The ET90000 Series combines powerful and intuitive scheduling with truly maintenance-free
More informationJunior Max (JR Max ) Controller
Get more done TM Junior Max (JR Max ) Controller stations Operating Instructions Thank you for purchasing this advanced, highly featured Irritrol Junior MAX controller. The Junior MAX is the latest addition
More informationAPPLICATIONS typical application: Lighting automation Other applications of the SO and SI line of controllers: HVAC automation Industrial automation OVERVIEW The S Series are microprocessor based I/O controllers
More informationFN:4181M5.DOC MC4181N SERIES MASTER CLOCKS MC4181N
FN:4181M5.DOC MC4181N SERIES MASTER CLOCKS MC4181N TABLE OF CONTENTS 1.0 INTRODUCTION 2.0 SPECIFICATIONS 3.0 INSTALLATION 4.0 GETTING STARTED 4.1 The Auto-Prompt Display 4.2 The Cursor, Entering Data 4.3
More informationT775U Series 2000 Electronic Stand-Alone Controller
T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote
More informationSite Installation Model MP-8433
Site Installation Model MP- Rev. //0 SCOREBOARD SITE INSTALLATION INSTRUCTIONS CAUTION: All American Scoreboards (AAS) recommends the sign be installed by a licensed contractor, and must meet all local
More informationDCL Time Controller WTDCL. Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group
DCL Time Controller WTDCL Universal Lighting Technologies is a subsidiary of Panasonic Electric Works Co., Ltd., a member of the Panasonic Group Table of Contents 1. Introduction 2. Operation 2.1. On/Off
More informationIP Roombox. Hotel Room Management
Hotel Room Management Hotel solutions Versatile room management system You need a simple solution which allows you to control all the hotel room electrical applications? Hager offers you a unique combination
More informationSHIELDED DIGITAL CABLES (1249C SERIES)
DS1 Central Office Twisted Pair Cabling DS1 (1249C SERIES) 26 AWG Polyolefin/PVC Tinned Copper Description 1249C cables are central office cables designed with dual PE/PVC insulated conductors, an inner
More informationSite Installation Model MP-8424
Site Installation Model MP- Rev. //0 SCOREBOARD SITE INSTALLATION INSTRUCTIONS CAUTION: All American Scoreboards (AAS) recommends the sign be installed by a licensed contractor, and must meet all local
More informationWeekly Timer. Mounting track 50 cm (1.64 ft) length PFP-50N 1 m (3.28 ft) length PFP-100N
Weekly Timer 1/4 DIN Size Timer Features Prompted Programming and Large LCD Display 24 hours x 7 days programming using just 5 switches 16 program steps and cycle operation Two independent 15 A control
More informationAnalog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/
> 8 channels for 2-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit > Module
More informationSix-Channel TDM Multiplexers for 3G, HD, SDI, and ASI. Installation and Operations. Manual
Manual DigiLink DLC156 Function modules Six-Channel TDM Multiplexers for 3G, HD, SDI, and ASI Installation and Operations Manual WWW.ARTEL.COM ii DLC156 Function Modules Installation and Operations Manual
More informationThis document last edited May 2015 for version Some commands may not be available in previous versions of firmware.
AP22 Screen Commands This document last edited May 2015 for version 2.90. Some commands may not be available in previous versions of firmware. Instructions To start any of the command screens below you
More informationPhilips LightMaster. KNX Timeclock Installation and Operation Manual
Philips LightMaster KNX Timeclock Installation and Operation Manual Philips LightMaster KNX Timeclock Installation and Operation Manual version 1.1 Specifications subject to change without notice. Copyright
More informationew FLEX SLX SPECIFICATIONS Polycarbonate, approx.1.10 x 1.22 x.56 H (2.97 cm x 3.12 cm x 1.4 cm) UL/cUL, CE COMMUNICATION SPECIFICATIONS
ew FLEX SLX An EssentialWhite Product Color Kinetics ew Flex SLX is a flexible LED string lighting solution that is a bright white-light version of the popular icolor Flex SLX. Designed for accent or perimeter
More informationwith EcoSystem Control Unit Installation and Operation Guide Please Read
with EcoSystem Control Unit Please Read Installation and Operation Guide The GRAFIK Eye QS with EcoSystem control unit allows for control of both lights and shades, without interfaces, using a single control
More informationRA-RS232, RB-RS232. Setup and Installation Guide Addendum For RadioRA RS232 Interface
RA-RS232, RB-RS232 Setup and Installation Guide Addendum For RadioRA RS232 Interface A Comprehensive Step-by-Step Guide for Programming and Operating the Lutron RadioRA RS232 Interface Note: Please leave
More informationCable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment E Cable Certification
General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from
More information