THE GARABI 2000 MW INTERCONNECTION BACK-TO-BACK HVDC TO CONNECT WEAK AC SYSTEMS

Size: px
Start display at page:

Download "THE GARABI 2000 MW INTERCONNECTION BACK-TO-BACK HVDC TO CONNECT WEAK AC SYSTEMS"

Transcription

1 THE GARABI 2000 MW INTERCONNECTION BACK-TO-BACK HVDC TO CONNECT WEAK AC SYSTEMS John Graham Birger Jonsson R.S. Moni Brazil Sweden India ABB Utilities AB, SE Ludvika, Sweden SUMMARY The Argentina - Brasil interconnection first phase of 1000 MW, reported elsewhere, [1] has recently been increased to 2000 MW total power delivery. The second phase is very similar to the first, also employing a back-to-back HVDC converter at Garabi, in Brasil, close to the border with Argentina. A back-to-back HVDC converter can be used when two asynchronous AC systems need to be interconnected for bulk power transmission or for AC system stabilization reasons. In an HVDC back-to-back station there are no overhead lines or cables separating the rectifier and the inverter, hence the DC current can be kept high and the DC voltage low. The low DC voltage means that the air clearance requirement is low, which is in favor of a compact design of the valve housings. This enabled the modular back-to-back HVDC concept to be developed. The back-to-back HVDC converter stations utilized at Garabi are of the modular type with Capacitor Commutated Converters (CCC). The CCC is used to ensure satisfactory performance at low short circuit levels and to reduce the impact of reactive power variations. 1 THE GARABI PROJECT 1.1 Introduction In April 1997, the governments of Argentina and Brazil signed an agreement to facilitate crossborder energy trading between the two countries. On May 5, 1998, the Brazilian Ministry of Mines and Energy, through Eletrobrás, Furnas and Gerasul, and the Argentinean government, signed a 20-year contract with CIEN, Companhia de Interconexão Energética, to import 1000 MW from the wholesale energy market in Argentina. CIEN is a company of the ENDESA group. As the Argentinean system operates at 50 Hz and Brazil's operates at 60 Hz, the inter-connection is made through HVDC frequency converters in back-to-back configuration, located at the Garabi Station in Brazil, close to the border with Argentina. Both phases link the 500 kv networks of Brazil and Argentina through 500 kv transmission lines, each nearly 500 km in length. This first phase of the Garabi Project entered operation in June 2000 and has been reported elsewhere [1]. In August of this year the second phase was put into commercial operation, raising the total transfer capacity to 2000 MW. The second phase is very similar to the first, employing the same modular back-to-back converters, with Capacitor Commutated Converters (CCC). Both phases link the 500 kv networks of Brazil and Argentina by 500 kv transmission lines, nearly 500 km in length, running from the Rincón de Santa Maria substation near Yacyretá in Argentina, to the Itá substation in Brazil. The Argentinean system operates at 50 Hz and Brazil's operates at 60 Hz, and the back-to-back frequency converters for both phases are integrated into the Garabi Station in Brazil, close to the border with Argentina. A simple one line diagram for the first phase in given in fig (1) below:

2 Figure (1): Garabi HVDC Back-to-back station, Phase 1, Simplified One Line Diagram It can be seen that the first phase has a connection with the 230 kv system in southern Brazil via a transformer station at Santo Ângelo. This was not foreseen at the time of initiating the work on the interconnection and was installed by Eletrosul to reinforce the system in the State of Rio Grande do Sul. The phase two interconnection does not connect at Santo Ângelo, although physically passing close in order to facilitate a future connection. Like the Garabi 1 project, the supply of the second 1100 MW phase also is based on a full EPC (Engineering, Procurement and Construction) contract including 500 kv transmission lines and the substation extensions in both countries. Engineering included all studies to satisfy requirements of national agencies as well as engineering studies to ensure that the system works satisfactorily under the wide range of operating conditions. Guarantees on the electrical performance include availability greater than 97%. This was possible because both contracts were based on technical specifications with true functionality, concentrating principally on the values of power to be transmitted and the physical location of the substations. This meant that each supplier could bid his most cost effective technical solution as long as the functional requirements were met and necessary guarantees were sufficient to fulfill the clients criteria. 1.2 System aspects The two electric systems are rather large, yet they are connected at relatively weak points within their networks. The Argentinean integrated system (SADI) has an installed capacity of about MW. However, the Rincón de Santa Maria substation is at the northeastern extreme, and although adjoining the Yaciretá generating station, may have a relatively low short circuit capacity. This can vary between 9000 and 3000 MVA, depending on the number of connected generators at Yaciretá. This has remained virtually unchanged between the two phases of the interconnection. The infeed point to Brazilian S/SE interconnected system was defined at the Itá 500 kv substation for the power purchase. The integrated Brazilian system has an installed capacity of MW, but the Itá substation is on the southern extension, remote from major generation, although a power plant of 1450 MW is coming online with one 290 MW generator now in operation. At the time set for commercial operation of the phase one, the short circuit capacity at Itá was calculated to be about 6000 MVA, dropping to 3500 MVA under contingency conditions, however now at entry of phase two the level is MVA, dropping to 5000 MVA under the worst considered contingencies. The location of the converter station, close to the proposed Garabi Hydroelectric power plant, was also defined in the power purchase documents for phase one and so set conditions for the complete interconnection. This effectively

3 defined the 50 Hz connection point as Rincón de Santa Maria, giving a transmission line length of 136 km, duplicated with an identical parallel line for phase two. However, in the case of the line to Itá, which has a length of 354 km, the first phase has a connection at Santo Ângelo, mentioned above, while the second goes directly, although the system is designed to permit the connection to be made. In addition the station at Garabi is designed to operate with the phase one and phase two converters either connected in parallel or operating individually. This gives a set of rather challenging operating conditions for a converter station where there is a guaranteed delivery of two times 1000 MW into a rather weak network. In order to fulfill all required operating situations, systems studies were carried out by ABB together with CEPEL (Centro de Pesquisas de Energia Electrica) to check compliance with the requirements of the system operators, both in Brazil and Argentina [2]. These studies included load flows over the full operating range at the given system voltage limits, verification of reactive interchange at the connection points and 500 kv / 50 Hz load rejection overvoltages. For the 50 Hz side, with the relatively short transmission line this presented little problem. The long 60 Hz line was a considerable challenge to avoid compensation at an intermediate point. For the chosen transmission line parameters, the short circuit capacity at the Garabi phase two 60 Hz side is about 2000 MVA, dropping to about 1600 MVA under contingency conditions. This was met by using Capacitor Commutated Converters(CCC), with minimum-sized ConTune harmonic filters. In this way fixed line reactors are used and the CCC allows that the converter has characteristics to absorb or supply reactive power as required by the system. The converter acts like a static compensator, giving smooth continuous control of voltage and power flow. The minimum size of the ConTune filters help to keep load rejection overvoltages within limits. However for the phase two expansion additional switched shunt reactors are needed on the 60 Hz side to cover all operating conditions. The resulting system configuration for the final arrangement with both phases in parallel is shown in figure kv / 60 Hz Block 4 Block 3 Garabí 2 Line 2 Tie-breakers Line 1 Shunt reactor Line 2 Tie-breakers Line 1 Block 2 Garabí 1 Block 1 AC filter Figure (2) Integrated Bus Arrangement The above diagram appears to be quite different from the arrangement used for the first phase, however in fact the two parts are identical with

4 respect to converter equipment and associated performance. The apparent difference comes from the change to a double breaker scheme for the 500 kv switchyards, compared to the modified ring bus used in phase one. This gives greater flexibility when the two phases are integrated. The second phase maintains the philosophy of having a filter bank associated with each converter and using a spare switched phase to be available for either of the converters. This allows the use of minimum sized ConTune filters, which alleviates the effects associated with line energisation and load rejection when large shunt capacitance is present. The filter banks have a total of four branches, two ConTune for 11 th and 13 th harmonics, plus two passive high pass tuned at 24 th and 36 th. The inductances of the tunable branches are adjusted continuously to compensate for temperature and frequency deviations The total fundamental frequency rating for the filter bank is 85 Mvar per 550 MW converter. With this rather low value the studies also have to take into account the value of the PLC noise filters connected on the lines from the station. These have fundamental ratings of 9 Mvar on the 50 Hz side and 22 Mvar on the 60 Hz. The CCC capacitors, as all converter design, are identical for the two phases, with values of 190 Mvar per 550 MW converter on the 50 Hz side and 322 Mvar on the 60 Hz side. The larger value on the 60 Hz side permits supply of reactive power to the system as required at full load. Thus it can be seen that the CCC capacitors not only fulfill the role of ensuring satisfactory commutation at low short circuit levels, but also satisfy steady state requirements of reactive power. This is illustrated in figures (3) and (4), and further discussed in item 2 below. U d CCC γ = constant Conventional γ = constant Qdc [MVAr] Qmax Qmin I d [pu I dn ] Pdc [MW] Figure (3) Ud vs Id Characteristics Figure (4) Reactive Power, 60 Hz Side 1.3 Integration As noted in the earlier paper the Garabi Project employed many new features: Commutated Converters (CCC) required to permit operation with low short circuit levels at the inverter Self tuning AC filters (ConTune) One redundant AC filter phase Modular out-door valve enclosures A new PC based control system, MACH2 AC breakers with optical CTs (Compact)

5 These features aided the integration of the two phases, especially the MACH2 control system and the 500 kv HPL Compact switching module. In the first case the powerful computers used for the control system permit the rearrangement of the control and protection systems as determined by the new layout. Further the integrated system can be tested in the factory to ensure that the software changes to the existing equipment will be satisfactory. This test was carried out prior to shipment of the actual phase two control equipment. These principles of the MACH2, namely extremely powerful computers, fully integrated software for all protection, control and monitoring functions, plus a comprehensive factory system test, are not unique to the modular back-to-back concept, but are utilized in all HVDC project now supplied by ABB [4]. Secondly the modular switchgear, designed primarily for ease of installation, can also be moved rather easily. The HPL Compact switching module includes all functions performed by a traditional circuit breaker bay; HPL circuit breaker, pantograph disconnectors, earthing switches, digital optical current transducer, common base frame and pre-wired control cubicle. The module is mounted on a single foundation for each phase. This results in a substantial reduction of required space and facilitates easy and fast maintenance of the breaker bay. This has resulted in rather short outage times being required for the necessary relocation of the switching modules from the ring bus in Garabi 1 to the double breaker scheme used for the integrated station. Figure 5 below shows Garabi 1 on the left with the original ring bus and Garabi 2 to the right with the double breaker scheme. Figure (5): Garabi 500kV yards and ConTune Filter Area The 500 kv transmission lines and the first converter block associated with phase two went into service in April this year (2002). The complete phase two started commercial operation in August following extensive system tests. This is via connection directly to Itá and the full integration of the two phases has yet to be completed. However the integration is a complex process involving both scheduled outage times and system testing. This process is on going and programmed for completion only next year.

6 2 MODULAR BACK-TO-BACK CONCEPTS 2.1 The CCC/ConTune Combination The converter used in the CCC concept is characterized by the use of commutation capacitors inserted in series between the converter transformers and the converter valves, see Figure 6. below. It makes it possible to operate HVDC in very weak networks and eliminates the need for synchronous compensators. Fig. (6): Single line diagram of a monopolar station with CCC and ConTune filter. This capacitor commutated converter is coupled with the ConTune filter in order to give the maximum benefits from a low shunt connected capacitance and a controllable reactive power source in the converter. As described in [3], the approach offers better electrical performance than a conventional converter by virtue of the following factors: Switchable shunt filter banks are no longer required for reactive compensation and are replaced by a series capacitor bank in which the reactive generation is a function of the load current flowing through the capacitor. Small fixed filter banks, optimized for filter performance, can be used providing lower load rejection overvoltages. Figure 7 indicates the reactive power balance variation for conventional and CCC based converters. The CCC based converters give a smooth variation avoiding voltage steps. The series capacitor provides a more positive resistance characteristic at the inverter as shown in Figure 3. In a conventional inverter, an increase in direct current results in a reduction in inverter commutating voltage due largely to a reduction in AC network voltage. With a series capacitor at the inverter, increasing current results in an increasing voltage across the capacitor, offsetting the drop in the AC network voltage. It is this factor that permits stable operation with low short circuit ratios and better commutation failure immunity. Another manifestation of this factor is the increased maximum power curve [3]. The series capacitor s impedance (dxc) is typically several times greater than the transformer s impedance (dxl), increasing the total secondary side impedance and reducing transformer and valve currents during DC side short circuits. Even though higher valve voltage ratings are required, the lower current stresses allow optimization of the converter transformer and valve. The series capacitor inserts a leading phase shift between the transformer secondary and the valves, compensating the naturally lagging characteristic of the converter. The converter s power factor, seen from the transformer s primary side, can be kept close to unity, or even become leading, allowing the converter to generate reactive power as may be noted in Figure 4. In Figure 4 the Qmin curve indicates reactive power generation, while the Qmax curve refers to absorption. Fig. (7): Reactive power conditions for a typical conventional converter and for a CCC.

7 2.2 Modular Construction The converter valves are in modular housings, factory assembled and tested, and were shipped to the site ready for reassembly and operation. The control equipment and auxiliaries were also factory assembled and tested to reduce the installation and commissioning time. In order to optimize the costs of the thyristor valves, as well as the DC side equipment, the DC current is kept as high as the standard thyristor rating and the valve cooling system can handle safely. This means that the DC voltage can be kept fairly low, and is thus chosen to meet the rated DC power required. The low DC voltage means that the air clearance requirement is low which favors a compact design of the valve housings. This has enabled the modular back-toback HVDC concept to be developed. The thyristor valves are air insulated at atmospheric pressure and installed in modular valve housings. In the case of Garabi each valve module contains two single valves, which means up to six valve modules per twelve-pulse converter. The modules are positioned in stacks of two, giving a quadri-valve type arrangement. This gives a convenient layout for the use of single phase, three winding converter transformer, as can be seen in figures 8 and 9. Figure(8): Converter Area The thyristor valves are suspended within the modular housing and are easily accessible for the maintenance crew. The housings also contain the surge arresters connected across the valves. The valve control units can be seen external to the valve modules, besides the access door. Figure 8 also shows the valve cooling modules, each one close to the converter block. This houses the water pumps and water treatment system. The water-to-air closed circuit coolers are located immediately behind the valve cooling module. This modular housing approach is used for all auxiliary and control equipment. The principle of factory assembly and testing has been used extensively to ensure complete and reliable delivery as well as fast erection times. In addition a weatherproof location with a controlled environment is ensured Figure (9): Valve Modules The modular concept has also been used for all converter bus breakers as described above, employing compact design, with breaker, disconnects and optical current transformer integrated into one unit. The modular concept used in the station, extended to converters, auxiliaries and switchgear has the considerable advantage of simplifying civil works, the design process being now restricted essentially to foundations, without the need for complex interfaces between buildings and equipment. This results in reduced costs for civil works and reduced construction times. The complete station, with converter capacity of 2200 MW, is constructed on an area of 367m by 670m, giving a very high utilization of land. In environmentally sensitive areas this is also considered a great advantage from a permitting

8 point of view. The ISO certification states that the design of the equipment and the construction at the site are performed in an environmentally acceptable way. 3. CONCLUSIONS The Argentina - Brasil interconnection, having now entered into commercial operation of the two 1100 MW phases, demonstrates the advantages of the modular back-to-back concept. The HVDC converters at Garabi are notable for two main characteristics, use of the CCC/ConTune combination and the construction using the modular design concept. The use of the CCC/ConTune combination permits secure operation at low short circuit levels and improves performance with respect to reactive power control. The modular design concept simplifies the civil design and ensures a safe and environmentally acceptable solution, as well as permitting reduced delivery times. REFERENCES 1. J. Graham, G. Biledt, Mauro Baleeiro, José Ramón Diago, Fco Javier Bugallo; Garabi the Argentina Brasil 1000 MW Interconnection; VIII Erlac, Cidade del Este, Paraguay, May John Graham, Don Menzies, Geir Biledt, Antônio Ricardo Carvalho, Wo Wei Ping, Acacio Wey; Electrical System Considerations for the Argentina-Brazil 1000 MW Interconnection; CIGRE Biennial, Paris, Don Menzies, Hans Eriksson, Fabiano Uchoas Ribeiro, Commissioning The Garabi I Back-to-Back Converter Station, Erlac Modern Control and Protection System for HVDC, Torbjörn Karlsson, Mats Hyttinen, Lars Carlsson and Hans Björklund 5. Capacitor Commutated Converters for HVDC, Tomas Jonsson, Per-Erik Bjorklund, IEEE Power Tech Conference, Stockholm, 1995.

REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA

REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA 21, rue d'artois, F-75008 Paris http://www.cigre.org B3-110 Session 2004 CIGRÉ REFURBISHMENT OF SECONDARY SYSTEMS IN HIGH VOLTAGE SUBSTATIONS LESSONS LEARNED IN VENEZUELA by E. PADILLA * L. CEDEÑO E. PELAYO

More information

Definitions. Common Corridor:

Definitions. Common Corridor: Definitions Common Corridor: Contiguous right-of-way or two parallel right-of-ways with structure centerline separation less than the longest span length of the two transmission circuits at the point of

More information

Research on Control Strategy of Complex Systems through VSC-HVDC Grid Parallel Device

Research on Control Strategy of Complex Systems through VSC-HVDC Grid Parallel Device Sensors & Transducers, Vol. 75, Issue 7, July, pp. 9-98 Sensors & Transducers by IFSA Publishing, S. L. http://www.sensorsportal.com Research on Control Strategy of Complex Systems through VSC-HVDC Grid

More information

Maschinenfabrik Reinhausen Germany Power Quality

Maschinenfabrik Reinhausen Germany Power Quality Maschinenfabrik Reinhausen Germany Power Quality Power Quality and Reliability Dr.-Ing. Mike Ifland / MR PQ Germany Israel/ Dec. 4 st 2014 Page 1 of 23 Agenda I MR Introduction I MR PQ Fields of activity

More information

Specification. NGTS Issue 1 October 1993

Specification. NGTS Issue 1 October 1993 The Electrical Standards for SHE Transmission s area are non-maintained versions of National Grid Technical Specifications that are applicable to the SHE Transmission System only. These specific versions

More information

GRIDCON POCOM POCOS POCOL MeDIUM VOLTAGe COMPeNSATION SySTeMS IN CABINeT DeSIGN. POWeR QUALITy

GRIDCON POCOM POCOS POCOL MeDIUM VOLTAGe COMPeNSATION SySTeMS IN CABINeT DeSIGN. POWeR QUALITy GRDCON POCOM POCOS POCOL MeDUM VOLTAGe COMPeNSATON SySTeMS N CABNeT DeSGN POWeR QUALTy 1 GRDCON POCOM POCOS POCOL GRDCON POCOM, POCOS, POCOL Compensation systems in a cabinet design GRDCON POCOM, POCOS

More information

Simulation of DFIG and FSIG wind farms in. MATLAB SimPowerSystems. Industrial Electrical Engineering and Automation.

Simulation of DFIG and FSIG wind farms in. MATLAB SimPowerSystems. Industrial Electrical Engineering and Automation. CODEN:LUTEDX/(TEIE-7235)/1-007/(2009) Industrial Electrical Engineering and Automation Simulation of DFIG and FSIG wind farms in MATLAB SimPowerSystems Francesco Sulla Division of Industrial Electrical

More information

Generator protection relay

Generator protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Off-the-shelf generator protection relay for small and medium sized power generators Three-phase time overcurrent and

More information

Toronto Hydro - Electric System

Toronto Hydro - Electric System Toronto Hydro - Electric System FIT Commissioning Requirements and Reports Comments and inquiries can be e-mailed to: FIT@torontohydro.com Customers without e-mail access can submit through regular mail

More information

MCR3 POWER EQUIPMENT. Microprocessor Controlled Constant Current Regulator. Compliance with Standards. Uses. Features

MCR3 POWER EQUIPMENT. Microprocessor Controlled Constant Current Regulator. Compliance with Standards. Uses. Features Microprocessor Controlled Constant Current Regulator Compliance with Standards FAA: ICAO: IEC: 61822 CENELEC: AC 150/5345-10 (current edition), L-828, L-829. Aerodrome Design Manual Part 5, para. 3.2 (current

More information

Detailed Design Report

Detailed Design Report Detailed Design Report Chapter 4 MAX IV Injector 4.6. Acceleration MAX IV Facility CHAPTER 4.6. ACCELERATION 1(10) 4.6. Acceleration 4.6. Acceleration...2 4.6.1. RF Units... 2 4.6.2. Accelerator Units...

More information

1993 Specifications CSJ , etc. SPECIAL SPECIFICATION ITEM CCTV Central Equipment

1993 Specifications CSJ , etc. SPECIAL SPECIFICATION ITEM CCTV Central Equipment 1993 Specifications CSJ 0922-33-042, etc. SPECIAL SPECIFICATION ITEM 8549 CCTV Central Equipment 1. Description. This Item shall govern for the furnishing and installation of closed circuit television

More information

V9A01 Solution Specification V0.1

V9A01 Solution Specification V0.1 V9A01 Solution Specification V0.1 CONTENTS V9A01 Solution Specification Section 1 Document Descriptions... 4 1.1 Version Descriptions... 4 1.2 Nomenclature of this Document... 4 Section 2 Solution Overview...

More information

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel

SPECIAL SPECIFICATION :1 Video (De) Mux with Data Channel 1993 Specifications CSJ 0924-06-223 SPECIAL SPECIFICATION 1160 8:1 Video (De) Mux with Data Channel 1. Description. This Item shall govern for furnishing and installing an 8 channel digital multiplexed

More information

SINCE 1989 Quality Products, Prompt Services, Trustful Relationships www.kmindustrialcorp.com KM Industrial Corporation has established itself as a trusted supplier of Electrical, Machinery and Industry

More information

GA A26497 SOLID-STATE HIGH-VOLTAGE CROWBAR UTILIZING SERIES-CONNECTED THYRISTORS

GA A26497 SOLID-STATE HIGH-VOLTAGE CROWBAR UTILIZING SERIES-CONNECTED THYRISTORS GA A26497 SOLID-STATE HIGH-VOLTAGE CROWBAR by J.F. Tooker, P. Huynh, and R.W. Street JUNE 2009 DISCLAIMER This report was prepared as an account of work sponsored by an agency of the United States Government.

More information

DLP200M 2 Relay Module for Heating and Cooling Plants

DLP200M 2 Relay Module for Heating and Cooling Plants Product Sheet TH6.24 Thermostat Type DLP200M DLP200M 2 Relay Module for Heating and Cooling Plants The DLP 200 M is a relay module for activation of loads (namely thermal actuators or circulators) in wireless

More information

10/13/2011 Planning Coordination Committee. Standards

10/13/2011 Planning Coordination Committee. Standards Document name Category System Performance Regional Criterion ( ) Regional Reliability Standard (X) Regional Criterion ( ) Policy ( ) Guideline ( ) Report or other Document date 12/01/2011 Adopted/approved

More information

PRINCIPLES AND APPLICATIONS

PRINCIPLES AND APPLICATIONS GENERATION & NETWORK Digital Automation Measuring and Control Devices AMS7000 PROCOM The optimum operation of an electrical network depends particularly on the reliability and the availability of the protection,

More information

Intelligent solutions for Onshore Power Supply

Intelligent solutions for Onshore Power Supply Intelligent solutions for Onshore Power Supply Dipl. Ing. H.-E. Schmidt Account Manager OPS SIEMENS AG GER IC 20099 Hamburg September 2012 Siemens AG 2012 Ship to shore connection Nordlandkai Lübeck, Germany

More information

Real Time Monitoring for SMART Grid Initiatives Synchronized Measurement & Analysis in Real Time SMART program by

Real Time Monitoring for SMART Grid Initiatives Synchronized Measurement & Analysis in Real Time SMART program by Real Time Monitoring for SMART Grid Initiatives Synchronized Measurement & Analysis in Real Time SMART program by Bharat Bhargava Armando Salazar Southern California Edison Co. IEEE PES General Meeting

More information

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-080D1750G358. Constant current LED driver DALI Dimmable. LED Driver.   Product description. Benefits. Interfaces. Linear / area dimming Constant current LED driver DALI Dimmable Product description Dimmable built-in constant current LED Driver Adjustable output current between 1,050 and 1,750mA via DIP switch Max.

More information

R&S SLx8000 Family of UHF/VHF Transmitters Efficient solutions for analog and digital broadcasting standards

R&S SLx8000 Family of UHF/VHF Transmitters Efficient solutions for analog and digital broadcasting standards Broadcasting Data Sheet 02.01 R&S SLx8000 Family of UHF/VHF Transmitters Efficient solutions for analog and digital broadcasting standards R&S SLx8000 Family of UHF/VHF Transmitters At a glance The UHF/VHF

More information

Improving Lightning Protection of Power Systems with Externally Gapped Line Arresters (EGLA)

Improving Lightning Protection of Power Systems with Externally Gapped Line Arresters (EGLA) Improving Lightning Protection of Power Systems with Externally Gapped Line Arresters (EGLA) Jonathan Woodworth ArresterWorks 1 Today's Presentation 1. Real Value of Arresters 2. Improving Distribution

More information

COHERENCE ONE PREAMPLIFIER

COHERENCE ONE PREAMPLIFIER COHERENCE ONE PREAMPLIFIER OWNER S MANUAL TABLE OF CONTENTS Introduction Features Unpacking Instructions Installation Phono Cartridge Loading Basic Troubleshooting Technical Specifications Introduction

More information

16 th Annual PQSynergy International Conference and Exhibition 2016

16 th Annual PQSynergy International Conference and Exhibition 2016 16 th Annual PQSynergy International Conference and Exhibition 2016 Er. Muhammad Najmi Bin Bohari MSc(Power Eng), B.Eng (EEE) P.Eng, MIES, M-CIGRE najmi@powerquality.sg Professional Engineer (Singapore).

More information

1:1 and 1:2 Redundant Low-Noise Ka-Band Block Converter Systems

1:1 and 1:2 Redundant Low-Noise Ka-Band Block Converter Systems R Back to Block/Fixed Tuned Converters 1:1 and 1:2 Redundant Low-Noise Ka-Band Block Converter Systems 1:1 1:1 AND 1:2 REDUNDANT LOW- NOISE Ka-BAND BLOCK CONVERTER SYSTEMS Specifications Options 1:1 Diagram

More information

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS

SINAMICS G130 / G150. Line harmonics filter. Operating Instructions 05/2010 SINAMICS SINAMICS G130 / G150 Line harmonics filter Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 / G150 Operating Instructions Mechanical installation 3 Electrical

More information

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA

HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA Section 00000 SECURITY ACCESS AND SURVEILLANCE HONEYWELL VIDEO SYSTEMS HIGH-RESOLUTION COLOR DOME CAMERA PART 1 GENERAL 1.01 SUMMARY The intent of this document is to specify the minimum criteria for the

More information

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver. Product description. Benefits. Interfaces.

HYL-035D0850G103. Constant current LED driver DALI Dimmable. LED Driver.   Product description. Benefits. Interfaces. Constant current LED driver DALI Dimmable Product description Dimmable Independent constant current Adjustable output current between 350 and 1,050mA via DIP switch Max. output power 35 W Up to 88 % efficiency

More information

Trends and Challenges of HV Cable Systems

Trends and Challenges of HV Cable Systems Trends and Challenges of HV Cable Systems Bruno Arnold Electrical Engineer FH Global Sales Far East, Latin America and India Pfisterer Business Unit PTS Cable Trends and Challenges of HV Cable Systems

More information

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, 8 Channels Type 9461/ > 8 channels for 2-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit > Module

More information

OPTICAL DISTRIBUTION STATION -

OPTICAL DISTRIBUTION STATION - optical distribution station is a high performance, four individual outputs node. With high output levels and performance to 862MHz, it provides an ideal platform for support of the evolving technologies

More information

National Park Service Photo. Utah 400 Series 1. Digital Routing Switcher.

National Park Service Photo. Utah 400 Series 1. Digital Routing Switcher. National Park Service Photo Utah 400 Series 1 Digital Routing Switcher Utah Scientific has been involved in the design and manufacture of routing switchers for audio and video signals for over thirty years.

More information

3AH3 Vacuum Circuit-Breakers

3AH3 Vacuum Circuit-Breakers Catalog HG 11.03 Edition 2018 3AH3 Vacuum Circuit-Breakers Medium-Voltage Equipment siemens.com/3ah3 2 3AH3 Vacuum Circuit-Breakers Siemens HG 11.03 2018 R-HG11-373.tif Contents 3AH3 Vacuum Circuit-Breakers

More information

SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment

SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1993 Specifications CSJ 0027-12-086, etc. SPECIAL SPECIFICATION 1987 Single Mode Fiber Optic Video Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of color

More information

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment

SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment 2004 Specifications CSJ 3256-02-079 & 3256-03-082 SPECIAL SPECIFICATION 6911 Fiber Optic Video Data Transmission Equipment 1. Description. Furnish and install Fiber Optic Video Data Transmission Equipment

More information

Process Transmitter RMA 422

Process Transmitter RMA 422 Technical Information TI 072R/24/ae Process Transmitter RMA 422 Multi-functional 1-2 channel top hat DIN rail unit with loop power supply, alarm set point monitoring, mathematics function and 1-2 analog

More information

High-Value 100 Series (Outdoor)

High-Value 100 Series (Outdoor) R Back to Synthesized/Tunable Converters High-Value 100 Series (Outdoor) HIGH-VALUE OUTDOOR COMMUNICATION CONVERTERS Specifications Outline Drawings Phase Noise System Diagram Control Accessories Options

More information

Hitachi Kokusai Electric Comark LLC

Hitachi Kokusai Electric Comark LLC Hitachi Kokusai Electric Comark LLC TRANSMIT TER OF THE FUTURE Solid State. Broadband. Affordable. The future has arrived. With rapid changes in solid state RF device technologies and design techniques,

More information

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT

1995 Metric CSJ SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1995 Metric CSJ 0508-01-258 SPECIAL SPECIFICATION ITEM 6031 SINGLE MODE FIBER OPTIC VIDEO TRANSMISSION EQUIPMENT 1.0 Description This Item shall govern for the furnishing and installation of color Single

More information

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment

SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment 1993 Specifications CSJ 0500-01-117 SPECIAL SPECIFICATION 1291 Fiber Optic Video Data Transmission Equipment 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic Video

More information

Mitigation of Cascading Outages and Prevention of Blackouts:System-Wide Corrective Control

Mitigation of Cascading Outages and Prevention of Blackouts:System-Wide Corrective Control 10th Mediterranean Conference on Power Generation, Transmission, Distribution and Energy Conversion 6-9 November 2016 Belgrade, Serbia Mitigation of Cascading Outages and Prevention of Blackouts:System-Wide

More information

Re-defining the utility-scale inverter

Re-defining the utility-scale inverter Re-defining the utility-scale inverter We believe in green energy in the ability to meet and contribute to growing power demand while supporting a smart grid that serves a smart society. Solution at a

More information

DLP600M 6+1 Relay Module for Heating and Cooling Plants

DLP600M 6+1 Relay Module for Heating and Cooling Plants Product Sheet TH6.25 Thermostat Type DLP600M DLP600M 6+1 Relay Module for Heating and Cooling Plants The DLP 600 M is a relay module for activation of loads (namely thermal actuators or circulators) in

More information

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130

Operating Manual (Edition 04/2004) sinamics. Line Reactors SINAMICS G130 Operating Manual (Edition 04/2004) sinamics Line Reactors SINAMICS G130 Contents 1. Safety Information 2 2. General 5 3. Mechanical Installation 6 4. Electrical Installation 8 5. Technical Specifications

More information

Experiences of CESC in Smart Grid Initiatives LT Network Automation. Anjan Mitra / Arka Ghosh

Experiences of CESC in Smart Grid Initiatives LT Network Automation. Anjan Mitra / Arka Ghosh Experiences of CESC in Smart Grid Initiatives LT Network Automation Anjan Mitra / Arka Ghosh CESC An Overview About 120 year old fully Integrated Energy Utility Oldest private electricity utility in India

More information

A MISSILE INSTRUMENTATION ENCODER

A MISSILE INSTRUMENTATION ENCODER A MISSILE INSTRUMENTATION ENCODER Item Type text; Proceedings Authors CONN, RAYMOND; BREEDLOVE, PHILLIP Publisher International Foundation for Telemetering Journal International Telemetering Conference

More information

TROJANUVTORRENTTM. Drinking Water Disinfection

TROJANUVTORRENTTM. Drinking Water Disinfection TROJANUVTORRENTTM Drinking Water Disinfection Drinking Water Treatment. No Compromises. Revolutionary technology platform from the industry leader UV s environmental and water quality benefits for disinfection

More information

SPECIAL SPECIFICATION 6735 Video Optical Transceiver

SPECIAL SPECIFICATION 6735 Video Optical Transceiver 2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6735 Video Optical Transceiver 1. Description. This Item governs the furnishing and installation of Video optical transceiver (VOTR) in field location(s)

More information

SPINNER BROADCAST EXPLANATION OF THE MULTI CHANNEL COMBINER SPECIFICATIONS

SPINNER BROADCAST EXPLANATION OF THE MULTI CHANNEL COMBINER SPECIFICATIONS EXPLANATION OF THE MULTI CHANNEL COMBINER SPECIFICATIONS Calculation of the maximum permissible output voltage Various signals are added up within the combiner. The peak voltages of the individual signal

More information

7000 Series RossGear Series RossGear

7000 Series RossGear Series RossGear 7000 Series RossGear 7000 Series RossGear AUDIO AND VIDEO FRAMES & ACCESSORIES VFR-7214 1RU Analog Video Products Mounting Frame page 6 VFR-7210 2RU Analog Video Products Mounting Frame page 6 VFR-7514

More information

KRF EMC Filters Installation, Operation and Maintenance Manual

KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters Installation, Operation and Maintenance Manual KRF EMC Filters limit high frequency noise, as well as: Reduce interference Protect sensitive equipment Eliminate drive cross-talk Meet FCC

More information

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15

Analog Input Module HART Ex n Inputs, 8 Channels Series 9461/15 > 8 channels for 2-wire HART transmitters > Inputs for Ex nl, Ex na and Nonincendive > Galvanic separation between inputs and system > Open-circuit and short-circuit monitoring for each field circuit >

More information

A Unique Power Supply for the PEP II Klystron at SLAC*

A Unique Power Supply for the PEP II Klystron at SLAC* I : SLAC-PUB-7591 July 1997 A Unique Power Supply for the PEP II Klystron at SLAC* R. Case1 and M. N. Nguyen Stanford Linear Accelerator Center Stanford University, Stanford, CA 94309 Presented at the

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 45W 1050mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 1,050 ma output power 45 W Nominal life-time up to 50,000

More information

0.1. Outage Management Process Summary

0.1. Outage Management Process Summary 0.1 Outage Management Process Summary Issue: 1.0 Issue Date: August 27, 2014 Table of Contents 1. Introduction... 4 1.1 Purpose... 4 1.2 Glossary... 4 State Transition Model... 8 2. Outage Management Processes...

More information

Gamma instabus. Technical product information

Gamma instabus. Technical product information Gamma instabus Technical product information Universal dimmer N 554D31, 4 x 300 VA / 1x 1000 VA, AC 230 V Universal dimmer N 554D31 Control of dimmable lamps, including LED without minimum load Output

More information

Fibre Optic Modem ODW-622

Fibre Optic Modem ODW-622 Fibre Optic Modem ODW-622 RS-232 to fibre optic link, redundant ring or multidrop applications The ODW-622 can be used to create either redundant ring or multidrop solutions for devices with RS-232 interfaces.

More information

Power Supply Testing: 400 Hz Operation

Power Supply Testing: 400 Hz Operation Power Supply Testing: 400 Hz Operation White Paper by: Brian Rinehart Special Projects Technical Director Crystal Group Inc. 850 Kacena Road., Hiawatha, IA 800.378.1636 crystalrugged.com Contact: leslie.george@crystalrugged.com

More information

SUNNY TRIPOWER 8000TL / 10000TL / 12000TL / 15000TL / 17000TL

SUNNY TRIPOWER 8000TL / 10000TL / 12000TL / 15000TL / 17000TL STP 8000TL-10 / STP 10000T-10 / STP 12000TL-10 / STP 15000TL-10 / STP 17000TL-10 SUNNY TRIPOWER 8000TL / 10000TL / 12000TL / 15000TL / 17000TL Economical Reliable Flexible Simple Maximum efficiency of

More information

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry.

SITOP power supply. Technical data, April SITOP Power Supply. Answers for industry. SITOP power supply Technical data, April 2010 SITOP Power Supply Answers for industry. SITOP reliable power supply Efficient operation of a machine or plant requires a reliable, constant power supply.

More information

High performance circuit breakers

High performance circuit breakers Series High performance Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific trip characteristics

More information

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output Driver LC 10W 350mA fixc lp SNC2 ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 350 ma Max. output power 10.2 W Up to 80 % efficiency For

More information

POWER MONITORS ENERIUM RANGE. Minimize your energy consumption and optimize your installation

POWER MONITORS ENERIUM RANGE. Minimize your energy consumption and optimize your installation POWER MONITORS ENERIUM RANGE Minimize your energy consumption and optimize your installation From 0.2s critical electricity metering to the collection of metering data on all utilities Electrical feeder

More information

Product Information. EIB 700 Series External Interface Box

Product Information. EIB 700 Series External Interface Box Product Information EIB 700 Series External Interface Box June 2013 EIB 700 Series The EIB 700 units are external interface boxes for precise position measurement. They are ideal for inspection stations

More information

I R T Electronics Pty Ltd A.B.N. 35 000 832 575 26 Hotham Parade, ARTARMON N.S.W. 2064 AUSTRALIA National: Phone: (02) 9439 3744 Fax: (02) 9439 7439 International: +61 2 9439 3744 +61 2 9439 7439 Email:

More information

MAXTECH, Inc. BRC-1000 Series. C-Band Redundant LNB Systems. Technology for Communications. System Block Diagrams

MAXTECH, Inc. BRC-1000 Series. C-Band Redundant LNB Systems. Technology for Communications. System Block Diagrams MAXTECH, Inc. Technology for Communications BRC-1000 Series C-Band Redundant LNB Systems Introduction Redundant LNB systems minimize system downtime due to LNB failure by providing a spare LNB and an automatic

More information

Digital Video Engineering Professional Certification Competencies

Digital Video Engineering Professional Certification Competencies Digital Video Engineering Professional Certification Competencies I. Engineering Management and Professionalism A. Demonstrate effective problem solving techniques B. Describe processes for ensuring realistic

More information

Satellite Up- and Downconverter Indoor / Outdoor

Satellite Up- and Downconverter Indoor / Outdoor Visit us at www.work-microwave.de Satellite Up- and Downconverter Indoor / Outdoor Single / Dual / Triple Band Single / Dual Channel S-, C-, X-, Ku-, K (DBS)-, Ka-, and Q-band WORK Microwave s satellite

More information

Nitrogen Oxide Trace Level Analyzer (NOy) Minimum Specifications

Nitrogen Oxide Trace Level Analyzer (NOy) Minimum Specifications Nitrogen Oxide Trace Level Analyzer (NOy) Minimum Specifications 1) General instrument specifications: a) Electronic temperature and pressure transducers capable of being turned off and on while the instrument

More information

LED Driver Compact fixed output

LED Driver Compact fixed output Driver LC 40W 900mA fixc C SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 50,000

More information

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series

LED Driver Linear / area dimming industry. Driver LC 200W 1050mA UNV ADV IND ADVANCED series Driver LC 200W 1050mA UNV ADV IND ADVANCED series Product description Independent constant current LED Driver For dry, damp and wet locations Max. output power 200 W Up to 93.7 % efficiency For luminaires

More information

SYNTHESIZED COMMUNICATION CONVERTERS

SYNTHESIZED COMMUNICATION CONVERTERS Dual-Conversion 1 khz or 125 khz Step Size SYNTHESIZED COMMUNICATION CONVERTERS 9600 SERIES 9400 SERIES MITEQ offers high-performance synthesized frequency converters in panel heights of 2 RU (9400 Series)

More information

Power Quality Solutions

Power Quality Solutions EPCOS Product Brief 2018 Power Quality Solutions Static Var Generator (SVG) PQvar Series EPCOS has been offering a comprehensive range of key components for Power Factor Correction (PFC) and Power Quality

More information

ACTIVE IF SPLITTER/COMBINER UHP-IFS

ACTIVE IF SPLITTER/COMBINER UHP-IFS ACTIVE IF SPLITTER/COMBINER UHP-IFS GENERAL DESCRIPTION AND INSTALLATION GUIDE DOCUMENT RELEASE 2 [UHP.IFS.2.EN] JUNE 2016 CONTENT Acronyms and Abbreviations... 4 Introduction... 5 Required level of qualification...

More information

ODW-621. RS-232 Point-to-point applications

ODW-621. RS-232 Point-to-point applications Re-timing Data rate up to 250 kbit/s 9-position D-sub connector Redundant power supply inputs Status interface for fault indication Fibre link fault indication (Red) Design for harsh environments 40 to

More information

Process transmitter RMA422

Process transmitter RMA422 Technical information TI072R/09/en Mat. No. 51001905 Process transmitter RMA422 Multifunctional 1-2 channel top hat DIN rail unit with intrinsically safe current input and loop power supply, alarm set

More information

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series

PHASED OUT. LED control gear Compact fixed output. Driver LC 40W 900mA fixc C SNC China Domestic ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current 900 ma Max. output power 40 W Nominal life-time up to 30,000 h For luminaires of protection class I and protection

More information

Chloride EDP Series Three-Phase UPS ( kva): The EDP Series UPS is designed

Chloride EDP Series Three-Phase UPS ( kva): The EDP Series UPS is designed R A H I G H E R L E V E L O F C O N F I D E N C E Chloride EDP Series Three-Phase UPS (12-3000 kva): The EDP Series UPS is designed for commercial users who require versatility for today s application

More information

LED Driver Compact dimming

LED Driver Compact dimming Driver CA 15W 180-350mA flexc PH-C SR ADV ADVACED series Product description Dimmable constant current ED Driver (SEV) Independent ED Driver with cable clamps Selectable output current between 180, 250

More information

Copyright 2014 ZES ZIMMER Electronic Systems GmbH. LMG600 Series Introduction

Copyright 2014 ZES ZIMMER Electronic Systems GmbH. LMG600 Series Introduction LMG600 Series Introduction ZES ZIMMER The Touchstone in Power Analysis Precision in Power is the guideline of. ZES ZIMMER is a German high-tech company specialized in developing, manufacturing and distribution

More information

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics

Operating Instructions 07/2007 Edition. SINAMICS G130/G150 Line harmonics filter. sinamics Operating Instructions 07/2007 Edition SINAMICS G130/G150 Line harmonics filter sinamics s Safety information 1 General 2 SINAMICS SINAMICS G130/G150 Operating Instructions Mechanical installation 3 Electrical

More information

Reduction of operating costs

Reduction of operating costs Broadcast and media Transmitter systems TV transmitters: the best even better Thanks to their combined features, TV transmitters from Rohde & Schwarz already had a leading position worldwide, but now they

More information

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing.

Troubleshooting. 1. Symptom: Status indicator (Red LED) on SSR is constant on. 2. Symptom: Output indicator (Yellow LED) on SSR is flashing. Product Data Electrical Data SST (Transmitter) SSR (Receiver) Supply voltage 18 30 V dc Max. Voltage ripple 15 % (within supply range) Current consumption 100 ma (RMS) 75 ma Digital - 100 ma Max. outputs

More information

1 Power Protection and Conditioning

1 Power Protection and Conditioning Power Protection and Conditioning MCR Hardwired Series Power Line Conditioning with Voltage Regulation The MCR Hardwired Series provides excellent noise filtering and surge protection to safeguard connected

More information

Synthesized Block Up- and Downconverter Indoor / Outdoor

Synthesized Block Up- and Downconverter Indoor / Outdoor Visit us at www.work-microwave.de Synthesized Block Up- and Downconverter Single / Dual / Triple Band Single / Dual Channel S-, C-, Ku-, K (DBS)-, Ka- and Q-band WORK Microwave s synthesized block converters

More information

clipping; yellow LED lights when limiting action occurs. Input Section Features

clipping; yellow LED lights when limiting action occurs. Input Section Features ELX-1A Rack-Mount Mic/Line Mixer Four inputs, one output in a single rack space Very-highery-high-quality audio performance High reliability Extensive filtering circuitry and shielding protect against

More information

Notes Generator Verification SDT Project

Notes Generator Verification SDT Project Notes Generator Verification SDT Project 2007-09 FERC Office 888 First Street, NE Washington, DC 20426 1. Administration a. The following were in attendance: Bob Snow, Cynthia Pointer, Lim Hansen, Keith

More information

M4000 Diagnostic Test System For Power Apparatus Condition Assessment

M4000 Diagnostic Test System For Power Apparatus Condition Assessment Knowledge Is Power SM The World Leader in Diagnostic Test Instruments and Knowledge Services for Electric Power M4000 Diagnostic Test System For Power Apparatus Condition Assessment The world s most advanced

More information

ex 800 Series ematrix System

ex 800 Series ematrix System Protecting Your Human Assets During Emergency ex 800 Series ematrix System The ex 800 Series ematrix System is a fully integrated and versatile public address system which is designed distinctively to

More information

WELDING CONTROL UNIT: TE 450 USER MANUAL

WELDING CONTROL UNIT: TE 450 USER MANUAL j WELDING CONTROL UNIT: TE 450 USER MANUAL RELEASE SOFTWARE No. 1.50 DOCUMENT NUMBER: MAN 4097 EDITION: MARCH 1998 This page is left blank intentionally. 2 / 34 TABLE OF CONTENTS SUBJECTS PAGE WELDING

More information

NERC Reliability Standard PRC-024 Generator Frequency and Voltage Protective Relay Settings

NERC Reliability Standard PRC-024 Generator Frequency and Voltage Protective Relay Settings NERC Reliability Standard PRC-024 024-1 Generator Frequency and Voltage Protective Relay Settings Rick Terrill Luminant Power Generation Compliance NERC Standards Drafting Team Member Reliability Standard

More information

PSI-MOS-RS232/FO 850 E Serial to Fiber Converter

PSI-MOS-RS232/FO 850 E Serial to Fiber Converter PSI-MOS-RS232/FO 850 E Serial to Fiber Converter perle.com/products/serial-fiber-converters/psi-mos-rs232-fo850e-rs232-to-fiber.shtml Connect RS232 devices to fiber optic cable Extend serial data up to

More information

DVM-3000 Series 12 Bit DIGITAL VIDEO, AUDIO and 8 CHANNEL BI-DIRECTIONAL DATA FIBER OPTIC MULTIPLEXER for SURVEILLANCE and TRANSPORTATION

DVM-3000 Series 12 Bit DIGITAL VIDEO, AUDIO and 8 CHANNEL BI-DIRECTIONAL DATA FIBER OPTIC MULTIPLEXER for SURVEILLANCE and TRANSPORTATION DVM-3000 Series 12 Bit DIGITAL VIDEO, AUDIO and 8 CHANNEL BI-DIRECTIONAL FIBER OPTIC MULTIPLEXER for SURVEILLANCE and TRANSPORTATION Exceeds RS-250C Short-haul and Broadcast Video specifications. 12 Bit

More information

High Performance Outdoor Test Translators

High Performance Outdoor Test Translators Input Output LO Frequency Frequency Frequency Model (GHz) (GHz) (GHz) Number RF Transmit-Band to RF Receive-Band 5.85 6.425 3.625 4.2 2.225 DN-WS-6.1/3.9 5.85 6.65 3.4 4.2 2.45 DN-WS-6.25/3.8 6.725 7.025

More information

Intelligent compressor solutions. EFC, EFCe Systems Electronic Frequency Control EFC. EFCe

Intelligent compressor solutions. EFC, EFCe Systems Electronic Frequency Control EFC. EFCe EFC, EFCe Systems Electronic Frequency Control Continuously variable speed control using frequency converter technology With the EFC and EFCe system Bock offers the most efficient means of adapting the

More information

STEVAL-ISA001V1. 6W Dual Output Supply using VIPer12A. Features. Blue angel. Applications

STEVAL-ISA001V1. 6W Dual Output Supply using VIPer12A. Features. Blue angel. Applications Features Switch mode General Purpose Power Supply Input: 85 to 264 VAC @ 50/60 Hz Output: 12V @ 0.5A Output Power (peak) 6W Burst Mode Operation in Standby for Blue Angel operation Current Mode Control

More information

MASTER DIALOG ERM 8-20kVA three/single phase ERT kVA three/three phase

MASTER DIALOG ERM 8-20kVA three/single phase ERT kVA three/three phase MASTER DIALOG ERM 8-20kVA three/single phase ERT 10-160kVA three/three phase The Master Dialog range uses advanced double-conversion on-line (VFI) technology with a transformer isolated inverter output

More information

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL

ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL ALM-6813/6812 INSTALLATION AND PROGRAMMING MANUAL Installation and programming Manual v2.2 1 MARSS Solar Defender SYSTEM This guidebook provides the essential instructions to install and configure the

More information